establishing primary airflow in wbcs systemstorontoashrae.com/resources/documents/ashrae chilled...

48
Establishing Primary Airflow in WBCS Systems Establishing Primary Airflow in WBCS Systems

Upload: others

Post on 18-Apr-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Establishing Primary Airflow in WBCS

Systems

Establishing Primary Airflow in WBCS

Systems

Page 2: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Chilled Beam Design Principles

How is capacity measured?

•Tested & reported as an assembly

•Is not simply a sum of component capacity

•ASHRAE Standard 200

How is capacity certified?

AHRI Standard 1240/1241 certification program

More information:

Page 3: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

3

Chilled Beam Design Principles

Page 4: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Agenda

• WBCS Concept

• Occupant Comfort

• Establishing Primary Airflow Rate

• Energy Impact

• Demand Control Ventilation

• WBCS Concept

• Occupant Comfort

• Establishing Primary Airflow Rate

• Energy Impact

• Demand Control Ventilation

4 2015-12-15 Establishing Primary Airflow

Page 5: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Focusing on what our customers care about

5 2015-12-15 Establishing Primary Airflow

o Comfort vs. Capacity

o System Design vs. Product Features

VS.

Page 6: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Water Borne Climate System Concept

6 2015-12-15

Page 7: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Transportation Costs

7 2015-12-15 Company Presentation

Air

10” duct

Capacity 9900 Btuh

(20 ft/s Δt 14°F)

Water

3/4” pipe

Capacity 9900 Btuh

(110 ft/m Δt 7°F)

Page 8: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

8

Treated fresh air

Cooling CoilNozzles

Inducedwarm room air

Supply air

Operates through induction

How a chilled beam works

Page 9: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

WBCS Basics

9

Page 10: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Comfort Modules & Chilled Beams

1-Way 2-Way 4-Way

1-W

ay

1-W

ay

Page 11: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Chilled Beams and Occupant Comfort

11 2015-12-15

Page 12: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Heating/Cooling Capacity & Air Distribution

• A chilled beam is a combination energy source

and air distribution system so the selection is

doubly important.

• The space air distribution is equally important

to capacity in determining the comfort level.

Poor air distribution will result in poor comfort

no matter how much capacity is available.

• A chilled beam is a combination energy source

and air distribution system so the selection is

doubly important.

• The space air distribution is equally important

to capacity in determining the comfort level.

Poor air distribution will result in poor comfort

no matter how much capacity is available.

Page 13: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Chilled Beam – Energy source + air diffuser

Page 14: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

14

Controllable by

chilled beam

Metabolic rate x

Clothing insulation x

Air temperature �

Radiant temperature x

Air speed �

Air direction / throw �

Humidity x

User adjustability �

ASHRAE Standard 55 Comfort Considerations

Page 15: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Air Distribution

Mixed SystemsMixed Systems

• All the air in the space is

mixed to same the same

temperature

• Overhead mixed air

systems use Coanda

effect

• Most beams are based

on mixed air approach

(overhead)

• All the air in the space is

mixed to same the same

temperature

• Overhead mixed air

systems use Coanda

effect

• Most beams are based

on mixed air approach

(overhead)

Displacement SystemsDisplacement Systems

• Air is introduced at floor

level at very low velocities

• Space is deliberately

stratified

• Only the occupant zone is

conditioned

• Air is introduced at floor

level at very low velocities

• Space is deliberately

stratified

• Only the occupant zone is

conditioned

15 2015-12-15 Company Presentation

Page 16: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

16

Coanda effect

2015-12-15

Thanks to the negative pressure, the air follows the ceiling instead of falling straight down when it leaves the module

When the air reaches the occupied zone, it has attained a temperature and speed that reduces the risk of draft

Page 17: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

17

Induction and Coanda Effect

Page 18: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Creating Coanda Effect

18

Diffuser nozzle design

• Beams have built in “Diffuser” technology

• Beam selection and placement to ensure comfort is

an important as when selecting diffusers

• “One big beam in a space may meet cooling load but

may not deliver the comfort that two smaller beams

would deliver”

Page 19: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Airflow Pattern

19 2015-12-15 Company Presentation

• Beams can offer wide range of airflow patterns to

suit space

Page 20: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

202015-12-15 Indoor Climate Systems - Water based or Air?

2-way discharge strategy • Uses only small area of the ceiling• Air volume distributed into narrow region

4-way discharge strategy• Maximizes use of available ceiling area• Air volume distributed diffusely, more slowly• Flexible discharge patterns / field adjustable

Beam Selection For Comfort

Page 21: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

WBCS Primary Airflow Analysis

21 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 22: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Compare Office Vs. School

2015-12-15 Company Presentation 22

Page 23: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Cooling Load Summary

23 2015-12-15 Company Presentation

Sensible Load Latent Load Total Load SHR

Btu/h Btu/h-ft² Btu/h Btu/h-ft² Btu/h Btu/h-ft²

Classroom 24756 24.8 7795 7.8 32551 32.6 0.76

Office 23116 23.1 2573 2.6 25688 25.7 0.9

Page 24: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Cooling Load Calculations

• Loads same regardless of HVAC system

• Fancoil, WSHP, GSHP and VRF need zone latent and sensible loads separate from outdoor air load

• WBCS need zone sensible load separate from zone latent load and outdoor air latent and sensible load

• Loads same regardless of HVAC system

• Fancoil, WSHP, GSHP and VRF need zone latent and sensible loads separate from outdoor air load

• WBCS need zone sensible load separate from zone latent load and outdoor air latent and sensible load

24 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 25: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

WBCS Primary Airflow Design

• The primary airflow rate must be the larger of;

• The air flow rate to meet the ventilation rate required

to deliver acceptable indoor air quality.

