engineering projects ( india ) ltdengineeringprojects.com/tender/uploadfiles/3228_vol-iii.pdf ·...

23
AN ISO 9001 & 14001 COMPANY TENDER DOCUMENT TENDER No: DLI/CON/710/563 FOR External & Internal Electrical works including Supply, Installation, Testing & Commissioning of Transformers, Electrical HT/LT Panels, Air-conditioning & Fire Fighting works for 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No.04- 3333, Action Area 1D, New Town, Kolkata”. VOLUME III PRICE BID/ BILL OF QUANTITY

Upload: others

Post on 30-Jan-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

AN ISO 9001 & 14001 COMPANY

TENDER DOCUMENT

TENDER No: DLI/CON/710/563

FOR

“External & Internal Electrical works including Supply, Installation, Testing & Commissioning of Transformers, Electrical HT/LT Panels, Air-conditioning & Fire Fighting works for 1st Phase (B+G+IV) of Administrative Building of New

Town Kolkata Development Authority at Plot No. DG/13, Premises No.04-3333, Action Area – 1D, New Town, Kolkata”.

VOLUME – III

PRICE BID/ BILL OF QUANTITY

Page 2: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Tender No: DLI/CON/710/563 Dated 13.02.2017

In figures In words In figures In words

1

External & Internal Electrical works

including Supply, Installation,

Testing & Commissioning of

Transformers, Electrical HT/LT

Panels, Air-conditioning, Generators

& Fire Fighting works for 1st Phase

(B+G+IV) of Administrative Building

of New Town Kolkata Development

Authority at Plot No. DG/13,

Premises No.04-3333, Action Area –

1D, New Town, Kolkata.

BIDDER'S FINANCIAL OFFER : Rs. (In Figure)

Rupees (In Words)

SL.

No.

Tender for External & Internal Electrical works including Supply, Installation, Testing & Commissioning of

Transformers, Electrical HT/LT Panels, Air-conditioning, Generators & Fire Fighting works for 1st Phase

(B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises

No.04-3333, Action Area – 1D, New Town Kolkata.

QUOTING SHEET

AMOUNT IN Rs. (after adding percentage

above, at par or below)

Rs. 7,13,23,260.00

(Rupees Seven

Crores Thirteen

Lakhs Twenty Three

Thousand Two

Hundred and Sixty

Only)

Seal & Signature of Bidder

DESCRIPTION ESTIMATED COST

(IN Rs.)

BIDDER'S PRICE

% QUOTE ABOVE /AT PAR/ BELOW

Page 3: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Engineering Projects (India) Ltd. (A Govt. Of India Enterprise)

Abstract Sheet

Tender No: DLI/CON/710/563

Tender for “External & Internal Electrical works including Supply, Installation, Testing & Commissioning of Transformers, ElectricalHT/LT Panels, Air-conditioning& Fire Fighting works for 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No.04-3333, Action Area – 1D, New Town Kolkata”.

Total Estimated Value: Rupees .Seven Cores thirteen lakh twenty thousand two hundred sixty only.

Note : The above prices are including of all taxes and duties etc..

Sl.No. Item Description Value(in Rs.)

1 HT Sub-Station 10997060.42

2 Generator & AMF panel 9619588.29

3 Air condition system with VRF 24635119.00

4 Compound Lighting 5470262.29

5 Fire 14812025.25

Total 65510055.25

Add Tender Premium-1 @ 8.44% 5529048.66

Total 71039103.91

Add Tender Premium-2 @ 0.40% 284156.41

Total= 71323260.32

Say= 7,13,23,260.00

Page 4: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 ELECTRICAL SECTION -I ( Sub Station)

Transformer & Accessories

Supply, installation, testing and commissioning of 750KVA, 11/0.433KV, 3 Phase, 4 wire, 50 Hz, ONAN transformer for indoor

duty with a -20% to +5% Off-load tap changer in the step of 1.25%, cable box at primary and secondary end with double float

buchholz relay protection, high winding & oil temparature sensors - Alarm & Trip, and at neutral earthing conductor with

control cabling from transformer to HT Breaker (to trip primary breaker) complete with all fittings, interconnection of control

cables and accessories , first filling of oil as per detailed technical specifications and as required.(Voltamp / ABB / Areva / Tesla)

2 Set 1,499,432.87 2,998,865.74

HT Panel

Supply, delivery, erection, testing and commissioning of Three (3) panel, 630 Amps, 11KV, 3-Phase, 50HZ, metal clad, dead

front, 350MVA rupturing capacity Vacuam Circuit Breaker as per the detailed specifications and drawings including

connections, etc. complete with following incommers and outgoings as required.(Siemens / ABB / Areva)

Incommer:

1 No. VCB Pannel having the following.

1 No. 630A, 11KV, 3 Phase, 50HZ, metal clad, dead front, 350 MVA rupturing capacity, Fully drawout type , Vacuum Circuit

Breaker(Breaker Breaking capacity -25KA).

1 No. 11KV/110V resin cast Potential Transformer with HRC fuses.having accuracy class-1 for metering

1 set of Phase indicating lamp with HRC fuses.

1 No. 0-15KV voltmeter with selector switch

1 set of indicating lamps to indicate ON,OFF,TRIP ,Spring Charge & TRIP CIRCUIT HEALTHY.)

2 No. Push Buttom for CLOSE and TRIP.

1 no.Trip /Neutral/Close Switch

1 no.Local/Remote Switch

1 No. 100/5-5A Current Transformer for metering and protection(accuracy class-

-0.5 for metering & 5P10 for protection)

1 No 0-100 Amps ammeter with selector switch.

1 set of CDG 61(2 No.O/C, 1 No. E/R relay (electromagnetic/electrostatic)

1 set of Undervoltage relay and Overvoltage relay.(Electromagnetic)

1 no 30V DC shunt trip coil & 1 no.30V DC closing coil.

1 No. Master Trip relay.(Electromagnetic)

1 No. Power factor meter.

1 no.Trivectormeter

1 no.Frequency Meter

Busbar:

11 KV, 350 MVA, 800 Amps Three Phase busbars of Cu.for Incomer & Outgoing

2 nos.Outgoings:

1 No. VCB Pannel having the following

1 No. 630A, 11KV, 3 Phase, 50HZ, metal clad, dead front, 350 MVA rupturing capacity, Fully drawout type , Vacuum Circuit

Breaker(VCB breaking capacity -25KA)

1 set indicating lamps to indicate ON, OFF, TRIP, SPRING CHARGED, TRIP CIRCUIT HEALTHY.

2 No. Push Buttom for CLOSE and TRIP.

1 no.Trip/Neutral/Close Switch

1 no.Local/Remote Switch

1 No. 50/5-5A Current Transformer for metering and protection.

1 No 0-50 Amps ammeter with selector switch.

1 set of CDG 61(2 No.O/C, 1 No. E/R relay (Electromagnetic/electrostatic).

1 No Master Trip Relay(Electromagnetic).

2 Set ofAuxiliary relay Buchholz,Oil & winding temp Protaction with alarm and trip signals.(Electromagnetic)

1 no.buzar with Push Buttor for common to the Switchboard

H.T. Panel as mentioed above

Electrical Interlocking between HT,LT & Generator set will be done accordingly as per scheme.Necessary scheme will be

intimated at the time of drawing approval.

3 Battery Chager:

Supply, delivery, erection, testing and commissioning of the battery charger panel complete with battery control cabling, etc.

as required.

Rate shall also include provision of minimum 200 AH 30/24 volt SMF.

VRLA Battery including Float cum Boost Thyrister/IGBT controlled.

battery charger with one no. as Hot standby suitable for operation at

240 volt AC 50 Hz supply,

1 No. AC Voltmeter (0 - 500 Volt).

1 No. DC Voltmeter.

1 No. DC Ammeter.

1 set of AC and DC indicating lamps.

1 No. DC Battery charging position indicator.

DCDB with 63A DP MCB as incomer and 16 nos SP MCB as outgoing complete as per specifications and suitable to above.

Control cabling between DC Distribution panel to the HT panel of the Substation with cable size 4C X 2.5 Sqmm. Copper cable.

