eurotherm 818
TRANSCRIPT
818
SERIES
Temperature controller
Productdata
FULL
Y CO
MPL
IANT
EUROTHERMONTROLS
The 818 controller is a truly flexible, advanced technology controller which combines
simplicity of operation with powerful control performance. All the high level functions
of the controller may be configured either from the front panel or via the
communications interface whilst the addition of hardware options is achieved by plug-in
modules.
The 818 has a clear vacuum fluorescent display in which the total instrument status is
indicated. Coupled with powerful control software this gives the operator and engineer
alike the ability to optimise process performance.
Since its launch over 100,000 units have been successfully installed worldwide.
Accuracy - The 818 has a low level I/P Analogue to Digital Converter which is
continuously corrected for drift. Operating at a speed of 8 updates per second this gives
very high stability and rapid response to process changes. All linearisations for the
numerous sensors, which are included as standard in the controller, are digitally
calculated to add high accuracy to the other attributes of this unit.
Communications - Two types of communications are available with the 818
controller:
1) Digital communications via an RS232 or RS422/485 interface link using the industrial
standard ANSI-X3.28 protocol bi-synch. This allows all the parameters of the controller
to be monitored or changed by a computer or PLC. Using the RS422/485 standard up to
100 controllers may be networked on a single link. The Baud rate may be set from 300
to 9600.
2) Analogue communications provides retransmission of various selected parameters
such as Process variable and Setpoint.
Also Analogue communication provides the facility to remotely vary selected parameters
such as Setpoint and Maximum power, by means of a dc signal.
Tuning - All versions of the 818 controller offer two separate PID loop tuning
algorithms (Auto Tuning and Adaptive Tuning ) which automate the tedious part of the
commissioning routine. The two algorithms may be used either separately or together
depending upon process needs.
When the tuning algorithms are used together with the Valve Positioner output the 818
makes use of an internal mathematical model of the motor being used in order to tune
correctly even where there is backlash or valve asymmetry.
Self Tune - The self-tuning algorithm is a ‘one-shot’ tuner which may be manually
initiated at any time, in order to retune for a new set of process conditions. When tuning
to a new setpoint, the self-tuner analyses the start up response to give an estimate of
the process with an on-off sequence, which determines the natural response of the
process so that new control parameters can be calculated and the Proportional, Integral
and Deriviative terms set automatically.
Adaptive Tune - The adaptive-tuning algorithm is designed to run continuously, in
the background, while normal PID control is taking place. The algorithm, is activated
when load disturbances cause deviations from setpoint, in excess of a predefined trigger
point. The algorithm then proceeds to analyse the closed loop response, while the
process value recovers from the initial disturbance and applies expert rules to retune the
loop. If this loop is already well tuned, no action is taken.
818 Temperature controller
TECHNICAL SPECIFICATION Quoted at 25°C unless otherwise statedInputsGeneral Input range -8.0mV to +60mV
Min span 5.0mV
Max span 68mV
Max zero offset 20% of span (in mV)
Common mode rejection <50µV display change for 264V rms at 50/60Hz
Series mode rejection <50µV display change for 50mV rms at 50/60Hz
Input impedance >1M ohm resistance (includes 0.6mA open circuit sensor current)
Resolution 12 bit for all ranges (14 bit max)
Sample period 125 milliseconds
Linearity error Better than ±0.1% of input span
Thermocouple Standards British BS4937 (1973) German DIN 43710 US ASTM E230 (1972)
Linearisation Better than +/-0.2°C for standard thermocouple. Effect of thermocouple lead resistance 0.5µV/ohm
CJC Internal or 0°C, 45°C, 50°C external
Internal CJC Error Typically 0.05°C/°C ambient change (20:1)
RTD Standards British BS1904 German DIN 43760 PT100
Linearisation Better than +/-0.2°C for standard resistance thermometers
Bulb Current 0.2mA
Connection 3 wire automatic lead resistance compensation
Lead compensation error With up to 22 ohms in all three leads no change in display indication
Volts Ranges Minimum span 5.00mV. For spans above 60.0mV an extenal attenuator mounted in an extension
block on the rear terminals is used
Input impedance >100k ohms
Current 0-20mA or 0-10mA. With all current ranges, burden resistors are mounted onto the rear terminals
2.5 ohms for 20mA input and 5 ohms for 10mA input. Offsets provided as software option
e.g. 4-20mA
Outputs Relay Maximum of 264V 2A ac into resistive load, with contact suppression. On/off or time proportional
Minimum voltage 30V rms or dc.