• The airflow rate to provide latent cooling in the zone.

• The airflow rate required to assist in meeting the zone

sensible cooling rate.

• The primary airflow rate must be the larger of;

• The air flow rate to meet the ventilation rate required

to deliver acceptable indoor air quality.

• The airflow rate to provide latent cooling in the zone.

• The airflow rate required to assist in meeting the zone

sensible cooling rate.

25 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 26: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Ventilation Rate

• Office

• Ventilation rate = 10 x 5 cfm

+ 0.06 x 1000 ft² = 110 cfm

• = 0.11 cfm/ft²

• Classroom

• Ventilation rate = 30 x 10 cfm

+ 0.12 x 1000 ft² = 423 cfm

• = 0.42 cfm/ft²

• Office

• Ventilation rate = 10 x 5 cfm

+ 0.06 x 1000 ft² = 110 cfm

• = 0.11 cfm/ft²

• Classroom

• Ventilation rate = 30 x 10 cfm

+ 0.12 x 1000 ft² = 423 cfm

• = 0.42 cfm/ft²

26 2015-12-15 Company Presentation

Page 27: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Latent Rate

27 2015-12-15 Company Presentation

75 °F DB

50% RH

64.6 gr/lb HR

Qp = Platent/(0.68 x (Wr - Wprimary air))

Page 28: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Sensible Rate

28 2015-12-15 Company Presentation

75 °F DB

50% RH

64.6 gr/lb HR

Qp = Psensible /(1.085 x ((Tr – Tp) + IR x (Tr – Ta))

Page 29: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Primary Airflow Summary

• Can’t go below ventilation rate

• Latent load usually dominates

• Offices 0.4 to 0.6 cfm/ft², 53 °F off coil

• Classroom 0.6 to 0.8 cfm/ft², 49 °F off coil (reheat required)

• Can’t go below ventilation rate

• Latent load usually dominates

• Offices 0.4 to 0.6 cfm/ft², 53 °F off coil

• Classroom 0.6 to 0.8 cfm/ft², 49 °F off coil (reheat required)

Ventilation Rate Latent Rate Sensible Rate

Btu/h cfm/ft² Btu/h cfm/ft² Btu/h cfm/ft²

Classroom 423 0.43 740 0.75 761 0.76

Office 110 0.11 461 0.46 333 0.33

2912/15/2015Intro to ComVent - Establish loads and

Primary Airflow

Page 30: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Primary Airflow Summary

• The zone sensible cooling load should be between 20 to 40 Btu/h·ft².

• The primary airflow will be most likely set by the zone latent load. A good range is 0.4 to 0.6 cfm/ft².

• A good office system has 1/3 of the load met by the primary air and 2/3 of the load met by the chilled beam coil.

• Assume an induction ratio between 2.5 to 3.5. Start with 3.

• The zone sensible cooling load should be between 20 to 40 Btu/h·ft².

• The primary airflow will be most likely set by the zone latent load. A good range is 0.4 to 0.6 cfm/ft².

• A good office system has 1/3 of the load met by the primary air and 2/3 of the load met by the chilled beam coil.

• Assume an induction ratio between 2.5 to 3.5. Start with 3.

30 2015-12-15 Company Presentation

Page 31: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Primary Airflow Summary

• The chilled water supply temperature should

be 2-3 °F above space dew point. 57 °F is a

common supply water temperature.

• The chilled water temperature range will be 4

to 6 °F. Consider putting the primary air

system in series with the chilled beams.

• The chilled water supply temperature should

be 2-3 °F above space dew point. 57 °F is a

common supply water temperature.

• The chilled water temperature range will be 4

to 6 °F. Consider putting the primary air

system in series with the chilled beams.

