Line Tra ps
-
7/26/2019 E_T_Line Traps
2/12
2
Ba sic Functio n o f Line Tra ps
Pow er Line C arrier (PLC ) is acom m on m ethod of Pow er SystemC om m unication, such as telepro-tection, voice and data com m uni-cation, etc. It has developed the
reputation of being one of them ost econom ical and reliable form sof com m unication and versatile inits application. Fig.2 show s a basicPLC system consisting of threedistinct com ponents:
signal carrying m edium (H Vtransm ission line)
com m unication apparatus(transm itters, receivers andassociated com ponents)
coupling/blocking equipm entsuch as coupling capacitors, linetuners (coupling devices) andLine Traps.
Line Traps are connected in seriesw ith H V transm ission lines. Them ain function of the Line Trap is topresent a high im pedance at thecarrier frequency band w hileintroducing negligible im pedanceat the pow er frequency. The high
im pedance lim its the attenuationof the carrier signal w ithin thepow er system by preventing thecarrier signal from being:
dissipated in the substation
grounded in the event of a faultoutside the carrier transm issionpath
dissipated in a tap line or abranch of the m ain transm issionpath.
Line Tra ps
Introduction
W ith over 40 years of successfulfield experience Trench is therecognized w orld leader in thedesign and m anufacture of air-core dry-type inductors for electric
utility applications. The uniquecustom design approach, alongw ith fully integrated engineeringand m anufacturing facilities inboth N orth A m erica and Europehave enabled Trench to becom ethe technical leader for highvoltage inductors w orld w ide.
Line Traps for Pow er Line C arrier(PLC) com m unication system srepresent a significant application
segm ent for high voltageinductors.
Fig. 1
Post moun ted
Lin e Traps
-
7/26/2019 E_T_Line Traps
3/12
3
Desig n a nd Construction
Line Traps are designed to m eetA N SI standard C 93.3, IEC stan-dard 353 or other internationalstandards.
The m ajor com ponents of a LineTrap are the m ain coil, tuningdevice and protective device(see Fig. 3).
Fig. 4
Suspension mounted
Line Traps
Fig. 2
Prin ciple scheme of a
PLC system
Tun ing
Device
Term ina l
Main
Coil
Pedes ta l
(Optional)
Lightning
Arrester
Bird Ba rrier (Optio na l)
Since Line Traps are series connec-ted w ith the H V transm ission line,they m ust be designed to w ith-stand the high m echanical forcesgenerated by the short circuit (s/c)current associated w ith the H Vtransm ission system .
Fig. 3
Line Trap
components
1 C oupling Capacitor 2 Line Tuner 3 Transm itter/Receiver
Line Trap Line Trap
Station A Station B
-
7/26/2019 E_T_Line Traps
4/12
4
Ma in Co il
The m ain coil of a Line Trap is anair-core dry-type pow er inductor.
Trench offers Line Traps w ith eitherof tw o w ell established w inding
technologies:
Encapsulated design (E-design)
O pen style design (O -design).
Both technologies fully com plyw ith pow er system and PLCrequirem ents and are thereforeapplied over the full range of com -m only specified m ain coil ratings.H ow ever, in the upper lim its ofinductance and current ratings the
encapsulated design is thepreferred concept (see Fig.5).
The w inding of the encapsulateddesign utilizes alum inum w ire orcable, w hereas the open stylew inding em ploys alum inum flat-bar conductor. A ll pow er currentcarrying com ponents utilizew elded connections.
H igh m echanical strength of thew inding is either achieved by resinim pregnated, fiberglass reinforcedencapsulation (E-design) or byfiberglass spacers w hich are resin
bonded betw een turns (O -design).
The w inding is term inated at bothends on a system of alum inumbars, denoted as the spiders w hichare tensioned together by fiber-glass ties (E-design) or fiberglassrods (O -design). These spiders areadditionally used for
the electrical connection to theLine Trap by term inal pads orstuds
providing the hardw are forlifting (lugs), m ounting (pede-stals) and corona protection (bells,rings)
connecting the tuning andprotective device across them ain coil.
