evapco for life - district energy
TRANSCRIPT
![Page 1: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/1.jpg)
EVAPCO FOR LIFE
![Page 2: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/2.jpg)
Important Criteria When Considering
Cooling Towers for Your DCP
Georges Hoeterickx
Director Business Development
Jelle Wagelmans
Sales Manager Middle East
![Page 3: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/3.jpg)
Important Criteria When Considering Cooling Towers For Your DCP
• Film Fill Types – Materials – Maintenance
• Cooling Tower Layout
• Thermal Performance Certification (CTI)
![Page 4: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/4.jpg)
Film Fill types – Materials – Maintenance
• Types of Fill & Selection Criteria
• Thermal Performance Ratings
• Material and Mechanical Properties
• Fill Life Time and Maintaining Tower Efficiency
![Page 5: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/5.jpg)
Fill Selection Criteria
• The water droplets generated by
splashing
• Heat exchange between water
droplets surface and air
Splash Type
Water Droplet
H.E.
Air
Splash Bar
![Page 6: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/6.jpg)
Fill Selection Criteria
• Heat exchange between water film
surface on PVC sheet and the air
Film Type
Water
H.E.
Air
PVC Sheet
![Page 7: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/7.jpg)
Fill Film Selection
• Fill is a media to create more water surface exposed to the air
• Fill increases the time air-water contact by retarding the progress of water
Increased heat transfer
![Page 8: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/8.jpg)
Fill Selection Criteria
Perforated Sheet Splash Bars Splash GridsFilm Fill
Water Quality
![Page 9: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/9.jpg)
Fill Selection Criteria
The selection of the FILL TYPE depends on the circulating water
characteristics:
• Type of water: sea, TSE, potable water
• Type of industry: power, chemical, paper, steel, DCP ...
• Water availability (concentration factor)
• Type of water treatment
![Page 10: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/10.jpg)
Water Quality
• Origin Suspended Solids in the circulating water:
– TSS of make up water
– Dust and airborne particles washed by the cooling tower
– Dispersants used to control the scaling
• Biological activity controlled with biocides injection
Fill Fouling Directly Related to Total Suspended Solids (TSS) & Biological Activity
TSS maximum concentration for each fill is only valid if
the Biological activity is controlled !
![Page 11: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/11.jpg)
Film Fill Types
Cross-Flutes
High Efficiency
![Page 12: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/12.jpg)
Cross Corrugated Film Fill Type
• Cross corrugated flutes require (very) good water quality
• Highest specific heat transfer
• Slow water / long air travel risk for fouling
• Crossed sheet design = high structural rigidity
![Page 13: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/13.jpg)
Film Fill Types
Cross-Flutes
High Efficiency
Offset-Flutes
Efficient
Low-Fouling
![Page 14: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/14.jpg)
Vertically Offset Flute Film Fill Type
• Offset flutes require good water but more forgiving than cross corrugated
• Highly efficient sheet texture and transitions
• Moderately fast water vs. air travel = low fouling risk
• Lower efficiency compensated by low pressure drop
![Page 15: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/15.jpg)
Film Fill Types
Cross-Flutes
High Efficiency
Offset-Flutes
Efficient
Low-Fouling
Vertical-Flutes
Anti-Fouling
![Page 16: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/16.jpg)
Vertical Flute Film Fill Type
• Vertical flutes handle severe water quality well with proper bacterial control
• Efficient sheet texture = very low fouling risk
• Fast water / air travel = very low fouling risk
• Very low pressure drop = better than splash
![Page 17: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/17.jpg)
Fill Type
High Performance
film fill 12 mm or
19mm Spacing
Cross Fluted
(EVAPAK®)
Low Fouling film fill
25 mm Spacing
Vertical Fluted
(TechClean™)
Anti-fouling film fill
19mm
Vertical Flow
(VertiClean™)
Splash Fill
Bars / Grids
(Opti-Bar™
Arch-Bar™
Opti-Grid™)
TTS (ppm) <25 <50 <100 >100
Bacteria Count (ppm) <10,000 <100,000 <1,000,000 >1,000,000
Bio & Scale Control Required Required Required Lower to none
Biological / Bacteria and Total Suspended Solids
Water Quality Comparison
Note: Fill spacing function of TDS
![Page 18: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/18.jpg)
Film Fill types – Materials – Maintenance
• Types of Fill & Selection Criteria
• Thermal Performance Ratings
• Material and Mechanical Properties
• Fill Life Time and Maintaining Tower Efficiency
![Page 19: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/19.jpg)
Thermal Performance Ratings
Counterflow Film Fill and Spray Test Cell
12
3
4
5
6
71. Forced draft fans
2. Airflow nozzle wall to
measure volumetric airflow
3. Turning vanes
4. Cold water collecting
troughs and mixing box
5. Counterflow fill test section
6. Hot water distribution pipes
and spray nozzles
