equipmentsseaconequipment.com/downloads/mbf-box-fan.pdf · equipments mbf box fan mbf range of...

24
SEACON EQUIPMENTS

Upload: dohuong

Post on 30-Mar-2018

252 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

Page 2: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF BOX FAN

MBF range of backward curve centrifugal fan give optimum performance and higher efficency yet low operation noise.

It is developed & tested with German technology with non-overloading characteristics. This set of ventilation fans is widely used in the market not only for the performance but also simple & easy installation thanks to its design.

• 20mm/40mm double skinned panel available in mineral wool steel or PU panel for ultra acoustic insulation.

• Panel of all side can be easily diassemble for inspection or maintenance.

• Air flow can be configured for straight throw or 90 ° direction.

• Best used for kitchen exhaust system. MBF box fan can replace the traditional bifurcated fan. It generate higher static pressure and motor can be located out of the air stream.

• For DV series, fan motors can be connected in delta configuration to run at high speed (1400rpm) or in star configuration to run at low speed (1000rpm).

• The multi-box fans come with 20 mm or 40mm double skinned panels with mineral wool or PU injection on all sides providing an effective acoustic insulation.

• The multi-box fans are designed for easy installation. These fans can be installed at a bend/elbow of a duct system to eliminate the pressure loss across the bend/elbow.

• Casing panels can be disassembled easily from all sides to facilitate easy maintainence and replacement of parts.

• Multi-box fans have low sound level due to the acoustic insulation.

• High efficiency & higher static pressure.

CONTENTS

NO LIABILITY FOR ERRORS! - SUBJECT TO TECHNICAL MODIFICATION!

MBF with backward curved impellersRange 355-450: with external rotor motorRange 500-710: with standard ZEC, IEC motor with B5 mounting Page

Technical information 3 - 4

Performance curves 5 - 22

Dimensions 23

Page 3: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

NO LIABILITY FOR ERRORS! - SUBJECT TO TECHNICAL MODIFICATION!

Panel insulation is provided by non flammable mineral fibre slab in accordance with DIN 4102. Thermal insulation K = 0,89 W/m²k in acc. with DIN 52210. Sound insulation RW = appr. 25 dB in acc. with DIN 52210.

The Lti accessories:• Speed controllers• flexible connections• counter flanges• shutters

The Lti performance curveshave been tested using a duct test chamber in accord-ance with DIN 24163. The values refer to an air density of 1,2 kg/m³ at 25° C.

Noise levels:The technical data show the A-rated sound pressure levels LPA. Tolerances in accordance with technical conditions of supply of fans DIN 24166, class 3. Noise level ca. 0,5 x Dpfa max.

The Seacon selection criteria:• Size• Air volume• Static pressure• Sound requirements

Rated data:P1: absorbed power at motor shaft [kW]P2: power at shaft [kW] IN: rated current [A]n: rated speed [1/min]C400: operating capacitor [μF]tR: ambient temperature [°C] max.tT: medium temperature [°C] max.Iso.kl.: insulation class motorIA / IN: proportion starting / rated curentWeight: total weight

Reference code

MBF 355 E 4 KS/KT

KS Side discharge, KT Top discgarge

V = 4/6 Poles, S = 6/8 Poles

E = single phase A.C.D = Three phase A.C.

Impeller diameter

Box Fan

Page 4: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBFBox fan

Rain cover

Non return damper

Flexible connectionsquare to round

Flexible connection

Mounting of MBF Accessories

Changing of air fl ow direction MBF

1

2

3

Air Flow

Air Flow

Air Flow

Air Flow

Page 5: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTSMBF 355

• Speed-controllable

• Modular system

• Integral thermal contacts

• Low sound level

• Maintenance-free and reliable

The MBF fan size 355 have impellers with aluminiumbackward curved blades, The MBF 355D2 is equippedwith IEC standard motors. The casing consists of analuminium frame, aluminium corners and 20 mm or 40mm double skin panels filled with mineral wool or PU insulation. Panels are removable and replacable,allowing flexible ventilation solutions.Motor protection by thermal contacts, to be connected to an external motor protection device.The box fans can be delivered for straight thru or easily rebuilt to 90° airflow direction. kitchen application is alsopossible as motor out of air stream configuration ispossible. Changing the airflow direction see page 4.

