CAT NO. JK-2012
Epoxy molded Automatic vacuum Recloser with microprocessor-based controller integrated RTU
JIN KWANG E&C CORPORATION 705, Buk-ri, Namsa-myeon, Cheoin-gu, Yongin-si, Gyeonggi-do, Korea Tel. +82-31-333-3444 Fax. +82-31-332-5300 http//www.jinkwang.co.kr E-mail : [email protected]
-
ISO 9001 certified www.jinkwang.co.kr
2
The JK-MREC automatic circuit reclosers are designed for use on overhead lines as well as substation application for distribution line of up to 38 kV. The recloser is supplied with controller. The controller is a microprocessor based controller that provides the protection, and data gathering and communication function in the capacity of control devices inherently reliable and intelligent. The recloser combines the high reliability of vacuum interruption and high dielectric strength of epoxy mold, in a compact, maintenance-free unit. The magnetic actuator provides consistent performance and high reliability.
Epoxy molded(solid) insulation - environmental-friendly product No maintenance needed during its entire lifetime / Long mechanical and interrupting life Compact design Phase Fault, Ground Fault, SEF & Under/Over Frequency Protection Cold Load Pickup, Inrush restraints, Phase Sync. Check, Hot Ling Tag 58 TC curves(IEC,ANSI,Recloser-innate, 4 user-defined) Two RS 232 ports for communication with PC and SCADA system
Duty cycle monitor/service of vacuum bottles
Type JK-MREC JK-SREC
Maximum System Voltage Rated Current Rated Frequency Mechanical Operation(Min.)
kV A
Hz C-O
15 630
50/60 10,000
27 630
50/60 10,000
38 630/800
50/60 10,000
Breaking Capacity
Rated symmetrical interrupting current Short Time Withstand Current(1sec) Making Current(peak) Cable Charging Transformer Magnetizing
A kA kA A A
12.5 12.5 32.5
5 22
12.5/16 12.5/16 32.5/40
5 22
12.5/16 12.5/16 32.5/40
5 40
Impulse Insulation Level(1.2×50μs)
Phase to Earth Across Interrupter
kV kV
110 110
150 150
170 170
Power Frequency Insulation Level, dry
Phase to Earth Across Interrupter
kV kV
40 40
60 60
70 70
Operation Control Circuit V V AC 220 V or AC 120
DC 24 V
Ambient Temperature °C -25 ~ + 70
Net Weight(Switch Body/ Control Cabinet) kg 160/50 180/50 220/50
GENERAL
KEY FEATURES
ELECTRICAL RATINGS
-
ISO 9001 certified www.jinkwang.co.kr
3
6
CONSTRUCTION - Automatic Vacuum Recloser Body
3
1
1
2
4 7 5 8
1. High voltage connection terminal 2. Epoxy module encapsulating vacuum
interrupter, current/voltage sensors 3. Manual trip and locking lever 4. Open/Close indicator(bottom side) 5. Operation counter(bottom side) 6. Mounting bracket 7. Lifting lug 8. Control receptacle to interface with
controller 9. Name plate
This design incorporates three Independentmagnetic actuators: one for pole. This minimizes the number of moving parts.The actuator armature is rigidly coupled to thevacuum interrupter moving contact by a lineardrive insulator within the support insulator.