31 2015-12-15 Company Presentation

Page 32: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

WBCS Energy Considerations

32 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 33: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Design vs. Annual Energy Usage

33 2015-12-15 Company Presentation

Fans

25%

Chiller

56%

Pumps

14%

Tower

5%

Design Day

Fans

44%

Chiller

32%

Pumps

21%

Tower

3%

Annual

Page 34: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Annual Cooling Load Profile

34 2015-12-15 Company Presentation

0

50

100

150

200

250

300

350

400

450

500

5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100

Ho

urs

Percent Cooling Load

Page 35: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Standard DOAS Unit

35 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 36: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Primary Airflow vs. Delta Humidity Ratio

12/15/2015 36

• All points of curve deliver same amount latent cooling to space

Platent = 0.68*Qp* (Wr – Wprimary air )

0

10

20

30

40

50

60

70

80

90

100

3.8 6.1 8.3 10.5 12.6 14.6 16.5

Pri

ma

ry A

irfl

ow

(cf

m)

Delta Humidity Ratio (gr/lb)

Page 37: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Cooling Capacity of Primary Airflow

37 12/15/2015

0

10

20

30

40

50

60

70

80

90

100

2062 1352 1043 864 753 678 625

Pri

ma

ry A

irfl

ow

(cf

m)

Primary Air Sensible Capacity (Btu/h)

• Primary cooling capacity drops off as airflow is reduced

• Shifts load to beam

Page 38: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Primary Airflow vs. Induction Ratio

38 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

0

10

20

30

40

50

60

70

80

90

100

1.1 2.8 4.4 5.9 7.4 8.9 10.2

Pri

am

ry A

irfl

ow

(cf

m)

Induction Ratio

• Higher beam load requires higher induction rate

• APD and noise become issue

Page 39: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

DOAS Energy Model Design Parameters

Off Coil DB SA DB SA HR Delta HR SA Airflow

F F gr/lb gr/lb cfm

55 56 62.6 3.8 100

54 55 60.3 6.1 62

53 54 58.1 8.3 46

52 53 55.9 10.5 36

51 52 53.8 12.6 30

50 51 51.8 14.6 26

49 50 49.9 16.5 23

39 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 40: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Annual Energy Usage Std DOAS Unit

40 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

0.0

100.0

200.0

300.0

400.0

500.0

600.0

700.0

100 62 46 36 30 26 23

An

nu

al E

ne

rgy

Usa

ge

(kW

h)

Primary Airflow (cfm)Rotor BIN Watts kWh SA Fan BIN Watts kWh

Chiller Plant BIN Watts kWh HW Plant BIN Watts kWh

RA Fan BIN Watts kWh

Page 41: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Energy Analysis Summary

• Fan work is dominant

• Generally shifting sensible load to beams from primary

is more efficient

• Practical limitation on induction ratio (5) and primary

air temperature (53 °)

• Reheat increases operating cost – only do it if you

have to (schools)

• Fan work is dominant

• Generally shifting sensible load to beams from primary

is more efficient

• Practical limitation on induction ratio (5) and primary

air temperature (53 °)

• Reheat increases operating cost – only do it if you

have to (schools)

41 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 42: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Demand Control Ventilation

Page 43: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Demand Control Ventilation

• Classrooms occupied 35%

• Offices occupied 22-38%

• ASHRAE Std 90.1

• 500 ft²

• 25 people per 1000 ft²

• greater than 3000 cfm

• ASHRAE Std 62

• Minimum airflow ≥ building load

component (Ra x Az)

• Classrooms occupied 35%

• Offices occupied 22-38%

• ASHRAE Std 90.1

• 500 ft²

• 25 people per 1000 ft²

• greater than 3000 cfm

• ASHRAE Std 62

• Minimum airflow ≥ building load

component (Ra x Az)

43 2015-12-15 Company Presentation

Page 44: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Demand Control Ventilation

• Vary Primary airflow based on

• Occupancy

• Temperature

• CO2

• VOC

• Vary Primary airflow based on

• Occupancy

• Temperature

• CO2

• VOC

44 2015-12-15 Company Presentation

06:00 07:00 08:00 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Time

Air Volume l/s

150

200

250

Saving

CAV

DCV

100

Page 45: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Impact of Reduced Primary Airflow on Induction

0

50

100

150

200

250

300

350

400

0 10 20 30 40 50 60 70 80 90 100 110 120 130

Chilled Beam Discharge(CFM)

Primary Airflow Demand(CFM)

Induced

Primary

Chilled Beam with

Integral Damper

Discharge,

chilled beam

with upstream

VAV damper

12/15/2015Intro to ComVent - Establish

loads and Primary Airflow45

Page 46: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Demand Control VentilationDemand Control Ventilation

Dampers

ZONEDOAS

Page 47: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

Demand Control Ventilation Summary

• DCV increases chilled beam turndown from 3 to 1 to

10 to 1

• Improves occupant comfort

• Spaces are rarely at design occupancy

• DCV allows significant fan power savings

• DCV control can be based on

• Occupancy sensor (single occupant office)

• CO2 or VOC (modulating for multi occupant

spaces)

• DCV increases chilled beam turndown from 3 to 1 to

10 to 1

• Improves occupant comfort

• Spaces are rarely at design occupancy

• DCV allows significant fan power savings

• DCV control can be based on

• Occupancy sensor (single occupant office)

• CO2 or VOC (modulating for multi occupant

spaces)

47 12/15/2015Intro to ComVent - Establish

loads and Primary Airflow

Page 48: Establishing Primary Airflow in WBCS Systemstorontoashrae.com/resources/Documents/ASHRAE Chilled Beam...Primary Airflow Summary • The zone sensible cooling load should be between

THANK YOU FOR YOUR TIME