Leakage current through contact suppression components = 2mA @264V ac 50Hz
Triac Maximum of 264V 1A ac into resistive load. On/off or time proportional
Minimum voltage 85V rms
Leakage current through snubber = 2mA at 264V ac 50Hz
Isolated logic 20mA at 15V min. On/off or time proportional
Cycle time 0.3 to 100 seconds at 50% power (relay 10 to 100 seconds)
Power feedback Normally fitted to any of the above when using output 1 (heat)
Analogue Isolated dc 0-10V at 20mA max or 0-20mA at 12 volts. Offsets provided as software option
i.e. 4-20mA. Output impedance on voltage ranges is <1.1 ohms (including connectors)
Retransmission Channel 2 (cool output) or channel 3 (alarm output) can be designated retransmission output of
setpoint, measured variable, error or output power
Retransmission output 10 volts span (max) range lying between 0 to +10 volts at 20mA max. 0-20mA (max) at 12 volts
(min). Offsets provided as software options i.e. 4-20mA
Output impedance on voltage ranges is <0.1 ohms (including connectors)
Retransmission resolution 12 bit effective
Retransmission linearity accuracy Better than 0.5% under all load conditions which are within specifications
Isolation Both output 1 and 2 are isolated from each other and the remainder of the instrument
Outputs (cont’d)Reverse/direct Time proportioning and analogue in output 1 (heat) can be configured either reverse or direct
Output 2 (cool), if time proportioning or analogue, is configured as acting the opposite to output 1
Non-linear Output 2 (cool), when not on/off, can be configured as either linear or non-linear characteristic. The
non linear characteristic is ideal for controlling water which may flash off to steam
Alarms Relays Maximum 264V 2A ac into resistive load, with contact suppression. Minimum switched
voltage 30 volts rms or dc
Leakage current through contact suppression components = 2mA @ 264V ac 50Hz
Hysteresis 0.1 - 10.0% variable, in 0.1% resolution
Type Full scale high and low; deviation high and low; deviation band
Range Alarms may be set over complete instrument range
ParametersControl Auto/Manual Bumpless transfer auto to manual and manual to auto. Manual output variable from
0 to 100% for heat outputs and -100% to +100% for heat/cool instruments
Local/remote Selection of full scale local or remote S/P or add external trim to F.S local or F.S external to local trim
setpoint
Dual P.I.D. Separate values of Pb, ti, td, Cr and RES are installed when Setpoint 2 (SP2) is selected
Commissioning * Proportional Band (PB) 0.1 to 999.9% based on the range ‘display max’ - ‘display min’ or 1 to span in Engineering Units
Integral Time (ti) Off, 1 to 9999 seconds or 1 to 150 minutes
**Travel Tme (tt) 10-1000 secs
Deadband (db) 0.1 - Pb (in %)
1 -Pb (in units)
Pot Min Limit (PI) 0-100%
Pot Max Limit (Ph) 0-100%
Manual reset (RES) -100 or 100% (automatically selected if integral time is ‘off’)
Derivative time(td) Off, 0.1 to 999.9 secs or 1-15 mins
Cut back (CBL/CBH) Off, 0.1 to display range for both low and high
Heat output limit (HL) 0 to 100%
Cool output limit (CL) 0 to -100%
Heat cycle time (HC) 0.3 to 100 seconds (10 to 100 secs for relay)
Cool cycle time (Cc) 0.3 to 100 seconds (10 to 100 secs for relay)
* Relay cool gain (Cr) 0.1 to 20.0 of proportional band (PB)
Heat-cool deadband (DB) -5 to +5% input range
Setpoint rate limit (Pr) 1 to 19999 units per min or hour with decimal position as display eg. XX.XXX display 0.001 to 19.999
Emissivity (PE) 0.01 to 1.00
Sensor break power (SbP) 0 to 100% (heat only) or - 100% to 100% (heat/cool) activated by 10% over or under range
* For on/off outputs proportional band and/or relative cool gain are replaced by deadband and relative
deadband
** Parameter for VP output only
CommunicationAnalogue input Voltage Max 10 volt range lying between -5.0 to 10.0 volts
Input impedance >75K ohms
Current 0-10mA, 0-20mA, offsets provided as software options e.g. 4-20mA
Input impedance 500 ohms mounted on rear terminals
Potentiometer supply 10 volt, 1mA max. potentiometer supply available
Configuration Isolated remote setpoint, remote trim, output power limit
Resolution 12 bit effective
Accuracy Better than 0.5%
Sample period 750 milliseconds
Analogue output Voltage Max. 10 volts, range lying between -5 volts to +10 volts internal impedance <0.1 ohms (including