SWITCHING DEVICE
MAGNETIC ACTUATOR
● Increased rel iabil i ty with min. 10,000 Mechanical operation
● Simple design ● Bi-stable : No power required to hold contacts in open or closed. ● Three individual actuators and three-phase
simultaneous operation
9
INSULATING MATERIAL
● Advanced epoxy encapsulating material ● Light weight & compact design for easy
installation & handling. ● Improved performance in heavily polluted area ● Increased weather durability and improved aging
INTEGRATED SENSORS
● Three(3) current(1000:1 A, ± 5 %) and six(6)sensors integrated in epoxy module for protection, and line voltage/current measurement ,
INDICATOR/COUNTER
● Contact position indicator : Easily visible from the ground
● Operation counter to record recloser operation
VACUUM INTERRUPTER
● High interrupting capacity ● Very compact dimension ● Low chopping current, limiting inductive
switching overvoltage to safe values ● Axial magnetic field minimizing contact
erosion and ensure a very long and reliable life
-
ISO 9001 certified www.jinkwang.co.kr
4
CONSTRUCTION – Microprocessor-based RTU-integrated Control(FTU-R200C)
1. LCD Display 2. LED indicator for CPU Run, System Error, External AC power supply and Battery fail 3. Up/Down(LCD Menu Operation) Buttons 4. RS232 port for Maintenance use 5. Ethernet / SCADA / Protection communication LED indicators 6. Battery & Lamp test button 7. Rest button for protection, Reclosing and Self-diagnosis error LED 8. LED indicators for Live line(source and load side), under voltage, Sync. Fail, fault current and
recloser status. 9. Reclosing & Protection enable/disable selector switches and its LED indicators 10. Remote/Local operation mode and Controller lock/unlock selector switches and its LED
indicators 11. Select(Two Step Control Command) Button & LED and Close/open switches and its LED
indicators.
C
-
ISO 9001 certified www.jinkwang.co.kr
5
FAULT DETECTION & PROTECTION Phase/Ground Fault Detection & Protection
Phase Fault Earth Fault Step Unit
Range Def. Range Def.
Pickup Current 10~900 400 5~900 60 1 A
Inrush Block NO/YES YES NO/YES YES
Fast Operation Time Curve
Type 1~58 1-A 1~58 2-B 1
Time Multiplier 0.05~2.00 1.00 0.05~2.00 1.00 0.01 sec
Time Adder 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec Min. Response
Time 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec
Reset Type RDMT/RIDMT RDMT RDMT/RIDMT RDMT RDMT(Definite Time) RIDMT(Inverse Time) Reset Definite
Time 0.00~100.00 0.00 0.00~100.00 0.00 0.01 sec
Delayed Operation Time Curve
Type 1~58 20-1 1~58 21-2 1
Time Multiplier 0.05~2.00 1.00 0.05~2.00 1.00 0.01 sec
Time Adder 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec Min. Response
Time 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec
Reset Type RDMT/RIDMT RDMT RDMT/RIDMT RDMT RDMT(Definite Time) RIDMT(Inverse Time) Reset Definite
Time 0.00~100.00 0.00 0.00~100.00 0.00 0.01 sec
Definite Time Protection
Range Def. Step Unit Comment
Phase Detection
Active OFF/ON OFF
Pickup Current 50~10000 1000 1 A
Detection Time 0.00~1.00 0.00 0.01 sec
Earth Detection
Active OFF/ON OFF
Pickup Current 50~10000 1000 1 A
Detection Time 0.00~1.00 0.00 0.01 sec
-
ISO 9001 certified www.jinkwang.co.kr
6
High Current Trip(HCT)
Range Def. Step Unit Comment
Phase Detection
Operation Count 0~4 0 1 ‘0' means disable.
Pickup Current 50~10000 2000 1 A
Detection Time 0.00~1.00 0.00 0.01 sec
Earth Detection
Operation Count 0~4 0 1 ‘0' means disable.
Pickup Current 50~10000 2000 1 A
Detection Time 0.00~1.00 0.00 0.01 sec
Cold Load Pick-up
Sensitive Earth Fault(SEF) Protection
Range Def. Step Unit Comment
Phase Detection
Pickup Multiplier 0~10 2 1 ‘0' means disable.
Duration Time 0.00~60.00 3.00 0.01 sec
Earth Detection
Pickup Multiplier 0~10 2 1 ‘0' means disable.