Trench can provide the com pleterange of standard ratings(inductance, continuous and s/c
current ratings, system voltage) inaccordance w ith IEC 353 or A N SIC 93.3 standards (see Fig.5).C ustom ized units are also availableto m eet specific custom er require-m ents, such as specific inductance,current (s/c or continuous), lowloss requirem ents, etc.
a
-
7/26/2019 E_T_Line Traps
5/12
Ra ted Current s Ra ted Induct a nce
IEC 353 IEC 353
C ontinuous Short-tim eA Series 1 m H at 100 kH z
kA /1sec
100 2,5 0,2 0,25 0,315 0,4 0,5 1,0 2,0
200 5 0,2 0,25 0,315 0,4 0,5 1,0 2,0
400 10 0,2 0,25 0,315 0,4 0,5 1,0 2,0
630 16 0,2 0,25 0,315 0,4 0,5 1,0 2,0
800 20 0,2 0,25 0,315 0,4 0,5 1,0 2,0
1000 25 0,2 0,25 0,315 0,4 0,5 1,0 2,01250 31,5 0,2 0,25 0,315 0,4 0,5 1,0 2,0
1600 40 0,2 0,25 0,315 0,4 0,5 1,0 2,0
2000 40 0,2 0,25 0,315 0,4 0,5 1,0 2,0
2500 40 0,2 0,25 0,315 0,4 0,5 1,0 2,0
3150 40 0,2 0,25 0,315 0,4 0,5 1,0 2,0
4000 63 0,2 0,25 0,315 0,4 0,5 1,0 2,0
C ontinuous Short-tim eA Series 2 m H at 100 kH z
kA /1sec
100 5 0,2 0,25 0,315 0,4 0,5 1,0 2,0
200 10 0,2 0,25 0,315 0,4 0,5 1,0 2,0
400 16 0,2 0,25 0,315 0,4 0,5 1,0 2,0
630 20 0,2 0,25 0,315 0,4 0,5 1,0 2,0
800 25 0,2 0,25 0,315 0,4 0,5 1,0 2,0
1000 31,5 0,2 0,25 0,315 0,4 0,5 1,0 2,0
1250 40 0,2 0,25 0,315 0,4 0,5 1,0 2,0
1600 50 0,2 0,25 0,315 0,4 0,5 1,0 2,0
2000 50 0,2 0,25 0,315 0,4 0,5 1,0 2,0
2500 50 0,2 0,25 0,315 0,4 0,5 1,0 2,0
3150 50 0,2 0,25 0,315 0,4 0,5 1,0 2,0
4000 80 0,2 0,25 0,315 0,4 0,5 1,0 2,0
Ra ted Current s Ra ted Induct a nceANSI C93.3 ANSI C93.3
C ontinuous Short-tim e
A kA /2secm H at 100 kH z
400 15 0,265 0,53 1,06 1,59 2,12 2,65
800 20 0,265 0,53 1,06 1,59 2,12 2,65
1200 36 0,265 0,53 1,06 1,59 2,12 2,65
1600 44 0,265 0,53 1,06 1,59 2,12 2,65
2000 63 0,265 0,53 1,06 1,59 2,12 2,65
3000 63 0,265 0,53 1,06 1,59 2,12 2,65
4000 80 0,265 0,53 1,06 1,59 2,12 2,65
5
N ote:
A ll ratings availablew ith E-design
Shaded ratings notavailable w ith O -design
Fig. 5
Values of contin uou s
curr ent, short time curr ent
and i nductance
-
7/26/2019 E_T_Line Traps
6/12
6
Tun ing De vice
The tuning device, connectedacross the m ain coil, form s ablocking circuit w hich provideshigh im pedance over a specifiedPLC -frequency range.
D epending on the type of tuning(see below ) the tuning deviceconsists of capacitors, inductorsand resistors, all having relativelylow pow er ratings, com pared tothe m ain coil. For environm entalprotection these com ponents arem ounted in one or m ore fiberglasshousings. The tuning device isinstalled inside the m ain coil.To m eet changing PLC frequencyrequirem ents the tuning device iseasily accessible for replacem entor field adjustm ent (if applicable).
The bandw idth of a Line Trap isthat frequency range over w hichthe Line Trap provides a certainspecified m inim um blocking im pe-dance or resistance. M inim umblocking resistance should bespecified if the potential exists forthe reactive com ponent of theLine Trap im pedance to resonatew ith the substation im pedance.
The achievable bandw idth can beexpanded by increasing the m aincoil inductance.D ifferent types of tuning m ay beexpanded by increasing the m aincoil inductance.