Battery Charger Panel as mentioned above

1 set 223,948.31 223,948.31

4 Safety Equipments

Supply and laying of 12 KV grade, 12mm, 1 metre wide anti skid chequered type rubber mat.100 sqmm 869.61 86,961.00

5 Supply and laying of 1.1 KV grade 12mm, 1 metre wide anti skid chequered type rubber mat. 500 sqmm 417.13 208,565.00

6 Supply and installation of Fire Buckets 13 litre capacity 4 Nos. duly filled with sand and GI pipe support stand for these buckets

including painting, etc. complete as required.4 Set 1,457.43 5,829.72

7 Supply and fixing shock treatment chart in English, Hindi and local language mounted on 5mm. Thick plywood and 3mm. Thick

plain glass front complete as required.4 Set 325.22 1,300.88

8 Supply and fixing of ISI marked 6.5 kg Co2 type portable fire extinguisher with necessary clamps, supports and trolley in Panel

room approved by ISI complete as required. 6 Set 7,374.01 44,244.06

ENGINEERING PROJECTS (INDIA) LIMITED

( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04-3333, Action Area - 1D, New Town

Kolkata

Tender No: DLI/CON/710/563

BILL OF QUANTITIES

1 set 1,716,938.39 1,716,938.39

2

Page 5: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

9 Supply, storing, handling and fixing in position First Aid Medical Box and an 'Artificial Respirator' complete as per technical

specifications as required.5 Each 522.17 2,610.85

10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12 1,034.24

11 Supply, installation, testing and commissioning of self contained emergency light unit consisting of 1X20 watt fluorescent tube

and dry type SMF battery for 1 hour backup complete as required.2 Each 2,012.93 4,025.86

12 H.T. Cables

Supply, laying, testing and commissioning of following sizes of 11KV grade multicore aluminium conductor XLPE armoured

power cable directly in duct/hume pipe as per IS : 7098(contractor to measure exact required quantity before supply as per

installation position) (Nicco / Polycab)

12.1 3C X 240 Sq.mm. 200 M 2,421.98 484,396.00

12.2 3C X 120 Sq.mm. 69 M 1,498.84 103,419.96

13 H.T. Cable Terminations.

Supplying and making end termination with heat shrinkable jointing kit(outdoor type) with Raychem kits complete with all

accessories including lugs suitable for following size 3 core, XLPE aluminium conductor cable of 11KV grade as required.

13.1 3C X 240 Sq.mm. 1 Each 19,311.20 19,311.20

13.2 3C X 120 Sq.mm. 1 Each 19,311.20 19,311.20

14 Supplying and making end termination with heat shrinkable jointing kit(indoor type) with Raychem kits complete with all

accessories including lugs suitable for following size 3 core, XLPE aluminium conductor cable of 11KV grade as required.

14.1 3C X 240 Sq.mm. 3 Each 12,401.79 37,205.37

14.2 3C X 120 Sq.mm. 4 Each 11,852.35 47,409.40

15 Supply and laying of following sizes non pressure NP2 class(light duty) RCC pipe(300mm) with collar joint with stiff mixture of

cement (1-cement : 2-fine sand) including testing the joints, etc. as per specification and required. 15 Metre 792.85 11,892.75

15.1 Cable Tray

Supply and Erecting of perforated type Hot dip G.I. cable tray of 14G of specific dimensions. The cable tray shall be hung from

ceiling/ fixed to wall with necessary ceiling suspensors, tee, nots, nuts etc, together with tees, bends etc. All necessary

required hard ware for mounting cable tray along with fabricated supports as per site condition shall be included in cable tray

rate. The tray shall be continuously earthed with included in cable tray rate. The tray shall be continuously earthed with 25 x 6

mm GI Flat. The cost of GI Flat shall be included along with cable tray rates complete as per specification.(Rattan Eng.)

15.2 150 x 75 mm 200 Meter 909.00 181,800.00

15.3 300 x 75 mm 150 Meter 1,616.00 242,400.00

16 LT CABLES

Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable supports provided, include

unloading, shifting upto site. The scope includes clamping of cables by ready made G.I. spacers, saddles or clamps fabricated

out of GI strip 3 mm thick. (NICCO /POLYCAB /SKYTONE / NATIONAL / GLOSTER/ECKO)

16.1 4C X 16Sq.mm. - Al stranded for Substation & lighting panel 350 Metre 197.96 69,286.00

16.2 3.5C X 300Sq.mm. - Al for FIRE PNL & Rising Main 160 Metre 1,356.43 217,028.80

16.3 3.5C X 400Sq.mm. - Al for trf, capacitor pnl, VRF & DG Set 550 Metre 1,732.15 952,682.50

17 LT Cable Terminations: Supplying & fixing of double compression type Brass glands & making joint with necessary AL. / CU.

crimping socket of long neck type connecting the same to various equipment like section pillar, switch, starter, motor etc. for

the following sizes:(COMET/ CONNECT WEL/ DOWELS)

17.1 4C X 16Sq.mm. - Al 4 End 104.54 418.16

17.2 3.5C X 300Sq.mm. - Al 8 End 631.76 5,054.08

17.3 3.5C X 400Sq.mm. - Al 32 End 631.76 20,216.32

18 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type connecting the same to various

equipment like section pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

18.1 4C X 16Sq.mm. - Al 4 Set 99.99 399.96

18.2 3.5C X 300Sq.mm. - Al 8 Set 1,422.59 11,380.72

18.3 3.5C X 400Sq.mm. - Al 32 Set 2,111.91 67,581.12

DISTRIBUTION PANEL

Main L.T panel complete as per Technical Specifications/ data sheets/ SLD and applicable standards.

Supply, delivery, erection, testing and commissioning of LT Panel, cubicle type, totally enclosed, free standing type, dust, damp

and vermin proof panel made up of 14 SWG CRCA sheet, complete with copper busbars, danger notice plate, interconnections

with suitable capacity copper leads / solid copper strips/rods, necessary interlocking, power coat painted and having incoming

and outgoing switchgears as mentioned below and complete as per technical specifications and as required.

1. All ACBs shall have 5 NO + 5 NC contacts

2. All relays to operate at 240Volts, Single phase, 50Hz, AC supply through UPS

Incommer:

2 Nos. ACB Panels each having following.

1 No. 1250A, 415/500V, Rated service short circuit rupturing capacity (Ics) 50 KA, Motorised, Fully Drawout type(EDO), Four

Pole, Air Circuit Breaker with microprocessor based overload, short circuit & earth fault trip including under voltage release

and lockable trip push button. ACB should have Icw=50KA for 1 sec.(L&T / ABB )

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB.

R, Y, & B Phase indicating lamps with 2A control SP MCBs

1000/5A CTs with CT shorting links for power factor inprovement panel suitable for giving signal to APFCR at less than 10% of

secondary ratio current.

All Incoming ACBs shall have multi function meter - parameters - digital multifunction meter EM6400 or equivalent shall

indicating A / V / KWH / PF / FREQ / DM / VAR with RS-485 port with suitable CTs, CT shorting links.

Busbar:

Set 2,327,487.43 2,327,487.43

19

1

Page 6: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

2000 AMP,50KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current ratio shall be 1 sq mm = 0.8 A.

Buscoupler:

1 Nos. ACB Panels each having following.

1 No. 1250A, 415/500V, Rated service short circuit rupturing capacity (Ics) 50 KA, Motorised, Fully Drawout type(EDO), Four

Pole, Air Circuit Breaker with microprocessor based overload, short circuit, Instanteneous & earth fault trip including under

voltage release and lockable trip push button. The ACB should have Icw=35KA for 1 sec.(L&T / ABB ).

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP

Push button to CLOSE the ACB

1 set of meter with ASS and CTs

OUTGOINGS:

5 No. MCCB as per following details / specifications:

630 Amps, 415V, 50KA(Ics) FP MCCB with variable current settings of 0.4 to 1.0 In and having microprocessor based O/L, S/C &

E/F protection release.(Legrand / L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB..

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

3 No. MCCB as per following details / specifications:

500 Amps, 415V, 35KA(Ics) FP MCCB with variable current settings of 0.4 to 1.0 In and having microprocessor based O/L, S/C &

E/F protection release.(Legrand / L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB

R,Y & B phase indicating lamps(LED type)with 2A control SP MCBs.

2 No. MCCB as per following details / specifications:

250 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /

L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.

2 No. MCCB as per following details / specifications:

150 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /

L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.

2 No. MCCB as per following details / specifications:

100 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /

L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.

4 No. MCCB as per following details / specifications:

63 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /

L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.

All Outgoing MCCBs shall have multi function meter - parameters - digital multifunction meter shall indicating A / V / KWH

with RS-485 port with suitable CTs, CT shorting links.

ASS/VSS : Make - KAYCEE/ L&T.

Main LT Panel as mentioned above (T/N/C switch should be provided all the Incomer/Outgoing/Buscoupler panel)

Electrical Interlocking between HT,LT & Generator set will be done accordingly as per scheme.Necessary scheme will be

intimated at the time of drawing approval.

19.3 Capacitor Panel (250 KVAR)

Supply, installation, testing, and commissioning of M.V. cubicle type, 14 SWG CRCA Sheet, totally enclosed free standing type,

dust, damp and vermin proof capacitor panel complete with busbars, M.V. danger notice plate, ammeter, ammeter selector

switch, indicating lamps, CT's , Extra heavy duty capacitors suitable for non linear loads upto 20% (L&T model MD-XL or

equivalent), contactors suitable for capacitor switching(current limiting contactor circuit to supress switching inrush current)

interconnections with suitable capacity aluminium leads / solid aluminium strips, rods, connection of incoming and outgoing

cables with thimbles, stove enamelled painted and having following incoming and outgoing switchgears complete as required.

Incommer:

1No. 500A, 415/500V , 35KA rupturing capacity, FP Moulded Case Circuit Breaker with thermal magneticx release having

varible current setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should have

spreader links & phase barriers.

