European Passive House In the California
context
Presented by Nabih Tahan, aia
Cree USA
January 18, 2012
Summary of Presentation
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
• Introduction • My perspective on Passive House- Europe and the USA • They are only rating / certification system – PH and LEED • How does PH work? Grant Street as quick example
• Obstacles and lessons learned • Recent PH related developments in Europe?
• Life Cycle Assessment – The big picture • Integrated “Systems Approach”
Experience in Austria – Low Energy Buildings
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Developed 2 Condominium Projects in Feistritz/Drau
-1st Project : Transformed barn into 15 units
-2nd Project: 13 new units
-Both project with prefabricated “OPEN” wall panels in “low energy” standard
Existing Barn
Original barn in front - New building behind
Low Energy Standard – • below 30 kWh / ft² / yr heating energy • well insulated, • air barrier, but not so air-tight, • no HRV • Construction was most impressive – pre fabricated to
precision
Lessons from Europe / Austria – Passive House
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
• Rigid, but effective education system • Building physics is part of the architectural education • Trade schools and guilds train construction workers from the basic
fundamentals to the master level
• Progression from standard house, to low energy house to
passive house, to carbon footprint.
• Recycling began after war - out of necessity
• Energy prices are high – lack of
fossil fuels, but rich in forests
St. Stephen’s Cathedral, Vienna Destroyed, but rebuilt after war
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
• Won the war
• Mobile Society • Always moving, looking for jobs, schools, opportunities • Why spend money on the building?
• Cheap Energy From Fossil Fuels • Build economical and fast and blast hot air or cold air to stay comfortable
• Government Subsidies – not based on efficiency • Tax deductions on mortgage interest and property taxes • Encouraged faster buying, selling and building
• Building Science • Not part of architectural education • Minimum training for construction workforce
USA - Last 50 years – Leads to LEED
COMPARISON OF PASSIVE HOUSE AND LEED
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
• PASSIVE HOUSE • Performance - Only energy consumption counts (in Kwh/ft²/year)
• On site energy - for heating and cooling (1.4 in Kwh / ft² / year)
• Source Energy – heating / cooling/ hot water, appliances, lighting – at the source. (11.3 in Kwh / ft² / year)
• Credit for solar thermal but not for PV
• LEED • Prescriptive – Only Points count
• Deals with more issues such as site, water use, materials, recycling, etc. • Do many points guarantee better performance?
• CURRENT TRENDS • In Europe – Tendency towards Life Cycle Assessment and carbon footprint
• In USA – Tendency toward energy performance and Zero Net Energy
Requirements of a Passive House
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
1. Annual Heating Requirements:
15 kWh/(m²a) = 1.4 kWh/ft²/yr or 4755 Btu/ft²/yr
2. Combined Source Energy:
Source energy is energy consumed on site (such as
heat, hot water, electricity), plus energy consumed in
the generation and transportation involved in supplying
energy to the site.
120 kWh/(m²a)= 11.2 kWh/ft²/yr or 38039 Btu/ft²/yr
3. Building Envelope Air-Tightness:
Air leakage through unsealed joints must be less than
0.6 the house volume per hour, at 50 pascal, measured
by a blower door test
Experiment in Berkeley – Grant Street
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Front Elevation Back Yard Back elevation
Back elevation Existing basement, only 7 foot high
Grant St. – P H Decisions - Obstacles
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
ZONING: • R-2 Allows 2 units • Need 2 parking spaces • Potential for 2nd unit • Make easy PH and
keep back yard land locked? Or
• Cantilever upstairs, add costs and thermal bridging issues?
EXISTING
NEW
Grant Street – PH decision - Obstacles
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
SOUTH FACING WINDOWS - Original submission accepted: Keep south
windows, upgrade wall - As response to revision for garage, forced
to remove 2 existing south facing windows. - Tried to keep windows but also upgrade
wall - Insulation and air-tightness from inside
Grant Street – PH decisions - Obstacles
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
DETAILING • Complicated
assemblies
As Built– 1st floor plan
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Front bedroom was originally submitted as garage. Plans were then revised to turn into bedroom
As Built– 2nd floor plan
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Grant Street – Lifting House and Cantilever
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
From a Passive House perspective, it would have been easier to meet the standard without the cantilever, and money could have invested in Passive House windows, more sophisticated heating system, etc. But, what about the potential for a 2nd unit as urban infill
Grant Street – Insulation against the ground
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
INSULATION BELOW SLAB
INSULATION OUTSIDE FOOTINGS
FLOOR BUILD UP ABOVE SLAB WITH
2 LAYERS OF 1 ½” RIGID INSULATION – R 19.6
Grant Street –Structural details - Framing
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Difficulties encountered by canteliver • No insulation under footings • Thermal bridging through
posts and beams, could have wrapped beams, but wanted to expose heavy timber
• Difficult to insulate around steel posts, not enough room.
