Engineered for flexibility and performance™
Flexible, High Efficiency Cooling and Heating Solutions.
Enfinity™
Console Water Source Heat Pumps1/2 to 1½ TonStandard Range – Model MHCGeothermal Range – Model MHW
Slope Top Unit
Flat Top Unit
2
With Enfinity Console Water Source Heat Pumps You Benefit From:■ The GentleFlo™ cross-tangential
fan wheel design provides whisper quiet operation while delivering maximum airflow required for proper air circulation
■ High efficiency, low operating costs
■ R-410A refrigerant with no ozone depletion potential or phase-out date
■ Easy, low cost design and installation
■ Open Choices™ controls feature allows easy, low cost integration with the Building Automation
System (BAS) of your choice
■ Boiler/tower or geothermal application flexibility
■ Quiet, reliable operation
■ Easy, low cost maintenance and service
■ Two Cabinet Styles – Choose a flat top or slope top unit in a high sill or low sill configuration to satisfy special application requirements
Enfinity™ Console Water Source Heat Pumps
Non-Ozone Depleting R-410A Refrigerant
Owner, Engineer and Contractor BenefitsThe Building Owner/Tenant■ High efficiency units reduce energy consumption/operating costs
and can contribute to earning points toward LEED® certification. ■ Open Choices control feature gives you the flexibility to select
standalone thermostat operation or easy, low cost integration with the BAS of your choice using an add-on communication module.
■ R-410A refrigerant has no ozone depletion potential or phase-out date, helping to minimize environmental impact and protect against refrigerant availability issues over the economic life of your equipment investment.
■ Quiet operation provided by Gentleflo™ cross-tangential fan wheel and quiet rotary compressor with low vibration mass plate design.
■ Double-sloped polymer drain pan and optional closed cell insulation promote superior indoor air quality.
■ Durable construction promotes long life, reliable operation.
The Engineer■ Boiler/tower or geothermal unit selections provide flexibility in
designing the system that best meets the performance and budget requirements of your project.
■ Multiple unit configurations reduce design time and cost.■ Multiple features and options give you the flexibility to select units
that closely match application requirements.
Installing Contractor / Service Personnel■ High sill or low sill design makes it easier to meet space
requirements of new construction and replacement applications.■ Easy access to water connections save time to help reduce installation costs.■ LED status lights on the control box behind the front panel allow
quick troubleshooting.■ Individual left and right end panels provide easy access to the unit
compressor, motor and unit controls with access to the fan section, coil and filter through the front panel.
■ A removable, non-corrosive, double sloped condensate drain pan provides positive condensate removal and is easy to access for service and maintenance.
3
Flexible Design with Added Features
Exploded View of Unit with Number Bullets
Console Water Source Heat Pumps – Models MHC & MHW1. Cabinets – Selectable flat top or slope top cabinet
configuration with multiple grille options. Individual panels – top, front and end panels are designed for easy removal and provide easy access to unit components for service and maintenance.
2. Compressor - High efficiency rotary type, using R-410A refrigerant with zero ozone depletion potential or phase-out date.
3. Gentleflo™ Fan – User selectable, multi-speed tangential fan system provides high efficiency and very quiet operation suitable for noise sensitive applications.
4. LED Annunciator – LED status lights display fault conditions to provide easy troubleshooting and diagnosis. Accessed by removing the left or right end panel to the control enclosure.
5. Filter– Units come standard with a 1/2" (12.7mm) thick disposable filter that is easy to access and replaced from the front of the unit without removing a panel.
6. Hinged Control Box– Provides added accessibility to plumbing end compartment for easier access for service.
7. MicroTech® III Unit Controller – Designed for flex-ibility, the main control board is used in stand-alone applications. An optional I/O expansion module can be used to control electric heat and multiple fan speeds. A separate LonWorks® or BACnet® communication module can be eas-ily snapped onto the board to accommodate the building automation system of your choice.
8. 2-Way Motorized Valve Packages (Option) –Factory installed or field-installed for variable pumping applications. Other valve options available upon request.
9. Double-Sloped Drain Pan – Made of durable, non-corrosive polymer, promotes positive condensate drainage for superior Indoor Air Quality (IAQ). Drain Pan is easy to remove for cleaning.
Air Dampers (Option) – Motorized or manually operated outside air dampers provide ventilation air.
Unit Flexibility– Selectable for standard (boiler/tower) or extended range (geothermal) applications to achieve the highest efficiency for your application requirements.
Flat Top, High Sill Unit
4
MicroTech III Unit ControllerThe MicroTech III unit controller is a standalone microprocessor-based control board conveniently located in the unit control box for accessibility. The board is designed to provide standalone control of a Water Source Heat Pump using a wall thermostat or a wall-mounted temperature sensor.
Each unit controller is factory programmed, wired, and tested for complete control of single zone, standalone operation of your McQuay Water Source Heat Pump.
Each unit controller orchestrates the following unit operations:
Enable heating and cooling to maintain setpoint Monitor discharge air temperature based on a room sensor Monitor leaving water temperature Enable fan and compressor operation Relay status of all vital unit functions Monitor all equipment protection controls Support optional control outputs
I/O Expansion ModuleFor added functionality, an optional I/O expansion module interconnects to the MicroTech III unit controller.
Adding an I/O Expansion Module (with an interconnect cable) allows for:
Monitoring of entering water temperature for boilerless electric heat control Outputs for optional electric heat
LonWorks® Communication ModuleThe MicroTech III unit controller can accept a plug-in LonWorks communication module to provide network communications and added functionality to easily integrate with an existing BAS.
The communication module can be factory- or field-installed and is tested with all logic required to monitor and control the unit.