1 set of phase indicating lamps with HRC fuses.

Incoming MCCB shall have multi function meter - parameters - digital multifunction meter shall indicating A / V / PF / VAR with

RS-485 port with suitable CTs, CT shorting links.

Busbar:

630 AMP,35KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current ratio shall be 1 sq mm = 0.8 A

Outgoings:

1 No. 100 KVAR capacitor bank each with 250 Amps TPN MCCB, 250A TP contractor suitable for capacitor switching with push

buttons and indicators.(Legrand / L&T /Havells)

Set 2,327,487.43 2,327,487.43

2 Set 430,027.70 860,055.40

19

1

Page 7: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 No. 50 KVAR capacitor bank each with 125 Amps TPN MCCB, 100A TP contractor suitable for capacitor switching with push

buttons and indicators.(Legrand / L&T /Havells) suitable for capacitor switching with push buttons and indicators.(Legrand /

L&T /Havells)

1no.40KVAR capacitor bank each with 100Amps TPN MCCB,100A TP contractor suitable for capacitor switching with push

button and indicators (Legrand/L&T/Havells)

1 No. 30 KVAR capacitor bank each with 63 Amps TPN MCCB, 63A TP contractor suitable for capacitor switching with push

buttons and indicators.(Legrand / L&T /Havells)

1 No. 20 KVAR capacitor bank each with 63 Amps TPN MCCB, 63A TP contractor suitable for capacitor switching with push

buttons and indicators.(Legrand / L&T /Havells)

1 No. 10 KVAR capacitor bank each with 32 Amps TPN MCCB, 32A TP contractor

suitable for capacitor switching with push buttons and indicators.(Legrand / L&T /Havells)

1 No. Electronic type, microprocessor based, Automatic power factor correction relay in 8 steps

10,973,060.42

2 Set 430,027.70 860,055.40

Page 8: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 Electrical Section II (Generator & AMF Panel )

LT cables

Supply ,Laying of cables on cable trays/Hume pipes/structural supports/undergrounds and

cable supports provided ,include unloading ,shifting upto site.The scope includes clamping of

cables by ready made G.I spacers,saddles or clamps fabricated out of GI strip 3 mm

thick.(Polycab/Havells/KEI)

3.5CX400sq.mm -for DG set

650 Metre 1,732.51 1,126,131.50

2 LT Cable Terminations

Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /

CU. crimping socket of long neck type connecting the same to various equipment like section

pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS).

3.5C X 400Sq.mm. - Al

32 End 631.76 20,216.32

3 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for the

following sizes:(COMET/ CONNECT WEL/ DOWELS).

3.5C X 400Sq.mm. - Al32 End 2,111.91 67,581.12

DG Set & accessories

Supply, installation, testing and commissioning of sound proof 750 KVA Diesel Generator set

comprising of water cooled radiator type, Diesel Engine with rated capacity of suitable BHP at

1500 rpm, direct injection type, 4 stroke, with suitable no. cylinders coupled to 750 KVA

brushless type 415 Volts, 50HZ, self exciting Alternator with suitable size of flexible coupling

and following main components, complete with all accessores conforming to technical

specifications and as required. Make :Kirloskar.

Cooling System : water cooled radiator type.

Exhaust System : Pipe, Chimney, silencer and supports (as approved by Pollution Control Board

/ Local Authorities ).

Fuel system : Day tank (990 litres-2 nos.) and their interconnecting piping system.

Lube oil system.

Air system.

Electronic Governer.

Starting System.

Coupling arrangement.

safety controls.

Instrument panel for engine.

Control panel with metering, interlocks and annunciations complete as per specifications.

Batteries, Boost and trickle battery charger.

Provision of Busduct connection from alternator terminals to AMF Panel, control cable, neutral

and equipment earthing complete as required.

Spring loaded cushy pads, foundation bolts, etc

Making cement concrete foundation with 1:2:4(1 cement ,2 course sand,4 graded

stone aggregate 40mm nominal size)suitable for DG set as perr recommendation of

manufacturer .

Sound proof canopy with openable doors,fresh air fans,control panel,as per requirement of

Pollution Control Board

All other minor civil,mechanical works including material supply and electrical works complete

as required..

This includes protection relays, meters etc complete. control cabling from AMF

DG set mentioned as above panel.

panel to DG set & LT panels is deemed to be included in this item.

AMF - PANEL (FOR 750 KVA ABOVE DG SET)

Supply, installation, testing and commissioning of M.V. cubicle type totally enclosed free

standing type, dust, damp, and vermin proof capacitor panel complete with busbars, M.V.

damper notice plate, ammeter, ammeter selector switch, voltmeter, voltmeter selector switch,

PF meter indicating lamps, CTs,

interconnections, interlocking between two feeders and bus coupler, with suitable capacity

aluminium leads / solid alumionium strips / rods, connection of incoming & outgoing cables

with thimbles, stove enamelled painted and having following incoming and outgoing

switchgears and as per technical bapecifications & as required.

1 Set 8,405,659.35 8,405,659.35

4

ENGINEERING PROJECTS (INDIA) LIMITED

( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04-3333,

Action Area - 1D, New Town Kolkata

Tender No: DLI/CON/710/563

BILL OF QUANTITIES

Page 9: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

1 No. ACB Panels each having following.

1 No. 1250A, 415/500V, rated service short circuit rupturing capacity (Ics) 50 KA, mororised,

fully drawout type(EDO), four pole, Air Circuit Breaker with microprocessor based overload,

short circuit & earth fault trip including under voltage release and lockable trip push button

ACB should have Icw=50KA for 1 sec.

1 set of indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB.

Push button to CLOSE the ACB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.

Incoming ACB shall have multi function meter - parameters - digital multifunction meter shall

indicating A / V / KWH with RS-485 port with suitable CTs, CT shorting links.

AMF Cubicle

1 No. frequency meter (45-55 HZ.)

1 set under voltage relay.

1set over voltage relay.

1 set under frequency relay.

1 set of Master trip / supervisory relay.

1 set of battery charger (with tricle and boost charger.).

1 set of DC voltmeter and ammeter.

1 set of Reverse power and Reactive power relay.

1 set R, Y, B, Breaker ON/OFF & other fault indication lamps.

1 set 8 window Alarm annunciator with separate hooter, accept, reset and rest push button.

1 No. Hooter.

1 No. Engine Cranking Relay.

1 set of Main supply voltage monitor, alternate voltmeter monitor and Engine starting relays.

1 set of Auxiliary relays, timer, push button and control fuses.

ENCLOSURE

Fabrication, PVC sleeving, control/ power wiring and necessary hardware for complete AMF

Panel

Total of DG Set & AMF Panel.

Electrical Interlocking between HT,LT & Generator set will be done accordingly as per

scheme.Necessary scheme will be intimated at the time of drawing approval.

9,619,588.29

1 Set 8,405,659.35 8,405,659.35

4

Page 10: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1.0 Electrical Section III ( AIR-CONDITIONING SYSTEM)

Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable

supports provided, include unloading, shifting upto site. The scope includes clamping of cables

by ready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick.

(KEI/POLYCAB /Havells)

0.00

1.1 3.5C X 95Sq.mm. - Al basement ventilation PNL 120 Metre 532.27 63,872.40

1.2 3.5C X 400Sq.mm. - Al for VRF PNL 550 Metre 1,732.51 952,880.50

2.0 LT Cable Terminations

Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /

CU. crimping socket of long neck type connecting the same to various equipment like section

pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

2.1 3.5C X 95Sq.mm. - Al 6 End 324.21 1,945.26

2.2 3.5C X 400Sq.mm. - Al 32 End 631.76 20,216.32

3.0 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for the

following sizes:(COMET/ CONNECT WEL/ DOWELS)

3.1 3.5C X 95Sq.mm. - Al 6 End 349.97 2,099.82

3.2 3.5C X 400Sq.mm. - Al 32 End 2,111.91 67,581.12

VRF Main Panel

Supply, installation, testing and commissioning of following outdoor type with sloping canopy

on the top, double door, M.V cubicle type totally enclosed, 14 SWG CRCA Sheet, IP-54

protected, free standing type, dust, damp and vermin proof, Distribution Board/Panel complete

with busbars, M.V. danger notice plate, interconnections with suitable capacity aluminium

leads/solid aluminium strips/rods, connection of incomming and outgoing cables with thimbles,

powder coat painted and having following incoming and outgoing switchgears complete as

required.

Incommer:

630 Amps, 415V, 50KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock

facility. MCCB should have spreader links & phase barriers.

1 set of phase indicating lamps with 2A SP control MCB.

Incoming MCCB shall have multi function meter - parameters - digital multifunction meter shall

indicating A / V with RS-485 port with suitable CTs, CT shorting links.

Busbar:

1000 AMP,50KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current ratio shall

be 1 sq mm = 0.8 A

Outgoings:

4 sets of the following:

150 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

1 set of phase indicating lamps with 2A SP control MCB.

