    Item

    No.Description Unit Quantity Rate Amount

    26

    Providing 2mm thick hard, antistatic, abrasion resistant, robust solvent

    free epoxy flooring (ESD flooring) with the following specifications.

    sqm

    2472 Rs 2497/ Rs 61,72,584/

    1. Surface Preparation

    Surface Preparation of concrete substrate with proper diamondgrinding /Proper Vacuum assisted shot blasting machine equipment to

    remove dust, laitance, other contaminants etc., and to form the

    required anchor profile on the floor substrate.

    2. Providing and applying 2 part water dispersed epoxy resin primer

    Sikafloor80 Promer @ 0.3 kg/m

    3. Installation of underlay Moisture barrier 2mm

    Providing and applying three part, self smoothing, solvent free,

    moisture barrier epoxy modified cement screed Sikafloor81 EpoCem

    at at thickness of 2mm @ approx. 2.25 kg/m/mm having Carbon

    dioxide diffusion coefficient CO = 4168 as per Klopfer Engelgried

    method, water vapour diffusion coefficient HO=252 as per DIN

    52615, Water absorption coefficient W=0.02 kg/m as per DIN 52617.

    When applied at minimum 2mm thickness it can be laid over high

    moisture content substrate and must be used when substrate moisture

    is more than 4%.

    4. Installation of low emission, electrostatic conductive, self

    smoothing epoxy resin system

    Supply and application of Sika Electrostatic conductive Epoxy Flooring

    System with electrode based in the following sequence:.

    i Over the surface, an epoxy resin based primer Sikafloor 161 shall

    be applied. The primer ia s two component material consisting of

    Component A and Component B; the mixing ratio would be 79:21, by

    weight.

    ii. The Earthing kit (Electrode) with copper tape shall be placed

    according to the specification mentioned above, The name of theearthing kit would be Sikafloor Leitset and the copper tape would be

    Sika Kupferleitband or equivalent

    iii. Over the primed surface, a conductive under of Sikafloor 220W

    should be applied. The conductive undercoat is a two component

    material, which should be mixed at the specified ratio like 83:17 (by

    weight) and applied using a brush or roller. This is water borne epoxy

    and the mixed density is 1.04kg/I.

    iv. Application of low emission, electrostatic conductive, self

    smoothing epoxy topping of 1.5mm thickness with Sikafloor 266 ECF CR

    including taking the conductivity measurements of top coat as per the

    technical specification. The product conforms to Compressive strength

    is 80N/mm as per EN 138922, Resistance to ground: RG10 to 10

    as per IEC 6134041 Flexural Strength is 39N/mm as per EN 138922,Shore D Hardness is 84 as per DIN 53 505 Abrasion resistance is 45mg

    (CS 10/1000/1000)(14days/+23C) as DIN 53 109 Taber Abrader Test)

    applied @ 2.1 Kg/sqm followed by Sikadur 502 @ 0.6 Kg/sqm. All in

    complete as per the manufacturers specifications and directions of the

    engineer in charge.

    ESD FLOOR REQUIREMENT AND SPECIFICATION

    Major Specification:

  • 7/30/2019 Epoxy and ESD Flooring

    2/4

    1. Electrical Resistance (On conductive black Coat): Surface resistance

    between 104 to 106 as per DIN IEC 6134041 Standard.

    2. Walkinvoltage: 100V to +100V as per DIN IEC 6134051 Standard.

    3. System Resistance: Less than 35M including floor concrete

    substrate etc as per DIN IEC 6134051 Standard.

    4. Compressive Strength: More than 80N/mm2 as per EN 1961

    Standard.

    5. Flexural Strength: More than 55N/mm2 as per EN 1961 Standard.

    6. Abrasion resistance: Maximum thickness reduction should not be

    more than 2mm as per IS 91621979/IS 12371980.

    7. Hardness: Shore D hardness of floor more than 85as per DIN53505.

    8. Tensile Strength: More than 15N/mm2 as per EN 1961 Standard.

    9. Pull Out Strength/Bond Strength: More than 1.5N/mm2 or concrete

    failure as per ISO4624 Standard.