7. Drift eliminators
![Page 20: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/20.jpg)
Thermal Performance Ratings
Counterflow Film Fill and Spray Test Cell
![Page 21: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/21.jpg)
Thermal Performance Ratings
- KaV/L
- ΔP
Production testing:
- Film fills - Drift eliminators
- Splash fills - Spray nozzles
Air rate:
1.5 5.0 m/s (300-1000 FPM)
Water rate:
45 160 m³/h (200-700 GPM)
![Page 22: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/22.jpg)
Thermal Performance Ratings
Fill Data
![Page 23: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/23.jpg)
Thermal Performance Ratings
![Page 24: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/24.jpg)
Thermal Performance Ratings
- Field data analysis
- Competitive analysis
- KaV/L
- ΔP
![Page 25: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/25.jpg)
Film Fill types – Materials – Maintenance
• Types of Fill & Selection Criteria
• Thermal Performance Ratings
• Material and Mechanical Properties
• Fill Life Time and Maintaining Tower Efficiency
![Page 26: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/26.jpg)
Cooling Tower Heat Exchange Surface
• This CTI specification covers the most common fills, splash fills, louvers,
drift eliminators, nozzles, and other small components for use in standard
properties, burning properties, and recommended testing procedures
employed to determine the defined values, whether processed from virgin
or reground material.
• Revised June 2010
CTI STD – 136 : Thermoplastic Materials Used for Film
Fill, Splash Fill, Louvers and Drift Eliminators
![Page 27: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/27.jpg)
ASTM E 84 tests for flame spread rating (FSR).
• Red oak flooring has FSR of 100
• Fiber cement board has a FSR of 0
Historical number Flame Spread Rating PVC Fills was 25.
Today : material with Flame Spread Rating of 5
ASTM E 84
Material and Mechanical Properties
![Page 28: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/28.jpg)
Material and Mechanical Properties
• Material thickness & UV protection determines life time of the fill
• Specify the fill material thickness “before” and “after forming” !
The forming process thins the material and
15 mills PVC fill before forming (can) become 10 mills after forming !
Film Fill Material Thickness & UV Protection
![Page 29: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/29.jpg)
Material and Mechanical Properties
How we know that specified numbers and qualifications are valid for the
materials supplied ?
Ask specific test reports
Remark
![Page 30: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/30.jpg)
Material and Mechanical Properties
PVC fill
• High strength (CTI STD 136)
• Extremely durable
• Self - extinguishing
• Surface wets – out well
• Can be glued in bundles
PP fill
• Durable but high creep rate, need
50 % thicker than PVC
• Very Flammable
• Poor wetting characteristics
• Cannot solvent bond
Materials
![Page 31: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/31.jpg)
Film Fill types – Materials – Maintenance
• Types of Fill & Selection Criteria
• Thermal Performance Ratings
• Material and Mechanical Properties
• Fill Life Time and Maintaining Tower Efficiency
![Page 32: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/32.jpg)
-0.5 0.0 1.0 2.0
Langelier saturation index: Recommended range
Corrosion inhibitors
recommended
Aggressive water Scaling water
Scaling inhibitors or
dispersants recommended
Safe zone : Acid
Langelier index depends on Ca content, Alkalinity ,TDS, temperatureTypical : Limit pH at 8.5-9 maximum
Water Treatment: Scaling
![Page 33: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/33.jpg)
Fill Life Time and Maintaining Tower Efficiency
• Maintenance :
Assure fill remains in good
condition
• Water treatment important to
control scale build-up
Scale Build-Up on PVC Fill Sheets
![Page 34: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/34.jpg)
Effect of Fouling on Fill & Cooling Tower Performance
Clean Fill
(48 kg/m³)1.6 mm Fouling
(448 kg/m³)
3,2 mm Fouling
(848 kg/m³)
Fill Life Time and Maintaining Tower Efficiency
![Page 35: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/35.jpg)
Estimate of Performance Loss vs. Fouling
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
0 100 200 300 400 500 600 700 800 900
Incr
eas
e in
Ap
pro
ach
(C
)
Weight Gain (kg/m3)
Fill Life Time and Maintaining Tower Efficiency
![Page 36: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/36.jpg)
Important Criteria When Considering Cooling Towers For Your DCP
• Film Fill Types – Materials – Maintenance
• Cooling Tower Layout
• Thermal Performance Certification (CTI)
![Page 37: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/37.jpg)
Cooling Tower Layout
• Arrangement
• Type of Enclosures
• Influence on Thermal Performance
• Clearance
• Type of Influence
![Page 38: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/38.jpg)
Arrangement
Single Row
![Page 39: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/39.jpg)
Arrangement
Back to Back (Double Row)
![Page 40: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/40.jpg)
Arrangement
Two Rows – Not Ideal for Recirculation!