MBF 355D2Voltage/Frequency V/50 Hz 400

Phase ~

Power W 2200

Currrent A 3.72

Max. air fl ow at air direction A/B m3/h 6900

R.p.m. min-1 2740

Max. temp. of transported air °C 250

Max. temp. of transported air when speed controlled °C 250

Sound Pressure level at 1m dB (A) 66

Weight kg 40

Insulation class, motor F

Enclosure class, motor IP 55

Page 6: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

B

MBF 355D2 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 83 70 72 76 78 77 74 69 62LwA Outlet dB (A) 85 72 74 78 80 79 76 71 77LwA Surrounding dB (A) 77 64 66 70 72 71 68 63 56

Measuring point: qv = 3000 m3/h, Ps = 1200 Pa

0

0

400

800

1200

1600

Ps

[Pa]

qv [m3/h]

MBF 355D2

8000600040002000

Page 7: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 355

• Speed-controllable

• Modular system

• Integral thermal contacts

• Low sound level

• Maintenance-free and reliable

The MBF fan size 355 have impellers with aluminiumbackward curved blades, The MBF 355D4/E4 is equippedwith external rotor motor. The casing consists of analuminium frame, aluminium corners and 20 mm or 40mmdouble skin panels filled with mineral wool or PUinsulation. The panels are easily removable andreplacable, allowing flexible ventilation solutions.Motor protection by thermal contacts are to beconnected to an external motor protection device.The Multibox fans can be delivered for straight thru or easily rebuilt to 90° air direction airflow.Changing the airflow direction see page 4.

MBF 355DV 355E4Voltage/Frequency V/50 Hz 400 230

Phase ~ 3 1

Power W 335 260

Currrent A 0.52 1.14

Max. air fl ow at air direction A/B m3/h 2800 2800

R.p.m. min-1 1300 1260

Max. temp. of transported air °C 250 250

Max. temp. of transported air when speed controlled °C 250 250

Sound Pressure level at 1m dB (A) 55 55

Weight kg 37 37

Insulation class, motor B B

Enclosure class, motor IP 54 IP 54

Page 8: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 355DV (BASE ON 4-POLE) Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 68 55 57 61 63 62 59 54 47LwA Outlet dB (A) 70 57 59 63 65 64 61 56 49LwA Surrounding dB (A) 62 49 51 55 57 56 53 48 41

Measuring point: qv = 1300 m3/h, Ps = 270 Pa

MBF 355E4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 68 55 57 61 63 62 59 54 47LwA Outlet dB (A) 70 57 59 63 65 64 61 56 49LwA Surrounding dB (A) 62 49 51 55 57 56 53 48 41

Measuring point: qv = 1300 m3/h, Ps = 250 Pa

B

B0

100

200

300

P [W

]

qv [m3/h]

0

0

100

50

150

250

350

200

300

400

Ps

[Pa]

qv [m3/s]

MBF 355E4

0.80.70.50.30.1 0.60.40.2

68

66

0 500 1000 20001500 2500

qv [m3/h]

4-POLE

00

100

5020

60

120

40

100

80

140

160

150

250

350

200

300

400

0 500 1000 20001500 2500

0 1000 1500500

0

Ps

[Pa]

qv [m3/s]

MBF 355DV

Low Speeds

High Speeds

0.80.70.50.30.1 0.60.40.2

68

66

5

3

qv [m3/h]

4-POLE

6-POLE

0

100

200

300

P [W

]

Page 9: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 400

• Speed-controllable

• Modular system

• Integral thermal contacts

• Low sound level

• Maintenance-free and reliable

The MBF fan size 400 have impellers with aluminiumbackward curved blades. The MBF 400 is equipped withexternal rotor or IEC motor. The casing consists ofaluminium frame, aluminium corners and 20 mm or 40mmdouble skin panels filled with mineral wool or PUinsulation. The panels are easily removable andreplacable, allowing flexible ventilation solutions.Motor protection by thermal contacts are to be con-nected to an external motor protection device. The box fans can be delivered for straight thru or easily rebuilt to 90° air flow direction. Kitchen application is possible as motor out of air stream configuration is possible.Changing the airflow direction see page 4.