1 No. 0-200 Amps ammeter with selector switch and CT's 200/5A.

3 sets of the following:

100 Amps, 415V, 10KA(Isc), FP MCCB with phase indicating lamps.

1 set of phase indicating lamps with 2A SP control MCB.

1 No. 0-100 Amps ammeter with selector switch and CT's 100/5A.

2 sets of the following:

63 Amps, 415V, 10KA(Isc), FP MCB with phase indicating lamps.

1 set of phase indicating lamps with 2A SP control MCB.

1 No. 0-100 Amps ammeter with selector switch and CT's 100/5A.

All MCBs are C-series type.

1 Set 266,640.00 266,640.00

4.0

ENGINEERING PROJECTS (INDIA) LIMITED

( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04-

Tender No: DLI/CON/710/563

BILL OF QUANTITIES

Page 11: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Basement Ventilation Panel:

Supply, installation, testing and commissioning of following M.V cubicle type totally enclosed,

14 SWG CRCA Sheet, IP-54 protected, free standing type, dust, damp and vermin proof,

Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections

with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incomming

and outgoing cables with thimbles, powder coat painted and having following incoming and

outgoing switchgears complete as required.

Incommer:

150 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock

facility. MCCB should have spreader links & phase barriers.

1 set of phase indicating lamps with HRC fuses.

Incoming MCCB shall have multi function meter - parameters - digital multifunction meter shall

indicating A / V with RS-485 port with suitable CTs, CT shorting links.

Busbar:

200 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current

ratio shall be 1 sq mm = 0.8 A.

Outgoings:

3 set of the following (Axial flow exhaust fan).

32 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock

facility. MCCB should have spreader links & phase barriers.

1 No. 3 Phase, DOL Starter for 7.5KW, pump motor with TP contactors, thermal overload relay,

Timer, Local Push Push Buttons and Auto-manual selector switch.

Single Phase preventer.

1 set of phase indicating lamp bwith 2A SP control MCBs.

Indicating Lamps for ON / OFF / TRIP indication with 2A SP control MCBs.

1 No. 0-100 Amps ammeter with selector switch and CT's 100/5A.

4.4 7 set of the following (Jet Fan)

32 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock

facility. MCCB should have spreader links & phase barriers.

1 No. 3 Phase, DOL Starter for 3.7KW, pump motor with TP contactors, thermal overload relay,

Timer, Local Push Push Buttons and Auto-manual selector switch.

Single Phase preventer.

1 set of phase indicating lamp with 2A SP control MCBs.

Indicating Lamps for ON / OFF / TRIP indication with 2A SP control MCBs.

1 No. 0-100 Amps ammeter with selector switch and CT's 100/5A.

All Outgoing MCCBs shall have multi function meter - parameters - digital multifunction meter

shall indicating A / V with RS-485 port with suitable CTs, CT shorting links.

1 Set 571,188.33 571,188.33

5.0 Supply of Aircooled Digital Scroll VRF SYSTEM Unit with R 410a Refrigerant, Aircooled

Condenser along with inbuilt microprocessor panel.

OUTDOOR UNIT (Mitsubishi,Carrier midea,Blue Ster)

5.1 63 HP - GROUND FLOOR 1 Each 1,405,420.05 1,405,420.05

5.2 12 HP - GROUND FLOOR 1 Each 359,455.97 359,455.97

5.3 63 HP - FIRST FLOOR 1 Each 1,405,420.05 1,405,420.05

5.4 57 HP - SECOND FLOOR 1 Each 1,332,695.00 1,332,695.00

5.5 54 HP - THIRD FLOOR 1 Each 130,949.53 130,949.53

5.6 50 HP - FOURTH FLOOR 1 Each 1,282,650.51 1,282,650.51

6.0 VRF INDOOR UNITS

6.1 COMPACT CASSETTE UNIT 0.6 TR 8 Each 33,979.43 271,835.44

6.2 COMPACT CASSETTE UNIT 0.6 TR 16 Each 34,277.38 548,438.08

6.3 LARGE CASSETTE UNIT 2.8 TR 4 Each 48,876.93 195,507.72

6.4 LARGE CASSETTE UNIT 2.3 TR 3 Each 42,089.73 126,269.19

6.5 LARGE CASSETTE UNIT 1.5 TR 1 Each 41,098.92 41,098.92

6.6 WALL MOUNTED UNIT 1.0 TR 6 Each 20,999.92 125,999.52

6.7 WALL MOUNTED UNIT 0.8 TR 4 Each 20,909.02 83,636.08

6.8 DUCTED UNIT 8.0 TR 10 Each 63,753.22 637,532.20

6.9 DUCTED UNIT 6.0 TR 6 Each 60,122.27 360,733.62

6.1 DUCTED UNIT 5.0 TR 6 Each 57,703.32 346,219.92

6.1 DUCTED UNIT 4.0 TR 11 Each 43,272.44 475,996.84

1 Set 266,640.00 266,640.00

4.0

Page 12: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

6.1 DUCTED UNIT 3.0 TR 6 Each 34,540.99 207,245.94

6.1 5.5 TR TREATED FRESH AIR UNIT 2 Each 47,614.43 95,228.86

6.1 3.5 TR TREATED FRESH AIR UNIT 2 Each 41,843.29 83,686.58

6.2 SUPPLY OF IMPORTED REFNET JOINTS 79 Each 7,434.61 587,334.19

6.2 CORDLESS CONTROLLER 42 Each 915.06 38,432.52

6.2 CORDED CONTROLLER 39 Each 3,139.08 122,424.12

6.2 2.0 TR (3 STAR) NON VRF STAND ALONE SPLIT UNIT FOR SERVER ROOM 3 Each 45,450.00 136,350.00

7.0 Price for Supply Installation & Commissioning of Ancillary Items for VRF

7.1 Installation & Commissioning of Digital Scroll VRF Units , with outdoor mounting, pressure

testing, nitrogen flushing etc16 Each 23,583.50 377,336.00

7.2 REF ( R - 410 ) VRF 130 Kg 1,959.40 254,722.00

7.3 V I Pads- VRF 16 Set 686.80 10,988.80

7.4 Installation of VRF Indoor Units 85 Each 1,767.50 150,237.50

7.5 Installation of stand alone split unit including copper pipe, control cable between indoor &

outdoor units, refrigerant gas etc.3 Each 4,913.65 14,740.95

7.6 Installation of Axial Fan units 10 Each 3,928.90 39,289.00

7.7 Installation of jet fan units 12 Each 2,060.40 24,724.80

7.8 installation of co sensor 4 Each 1,572.57 6,290.28

7.9 Supply and Installation of imported REFNET JOINTS 1 LOT 38,814.30 38,814.30

7.1 Refrigerant Piping with insulation

Suction/ Liquid line with Nitrile rubber insulation(Nippon/Nissan/Rajco//Totaline)

7.1 1 3/8" OD 140 Rmt 1,920.01 268,801.40

7.1 15/8" OD 145 Rmt 2,232.10 323,654.50

7.1 11/8" OD 200 Rmt 1,395.82 279,164.00

7.1 7/8" OD 285 Rmt 1,094.84 312,029.40

7.2 5/8" OD 180 Rmt 805.98 145,076.40

7.2 3/4" OD 320 Rmt 968.59 309,948.80

7.2 3/8" OD 160 Rmt 507.02 81,123.20

7.2 1/2" OD 485 Rmt 604.99 293,420.15

7.2 1/4" OD 240 Rmt 369.66 88,718.40

8.0 HDPE Drain piping with insulation

8.1 40 mm. 100 Rmt 298.96 29,896.00

8.2 32 mm 200 Rmt 259.57 51,914.00

8.3 25 mm 400 Rmt 219.17 87,668.00

9.0 Electricals/Cables

Control Cable 2C x 1.5 sqmmfor VRF unit1400 Rmt 158.57 221,998.00

10.0 GSS Ducting 24G with hangers, supports etc.

10.1 24 G 1050 Sqmtr 785.78 825,069.00

10.2 22 G 300 Sqmtr 914.05 274,215.00

10.3 DUCT THERMAL INSULATION WITH13 MM AL. FOIL FACED GLASS WOOL (TAIL END) 750 Sqmtr 874.66 655,995.00

10.4 Duct Acoustic Insulation with 12 mm thick FGP (48Kg/cum) RP Tissue + 36g Aluminium

Perforated Sheet200 Sqmtr 661.55 132,310.00

10.5 Air distribution Discrete Grilles / Diffusers

10.6 GI Duct Dampers 10 Smt 4,484.40 44,844.00

10.7 Supply air grilles/diffusers air grille with VCD and air box 20 Smt 9,039.50 180,790.00

10.8 Return air grilles/diffusers air grille with VCD 28 Smt 8,682.97 243,123.16

10.9 Fresh air packaged with BIRD SCREEN/COWL/DAMPER 18 Each 4,129.89 74,338.02

10.10 Flexible fire retardent canvass connection 43 Each 2,161.40 92,940.20

11.0 BASEMENT VENTILLATION SYSTEM

Axial fan 800mm Dia Tube axial Type Fan is suitable for 3~, 400 V, 50 Hz power supply and for

300°C & 2 hrs operation.