D ifferent types of tuning m ay besupplied.
Single Frequency Tuning
If narrow blocking bands arerequired single frequency tuning isthe sim plest and m ost econom icaltype of tuning available. Fig.6show s a typical schem atic andblocking characteristic. W ithin thisnarrow band, how ever, highblocking im pedance can be provi-ded, resulting in excellent PLCsignal isolation.
D ouble Frequency Tuning
The double frequency tuningarrangem ent blocks tw o relativelynarrow bands of frequencies.O therw ise, the blocking characte-ristic is sim ilar to single frequencytuning.
For proper operation and isolationof the tuned bands a m inim umfrequency separation m ust bem aintained betw een the peaktuning frequencies. This is 25 kH z
or 25 % of the upper tuningfrequency peak, w hichever isgreater. Fig.7 show s a typicaldouble frequency schem atic andblocking characteristic.
Fig.6
Sin gle frequency tun in g
Fig.7
Double frequency tun in g
Fig.8
Wideband tunin g
b
Z Blocking im pedance
R Resistive com ponent
f C arrier frequencyf m Resonant frequency
(G eom etric M ean Frequency
G M F)
f 1 f 2 Frequency lim its of
blocking im pedance
f 1 f 2 Frequency lim its of
resistive blocking im pedance
-
7/26/2019 E_T_Line Traps
7/12
7
Fig.10
Selftun ed Lin e Trap
blocking characteristics
W ideband Tuning
W ideband tuning is the m ostcom m on type of tuning as itefficiently utilizes the m ain coilinductance. W ideband tuned LineTraps are suitable for m ulti-chan-
nel applications, since relativelyconstant im pedance is obtainedover a broad frequency range. Thistype of tuning provides high band-w idth flexibility for future changesor expansion of PLC frequencies.PLC channels can be placedanyw here w ithin the blockedbandw idth.Fig.8 show s a typical w idebandfrequency Line Trap schem atic andblocking characteristic.
Selftuned Line Traps
Selftuned Line Traps do not requirethe use of tuning devices. Theblocking characteristic as show n inFig.10 is achieved by sim ply utili-zing the self-capacitance of the
m ain coil w inding. The inductanceof a selftuned Line Trap is higherthan that of a tuned Line Trap.
Fig. 9
Suspension mounted 380 kV,
1.0 mH, 2100 A Line Trap
-
7/26/2019 E_T_Line Traps
8/12
8
Prot ective Device
The protective device is a surgearrester connected in parallel w iththe m ain coil and the tuningdevice. It protects the m ain coiland the tuning device by reducing
the transient overvoltages to levelscorresponding to distributionvoltage class insulation.
The insulation level of the m aincoil and tuning device is coordinatedw ith the surge arrester protectivecharacteristics.
Trench Line Traps are equippedw ith advanced m etal-oxide typesurge arresters having a discharge
current rating of 10kA . Surgearresters w ith higher dischargecurrent or high energy dissipationarrangem ents are also available onspecific request.
Mount ing a nd Connection
Trench Line Traps can be m ountedin several configurations. Suspen-sion m ounted Line Traps areavailable w ith either single pointorm ulti-point suspension brackets.Line Traps can also be pedestalm ounted directly onto couplingcapacitors (CCs), capacitive voltagetransform ers (C VTs) or station postinsulators. Trench offers severaltypes of m ounting pedestals:
single insulator support pedestal
m ulti-insulator support pedestal
insulated pedestal
O ther than the insulated pedestal,all pedestals are electricallyconnected to the low er term inalof the Line Trap, and as such canbe used as both the electrical and
m echanical connection to the C Cor C VT (see Fig.11a). Should it benecessary to utilize the upper LineTrap term inal as the connection tothe C C or C VT, a pedestal insulatedfrom the bottom end (bottomspider) of the Line Trap m ust beused in conjunction w ith a specialinsulated connection rod suppliedby Trench (see Fig.11b).A ll pedestals can be custom m adeto suit custom er requirem ents.