MBF 400DV 400E4 400E6Voltage/Frequency V/50 Hz 400 230 230

Phase ~ 3 1 1

Power W 460/310 520 160

Currrent A 0.85/0.5 2.2 0.75

Max. air fl ow at air direction A/B m3/h 4000 4050 2700

R.p.m. min-1 1340 1360 890

Max. temp. of transported air °C 250 250 250

Max. temp. of transported air when speed controlled °C 250 250 250

Sound Pressure level at 1m dB (A) 49 49 35

Weight kg 59 59 49

Insulation class, motor F F F

Enclosure class, motor IP 54 IP 54 IP 54

Page 10: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 400E4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 72 59 61 65 67 66 63 58 51LwA Outlet dB (A) 74 61 63 67 69 68 65 60 53LwA Surrounding dB (A) 56 43 45 49 51 50 47 42 35

Measuring point: qv = 1900 m3/h, Ps = 350 Pa

MBF 400DV (BASE ON 4-POLE) Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 72 59 61 65 67 66 63 58 51LwA Outlet dB (A) 74 61 63 67 69 68 65 60 53LwA Surrounding dB (A) 56 43 45 49 51 50 47 42 35

Measuring point: qv = 1500 m3/h, Ps = 350 Pa

B

B

0

0

0

200

300

400

500

100

50

150

250

400

350

200

300

450

P [W

]

qv [m3/s]

MBF 400E4/E6

1.210.60.2 0.80.4

1000 2000 40003000

2000 250015001000500

5

0

20

60

120

40

100

80

140

160

180

Ps

[Pa]

0

qv [m3/h]

290

231

173

116

0

0

100

50

150

250

400

350

200

300

450

1000 2000 40003000

2000 250015001000500

0

200

300

400

500

Ps

[Pa]

qv [m3/s]

MBF 400DV

1.210.60.2 0.80.4

3 5

5

3

0

20

60

120

40

100

80

140

160

180

0

4-POLE

6-POLE

qv [m3/h]

P [W

]

Low Speeds

High Speeds

116

173

231

290

4-POLE

6-POLE

Page 11: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 450

• Speed-controllable

• Modular system

• Integral thermal contacts

• Low sound level

• Maintenance-free and reliable

The MBF fan size 450 have impellers with aluminiumbackward curved blades. The MBF 450 is equipped withexternal rotor or IEC motor. The casing consists ofaluminium frame, aluminium corners and 20 mm or 40mmdouble skin panels filled with mineral wool or PUinsulation. The panels are easily removable andreplacable, allowing flexible ventilation solutions.Motor protection by thermal contacts are to be con-nected to an external motor protection device. The box fans can be delivered for straight thru or easily rebuilt to 90° air direction airflow. Kitchen application is also possible as motor out of air s t r e a m configuration is possible. Changing the airflow direction see page 4

MBF 450DV 450E4 450E6Voltage/Frequency V/50 Hz 400 230 230

Phase ~ 3 1 1

Power W 690/300 740 300

Currrent A 1.3/0.64 3.5 1.65

Max. air fl ow at air direction A/B m3/h 5500 5500 3660

R.p.m. min-1 1230/870 1360 840

Max. temp. of transported air °C 250 250 250

Max. temp. of transported air when speed controlled °C 250 250 250

Sound Pressure level at 1m dB (A) 49 49 36

Weight kg 59 59 49

Insulation class, motor F F F

Enclosure class, motor IP 54 IP 54 IP 54

Page 12: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 450E4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 75 62 64 68 70 69 66 61 54LwA Outlet dB (A) 77 64 66 70 72 71 68 63 56LwA Surrounding dB (A) 59 46 48 52 54 53 50 45 38

Measuring point: qv = 3900 m3/h, Ps = 250 Pa

MBF 450DV (BASE ON 4-POLE) Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 74 61 63 67 69 68 65 50 53LwA Outlet dB (A) 76 63 65 69 71 70 67 62 55LwA Surrounding dB (A) 59 46 48 52 54 53 50 45 38

Measuring point: qv = 3000 m3/h, Ps = 300 Pa

B

B

MBF 450E6 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 67 54 56 61 62 62 58 53 45LwA Outlet dB (A) 69 56 58 63 64 64 60 55 47LwA Surrounding dB (A) 51 38 40 45 46 46 42 37 29