Grant Street - Insulation
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
FILTER FABRIC STAPLED AND GLUED TO
STUDS
BLOWN IN, DRY, CELLULOSE
INSULATION
Grant Street – Air-tightness
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
- Sealing plywood from exterior
- Expandable foam at opening
SEAL BETWEEN MUDSILL AND SLAB SEAL ALL PLYWOOD JOINTS AND INTERSECTIONS
SEAL AND FOAM JOINTS AND
INTERSECTIONS
Grant Street - ventilation
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Grant Street - Heating
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Peak Heating Load: Title 24 – 20,000 btus Passive House - 5000 btu’s
12” water to air heating or cooling coil
Grant Street - Rainscreen
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
• Rainscreen, but no exterior insulation under cantilever,
Review obstacles to reaching PH standard
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Either cantilever, or no 2nd unit Insulate around steel posts Insulation and air-tightness Difficulties due to existing construction
No South facing windows – too close to property line
Code Regulations • Parking Requirements • No windows – property lines Construction difficulties • Existing conditions Where to spend the money – what are the trade offs? • What is most critical, energy use of house, energy
use of site or total impact on the environment? How do these decisions affect the Passive House Standard and PHPP?
Grant Street – Energy Consumption
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Grant Street – Lessons Learned
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
What is the future – What are Europeans doing now?
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
• PLAYERS • Clients / homeowners • Energy Consultants • Builders • Architect • Engineer
• Systems Approach • Prefabrication • New Buildings • Retrofits
• Life Cycle Assessment
• Impact of the entire building on the environment • New technologies, but not only through spread sheets, but also
through design, construction, product manufacturing, job creation
What can we adapt now, so we don’t wait 5 to 10 years to catch up?
LIFE CYCLE OF BUILDINGS AND PRODUCTS
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
MATERIAL SELECTION
MANUFACTURE
ON-SITE
OFF-SITE CONSTRUCTION
OCCUPANCY
MAINTENANCE DEMOLITION
RECYCLE / REUSE
DISPOSAL
Big Picture – Forestry Carbon Cycle - Life Cycle Assessment
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Passive House is a concept that can improve the performance of all buildings.
AB32
EXISTING HOMES
25% of existing homes must decrease their purchased energy by 70% from 2008 levels 75% of existing homes must decrease their purchased energy by 30% from 2008 levels 100% of existing multi-family homes have a 40% decrease in purchased energy from 2008 levels
2006 – California Global Warming Solution Act sets an economy-wide cap on California greenhouse gas emissions
1
3
2
4
TAKE WORST FIRST
Finger jointed framing lumber
Cross Laminated Timber
Glue laminated timber
Structural members
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
Manufacturing – Engineered, High Performance Timber Products
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
TRADITIONAL METHOD
DESIGN – BID - BUILD INTEGRATED DESIGN PROCESS
Methods of Delivering Buildings
“Systems Approach” - New - Prefabrication
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
“System Approach” - Retrofit - Prefabrication
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
“System Approach” - Retrofit - Prefabrication
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
“Systems Approach” - Cree - Life Cycle Tower
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
A 20 story building needs approx. 5.000 m3 of glulam beams. Net annual growth on timberland in the United States is estimated at 755,490,565 cubic meters. 2,069,837 cubic meters per day 86, 243 cubic meters per hour 1,437 cubic meters per minute So, it would take about 3.5 minutes of growth to replace 5,000 cubic meters
“Systems Approach” - Cree - Life Cycle Tower
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com © Copyright 2011
NorCal ADPSR
Cree 2440 Grant St. Berkeley, Ca. 94703- P: 510-848-2514 F: 510-684-0978 - www.creebyrhomberg.com ©
Copyright 2011
European Passive House In the California
context
Presented by Nabih Tahan, aia
Cree USA
January 18, 2012
The Natural Change in Urban Architecture
Nabih Tahan, AIA
2440 Grant St. Berkeley, Ca. 94703
Tel: 510-848-2514 510-684-0978 cell
Email: [email protected]
www.creebyrhomberg.com