11.1 30000 CMH 10 Each 126,250.00 1,262,500.00

11.2 315mm dia Jet Fan is suitable for 3~, 400 V, 50 Hz power supply and for 300°C & Hrs operation.

CFD analysis price is Included in our offer.12 Each 60,600.00 727,200.00

11.3 CO SENSOR 8 Each 25,250.00 202,000.00

12.0 Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable

supports provided, include unloading, shifting upto site. The scope includes clamping of cables

by ready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (Havells

/POLYCAB /KEI)

12.1 3.5C X 16Sq.mm. - PVC/Cu ARM, stranded, from VRF Panel to unit. 120 Metre 1,300.88 156,105.60

12.2 3.5C X 25Sq.mm. - PVC/Cu ARM, stranded, from VRF Panel to unit. 250 Metre 1,761.44 440,360.00

12.3 3.5C X 120Sq.mm. - PVC, Al, stranded as incommer from Rising Main 320 Metre 1,037.27 331,926.40

12.4 3.5C X 150Sq.mm. - PVC, Al, stranded as incommer from Rising Main 80 Metre 1,203.92 96,313.60

Page 13: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

13.0 Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /

CU. crimping socket of long neck type connecting the same to various equipment like section

pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

13.1 4C X 16Sq.mm. - Cu 8 End 104.54 836.32

13.2 3.5C X 25Sq.mm. - Cu 24 End 160.59 3,854.16

13.3 3.5C X 120Sq.mm. - Al 8 End 324.21 2,593.68

13.4 3.5C X 150Sq.mm. - Al 2 End 324.21 648.42

14.0 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for the

following sizes:(COMET/ CONNECT WEL/ DOWELS)

14.1 4C X 16Sq.mm. - Cu 8 End 99.99 799.92

14.2 3.5C X 25Sq.mm. - Cu 24 End 125.75 3,018.00

14.3 3.5C X 120Sq.mm. - Al 8 End 452.99 3,623.92

14.4 3.5C X 150Sq.mm. - Al 2 End 477.23 954.46

15.0 VRF Panel (Type - 1)

Supply, installation, testing and commissioning of following outdoor type Distribution Board

with sloping canopy on the top, IP-65 protected, double door, M.V. cuble type totally enclosed,

14 SWG CRCA Sheet, free standing type, dust, damp and vermin proof, MV Panel complete with

busbars, M.V. danger notice plate, interconnections witrh suitable capacity aluminium

leads/solid aluminium strips/rods, connection of incomming and outgoing cables with thimbles,

stove enamelled painted and having following incomming and outgoing switchgears complete

as required for VRF Panel.

Incommer:

125 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock

facility. MCCB should have spreader links & phase barriers.

1 set of phase indicating lamps with HRC fuses.

Incoming MCCB shall have multi function meter - parameters - digital multifunction meter shall

indicating A / V with RS-485 port with suitable CTs, CT shorting links.

Busbar:

200 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current ratio shall

be 1 sq mm = 0.8 A

Outgoings:

4 Nos. 50 Amps 415V, FP MCB, 10KA with phase indicating lamps.

1 No. 0-100 Amps ammeter with selector switch and CT's 100/5A with each feeder.

All MCBs are C-series type.

VRF Panel (Type - 1) as above.

6 set 202,000.00 1,212,000.00

VRF Panel (Type - 2)

Supply, installation, testing and commissioning of following outdoor type Distribution Board

with sloping canopy on the top, IP-65 protected, double door, M.V. cuble type totally enclosed,

14 SWG CRCA Sheet, free standing type, dust, damp and vermin proof, MV Panel complete with

busbars, M.V. danger notice plate, interconnections witrh suitable capacity aluminium

leads/solid aluminium strips/rods, connection of incomming and outgoing cables with thimbles,

stove enamelled painted and having following incomming and outgoing switchgears complete

as required for VRF Panel.

Incommer:

160 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

Extended rotary operating mechanism with door interlock with defeat feature and padlock

facility. MCCB should have spreader links & phase barriers.

1 set of phase indicating lamps with HRC fuses

Incoming MCCB shall have multi function meter - parameters - digital multifunction meter shall

indicating A / V with RS-485 port with suitable CTs, CT shorting links.

Busbar:

250 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current ratio shall

be 1 sq mm = 0.8 A.

Outgoings:

5 Nos. 50 Amps 415V, FP MCB, 10KA with phase indicating lamps.

1 No. 0-100 Amps ammeter with selector switch and CT's 100/5A with each feeder.

All MCBs are C-series type.

VRF Panel (Type - 1) as above

17.0 OTHER FITTING

17.1 32A FP SFU ISOLATOR (for 12HP outdoor unit at Gnd Fl. ) Make : Laygrad 1 No. 2,020.00 2,020.00

17.2 Supply and fixing 250 Volt , 6-10A per way, (2+6) way SPN MCBDB with SS enclosure double

door with IP 42/43 protrction with 1 no 40 A DP isolator as a incomer and 5 nos SPMCBs (C

curve 10 KA) as outgoing concelled in wall after cutting the wall and mending good damages to

original finish including interconnection with suitable size of copper wire and neutral link &

protrction for earthing attachment . Make : Legrand.

1 No. 3,354.21 3,354.21

18.0 Electrical Rising main & Tap off boxes for VRF

1 set 227,250.00 227,250.00

16.0

Page 14: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

18.1 Supply, erection, testing and commissioning of 1000 Amps, FP internally earthed Al. Rising

Main System, IP54, 50KA breaking capacity along with all necessary fabrication of supports and

other accessories works complete as per specification, through the shaft/ceiling/wall of

different floor as required including end feed units with MCCB & tap off boxes of rating as

follows at every floor . All joints / tees bends / phase change over boxes etc are deemed to be

included in the supply. Arrangement for future extention arrangement upto eight floor has to

included and complete as required of make MDS-Legrand/C&S or approved equivalent.

35 Mtr. 25,425.74 889,900.90

18.2 End Feed Unit, 1000A, ACB, 50KA 1 Each 145,736.94 145,736.94

18.3 Tap Off boxes, 160A, 25KA for Gnd Floor 1 Each 43,680.48 43,680.48

18.4 Tap Off boxes, 125A, 25KA for 1st Fl, 2nd Fl, 3rd Fl & 4th Fl. 4 Each 41,072.66 164,290.64

19.0 BASEMENT VENTILATION SYSTEM

LT CABLES

Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable

supports provided, include unloading, shifting upto site. The scope includes clamping of cables

by ready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (Havells

/POLYCAB /KEI)

19.1 3C X 2.5 Sq.mm. - PVC/Cu ARM, stranded, for Jet Fan. 300 Metre 341.38 102,414.00

19.2 3C X 10 Sq.mm. - PVC, Al, stranded, for Axial Fan 250 Metre 310.07 77,517.50

19.3 3.5C X 150 Sq.mm. - PVC, Al, stranded, as incommer. 70 Metre 1,203.92 84,274.40

20.0 Cutting channel of 40mm X 40mm size on masonry wall incl. S&F heavy gauge 19 mm dia 3 mm

thick polythene pipe by means of iron hooks and supplying and drawing 18 SWG GI Wire fish

wire incl. mending good damages to building works

1400 RM 74.49 104,286.00

21.0 Supplying and Drawing 1.1 KV, 2 x 22/0.3 (1.5 sqmm), single core, stranded, 'FR' PVC insulated&

unsheathedsingle core stranded copper wire (approved make) of the following sizes in the

prelaid 19mm dia 3mm thick polythene pipe and by the prelaid 18 SWG GI Wire fish wire and

making necy. connection as required for VRF unit/ CO Sensor.