Measuring point: qv = 2300 m3/s, Ps = 130 Pa

0

0

0

100

50

150

250

400

350

200

300

500

450Ps

[Pa]

qv [m3/h]

MBF 450E4/E6

1.61.2 1.410.60.2 0.80.4

1000 2000 4000 50003000

1000 1500 2000 2500 3000 3500500

0

20

60

120

40

100

80

140

160

180

200

0

4-POLE

6-POLE

qv [m3/h]

0

200

400

600

800

P [W

] 0

116

173

231

290

0

0

Ps

[Pa]

1000 2000 4000 50003000

0

0

200

400

600

800

200

100

300

500

400

600

P [W

]

MBF 450DV

1.61.2 1.410.60.2 0.80.4

3 5

5

3

1000 1500 2000 2500 3000 3500500

0

20

60

120

40

100

80

140

160

180

200

220

240

260

0

4-POLE

6-POLE

qv [m3/h]

0

116

173

231

290

Page 13: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 500

• Speed-controllable

• Modular system

• Low sound level

• Maintenance-free and reliable

The MBF fan size 500 have impellers with aluminiumbackward curved blade. The MBF 500 is equipped withIEC motor. The casing consists of aluminium frame,aluminium corners and 20mm or 40mm double skin panelsfilled with mineral wool or PU insulation. The panels areeasily removable and replacable, allowing flexibleventilation solutions.Motor protection by thermal contacts are to beconnected to an external motor protection device. The box fans can be delivered for straight thru or easily rebuilt to 90° direction airflow. Kitchen application is also possible as motor out of air stream configuration is possible. Changing the airflow direction see page 4

MBF 500D4 500D6 500E4 500E6Voltage/Frequency V/50 Hz 400 400 230 230

Phase ~ 3 3 1 1

Power W 1500 750 1500 750

Currrent A 3.5 1.97 10.5 4.8

Max. air fl ow at air direction A/B m3/h 9000 6000 9000 6000

R.p.m. min-1 1390 915 1360 890

Max. temp. of transported air °C 250 250 250 250

Max. temp. of transported air when speed controlled °C 250 250 250 250

Sound Pressure level at 1m dB (A) 56 46 56 46

Weight kg 68 60 68 60

Insulation class, motor F F F F

Enclosure class, motor IP 55 IP 55 IP 55 IP 55

Page 14: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 500D4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 78 65 67 71 73 72 69 64 57LwA Outlet dB (A) 80 67 69 73 75 74 71 66 59LwA Surrounding dB (A) 63 50 52 56 58 57 54 49 42

Measuring point: qv = 7000 m3/h, Ps = 320 Pa

MBF 500E4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 79 66 68 72 74 73 70 65 58LwA Outlet dB (A) 81 68 70 74 76 75 72 67 60LwA Surrounding dB (A) 63 50 52 56 58 57 54 49 42

Measuring point: qv = 7000 m3/h, Ps = 320 Pa

B

B

MBF 500D6 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 67 54 56 61 62 62 58 53 45LwA Outlet dB (A) 69 56 58 53 54 54 60 55 47LwA Surrounding dB (A) 53 40 42 47 48 48 44 39 31

Measuring point: qv = 4000 m3/h, Ps = 190 Pa

MBF 500E6 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 67 54 56 61 62 62 58 53 45LwA Outlet dB (A) 69 56 58 53 54 54 60 55 47LwA Surrounding dB (A) 53 40 42 47 48 48 44 39 31

Measuring point: qv = 4000 m3/h, Ps = 190 Pa

1300

1200

1100

1000

900

800

MBF 500E4/E6

4000

20

200

100

500

400

600

80005000 6000 7000

300

Ps

[Pa]

4000 4500 5000 55002500 3000 3500

4-POLE

6-POLE

qv [m3/h]20

60

120

40

100

80

140

160

180

200

220

240

260

4000

20

200

100

500

400

600

P [W

]

80005000 6000 7000

300

MBF 500D4/D6Ps

[Pa]