Duration Time 0.00~60.00 3.00 0.01 sec
Range Def. Step Unit Comment
Pickup Current(3I0) 2~20 5 1 A
Pickup Voltage(-3V0) 10~80 30 1 % Rated Phase
Voltage Max. Torque Angle 0~345 90 15 Degree Leading
Detection Time 0.1~30.0 1.0 0.1 sec
Inrush Block NO/YES YES
Function In Use OFF/ALARM/TRIP OFF
-
ISO 9001 certified www.jinkwang.co.kr
7
Directional Blocking Protection
Range Def. Step Unit Comment
Phase Detection
Trip Direction OFF/FWD/REV/ALL FWD
3V1 Threshold 0~100 20 1 %
3I1 Threshold 0~100 20 1 %
3I1 Max. Torque Angle 0~355 60 5 Degree
Earth Detection
Trip Direction OFF/FWD/REV/ALL FWD
-3V0 Threshold 0~100 20 1 %
3I0 Threshold 0~100 20 1 %
3I0 Max. Torque Angle 0~355 60 5 Degree
Inrush restraints
Range Def. Step Unit Comment
2nd Harmonic 5~50 20 1 %
Detection Time 0.02~1.00 0.02 0.01 sec
Function In Use OFF/ON ON
Open Line Detection(Loss of Phase)
Range Def. Step Unit Comment
Volt ON Level 50~90 80 5 %
Volt OFF Level 35~75 50 5 %
Delay Time 0.1~30.0 0.4 0.1 sec
Function In Use OFF/ON ON
Phase Sync. Check
Range Def. Step Unit Comment
Phase Difference 5~60 30 1 Degree
Dalay Time 0.1~30.0 0.1 0.1 sec
Function In Use OFF/ON ON
-
ISO 9001 certified www.jinkwang.co.kr
8
Under Voltage Protection
Range Def. Step Unit Comment
Pickup Level 0.30~0.95 0.80 0.01 PU
Delay Time 0.0~180.0 1.0 0.1 sec
Function In Use OFF/ARAMP/TRIP OFF
Over Voltage Protection
Under Frequency Protection
Auto Reclosing Sequence
Range Def. Step Unit Comment
Phase
Operation Count 1~4 4 1
Instantaneous Count 0~4 2 1
Earth
Operation Count 1~4 4 1
Instantaneous Count 0~4 2 1
Range Def. Step Unit Comment
Pickup Level 1.05~1.50 1.20 0.01 PU
Delay Time 0.0~180.0 1.0 0.1 sec
Function In Use OFF/ARAMP/TRIP OFF
Range Def. Step Unit Comment
Pickup 47.00~59.98 49.80 0.01 Hz
Delay Time 0.03~10.00 0.10 0.01 sec
Function In Use OFF/ARAMP/TRIP OFF
-
ISO 9001 certified www.jinkwang.co.kr
9
Range Def. Step Unit Comment
Phase/ Earth Reclosing
Reclose Interval 1st 0.5~180.0 0.6 0.1 sec
Reclose Interval 2nd 1~180 2 1 sec
Reclose Interval 3rd 1~180 15 1 sec
Reset Time 3~180 30 1 sec
SEF Reclosing
Operation Count 1~4 4 1
Reclose Interval 1st 0.5~180.0 0.6 0.1 sec
Reclose Interval 2nd 1~180 2 1 sec
Reclose Interval 3rd 1~180 15 1 sec
Reset Time 3~180 30 1 sec
MEASUREMENT Current RMS(A) & Phase angle(°) Ia, Ib, Ic, In Sequence Component I1, I2, I0 True RMS Ia, Ib, Ic Reading Range 2~12, 500A(External CT Ratio 1,000 : 1) Accuracy 2~600A ±0.5% or ±1A
600~12,000A ±3%
Voltage RMS(kV) & Phase angle(°) Va, Vb, Vc, Vr, Vs, Vt Sequence Component V1s, V2s, V0S, V1L, V2L, V0LS, True RMS Va, Vb, Vc, Vr, Vs, Vt Phase Angle Difference(°)
∠Va - ∠Vr
Reading Range 0.1~26kV Accuracy ±0.5% or ±0.1kV
Power Active Power(kW) A-Phase, B-Phase, C-Phase, 3-Phase Total Reactive Power(kVAR) A-Phase, B-Phase, C-Phase, 3-Phase Total, Apparent Power(kVA) A-Phase, B-Phase, C-Phase, 3-Phase Total Reading Range -32767~32767 Accuracy ±1%
-
ISO 9001 certified www.jinkwang.co.kr
10
Power Factor A-Phase, B-Phase, C-Phase, 3-Phase Total Lead/Lag Display Reading Range 0~1.0 Accuracy ±2%