1400 RM 40.40 56,560.00

22.0 Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /

CU. crimping socket of long neck type connecting the same to various equipment like section

pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

22.1 3C X 2.5Sq.mm. - PVC/Cu ARM, stranded, for Jet Fan. 24 End 59.09 1,418.16

22.2 3C X 10Sq.mm. - PVC, Al, stranded, for Axial Fan 20 End 104.54 2,090.80

22.3 3.5C X 150Sq.mm. - PVC, Al, stranded, as incommer. 2 End 324.21 648.42

23.0 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for the

following sizes:(COMET/ CONNECT WEL/ DOWELS)

23.1 3C X 2.5Sq.mm. - PVC/Cu ARM, stranded, for Jet Fan. 24 set 52.52 1,260.48

23.2 3C X 10Sq.mm. - PVC, Al, stranded, for Axial Fan 20 set 72.72 1,454.40

23.3 3.5C X 150Sq.mm. - PVC, Al, stranded, as incommer. 2 set 531.26 1,062.52

24,635,119.19

Page 15: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 Electrical Section IV ( COMPOUND LIGHTING )

Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable

supports provided, include unloading, shifting upto site. The scope includes clamping of cables

by ready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (Havells

/POLYCAB /KEI)

1.1 3C X 2.5Sq.mm. - PVC/Cu ARM, stranded, for Campus Lighting pnl outdoor lighting 500 Metre 127.26 63,630.00

1.2 4C X 10Sq.mm. - Al stranded for Campus Lighting pnl outgoing 500 Metre 105.04 52,520.00

1.3 4C X 16Sq.mm. - Al stranded for Substation & lighting pnl 350 Metre 139.38 48,783.00

2 Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /

CU. crimping socket of long neck type connecting the same to various equipment like section

pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

2.1 4C X 10Sq.mm. - Al, 20 End 69.69 1,393.80

2.2 4C X 16Sq.mm. - Al 4 End 69.69 278.76

3 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for the

following sizes:(COMET/ CONNECT WEL/ DOWELS)

3.1 4C X 10Sq.mm. - Al, 20 End 48.48 969.60

3.2 4C X 16Sq.mm. - Al 4 End 66.66 266.64

4 Campus / Outdoor Lighting Panel

Supply, installation, testing and commissioning of following outdoor type Lighting Distribution

Board with Synchronous Timer / Timer Circuit for automatic controlling, sloping canopy on the

top, IP-65 protected, double door, M.V. cuble type totally enclosed, 14 SWG CRCA Sheet, free

standing type, dust, damp and vermin proof, MV Panel complete with busbars, M.V. danger

notice plate, interconnections witrh suitable capacity aluminium leads/solid aluminium

strips/rods, connection of incomming and outgoing cables with thimbles, stove enamelled

painted and having following incomming and outgoing switchgears complete as required for

campus / outdoor lighting.

Incommer:

40 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current

setting of 0.8 to 1.0 In.

1 set of phase indicating lamp with HRC fuses.

Timer

All incoming with 40A DIGITAL, 365 DAYS, 24 HRS. PROGRAMMABLE TIMER with suitable

contactor.

Busbar:

100 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length - Current ratio shall

be 1 sq mm = 0.8 A

Outgoings:

4 Nos. 20 Amps 415V, FP MCB phase indicating lamps.

9 Nos. 10 Amps 415V, DP MCB phase indicating lamps.

All MCBs are C-series type.

3 set 51,533.54 154,600.62

5 Campus / Outdoor Lighting Panel as above

Supply, Installation, testing & commissioning of standard light fittings and lighting accessories

including lamp and other accessories as required.The scope shall include, providing of all

hardware such as downrod, nuts,anchor fastners, bolts, screws, cleats, clamps, Lugs, PVC

insulated wires / cables (CROMPTON GREAVES / BAJAJ / PHILIPS)

5.1 Excavation in all sorts of soils including hard rock/ murrum for required depth and back filling.

Contractor's scope of work under this item shall include disposal of surplus earth and shoring,

shuttering and dewatering if required. Excavation shall be done as per directions of Engineer-in-

charge.

600 Rmt 190.89 114,534.00

5.2 Supplying and spreading fine sand for a thickness of 100 mm. and providing and laying bricks

for cable protection. on all the three sides.600 Rmt 124.23 74,538.00

5.3 Supply & fixing of 25mm. external dia rigid PVC conduit laid in floor/wall etc for laying of

cable/GI wire by cutting & making good for damages , inclusive of all tees, bends, elbows,

reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe

hooks etc. complete as per the direction of EIC.

600 M 46.46 27,876.00

ENGINEERING PROJECTS (INDIA) LIMITED

( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04-

Tender No: DLI/CON/710/563

BILL OF QUANTITIES

Page 16: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

6 Supply, installation, testing and commissioning of 5.6 mtr above ground, seamless conical

tapering GI poles with single seamless conical tapering suitable length of GI bracket of

approved shape & suitable for mounting with 28W LED fixture & Solar Panel of approved make.

The rates shall be inclusive of necessary foundation (min. 450 x 450 x 750 mm, M:15) with

anchor bolts coping with baseplate, etc. complete. The pole shall have concealed type (flush

door with proper strengthening to the cutout of the door opening) junction box with loop in

loop out connector (bakelite connector of 15A) and MCB for fixture.

a) 40 mm diameter GI pipe with long bend for each cable entry .

b) Wiring up to the light fixture from the junction box using 3nos x 2.5 sq.mm. flexible copper

wires of specified make.

c) Excavation & back filling for erection of poles. Debris to be removed from the site to suitable

location instruction of the engineer incharge.

d) Earthing with GI earth spike, size 1822 length X 20 mm. dia directly driven in soil below

ground level & interconnection of spike with poles / looping box with 6 SWG GI wire (2 runs). GI

protection for earthing lead of suitable length (Av. 3 mtr. approx.) for pole earthing & looping

box earthing.

40 set 106,050.00 4,242,000.00

7 Supply, installation, testing and commissioning of BOLLARD, GARDINA 2, 1x26W CFL(TU),

HAVELLS CAT NO. LHLC02126099 or approved equivalent, complete with base & log

bolts,terminal box etc. for garden & wiring through 3CX2.5 sqmm. copper armoured cable.

a) 25 mm diameter GI pipe with long bend for each cable entry .

b) Providing necessary foundation with 300mmX300mmX300mm. Deep 1:3:6 ratio cement

concrete complete as required.

c) Excavation & back filling for erection . Debris to be removed from the site to suitable location

instruction of the engineer incharge.

30 set 8,561.42 256,842.60

8 Supply, installation, testing and commissioning of JETA 6, 1X400W MH Set, HAVELLS CAT NO.

LHFY40140C99 with lamp or approved make, outdoor fittings as integral architectural flood

lightings, terminal box, etc. of building complete with all accessoies and necessary electrical

wiring through 3CX2.5 sqmm. copper armoured cable.

a) 25 mm diameter GI pipe for each cable entry .

b) Providing necessary foundation with 300mmX300mmX300mm. Deep 1:3:6 ratio cement

concrete complete as required.

c) Excavation & back filling for erection. Debris to be removed from the site to suitable location

instruction of the engineer incharge.

15 set 13,171.41 197,571.15

9 Supply, installation, testing and commissioning of Impact popular arrylic IP 65, 1X 70W SON,

Havells Cat No. LHRY28170D99, street light fixture, outdoor fitting, with 70 Watts Sodium

Vapour lamp complete with control gear, acrylic cover, terminal box, etc. and its wiring with

2CX2.5 sq.mm. PVC insulated copper wire and 1.5 sq.mm. PVC insulated copper earth wire

from control box complete as required to be connected with Substation DB.(wiring for the same

shall be paid in rmt)

4 Each 5,400.28 21,601.12

10 Garden spike and mini flood luminaires, 1 X 50W E-27 for garden use (Make : Bajaj) 20 Each 2,594.77 51,895.40

11 Supply, installation, testing and commissioning of Water body light philips cat no. EW Graze

power Wee narrow 2700K or equivalent model from approved makes as required.

The above installations shall be completed as per specifications and as required.20 Each 7,836.99 156,739.80

12 SITC of IP66 Water Tight Junction Box 139mm x 115mm x 70mm With necessary clamp for

mounting of the J.B. (All the cable / wire connections to the DB shall be with the Water tight IP

66 Polyamide Glands, open Holes should be sealed with the IP65 Grommets only ) J. B. Should

be provided with cable connectors to connect 1 nos. of 4.0 sq. mm. x 2 core cables + Earth wire

& 6 nos. of 2.5 sq. mm x 2 core wires + Earthing wires.(Make of Hensel make cat.no. KD5065 +

Connectors + IP65 Glands + IP65 Grommets or equivalent) (wiring for the same shall be paid in

rmt) - fountain, ramp light, etc. from Campus lighting Panel (wiring for the same shall be paid in

rmt).

4 Each 1,055.45 4,221.80

5,470,262.29

Page 17: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 Electrical Section -V ( Fire)

INSIDE PUMP HOUSE

Providing & fixing, testing and

commissioning of electrically driven high

pressure centrifugal fire hydrant and sprinkler

pump, suitable for automatic operation

consisting of the following:

Horizontal, end suction centrifugal pump,

suitable for operation on 415 volts ± 6%, 3

phase, 50 HZ A.C supply. The installation

shall be complete with flexible coupling and

coupling guard as required. Fire pump shall

have C.I. casing, CS diffusers, bronze impeller

(hard finished and dynamically balanced) and

S.S. (304) Shaft with mechanical seal, capable

for delivering head to ensure a minimum

pressure of 3.5 Kg/Sqcm at the farthest or

topmost hydrant / sprinkler. The installation

shall be complete with necessary pressure

gauge with gun metal shut off cock on delivery

side.

Squirrel cage induction motor, TEFC type

suitable for operation on 415 volts, 3 phase 50

HZ A.C supply, for the above pump with

synchronous speed of 2900 RPM, conforming

to IP 55 protection & class F insulation. The

motor shall conform to IS 325-1978 (up to

2 Sets 235,000.00 470,000.00

2 Providing & fixing, testing and

commissioning of Diesel Engine driven fire

pump suitable for automatic operation

comprising of the following and conforming

to BS 649/IS 10002 all amended upto date.