4000 4500 5000 55002500 3000 3500

20

60

120

40

100

80

140

160

180

200

220

240

260

1300

1200

1100

1000

900

800

4-POLE

6-POLE

qv [m3/h]

385

355

325

295

265

235

P [W

] 385

355

325

295

265

235

Page 15: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 560

• Speed-controllable

• Modular system

• Low sound level

• Maintenance-free and reliable

The MBF fan size 560 have impellers with aluminiumbackward curved blade. The MBF 560 is equipped withIEC motor. The casing consists of aluminium frame,aluminium corners and 20mm or 40mm double skin panelsfilled with mineral wool or PU insulation. The panels areeasily removable and replacable, allowing flexibleventilation solutions.Motor protection by thermal contacts are to beconnected to an external motor protection device. The box fans can be delivered for straight thru or easily rebuilt to 90° direction airflow. Kitchen application is also possible as motor out of air stream configuration is possible. Changing the airflow direction see page 4

MBF 560D4 560D6 560E4 560E6Voltage/Frequency V/50 Hz 400 400 230 230

Phase ~ 3 3 1 1

Power W 2200 750 2200 750

Currrent A 4.36 2.2 1.97/2.6 4.8

Max. air fl ow at air direction A/B m3/h 12000 8000 12000 8000

R.p.m. min-1 1440 915 1430 890

Max. temp. of transported air °C 250 250 250 250

Max. temp. of transported air when speed controlled °C 250 250 250 250

Sound Pressure level at 1m dB (A) 57 48 57 48

Weight kg 130 110 130 110

Insulation class, motor F F F F

Enclosure class, motor IP 55 IP 55 IP 55 IP 55

Page 16: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 560D6/MBF 560E6 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 70 57 59 64 65 65 61 56 48LwA Outlet dB (A) 72 59 61 66 67 67 63 58 50LwA Surrounding dB (A) 55 42 44 44 50 50 46 41 33

Measuring point: qv = 5000 m3/h, Ps = 260 Pa

MBF 560D4/MBF 560E4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 79 66 68 72 74 73 70 65 58LwA Outlet dB (A) 81 68 70 74 76 75 72 67 60LwA Surrounding dB (A) 64 51 53 57 59 58 55 50 43

Measuring point: qv = 8000 m3/h, Ps = 500 Pa

B

4000

0

2500

2300

2100

1900

1700

P [W

]

80005000 6000 7000

1500

10000 12000

1100

100

300

500

700

900Ps

[Pa]

4000 5000 6000 8000

4-POLE

6-POLE

qv [m3/h]

020

60

100

140

180

220

260

300

340

380

420

460

MBF 560

2000 3000

740

680

620

560

500

440

Page 17: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 560-L

• Speed-controllable

• Modular system

• Low sound level

• Maintenance-free and reliable

The MBF fan size 560 have impellers with aluminiumbackward curved blade. The MBF 560 is equipped withIEC motor. The casing consists of aluminium frame,aluminium corners and 20mm or 40mm double skin panelsfilled with mineral wool or PU insulation. The panels areeasily removable and replacable, allowing flexibleventilation solutions.Motor protection by thermal contacts are to beconnected to an external motor protection device. The box fans can be delivered for straight thru or easily rebuilt to 90° direction airflow. Kitchen application is also possible as motor out of air stream configuration is possible. Changing the airflow direction see page 4

MBF 560D4-L 560D6-LVoltage/Frequency V/50 Hz 400 400

Phase ~ 3 3

Power W 3000 1100

Currrent A 6.06 3.04

Max. air fl ow at air direction A/B m3/h 14000 9330

R.p.m. min-1 1410 960

Max. temp. of transported air °C 250 250

Max. temp. of transported air when speed controlled °C 250 250

Sound Pressure level at 1m dB (A) 67 50

Weight kg 135 117

Insulation class, motor F F

Enclosure class, motor IP 55 IP 55

Page 18: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 560D6-L Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 70 57 59 64 65 65 61 56 48LwA Outlet dB (A) 72 59 61 66 67 67 63 58 50LwA Surrounding dB (A) 55 42 44 49 50 50 46 41 33

Measuring point: qv = 5000 m3/h, Ps = 280 Pa

B

5000

0

90006000 7000 8000 10000 11000

1100

100

300

500

700

900Ps

[Pa]