![Page 41: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/41.jpg)
Arrangement
Two Rows – Not Ideal for Recirculation!
![Page 42: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/42.jpg)
Arrangement
Stairway Space Required!
![Page 43: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/43.jpg)
Type of Enclosures
Free Field Installation
![Page 44: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/44.jpg)
Type of Enclosures
Solid Walls Enclosures
![Page 45: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/45.jpg)
Type of Enclosures
• % Free open area louvers
• Pressure drop through louvers
• Orientation
Louvered Walls Enclosures
![Page 46: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/46.jpg)
Type of Enclosures
Effective louver wall height
=
1.2 x air inlet height
Louvered Walls
Air InletHeight
EffectiveLouverWall Height
![Page 47: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/47.jpg)
Type of Enclosures
• Air flow takes the path of least resistance.
• Equilibrium Point : vertical downward air flow air flow through louvers
Louvered Walls
Wall Type Louver Solid
Net Vertical Air Velocity ≤ 600 FPM 400 FPM
Net Louver Air Velocity ≤ 500 FPM N/A
![Page 48: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/48.jpg)
Influence on Thermal Performance
• Net free open area
• Air flow obstruction
– Enclosure structural framing
– Piping
– Walkways
• Clearance
![Page 49: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/49.jpg)
Clearance
• Minimal impact
• No correction required
Case 1
![Page 50: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/50.jpg)
Clearance
Case 2
• 2 x air inlet height < clearance < air
inlet height + wall height
• Add 5 Pa (0.02 in WG)
• Risk for recirculation!
![Page 51: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/51.jpg)
Clearance
• 1 x air inlet height < clearance < 2
x air inlet height
• Add 10 Pa (0.04 in WG)
• High risk for recirculation!
Case 3
![Page 52: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/52.jpg)
Type of Influence
• Increased pressure drop
• Mal-distribution of air
– Increased static pressure
– Hot water bypass
• Recirculation
– Height of enclosure
– Solid or louvered wall
– Clearance
![Page 53: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/53.jpg)
Layout
IF YOU OBSTRUCT THE AIR TO THE COOLING TOWER
THE COOLING TOWER DESIGN / THERMAL
PERFORMANCE WILL BE AFFECTED
![Page 54: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/54.jpg)
Important Criteria When Considering Cooling Towers For Your DCP
• Film Fill Types – Materials – Maintenance
• Cooling Tower Layout
• Thermal Performance Certification (CTI)
![Page 55: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/55.jpg)
CTI Standards
• STD-105
Code/Procedure for CT Thermal Performance Testing on Site
• STD-201
Certification Program: Thermal Performance of Packaged CT’s
• STD-202
Voluntary Program for Custom/Field Erected Cooling Towers
![Page 56: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/56.jpg)
CTI STD-105
• Test Conditions: max. variations
– Wet-bulb: +/- 8.5°C (15°F)
– Range: +/- 20%
– Water flow: +/- 10%
• Instrumentation
• Measurements
• Evaluation of results
![Page 57: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/57.jpg)
CTI STD-201
• Certification Scope:
– Wet-bulb: 12.8°C to 32.2°C (55°F to 90°F)
– Range: ≥ 2.2°C (4°F)
– Approach: ≥ 2.8°C (5°F)
– Inlet T: ≤ 51.7°C (125°F)
• Standard models
• Accessories
![Page 58: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/58.jpg)
CTI STD-202
• Participants allow CTI to publish thermal performance test results
• Field test must be executed by CTI licensed test agency
• Participants:
– Composite Cooling Solutions, L.P. (CCS)
– Evaptech Inc. (Evapco Inc.)
– SPX Cooling Technologies, Inc (Marley)
![Page 59: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/59.jpg)
CTI STD-202
![Page 60: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/60.jpg)
CTI STD-202
• Performance tests demonstrate the actual thermal performance
• Lower outlet water temperature chiller efficiency increases
• More efficient DCP lower energy consumption
Benefits for Owners/Operators
![Page 61: EVAPCO FOR LIFE - District Energy](https://reader031.vdocuments.site/reader031/viewer/2022012104/616a1c7411a7b741a34eed19/html5/thumbnails/61.jpg)
Innovations for LIFE
• Taking
• Quality & Service
• to a Higher Level