connectors)
Impedance Load must be >500 ohms
Current 0-20mA (max) at 12 volts min offsets provided as software options e.g. 4-20mA
Configuration Setpoint, measured value, error, or output power (excludes use of channel 2 or 3 as retransmission)
Resolution 12 bit
Linearity accuracy Better than 0.5% under all load conditions which are within specification
Digital Protocol Variable speed link. ASCII format RS232 or RS422/485 protocol ANSI X 3.28 (1976)
2.5 A4 variable baud rates of 300, 600, 1200, 2400, 3600, 4800 and 9600 alternatively Modbus® RTD
or J-Bus® RTD at variable baud rates of 600, 1200, 2400, 3600, 4800 and 9600
Isolation Between communication link and all other inputs and outputs meets IEC348, UL1092 and VDE 411 and
BS4743 standard
Format Start bit - seven data bits - even parity bit - one stop bit (ANSI protocol)
Start bit - eight data bits - one stop bit (ModBus® or J-Bus® protocol)
Unit Address Two digits (00 - 99)
Logic inputs Drive Pulled up to +5 volts in reset state: must be pulled down to 0 volts with an impedance of <100 ohms to
activate
Isolation Logic inputs not isolated from one another or measured value input but isolated from all other inputs and
outputs. As defined under General Electrical Safety.
Voltage Level Limits For logic input active the input level must be less than 0.70 volts for logic in-active the input level must be
greater than 4.00 volts
Input Current 0.5mA maximum
Configuration Auto/manual: Remote/local; Dual P.I.D. Adaptive/self tune; keylock; Ramp enable
(one only per logic input) Remote up/down key; Parameter modification security
Auto Tune Self-tune (ST) A single shot approach which freezes three term parameter after defined period
Adaptive tune (AT) A continuous appraisal and re-defining of three term parameters
General The 818S is compliant with the ‘Low Voltage Equipment Directive’ and the ‘EMC Directive’ when installation instructions are followedDisplay Upper Display 5 x 7 segment 12mm high fluorescent indicator. Display range +19999 to -9999
Lower Display 5 x 7 segment 5mm high fluorescent indicator
Resolution ± 1 least significant digit
Calibration Error Better than ±0.25% span
Environmental Supply Voltage 85 to 264V ac, 17 to 40V ac or 20 to 40V dc
Supply Frequency 48 to 62Hz
Power Consumption 8.5 watts
Operating Temperature 0 - 55°C
Supply Fuse 500mA (anti surge)
EMC Emissions: EN 50081-2 (94)Immunity: Follows the general requirements of EN 50082-2 (95)
Radiated fields may cause PV or remote input to deviate by 1% of spanSee Technical Construction File for details
Creepage Clearences conform to IEC 348, UL 1092 and VDE 411 and BS4743 standards
Relative humidity 0 to 90% non-condensing
Storage temperature -10 to 70°C
Panel Sealing The instrument fascia meets IP54 when mounted into a cutout as defined below and fitted
with the optional gasket
Electrical safety EN 61010 (93), Installation category II, polution degree 2Installation category II Voltage transients on any mains power connected to the instrument must not exceed 2.5kVPollution degree 2 Conductive pollution must be excluded from the cabinet in which the instrument is mounted
Ambient temperature coefficient Typically ±50 ppm/°C of instrument input span. Excluding CJC on the thermocouple instruments
Warm up drift <±0.5% of display range (from 1 to 30 mins)
Supply voltage coefficient <±0.1% of display range over full supply voltage range
Mechanical Customer Connections Screw terminals with terminal cover (fastons optional)
Dimensions 96mm(H) x 96mm(W) x 219mm(D)( including terminal cover)
Mounting Plug in with panel mounting sleeve - Panel cutout 92 x 92mm + 0.8 - 0.0mm to DIN 43710
Weight 1.2Kg (2.6lbs) including sleeve and clamp
Vibration BS2011 EA, EB, FC
ORDERING CODE
Input Code
Thermocouple TC
Resistance thermometer RTD
0-20mA 0mA20
4-20mA 4mA20
0-5V 0V5
1-5V 1V5
2-10V 2V10
-8mV +8mV 8mV8
Pyrometer PYR
Output 1 & 2 Code
Output 1 Output 2
Prefix Prefix
Reverse acting control R
Direct acting control D
Control on output 2
(opposite action to output 1) C
Retransmission of:
Process variable M
Setpoint S
Error E
Power W
Note 1: For normal temperature control select
Reverse Acting Control
Output 2 action opposite of output 1.