Frequency Reading Range 45 ~ 55Hz (System Frequency : 50Hz)
55 ~ 65Hz (System Frequency : 60Hz) Accuracy ±0.02%
Energy Positive kWh A-Phase, B-Phase, C-Phase, 3-Phase Total Negative kWh A-Phase, B-Phase, C-Phase, 3-Phase Total Capacitive Positive kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Capacitive Negative kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Inductive Positive kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Inductive Negative kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Reading Range 0~65535(Rollover) Accuracy ±2%
Harmonic Total Harmonic Distortion (%) 3-Phase Current THD (Ia, Ib, Ic, I3ph)
Source side 3-Phase Voltage THD (Va, Vb, Vc, V3ph) 2nd~31st Harmonic RMS(A, kV) Ia, Ib, Ic, Va, Vb, Vc
Demand Current and Power
Configurable Demand Interval 5, 10, 15min (Default 15min)
2nd~31st Harmonic RMS(A, kV) Ia, Ib, Ic, Pa, Pb, Pc, P3ph, Qa, Qb, Qc, Q3ph
Daily Max Current and Power are Stored
COMMUNICATION
Telecommunication port RS232C 9-Pin Male Connector DCD(1), Rx(2), Tx(3), DTR(4), GND(5) DSR(6), RTS(7), CTS(8), NC(9) Speed(Baud Rate) 1200, 2400, 4800, 9600, 19200 BPS
Suppots Modam Control CTS, DCD Signal Timeout Configurable
RTS Off-delay Configurable
Optical Isolation
ESD, Transient Noise Protection
-
ISO 9001 certified www.jinkwang.co.kr
11
Protocol for SCADA DNP3.0 or IEC60870-5-101
EVNET RECORDING
Event List Sub Items Max.
I/O Events Status change of binary Input/Output 1023
Function Events Operated status of Protection Function 1023
System Events Setting change, Reset, Self Dignosis 255
Fault I Events Latest fault current, phase and time 255
PQM Events Operated status of PQM Function 255
Demand I,P,Q Events Each phase daily average load current, active power and reactive power with time 1023
Max. I,P,Q Events Each phase daily Peak load current, active power and reactive power with time 1023
MAINTENANCE SOFTWARE(FTUMan)
Setting & Configuration changes
Event & Waveform load
Measurement & Status display
Waveform File upload and convert
SCADA monitors protocol data frame between devices
-
ISO 9001 certified www.jinkwang.co.kr
12
ENVIRONMENTAL CONDITIONS
Ambient Temperature Storage Temperature Humidity Dielectric withstand Impulse voltage Insulation resistance High frequency disturbance Fast transient noise Radio frequency noise Vibrations Mechanical Shock Enclosure protection
- 25 ~ +70°C, KSC 0220/1 - 40 ~ +85°C < 95%RH IEC 60255-5, 2kV IEC 60255-5, 6kV for current input circuit IEC 60255-5, 4kV for voltage, power input & Contacts I/O IEC 60255-5, >500MΩ (DC500V) IEC 61000-4-12 class 3 (2.5kV) IEC61000-4-4 class 4 (4kV) IEC 61000-4-3 10V/m IEC 60255-21-1 class 2 IEC 60255-21-2 class 2 IP54
-
ISO 9001 certified www.jinkwang.co.kr
13
11 kV Automatic Vacuum Recloser body
25.8 kV Automatic Vacuum Recloser body
DIMENSIONAL INFORMATION
-
ISO 9001 certified www.jinkwang.co.kr
14
38 kV Automatic Vacuum Recloser body
Microprocessor-based RTU-integrated Control
-
ISO 9001 certified www.jinkwang.co.kr
15
[ Substation mounting ]
[ Single pole mounting ]
TYPICAL INSTALLATION LAYOUT(POLE MOUNTING)