evolution of tungsten degradation under combined high

1
Mitglied der Helmholtz-Gemeinschaft Th. Loewenhoff, A. Bürger, J. Linke, G. Pintsuk, A. Schmidt, C. Thomser L. Singheiser, Forschungszentrum Jülich, EURATOM Association, 52425 Jülich, Germany Introduction ? ELMs occur in normal operation at a rate of 1 Hz more than 10 events during estimated ITER divertor lifetime ELMs deploy ~0.5 MJ/m² in 0.2 – 0.5 ms pulses high power density and high number of events can cause surface roughening, cracking & melting of plasma facing components heat loads during ELMs occur additionally to the steady state heat load of 5 – 10 MW/m² that results in different surface temperatures synergistic effects of steady state and transient heat loads 6 ? ? The importance of ( ) edge localized modes ELMs Experiment Thermal loads on ITER wall / divertor Thorsten Loewenhoff | Forschungszentrum Jülich | Institute of Energy and Climate Research IEK-2 | Association EURATOM - FZJ | [email protected] Conclusions Evolution of tungsten degradation under combined high cycle ELM and steady state heat loads 10 0 10 -4 10 -3 10 3 10 2 10 1 10 -2 10 -1 10 5 10 4 10 3 10 2 10 1 10 0 off-normal normal disruptions VDEs divertor: 5 MW/m², 450 s, n ~ 3000 ELMs: 1 GW/m², 0.5 ms, n > 10 6 power density [MW/m²] pulse duration [s] Electron beam facility JUDITH 2 ? ? ? ? ? max. power 200 kW acceleration voltage 40 – 60 kV pulse duration 5 μs - CW EB diameter > 3 mm (FWHM) diagnostics: video & IR camera, fast pyrometer ( t = 10 μs, T = 350 °C, T = 3500 °C) D min min max Layout data ? ? ? EB is of Gaussian shape, while ELMs’ footprints occur on a wider scale use of circular loading pattern to increase „homogeneously“ loaded area around centre pattern also increases stability with respect to beam width fluctuations test components: W tiles brazed to actively cooled copper cooling block EB power distribution at 44 kW* *with 45 % reflection (tungsten surface) t = 05 μs t = 10 μs t = 15 μs t = 20 μs t = 25 μs t = 30 μs t = 35 μs t = 40 μs EB guidance – circular pattern Tests with pure tungsten tiles This work, supported by the European Communities under the contract of Association between EURATOM/Forschungszentrum Jülich, was carried out within the framework of the European Fusion Development Agreement. The views and opinions expressed herein do not necessarily reflect those of the European Commission. Surface condition after testing pure W at T 200 °C (0 MW/m² SSHL) HFF [MW/m² ] s 10 15 5 0 Dt = 0.48 ms f = 25 Hz ELM abs. coeff.: 0.55 0.22 0.33 0.11 0 10 3 10 4 10 5 10 6 10 7 10 2 number of pulses energy density [MJ/m²] cr network no damage roughening -10 -5 0 5 10 y [mm] -5 0 5 10 -10 x [mm] 700 600 500 400 300 200 100 0 Power density [MW/m²] 700 600 500 400 300 200 100 0 Power density [MW/m²] Results LM picture of undamaged surface 1,000 x HFF 9 MW/m 2 s 1,000 x HFF 12 MW/m 2 s 1,000,000 x HFF 6 MW/m 2 s 1,000 x HFF 9 M 10 MW/m² SSHL W/m + 2 s 100,000 x HFF 6 MW/m + 10 MW/m² SSHL 2 s 100,000 x HFF 6 MW/m 2 s Surface condition after testing pure W at T 700 °C (10 MW/m² SSHL) HFF [MW/m² ] s no damage roughening cr network small cr cr+melting 0.22 0.33 0.11 0 energy density [MJ/m²] 10 3 10 4 10 5 10 6 10 7 10 2 number of pulses 10 15 5 0 Dt = 0.48 ms f = 25 Hz ELM abs. coeff.: 0.55 ? ? ? ? material: sintered & double forged W elongated grains, oriented parallel to the loaded surface (aspect ratio ~0.4) sample size: W tiles of 12 x 12 x 5 mm³, loaded area: 3.5 – 12 mm² (depending on heat flux factor (HFF)) active cooling: water with T = 100 °C (module starting/equilibrium temperature) at p = 3 MPa, tube Ø 8 mm test mode: 400 s load (f = 25 Hz, pulse t = 0.48 ms) 10,000 pulses, 20 s break (back to equilibrium temperature), tests done with and without additional steady state heat load (SSHL) of 10 MW/m² ELM D heat load ? ? ? ? ? ? tests showed the feasibility of ELM-like loading in JUDITH 2 for up to 10 pulses and additional steady state heat load up to 10 MW/m² results show a dependency of material degradation on the number of pulses, the power density and the steady state heat load (surface temperature) for higher temp. (700 °C, SSHL 10 MW/m²) the degradation appears earlier (in terms of number of pulses) and is more severe (e. g. additional melting) the overall damage threshold is located between HFF 3 – 6 MW/m ( energy density 0.07 – 0.13 MJ/m²) roughening as precursor: roughening is always followed by cracking at higher number of pulses erosion of crack edges and/or melting takes place after cracking, depending on surface temperature 6 2 s simulation of heat loading conditions and temperatures as expected for the ITER divertor Test module 10 MW/m² SSHL Surface temperature (HFF 3 ) MW/m 2 s e = 0.2 Temp. [°C] 900 850 800 750 700 650 950 1000 20 30 40 50 60 70 80 t [ms] 10,000 x HFF 9 MW/m + 10 MW/m² SSHL 2 s 100,000 x HFF 9 MW/m + 10 MW/m² SSHL 2 s