Horizontal, split casing centrifugal pump,

suitable for operation on 415 volts ± 6%, 3

phase, 50 HZ A.C supply. The installation

shall be complete with flexible coupling and

coupling guard as required. Fire pump shall

have C.I. casing, CS diffusers, bronze impeller

(hard finished and dynamically

balanced) and SS (304) shaft with

mechanical seal, capable for delivering head to

ensure a minimum pressure of 3.5 Kg/Sqcm at

the farthest or topmost hydrant / sprinkler.

The installation shall be complete with

necessary pressure gauge with gun metal shut

off cock on delivery side.

Heat exchanger cooled (secondary cooling)

diesel engine of speed 1500 RPM suitable for

the above pump with automatic starting

mechanism and other accessories including

fuel tank (fabricated from 3mm MS sheet,

painted with two coats of synthetic enamel

paint over a coat of primer) of capacity

adequate to sustain pump operation for 8

hours continuous working. The tank shall be

1 Set 727,200.00 727,200.00

ENGINEERING PROJECTS (INDIA) LIMITED

( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development

Tender No: DLI/CON/710/563

BILL OF QUANTITIES

Page 18: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

3 bolts.

Capacity : 2850LPM.

Head : 80 M

Supply, installation, testing and commissioning

of Jockey pump (pressurisation pump) of the

following duty:

Horizontal end suction Centrifugal pump,

suitable for operation on 415 volts ± 6%, 3

phase, 50 HZ A.C supply. The installation

shall be complete with Flexible coupling and

coupling guard, complete as required.

Jockey pump shall be of stainless steel

construction.

Horizontal, end suction centrifugal pump,

suitable for operation on 415 volts ± 6%, 3

phase, 50 HZ A.C supply. The installation

shall be complete with flexible coupling and

coupling guard as required. Fire pump shall

have C.I. casing, CS diffusers, bronze impeller

(hard finished and dynamically balanced) and

S.S. (304) Shaft with mechanical seal, capable

for delivering head to ensure a minimum

pressure of 3.5 Kg/Sqcm at the farthest or

topmost hydrant / sprinkler. The installation

shall be complete with necessary pressure

gauge with gun metal shut off cock on delivery

side. (The pump should be tested for bench

mark at factory and shall be gotten approved

1 Set 95,950.00 95,950.00

4 Providing & fixing MS Class ‘C’ diesel engine

exhaust pipe (including all fittings, clamps,

steel support) of suitable dia for the engine.

The pipe shall be provided with 12 mm thick

supercera ceramic fibre rope.

150 mm dia

36 RM 1,818.00 65,448.00

5 Providing & fixing dial type (150 mm) pressure

gauge suitable for working pressure of 250 PSI. 5 Each 1,111.00 5,555.00

6 Providing & fixing testing and commissioning

of adjustable pressure switches for

jockey pump/ electric pump along with control

wiring up to main panel as required 8 Each 2,222.00 17,776.00

Control Panel for Fire Pumps.

Fabricating & supply, installing, testing and

commissioning of compartmentalised

common control Panel for Electrical Motor

driven pumps.

and diesel engine driven pump.

INCOMING.

1 nos.630 A TPN MCCB (25KA)

PVC Sleeves.

1 set RYB indicating lamps with individual HRC

Control fuses.

1 No. 96 sq.mm 0-600 Amps. Ammeter with

selector switch and suitable rated.

current transformers.

1 No. 0-500V 96 sqmm Voltmeter with

selector Switch.

1 Nos 600 A, 4 POLE ATS (ASCO 300 Series)

OVER LAPPING NEUTRAL.

OUTGOING

Feeder for Main Fire Pump - 2 Nos.

1 Nos 250 A TP MCCB.

DOL starter with TP Contractors and indicating

lamps ON/OFF/TRIP push.

Buttons

2 Nos. Automanual Switch.

1 set 186,850.00 186,850.00

7

Page 19: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

DIESEL ENGINE PUMP (STAND BY OPERATION) -

1 No.

20 Amps DPMCB - 2 Nos

Battery charger with transformers with

rectifier resistence DC ammeter, DC

voltmeter, Trickle/Booster/Off selector switch -

2 nos

1 set of indicating lamps for the following :

Phase indication

Battery charger on

DC supply on

Control switch on

Engine fails to start

Pump on

Low oil pressure.

High water temperature.

Auto manual selector switch.

1 sets of push button stations for the following

:

Engine start.

Engine stop

Engine hooter ACK.

Engine Fault reset.

Selector switches (Engine control, mode All the components shall be housed in a

common cubical made of 16 SWG MS Sheet

with required stiffners (if required) The Panel

shall be powder coated of approved color

both inside & outside. The Panel shall be

powder coated of approved colour both inside

& outside. The Panel shall have both bottom &

top cable entry provisions and panel shall be 8 1100 V GRADE POWER / CONTROL CABLES

Supply, laying, testing & commissioning of

FRLS, PVC outer sheathed, steel armoured,

aluminium/copper condoctor,1100 V grade

power cables with glands etc. The cables shall

be laid in tray/hume pipe/in trenches/on

walls/floor etc.as required. For cables laid

outdoor the rate shall include Earth excavation 8.1 3.5 C x 70 sq mm YFY for Main Pumps 35 Meter 757.50 26,512.50

8.2 4 C x 10 sq mm YFY for Jockey Pumps 20 Meter 242.40 4,848.00

8.3 12 C x 2.5 sq mm for Diesel Engines 20 Meter 459.55 9,191.00

8.4 2 C x 2.5 sqmm for instrumentation 55 Meter 191.90 10,554.50

9 G.I Earthing strips of 50 mm x 6 mm thick strip

shall be run on floor/ceiling/walls etc from Fire

Pumps to MCC Panel

30 Meter 85.85 2,575.50

10 Supply,installation,testing & commissioning of

MS Pipes IS : 1239/3589 with painting, one

coat of primer with two coats of synthetic

enamel paint of approved color/shade.(Above

Ground Piping)

10.1 200 mm Nb (6.35 mm thick. IS-3589) 36 RM 2,020.00 72,720.00

10.2 150 mm Nb 24 RM 1,717.00 41,208.00

10.3 100 mm Nb 6 RM 1,111.00 6,666.00

10.4 50 mm Nb 18 RM 454.50 8,181.00

10.5 25 mm Nb 6 RM 277.75 1,666.50

11Supply,installation,testing & commissioning of

CI Gate Valve as per IS : 14846 (PN 10) and non

rising spindle type with flanges,

bolts, nuts, washers, gaskets, etc.

11.1 150 mm Nb 3 Each 11,110.00 33,330.00

11.2 100 mm Nb 1 Each 6,060.00 6,060.00

11.3 c) 50 mm Nb 2 Each 3,535.00 7,070.00

12Supply, installation, testing & commissioning

of CI Non Return Valve as per IS : 5312 (PN 16)

swing check type with required

flanges, nuts, bolts, gaskets etc.

12.1 150 mm Nb 4 Each 10,100.00 40,400.00

12.2 50 mm Nb 1 Each 3,535.00 3,535.00

12.3 40 mm Nb 4 Each 3,030.00 12,120.00

1 set 186,850.00 186,850.00

7

Page 20: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

13Supplying, Installation, testing &

commissioning of Aluminium Di- Cast Butterfly

valves (PN 16) standard lever operated type

with flanges,nuts & bolts, gaskets etc.

40 mm Nb

4 Each 2,828.00 11,312.00

14 Supplying, Installation, testing &

commissioning Gun Metal screw type Ball

Valve.

25 mm Nb

14 Each 1,010.00 14,140.00

15Supply,installation,testing & commissioning of

CI Foot valve wuth suction strainer with

companion flanges,gaskts,nuts,bolts etc

15.1 200 mm Nb 3 Each 12,120.00 36,360.00

15.2 80 mm Nb 1 Each 5,050.00 5,050.00

16Hydrant System

Supply,installation,testing & commissioning of

MS Pipes IS : 1239 (medium grade) with

painting, one coat of primer with two coats of

synthetic enamel paint of approved

color/shade.( Above Ground Piping )

16.1 150 mm Nb 448 RM 1,717.00 769,216.00

16.2 100 mm Nb 55 RM 1,111.00 61,105.00

16.3 80 mm Nb 100 RM 858.50 85,850.00

17Supply,installation,testing & commissioning of

MS Pipes IS : 1239 (medium grade) being laid

in trenches/hume pipe support complete with

necessary fitiings e.g bends,flanges etc and

insulated with Anticorrosive bitumen primer

and wrapped with 3 mm thick Polymer

corrosion resistant tape.

150 mm Nb

20 RM 2,020.00 40,400.00

18Supply,installation,testing & commissioning of

Hume pipe with jointing collars NP2 for laying

of under ground pipe.

300 mm dia

24 RM 2,424.00 58,176.00

19Supplying, Installation, testing &

commissioning of Aluminium Di- Cast Butterfly

valves (PN 16) standard lever operated type

with flanges,nuts & bolts, gaskets etc.