Note 2: The Retransmission option is not available
with Analogue Comms, or when retransmission
specified in alarm 1
Output 1 Output 2
Relay linear RLY RLY
Relay non linear - RLYN
Relay ON/OFF *RLYF RLYF
Logic linear LGC LGC
Logic non linear _ LGCN
Logic ON/OFF *LGCF LGCF
Triac Linear TRI TRI
Triac non linear _ TRIN
Triac ON/OFF *TRIF TRIF
No output NONE NONE
Isolated 0-5V 0V5 0V5
Isolated 0-10V 0V10 0V10
Isolated 1-5V 1V5 1V5
Isolated 2-10V 2V10 2V10
Isolated 0-10mA 0mA10 0mA10
Isolated 0-20mA 0mA20 0mA20
Isolated 4-20mA 4mA20 4mA20
Communications
Digital
Type Code Function Code
None NONE None NONE
Digital RS232 232 Baud rate 9600 96
Digital RS485 485 Baud rate 4800 48
J-Bus®RS232 J32 Baud rate 3600 36
J-Bus®RS485 J85 Baud rate 2400 24
M-Bus®RS232 M32 Baud rate 1200 12
M-Bus®RS485 M85 Baud rate 600 06
Baud rate 300 03
Analogue
Input type Retrans function
Prefix 1st digit Prefix 1st digit
Remote setpoint X Process variable M
Remote trim T Setpoint S
Remote S/P with:
Local trim L Error E
O/P max power W Power W
Code Code
2nd digit 2nd digit
Input type onwards Retrans func. onwards
None NONE None NONE
0-20mA 0mA20 0-20mA 0mA20
4-20mA 4mA20 4-20mA 4mA20
0-5V 0V5 0-5V 0V5
0-10V 0V10 0-10V 0V10
1-5V 1V5
2-10V 2V10
-5 to +5V 5V5
Option Code
Faston terminal FN
Screw terminal SN
Faston 24V ac/dc FN24
Screw 24V ac/dc SN24
Motor Valve Controller
Output 1 Output 2
Relay output VPR
Triac output VPT
with feedback pot FB
without feedback pot NONE
Note: With MVC no output 2 prefix is required.
With output 2 prefix M, S, E, W only dc ouputs
apply
* ON/OFF on O/P1 restricts O/P2 to ON/OFF
unless prefix M, S, E, W
Alarms 1 & 2 1st & 2nd digit Code
None NONE
Deviation band DB
Deviation high DH
Deviation low DL
Full scale high FH
Full scale low FL
Relay State in Alarm 3rd digit Code
Energised E
De-energised D
Note: On valve positioner version using a
Feedback pot. (FB in output 2) Alarm 2 must be
‘NONE’
Type Code
0-20mA 0mA20
4-20mA 4mA20
0-5V 0V5
1-5V 1V5
2-10V 2V10
Alarm 1 Retransmission Prefix to code
Process variable M
Setpoint S
Error E
Power W
Alarm 2 Remote input Prefix to code
Remote setpoint X
Remote trim T
Remote S/P with local trim L
Maximum output power W
Alarm channels can be used for analogue inputs/
outputs if not required for alarms
Note: Only one retransmission output and one
remote input is allowed within the controller
818S
Basic Comms Comms Display Display Dig Dig SoftwareProduct Input Output 1 Output 2 Alarm 1 Alarm 2 Type Funct. Option Curve Min Max Units Input 1 Input 2 Options
Display Min/Display Max
These should be selected from the recommended
minimum and maximum ranges shown in Curve.