Upload: others

Post on 23-Dec-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Mitg

lied

de

rH

elm

ho

ltz-G

em

ein

sch

aft

Th. Loewenhoff, A. Bürger, J. Linke, G. Pintsuk, A. Schmidt, C. ThomserL. Singheiser,

Forschungszentrum Jülich, EURATOM Association, 52425 Jülich, Germany

Introduction

� ELMs occur in normal operation at a rate of ≥ 1 Hz

more than 10 events during estimated ITER divertor lifetimeELMs deploy ~0.5 MJ/m² in 0.2 – 0.5 ms pulses

high power density and high number of events can cause surfaceroughening, cracking & melting of plasma facing components

heat loads during ELMs occur additionally to the steady state heat load of5 – 10 MW/m² that results in different surface temperatures

synergistic effects of steady state and transient heat loads

6

The importance of ( )edge localized modes ELMs

Experiment

Thermal loads on ITER wall / divertor

Thorsten Loewenhoff | Forschungszentrum Jülich | Institute of Energy and Climate Research IEK-2 | Association EURATOM - FZJ | [email protected]

Conclusions

Evolution of tungsten degradation under combinedhigh cycle ELM and steady state heat loads

10010-4 10-3 10310210110-2 10-1

105

104

103

102

101

100off-normal

normal

disruptions

VDEs

divertor: 5 MW/m², 450 s, n ~ 3000

ELMs: 1 GW/m², 0.5 ms, n > 106

po

we

r d

en

sity [

MW

/m²]

pulse duration [s]

Electron beam facility JUDITH 2

max. power 200 kWacceleration voltage 40 – 60 kVpulse duration 5 µs - CWEB diameter > 3 mm (FWHM)diagnostics: video & IR camera,

fast pyrometer ( t = 10 µs,

T = 350 °C, T = 3500 °C)