4000 6000

1440 R.P.M.

960 R.P.M.

qv [m3/h]

020

60

100

140

180

220

260

300

340

380

420

460

3000 5000 7000

MBF 560D4/D6-L

MBF 560D4-L Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 79 66 68 72 74 73 70 65 58LwA Outlet dB (A) 81 68 70 74 76 75 72 67 60LwA Surrounding dB (A) 64 51 53 57 59 58 55 50 43

Measuring point: qv = 9000 m3/h, Ps = 500 Pa

2500

2300

2100

1900

1700

P [W

]

1500

740

680

620

560

500

440

Page 19: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 630

• Speed-controllable

• Modular system

• Low sound level

• Maintenance-free and reliable

The MBF fan size 630 have impellers with aluminiumbackward curved blade. The MBF 630 is equipped withIEC motor. The casing consists of aluminium frame,aluminium corners and 20mm or 40mm double skin panelsfilled with mineral wool or PU insulation. The panels areeasily removable and replacable, allowing flexibleventilation solutions.Motor protection by thermal contacts are to be con-nectedto an external motor protection device. The box fans canbe delivered for straight thru or easily rebuilt to 90°direction airflow. Kitchen application is also possible asmotor out of air stream configuration is possible.Changing the airflow direction see page 4

MBF 630D4 630D6 630D4-L 630D6-LVoltage/Frequency V/50 Hz 400 400 400 400

Phase ~ 3 3 3 3

Power W 4000 1500 5500 1500

Currrent A 8 3.7 11 3.7

Max. air fl ow at air direction A/B m3/h 16000 10600 20000 13333

R.p.m. min-1 1400 910 1440 910

Max. temp. of transported air °C 250 250 250 250

Max. temp. of transported air when speed controlled °C 250 250 250 250

Sound Pressure level at 1m dB (A) 69 54 70 55

Weight kg 135 135 170 170

Insulation class, motor F F F F

Enclosure class, motor IP 54 IP 54 IP 54 IP 54

Page 20: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 630D4-L Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 92 57 74 84 86 87 86 80 71LwA Outlet dB (A) 94 58 75 86 87 89 89 83 73LwA Surrounding dB (A) 83 52 70 76 78 77 76 64 66

Measuring point: qv = 15000 m3/h, Ps = 650 Pa

MBF 630D4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 87 74 76 80 82 81 78 73 66LwA Outlet dB (A) 89 76 78 82 84 83 80 75 68LwA Surrounding dB (A) 76 63 65 69 71 70 67 62 55

Measuring point: qv = 7000 m3/h, Ps = 911 Pa

B

B

MBF 630D4

2000

3000

4000

5000

P [W

] 1160

1730

2310

2900

MBF 630D6-L Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 80 44 60 72 72 75 74 68 62LwA Outlet dB (A) 81 45 62 73 74 76 76 70 60LwA Surrounding dB (A) 65 38 40 56 58 58 60 55 48

Measuring point: qv = 10000 m3/h, Ps = 300 Pa

P [W

]

1065

1155

1245

1335

1425

1075

8000

100

400

200

600

1000

800

1200 MBF 630D4-L/D6-L

1400010000 180001600012000

4800

4200

3600

3300

4500

3900

Ps

[Pa]

Ps

[Pa]

800070006000 10000 11000 120009000

30000 6000

4-POLE

4-POLE

6-POLE

6-POLE

qv [m3/h]

qv [m3/h]

0

0

50

50

100

100

350

300

150

150

400

350

200

200

450

400

250

250

500

300

550

600

450

500

0 4000 8000 12000 16000

0

400

200

1000

800

600

1200

MBF 630D6 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 74 61 63 68 69 69 65 60 52LwA Outlet dB (A) 76 63 65 70 71 71 67 62 54LwA Surrounding dB (A) 61 49 51 54 56 56 52 47 39