    10. Gloss: 75% as per IS 1011988 Standard.

    11. Chemical Resistance: Resistance to acids, caustic soda, liquid soap,

    IPA etc as per IS 46311968.

    12. Water absorption: Less than 0.5% as per ASTM D570.

    13. Slip resistance:Better than R11 as per Employers Liability Insurers

    Institute of safety at work (BIA).

    14. Low VOC.

    15. Temporary Moisture Barrier underlay screed:

    a. Layer thickness Min. 2mm must be applied.

    b. CarbonDiOxide Diffusion Coefficient (CO2) Co2~4168 acc.

    Carbonation Resistance for 3mm thickness R~12.5M.

    c. Water Absorption Coefficient W W ~ 0.02 Kg/m2 X h0.5 acc. To

    DIN 52 617.

    d. Water Vapor Diffusion Coefficient (H2O) H2O~252 acc.

    Equivalent air Layer Depth for 3mm Thickness SD~0.75m.

    e. EModulus Static: ~19.9 KN/mm2 (at +20oC)

    ~23.2 KN/mm2 (at 20oC).

    f. Compressive Strength 60 N/mm2 as per IS 91621979.

    g. Flexural Strength 18 N/ mm2 as per IS 91621979.

    h. Bond Strength 4.1 N/ mm2 according to EN 138928.

    i. Production Description A three part, Epoxy modified

    Cementitious, fine textured mortar for self smoothing floor screeds

    used as temporary barrier.

    16. Particle emission Certificate according to CSM statement of

    Qualification ISO 146441, class3.

    17. Out gassing Emission Certificate according to CSM statement of

    Qualification ISO 146448, class3.

    Construction/Configuration:

    Details of construction above concrete floor are as follows,

    1. Epoxy Moisture barrier to avoid any moisture relateddeboning/blisters of floor in future or during application.

    2. Epoxy Scrape coat as per requirement depending on actual condition

    of concrete substrate.

    3. Primary coat as binder.

    4. Electrodes as per requirements to be embedded inside the floor (NO

    cupper strips/copper grid or external lying of electrodes are permitted).

    5. Epoxy Conductive code for providing uniform conductivity of ESD

    flooring.

  • 7/30/2019 Epoxy and ESD Flooring

    3/4

    6. Epoxy load bearing top coat of required thickness and color as per

    our selection from RAL Shade.

    General Condition:

    1. Warranty to be provided for blisters, de bonding and loss of ESD

    property due to material degradation.

    2. Scratch resistance coating and preventive maintenance

    methodology, facility, provision to be provided.

    3. After sale service to be provided immediately for full warranty period

    free of cost.4. Repair, relaying charges will be paid for repair, relaying etc due

    damages caused by us on actual.

    Substrate Requirement:

    1. Compressive strength of concrete should be floor more than

    25N/mm2.

    2. Pull out strength of concrete should be more than 1.5N/mm2.

    3. Undulation of floor less than 5mm on a span of 10meter.

    4. Floor surface to be free from laitance, grease, oil,

    inorganic/organic acids, polyurethane etc.

    5. Surface should be free from voids, cracks, potholes etc.

    6. High spots to be eliminated.

    7. Metal panels/parts to be eliminated.

    8. Expansion joints if any to be identified.

    9. At least 15mm clearance to be provided from floor to door etc.

    27

    Providing 2mm thick hard, abrasion resistant, robust solvent free epoxy

    flooring (Non ESD flooring) with the following specifications.

    sqm 960 Rs 1356/ Rs 13,01,760/

    1. Surface Preparation

    Prepare the dry concrete surface using proper diamond grinding

    equipment to remove any loose material, contaminations and laitance

    to provide a sound, fine gripping surface. Clean the entire floor area

    using a powerful industrial vacuum cleaner.