Include decimal point position - This is especially
important on linear range
Input Coding
Curve - Select from the range shown
Linear type Min and max. ranges Recommended ranges Code
Iron constantan J -210C to 1200C 0C to 600C 01
Fe/Konst (DIN) L -200C to 900C 0C to 600C 02
Ni Cr/Ni Al K -270C to 1372C -250C to 1200C 03
Ci/Con T -270C to 400C -250C to 400C 04
Pt13%Rh/Pt R -50C to 1767C 0C to 1600C 05
Pt10%Rh/Pt S -50C to 1767C 0C to 1600C 06
Pt30%Rh/Pt6%Rh B 40C to 1820C 400C to 1820C 08
W/w26%Re -70C to 2000C 0C to 2000C 09
W5%Re/W26% 10C to 2320C 10C to 2300C 11
Ni Cr/Con E -270C to 1200C 0C to 780C 12
Pt10%Rh/Pt40%Rh 200C to 1800C 200C to 1800C 23
W5%Re/W26%Re C 0C to 2500C 0C to 2300C 24
Pt20%Rh/Pt40%Rh 0C to 2000C 0C to 1600C 25
Platinel 11 -100C to 1370C 0C to 1200C 28
W/W26%Re 0C to 2010C 0C to 2010C 29
Ni/Ni18%Molybednum 0C to 1100C 0C to 1100C 33
W3%Re/W25%Re D -30C to 2410C 0C to 2400C 35
W/Res5%W/Re26% 0C to 2000C 0C to 2000C 38
Nicrosil/Nisil N -270C to 1300C 0C to 1300C 45
Pt100 ohm at 0°C -200C to 850C -200C to 800C 70
Pyrometer (Q004 Land) 700C to 1550C 800C to 1550C 48
Pyrometer (Q003 Land) 600C to 1500C 700C to 1400C 51
Pyrometer RO 26 0C to 500C 100C to 500C 54
Pyrometer IVDI 1000C to 2500C 1000C to 2500C 61
Pyrometer DTI 750C to 2500C 1200C to 2500C 62
Pyrometer RO 23 700C to 1700C 800C to 1700C 64
Pyrometer FP/GP 10 450C to 900C 500C to 900C 82
Pyrometer FP/GP 11 600C to 1300C 700C to 1300C 83
Pyrometer FP/GP 12 750C to 1850C 1000C to 1850C 84
Pyrometer FP/GP 20 300C to 750C 400C to 750C 85
Pyrometer FP/GP 21 500C to 1100C 500C to 1100C 86
Linear -9999 to 19999 -9999 to 19999 00*
Square root -9999 to 19999 -9999 to 19999 92*
Units
NONE
°C
°F
K
MV
V
MA
%
(or specify up to 5 characters)
* For linear inputs sensitivity must not be less than
5µVs/digit
Digital Inputs
Dig I/P 1 Dig I/P 2
None NO NO
Auto manual AM AM
Local remote LR LR
Adaptive tune AT -
Keylock KL -
DIG I/P 1 up key* UK -
DIG I/P 2 down key* - DK
Parameter security PS -
Self tune - ST
SP 2/SP 1** S2 S2
PID 2/PID1 - P2
Ramp - RP
* These options must be selected together. If
selected no other input is possible
** Not available with remote trim
Software Options
Function Code
Manul key enabled E
Manual key disabled D
Cold junction Code
Non T/C input N
Internal compensation IN
External 0°C ref 0
External 45°C ref 45
External 50°C ref 50
Function Code
Integral and deriavative in secs S
Integral and derivative in mins M
Integral and derivative in secs with
dual PID SS
Integral and derivative in mins with
dual PID MM
Function Code
Power feedback P*
No power feedback N
* Not available on dc or VP outputs therefore
enter N
Part No. HA021479 Iss 7 Printed in England 0697
© Copyright Eurotherm Controls Limited 1990All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Controls Limited. Every effort hasbeen taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our products which could, without notice, result inamendments or omissions to this specification. We cannot accept responsibility for damage, injury loss or expenses resulting therefrom.
DIMENSIONAL DETAILS
9 mm max. thickness
Panel cut-out 92 x 92 +0.8 -0 mm
96 mm
96 m
m
12 mm * 201 mm Excluding Terminal Cover
* 219 mm Including Terminal Cover
Dimensions apply to both screw and faston versions of sleeve without the gasket fitted
* These dimensions will decrease by 1.5 mm when the gasket is fitted
EUROTHERM CONTROLS LIMITEDUK SALES OFFICEEurotherm Controls LimitedFaraday Close, DurringtonWorthingWest Sussex BN13 3PLTelephone Sales: (01903) 695888
Technical: (01903) 695777Service: (01903) 695444
Fax (01903) 695666
Sales and support in over 30 countries worldwideFor countries not listed enquiries/orders to:Eurotherm Controls LimitedExport Dept., Faraday Close, Durrington, Worthing West Sussex, BN13 3PL Telephone (01903) 268500Fax (01903) 265982Telex 87114 EUROWG G