Measuring point: qv = 6000 m3/h, Ps = 300 Pa

9000

Page 21: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 710

• Speed-controllable

• Modular system

• Low sound level

• Maintenance-free and reliable

The MBF fan size 710 have impellers with aluminiumbackward curved blade. The MBF 710 is equipped withIEC motor. The casing consists of aluminium frame,aluminium corners and 20mm or 40mm double skin panelsfilled with mineral wool or PU insulation. The panels areeasily removable and replacable, allowing flexibleventilation solutions.Motor protection by thermal contacts are to beconnected to an external motor protection device. The box fans can be delivered for straight thru or easily rebuilt to 90° direction airflow. Kitchen application is also possible as motor out of air stream configuration is possible. Changing the airflow direction see page 4

MBF 710D4 710D6Voltage/Frequency V/50 Hz 400 400

Phase ~ 3 3

Power W 11000 3000

Currrent A 20.1 6.03

Max. air fl ow at air direction A/B m3/h 24000 16000

R.p.m. min-1 1440 960

Max. temp. of transported air °C 250 250

Max. temp. of transported air when speed controlled °C 250 250

Sound Pressure level at 1m dB (A) 76 66

Weight kg 200 160

Insulation class, motor F F

Enclosure class, motor IP 54 IP 54

Page 22: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

MBF 710D4 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 97 90 92 88 87 90 81 75 67LwA Outlet dB (A) 92 64 76 79 84 90 82 76 66LwA Surrounding dB (A) 84 56 68 71 76 82 74 68 58

Measuring point: qv = 17000 m3/h, Ps = 1000 Pa

B

MBF 710D4/D6

8500

7000

6000

8000

6500

7500

MBF 710D6 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8kLwA Inlet dB (A) 79 66 68 73 74 74 70 65 57LwA Outlet dB (A) 81 68 70 75 76 76 72 67 59LwA Surrounding dB (A) 67 54 56 61 62 62 58 53 45

Measuring point: qv = 10000 m3/h, Ps = 500 Pa

P [W

]

1775

1925

2525237522252075

Ps

[Pa]

80000 12000 14000 1600010000

4-POLE

6-POLE

qv [m3/h]

0

50

100

350

150

400

200

450

250

550

500

300

600

650

0 1800012000 2400022000200001600014000

0

900

100

300

1300

700

500

1100

Page 23: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SEACONEQUIPMENTS

NO LIABILITY FOR ERRORS! - SUBJECT TO TECHNICAL MODIFICATION!

DIMENSIONS

Short casing KS

AB

C

la

di

A

B

la

50D

di

L

MBF Box Fan A B Øla Ødi C D L355 500 420 355 224 - - 500

400 670 590 404 253 325 - 670

450 670 590 454 286 325 - 670

500 670 590 504 321 370 - 800

560 800 720 570 361 - 300 800

630 800 720 635 407 - 335 800

630L 1000 920 715 460 - 385 800

710 1000 920 715 460 - 385 800

Page 24: EQUIPMENTSseaconequipment.com/downloads/MBF-Box-Fan.pdf · EQUIPMENTS MBF BOX FAN MBF range of backward curve centrifugal fan give optimum performance and higher ... • Best used

SPECIFICATIONS AND DESIGN ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE.

SEACON ENGINEERING EQUIPMENTS PTE. LTDSpecialised Engineering and HVAC Equipment Supplier10 Anson Road #05-17 International Plaza Singapore 079903Co. Reg. No. : 200917905H GST Reg. No. : 200917905HWebSite: http://seaconequipment.comEmail : [email protected], [email protected]

SEACONEQUIPMENTS

Specialize in HVAC Manufacturing:

• Air-Cooled Condensing Unit• Chillers Unit• Package Unit• Stainless Steel AC Unit• Ex-Proof Unit• Custom-made AC unit

From Marine to Industrial to Commercial air conditioning unit. We provide you the best support and designs to your needs.

邱志强Kasdi Qiu (ชิวจ ือเช ียง)HP. : +65 9795 0350DirectorE-mail : [email protected]

SEACONEQUIPMENTS

Specialised Engineering and HVAC Equipment Supplier10 Anson Road #05-17 International Plaza Singapore 079903Phone: +65 9795 0350 Fax: +65 6762 2664Co. Reg. No. : 200917905H GST Reg. No. : 200917905HWeb Site: http://seaconequipment.com Email : [email protected]

SEACON ENGINEERING EQUIPMENTS PTE. LTD

Specialize in:HVAC Equipment ManufacturerMarine Offshore DesignEngineering DesignEngineering Drawing