Term inals supplied on the Line Trapscan be either pad or stud type.Each type is m anufactured tom eet the applicable IEC or N EM Astandards.In addition, term inals can belocated on virtu ally any spider arm, ensu-
rin g total flexibi lity to meet ind ividu al re-
quir ements. Term in al details and term i-
nal ori entati on ar e shown in Fig.12 and
Fig.13.
c
Fig. 11a Fig. 11b
Station
Station
Line
Line
C ouplingC apacitor
C ouplingC apacitor
Line Trap conn ection
-
7/26/2019 E_T_Line Traps
9/12
9
Fig.12
Fig. 12Term inal orientation(by special request m ay be situatedat any spider arm location.N um ber of spider arm s is obtainedfrom actual quotation draw ing,
typically 4, 6 or 8)Et: is used to define the topterm inal location, at centre or atany of the spiders.Eb: is used to define the bottomterm inal location; at centre or atany of the spider arm s.
Fig. 13Standard term inal types plated orbare alum inum
N ote:U nless otherw ise specified, flatterm inal pads w ill be verticallyoriented to reduce eddy currentheating. (ie. term inals oriented sothat the coils axis is in the planeof the term inal.)
Fig.13
Top view
-
7/26/2019 E_T_Line Traps
10/12
10
C alculation of tapping loss (A t)
and blocking attenuation (A b)
Z1 = C haracteristic im pedance of
the line
The im pedance of substation Zsis
assum ed to be 0 O hm s.
Center Frequency (fc)
fc is the m ean frequency of
the blocked bandw idth lim itfrequencies (f1, f2).
Definiton of Blocking
Term s
The blocking requirem ent of aLine Trap is dependent on thecharacteristic im pedance of the
transm ission line w here Pow erLine C arrier is to be applied. TheLine Trap blocking requirem ents
can be specified in term s of:
Blocking Im pedance (Zb):
Zb is the com plex im pedance of
the com plete Line Trap w ithin aspecified PLC frequency range.
Blocking Resistance (Rb):
R
b
is the value of the resistive
com ponent of the blockingim pedance, w ithin a specifiedPLC frequency range.
Tapping Loss (A t)
A t, also know n as Insertion
Loss, is a m easure of the lossof pow er sustained by a carrierfrequency signal due to thefinite blocking ability of the LineTrap. The tapping loss of an
ideal Line Trap should be verylow and approach zero.
Blocking A ttenuation (A b)
A b is a m easure of the relative
transm itted carrier frequencysignal w hich enters the trappedcircuit section of netw ork. Theblocking attenuation of an idealLine Trap should be infinitelyhigh.
Equ.I A t (dB) = 20 log 10 (1+ ___)Z12Zb
Equ.II A b (dB) = 20 log 10 (1+ ___)Zb
Z1
fc=f1xf2
-
7/26/2019 E_T_Line Traps
11/12
11
1,0 m H Line Tra p
0,315 m H Line Tra p0,2 m H Line Tra p
0,5 m H Line Tra p
-
7/26/2019 E_T_Line Traps
12/12
Trench A ustria G m bHPaschinger Strasse 49, Postfach 13A -4060 Linz-Leonding/A ustriaPhone +43.732.6793-0Fax +43.732.671341E-M ail sales@ TrenchA ustria.at
Trench Brasil LTD AVia Expressa de C ontagem , 2685C EP 32370-485
C ontagem , M G - BrasilPhone 55. 31. 391-5959Fax 55. 31. 391-1828E-M ailtrenchbrasil@ ca.trenchgroup.com
Trench Lim itedC oil Product D ivision71 M aybrook D rive, ScarboroughO ntario, C anada M 1V 4B6Phone (416) 298-8108Fax (416) 298-2209E-M ail sales@ ca.trenchgroup.com
Trench Lim ited
Instrum ent Transform er D ivision390 M idw est Road, ScarboroughO ntario, C anada M 1P 3B5Phone (416) 751-8570Fax (416) 751-6952E-M ail sales@ ca.trenchgroup.com
Trench France S.A .16, rue du G nral C assagnouB.P. 70F-68302 St-Louis C edex/FrancePhone +33.3.89 70 23 23Fax +33.3.89 67 26 63E-M ail sales@ trench-france.com
Trench G erm any G m bHN rnberger Strasse 19996050 Bam berg/G erm anyPhone +49.951.1803-0Fax +49.951.1803-224E-M ail sales@ trench.de
Trench Sw itzerland A GLehenm attstrasse 353C H -4028 Basel/Sw itzerlandPhone +41.61.315 51 11Fax +41.61.315 59 00E-M ail sales@ trench.ch
www.trenchgroup.com
Sub ject to change w ithout no tice04.2000
E 231