� min

min max

Layout data

EB is of Gaussian shape, while ELMs’ footprints occur on a wider scale

use of circular loading pattern to increase „homogeneously“ loadedarea around centre

pattern also increases stability with respect to beam width fluctuationstest components: W tiles brazed to actively cooled copper cooling block

EB power distribution at 44 kW*

*with 45 % reflection (tungsten surface)

t = 05 µs t = 10 µs t = 15 µs t = 20 µs

t = 25 µst = 30 µst = 35 µst = 40 µs

EB guidance – circular pattern

Tests with pure tungsten tiles

This work, supported by the European Communities under the contract of Association between EURATOM/Forschungszentrum Jülich, was carried out within the framework of the European Fusion Development Agreement. The views and opinions expressed herein do not necessarily reflect those of the European Commission.

Surface condition after testing pure W at T 200 °C (0 MW/m² SSHL)≈

HF

F [

MW

/m²

]√

s 10

15

5

0

�t = 0.48 msf = 25 HzELM

abs. coeff.: 0.55

0.22

0.33

0.11

0103 104 105 106 107102

number of pulses

en

erg

y d

en

sity [

MJ/m

²]cr network

no damage

roughening

-10-5

05

10

y [mm]

-5

0

5

10

-10

x [mm]

700600500

400300

200

1000

Pow

er

density [M

W/m

²] 700

600

500

400

300

200

100

0

Pow

er

density [M

W/m

²]

Results

LM picture of undamaged surface

1,000 x HFF 9 MW/m2√s

1,000 x HFF 12 MW/m2√s 1,000,000 x HFF 6 MW/m

2√s

1,000 x HFF 9 M 10 MW/m² SSHLW/m +2√s

100,000 x HFF 6 MW/m + 10 MW/m² SSHL2√s

100,000 x HFF 6 MW/m2√s

Surface condition after testing pure W at T 700 °C (10 MW/m² SSHL)≈

HF

F [M

W/m

²]

√s

no damage

roughening

cr network

small cr

cr+melting0.22

0.33

0.11

0

energ

y d

ensity [M

J/m

²]

103 104 105 106 107102

number of pulses

10

15

5

0

�t = 0.48 msf = 25 HzELM

abs. coeff.: 0.55

material: sintered & double forged W elongated grains, oriented parallel to the loaded surface (aspect ratio ~0.4)sample size: W tiles of 12 x 12 x 5 mm³, loaded area: 3.5 – 12 mm² (depending on heat flux factor (HFF))active cooling: water with T = 100 °C (module starting/equilibrium temperature) at p = 3 MPa, tube Ø 8 mm

test mode: 400 s load (f = 25 Hz, pulse t = 0.48 ms) 10,000 pulses, 20 s break (back to equilibrium

temperature), tests done with and without additional steady state heat load (SSHL) of 10 MW/m²

→ELM �

he

at

loa

d

tests showed the feasibility of ELM-like loading in JUDITH 2 for up to 10 pulses and additional steady state heat load up to 10 MW/m²

results show a dependency of material degradation on the number of pulses, the power density and the steady state heat load (surface temperature)for higher temp. (700 °C, SSHL 10 MW/m²) the degradation appears earlier (in terms of number of pulses) and is more severe (e. g. additional melting)

the overall damage threshold is located between HFF 3 – 6 MW/m ( energy density 0.07 – 0.13 MJ/m²)roughening as precursor: roughening is always followed by cracking at higher number of pulseserosion of crack edges and/or melting takes place after cracking, depending on surface temperature

6

2√s →

simulation of heat loading conditions and temperatures as expected for the ITER divertor→

Test module

10 MW/m² SSHL

Surface temperature (HFF 3 )MW/m2√s

� = 0.2Tem

p. [°

C]

900

850

800

750

700

650

950

1000

20 30 40 50 60 70 80

t [ms]

10,000 x HFF 9 MW/m + 10 MW/m² SSHL2√s

100,000 x HFF 9 MW/m + 10 MW/m² SSHL2√s