    2. Providing and applying 2 part water dispersed epoxy resin primer

    Sikafloor80 Primer approx at the rate of 0.3 kg/sqm

    3. Installation of underlay Moisture barrier 2mm

    Providing and applying three part, self smoothing, solvent free,

    moisture barrier epoxy modified cement screed Sikafloor 81 EpoCem

    at thickness of 2mm @ approx. 4.5 kg/m having Carbon dioxide

    diffusion coefficient CO = 4168 as per Klopfer Engelgried method,

    water vapour diffusion coefficient HO=252 as per DIN 52615, Water

    absorption coefficient W=0.02 kg/m as per DIN 52617. When applied

    at minimum 2mm thickness it can be laid over high moisture content

    substrate and must be used when substrate moisture is more than 4%.

    4. Providing and applying epoxy resin based primer Sikafloor 161

    shall be applied. The primer is a two component A and Component B;

    the mixing ration would be 79:21, by weight.

    5. Installation of self laveling epoxy requirement

  • 7/30/2019 Epoxy and ESD Flooring

    4/4

    Providing and applying four part, self smoothing solvent free, coloured,

    smooth glossy, epoxy resin screed Sikafloor266CR@ approx. 2.5

    kg/m (including Sikadur 501) having compressive strength of N/mm

    EN 138922, Flexural strength of 39N/mm as per EN 138922, Shore D

    Hardness 84 As per DIN 53 505 abrasion resistance 45mg (CS

    10/1000/100) DIN 53 109 (Taber Abrader Test). All in complete as per

    the manufacturers specifications and directions of the engineer in

    charge.

    52

    Providing water proofing treatment with two coats of polyurethane of

    approved manufacture "UNISEAL WS1" / "TECHCOAT61P" or

    equivalent for the sunken floors. The sunken slab and the side vertical

    walls should be finished smooth with cement plaster (Cement plaster

    will be measured and paid for separately as an item), the surface should

    be absolutely dry, free from dust, grease, oil and loose particles.

    Providing necessary scaffolding wherever required and cleaning the

    surface etc., complete all as per the manufacturer's specifications.

    NOTE:

    1) The sunken floor shall be tested after the treatment for water

    tightness by impounding water for a period of 48 hours.

    2) Performance guarantee for a period of 10 years be obtained from the

    contractors/manufacturers of the paint.

    sqm 275 Rs 578/ Rs 1,58,950/

    3) The coverage capacity for "UNISEAL WS1" or equivalent for a

    smooth surface should be 3.717sqm/kg (40sft/kg) for the first coat and

    4.647sqm/kg (50sft/kg) for the second coat and for a roughsurface the

    coverage should be 2.788 sqm/kg (30 sft/kg) for the first coat and 3.717

    sqm/kg (40 sft/kg) for the second coat respectively as per the

    manufacturer's specifications. The coverage capacity for "TECHCOAT

    61P" (Rubber based polyurethane) or equv, for a smooth surface should

    be 4.182sqm/ltr (45 sft/ltr) for the first coat and 4.647sqm/ltr (50sft/ltr)

    for the second coat and for a rough surface the coverage should be

    3.717 sqm/ltr (40sft/ltr) for the first coat and 4.182sqm/ltr (45sft/ltr)

    for the second coat respectively as per the manufacturers specification

    at all heights.Total Rs 76,33,294/

    Terms & condistions:

    1. The above mentioned work will done by our Authorised applicator

    M/s SK Engineers, Hyderabad with Dr Fixit Materials with in 1 months

    once we receive the WO & Advance at our end.

    2. Taxes are extra on the aove mentioned price.

    3. Payment: 60% of the WO must be as an advcance , 25% as an RA bills

    & balnace after completion of the work.

    4. The work order must be on the name of M/s SK Enigneers,

    Hyderabad.

    4. Cement, Sand, Water , babychips, electricity , bricks & labouraccomodation will be paid by you with the free of cost for this work.

    regards

    Sreekanth G

    ASM CC Projects

    Pidilite Industries Ltd

    Hyderabad

    9849401362