150 mm Nb

4 Each 2,828.00 11,312.00

20 Supply,installation,testing & commissioning of

CI Non Return Valve as per IS dual plate wafer

type with required flanges, nuts, bolts,

gaskets etc.

150 mm Nb.

4 Each 1,313.00 5,252.00

21Supply,installation,testing & commissioning of

25 mm Nb GM Air Release Valve on Hydrant

and Sprinkler riser

21.1Providing & fixing dial type (150 mm) pressure

gauge suitable for working pressure of 250 PSI

on top of Hydrant Riser

2 Each 1,111.00 2,222.00

22 Supply,installation,testing & commissioning of

Fire Hydrant eqiupments as follows:

22.1 SS Single head Hydrant Valve as per Is 5290

with 63 mm dia instantaneous couplings &

80mm dia flanged inlet,Blank caps,chain.

For External/Yard Hydrant System

6 Each 5,454.00 32,724.00

22.2 SS Single head Landing Valve as per Is 5290

with 63 mm dia instantaneous couplings &

80mm dia flanged inlet,Blank caps,chain.

For Internal Hydrant System

15 Each 5,454.00 81,810.00

Page 21: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

22.3 One length of 15 m long,63 mm dia RRL Hose

with SS instantaneous couplings and copper

binding for internal Hydrant.

15 Each 4,545.00 68,175.00

22.4 Two length of 15 m long,63 mm dia CP Hose

with SS instantaneous couplings and copper

binding for external Hydrant.

12 Each 4,040.00 48,480.00

22.5 SS short Branch Pipe with 16 mm nozzle. 21 Each 1,818.00 38,178.00

22.6 CRCA Hose cabinet accompanied 1 no RRL

Hose,Branch Pipe for Internal Hydrant.15 Each 2,020.00 30,300.00

22.7 CRCA Hose cabinet accompanied 2 nos. CP

Hose,Branch Pipe for External Hydrant.6 Each 1,616.00 9,696.00

22.8 Fire First Aid Hose Reel drum with 20mm Nb

Thermo Plast Hose of 30 mtr in lenghth and

dual type (jet+spray) nozzle complete.15 Each 5,858.00 87,870.00

22.9 4 way Fire Brigade Inlet connection, 63 mm dia

in built dia SS non return valve1 Each 5,050.00 5,050.00

22.10 4 way Fire Water Reservoir Inlet connection, 1 Each 5,050.00 5,050.00

23 Fire Water Sprinkler System

Supply, installation, testing &

commissioning of MS Pipes IS : 1239/3589 with

painting, one coat of primer with two coats of

synthetic enamel paint of approved 23.1 150 mm Nb 160 RM 1,717.00 274,720.00

23.2 100 mm Nb 119 RM 1,111.00 132,209.00

23.3 80 mm Nb 398 RM 858.50 341,683.00

23.4 65 mm Nb 195 RM 505.00 98,475.00

23.5 50 mm Nb 91 RM 454.50 41,359.50

23.6 40 mm Nb 391 RM 479.75 187,582.25

23.7 32 mm Nb 484 RM 404.00 195,536.00

23.8 25 mm Nb 2100 RM 277.75 583,275.00

24 Supplying, Installation, testing &

commissioning of Aluminium Di- Cast Butterfly

valves (PN 16) standard lever operated type

with flanges,nuts & bolts, gaskets etc.

100 mm Nb

10 Each 3,636.00 36,360.00

25 Supply, installation, testing & commissioning

of CI Non Return Valve as per IS dual plate

wafer type with required flanges, nuts, bolts,

gaskets etc.

100 mm Nb

10 Each 5,353.00 53,530.00

26 Supplying, Installation, testing &

commissioning Gun Metal screw type Ball

Valve.

25 mm Nb

40 Each 1,010.00 40,400.00

27Supplying, Installation, testing &

commissioning Standard response quartzoid

bulb type sprinkler with 15 mm screwed end

connection of 68 deg. C temparature rating

and Sprinkler shall must be UL listed.

27.1 Upright Sprinkler 442 Each 202.00 89,284.00

27.2 Pendent Sprinkler 631 Each 202.00 127,462.00

27.3 Sidewall sprinker for Ramp area 225 Each 222.20 49,995.00

28 Supplying, Installation, testing &

commissioning Stainless steel corrogated

flexible pipe (hose) for dropping sprinklers

below

false ceiling,pipe shall be UL listed

214 Each 1,313.00 280,982.00

29Supplying, Installation, testing &

commissioning of Sprinkler control valve ( ICV

) with motor gong bell and trims as required.

150 mm Nb

3 Each 45,450.00 136,350.00

30 Supplying, Installation, testing &

commissioning of Water Flow switch.11 Each 2,474.50 27,219.50

31Providing & fixing dial type (150 mm) pressure

gauge suitable for working pressure of 250 PSI

on top of Sprinkler Riser

2 Each 1,111.00 2,222.00

32 Steel structure & supports 1 Lot 35,350.00 35,350.00

Page 22: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

Fire Extinguishers and Fire Check Door

Supply, installaing and commissioning of

Portable Fire Extinguishers of following type &

capacity

33 Carbon Di-oxide type Fire Extinguishers

33.1 2.0kg capacity 15 Each 3,333.00 49,995.00

33.2 4.5 kg capacity 20 Each 5,050.00 101,000.00

34 Dry chemical type Fire Extinguishers

34.1 5.0 Kg capacity 70 Each 1,313.00 91,910.00

34.2 10.0 kg capacity 10 Each 1,616.00 16,160.00

35 WCO2 type Fire Extinguishers

35.1 9.0 ltrs capacity 40 Each 1,414.00 56,560.00

35.2 Mechanical Foam

35.3 9.0 ltrs capacity 8 Each 1,616.00 12,928.00

35.4 Fire Buckets round bottom type enamel

painted white inside, red outside with lid and

mounting Bracket.

8 Each 454.50 3,636.00

35.5 2 hours Rated Wooden Fire Check Door

(Frame & Shutter) with paint finish.( Frame &

Shutter ) with paint finish. ( Two nos )

200.00 sqm 6,767.00 1,353,400.00

35.6 Moduler type Clean Agent Fire Extinguishers,

Capacity 4.0 Kg capacity 39.00 Each 17,170.00 669,630.00

35.7 Moduler type ABC Fire Extinguishers, Capacity

5.0 Kg capacity5.00 Each 7,070.00 35,350.00

36 SIGNAGES

36.1 Photoluminescence signages " FIRE EXIT " 40 Each 378.75 15,150.00

36.2 Floor identification signages 20 Each 151.50 3,030.00

36.3 Electronic signages with emergency battery

back up for 12 hours16 Each 2,020.00 32,320.00

36.4 Fire Notice 8 Each 505.00 4,040.00

37 Fire Alarm and Detection System

Providing & Fixing, testing & commissioning of

Addressable Pull type Manual Call point with

all necessary fittings and consumables

56 Each 3,181.50 178,164.00

38 Providing & Fixing, testing & commissioning of

Addressable Hooter cum Strobe/ Flasher with

all necessary fittings and consumables40 Each 3,333.00 133,320.00

39 Providing & Fixing, testing & commissioning of

Addressable Photo Electric Smoke Detector

with all necessary fittings and consumables449 Each 2,979.50 1,337,795.50

40 Providing & Fixing, testing & commissioning of

Addressable Heat Detector with all necessary

fittings and consumables12 Each 2,929.00 35,148.00

41 Providing & Fixing, testing & commissioning of

Addressable Fault Isolator Modules with all

necessary fittings and consumables19 Each 2,525.00 47,975.00

42 Providing & Fixing, testing & commissioning of

Addressable Monitor Modules with all

necessary fittings and consumables10 Each 2,828.00 28,280.00

43 Providing & Fixing, testing & commissioning of

Addressable Duct Sensor Detector with all

necessary fittings and consumables425 Each 6,565.00 2,790,125.00

44 Providing & Fixing, testing & commissioning of

Addressable Control Modules with all

necessary fittings and consumables225 Each 3,333.00 749,925.00

45 Providing & Fixing, testing & commissioning of

Response Indicator170 Each 85.85 14,594.50

46 Providing & Fixing, testing & commissioning of 300 Each 707.00 212,100.00

47 Providing & Fixing, testing & commissioning of

250 watt RMS output solid state Amplifier with

Microphone

1 Set 25,250.00 25,250.00

Page 23: ENGINEERING PROJECTS ( INDIA ) LTDengineeringprojects.com/Tender/UploadFiles/3228_VOl-III.pdf · 2018-07-27 · 10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12

Sl. Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

48 Providing & Fixing, testing & commissioning of

Microprocessor based Intelligent Fire Alarm

Panel With battery and battery chargers,The

FACP shall have provision of Loop expansion

and shall be networkable type. Provision for

interfacing with other systems such as SCADA

/ IBMS with all required hardware and

software.

1 Set 277,750.00 277,750.00

49 Providing & Fixing, laying and termination of

Power and Control cable .

PVC sheathed and insulated copper Armour

3000 RM 146.45 439,350.00

14,812,025.25