The LonWorks communication module is LonMark 3.4 certified for BAS integration to provide centralized scheduling and management of multiple heat pumps.
An amber, on-board status LED indicates the status of the MicroTech III LonWorks module.
BACnet Communication ModuleThe MicroTech III unit controller can accept a plug-in BACnet communication module to provide network communications and added functionality to easily integrate with an existing BAS. The communication module can be factory- or field-installed and is tested with all logic required to monitor and control the unit.
It is designed to be linked with a centralized building automation system (BAS) through a BACnet communications network for centralized scheduling and management of multiple heat pumps.
I/O Expansion Module
MicroTech® III Unit Controller – A Complete Control Solution
BACnet Communication Module
LonWorks Communication Module
MicroTech III Unit Controller
Wireless Temperature ControlThe T9000 Wireless Temperature Control is designed to provide precision temperature control without the installation labor and expense of wiring.
• Powered by AA batteries• Mounts in any suitable location that will
provide good temperature control. • Large LCD display provides the user
with current room temperature, set point temperature, time, program interval and other system status information.
Remote Control Node (RCN)Used with the Wireless Tempera tu re Cont ro l , the RCN interfaces with specific HVAC equipment, and communicates with its thermostat using unlicensed 900 MHz, radio frequency energy.
Room Temperature Sensors• Set Point Adjustment (55° - 95°F)• Set Point Adjustment (-3° to +3°F)
The fast, easy solution for temperature sensing problems.
Programmable Electronic (P/N 668810301)
Non-Programmable Electronic(P/N 668811201)
Programmable Electronic(P/N 668811101)
Non-Programmable Electronic (P/N 668811001)
5
Sensor 669088101• Status LED• Override Button
Thermostats & Sensors – Complete Control Solutions
Thermostats Features Wall Mounted Unit Mounted
668810301 668811201 668811001 668811101 7-Day Programmable Electronic ● ● Non-Programmable Electronic ● ● Auto Changeover ● ● ● ● Two-Speed Fan Control ● ● ● ● Button Lockout Function ● ● Hardwired ● ● ● ● Configurable ● ● Single-Stage Heat/Cool Systems ● ● ● ● Single-Stage Heat/Non Heat Pump Systems ● ● Single-Stage Heat Pump Systems ● ● Field Calibration ● ● Backlit Display ● ● ● ● Selectable Fahrenheit or Celsius ● ● Title 24 Compliant / No Batteries Required ● ● SimpleSet™ Field Programming ● ● ● Status Indicator Light ● ● Relay Outputs (minimum voltage drop in thermostat) ● ● ● ●
Remote Temperature Sensor Compatibility ● ● ● ●
ThermostatsEasy-to-operate comfort command centers provide a complete range of deluxe features. Choose between a 7-day programmable or a non-programmable thermostat for temperature control to match your application, provide convenience and help save energy.
Wall Mounted Unit Mounted
Programmable Non-programmable
Sensor 667720401(Standard Sensor Only)
Sensor 668900801• Set Point Adjustment• LED • Override feature
Page Headline Here Page Headline Here
6
Dimensional Data - High Sill Unit Size 007-012
Flat Top Unit – High Sill, Left Hand Piping
Slope Top Unit – High Sill, Right Hand Piping
Top View
Right End View
Dimensions
Note: Dimensions are approximate*Unit size 007 not available at time of publication. Please consult your McQuay Representative for specific availability.
N P Q R S T U V W X Y
4¼" 10¼" 13/5" 5¼" 7½" 10¾" 18¾" 6⅝" 6" 3¼" 25" (108mm) (260mm) (41mm) (134mm) (192mm) (273mm) (476mm) (168mm) (152mm) (83mm) (635mm)
Unit Size A B C D E F G H J K L M
*007-012 46" 45⅜" 16½" 12½" 7" 8⅞" 0.6" 2¼" 6⅞" 51/5" 6¾" 3½" (1168mm) (1153mm) (418mm) (318mm) (181mm) (225mm) (14mm) (57mm) (175mm) (132mm) (172mm) (90mm)
Front View
Top View
Left End View Front View
Page Headline Here Page Headline Here
7
Flat Top Unit – Low Sill, Left Hand Piping
Dimensional Data - Low Sill Unit Size 007-012Slope Top Unit – Low Sill, Right Hand Piping
Unit Size A B J K L M N P Q R S T
*007-012 46" 45⅜" 4⅜" 2¾" 4¼" 1" 1¾" 10¼" 13/5" 51/5" 7½" 10¾"
(1168mm) (1153mm) (111mm) (70mm) (108mm) (26mm) (45mm) (260mm) (41mm) (131mm) (192mm) (273mm) U V W X Y
16.2" 6⅝" 6" 3¼" 22½" (410mm) (168mm) (152mm) (83mm) (572mm)
Dimensions
Note: Dimensions are approximate*Unit size 007 not available at time of publication. Please consult your McQuay Representative for specific availability.
Top View
Right End ViewFront View
Top View
Left End View Front View
Page Headline Here Page Headline Here
8
Dimensional Data - High Sill Unit Size 015-018Slope Top Unit – High Sill, Right Hand Piping
N P Q R S T U V W X Y
4¼" 10¼" 13/5" 5¼" 7½" 10¾" 18¾" 6⅝" 6" 3¼" 25" (108mm) (260mm) (41mm) (134mm) (192mm) (273mm) (476mm) (168mm) (152mm) (83mm) (635mm)
Unit Size A B C D E F G H J K L M
015-018 54" 53⅜" 20½" 12½" 7" 8⅞" 0.6" 2¼" 6⅞" 51/5" 6¾" 3½" (1372mm) (1356mm) (519mm) (318mm) (181mm) (225mm) (14mm) (57mm) (175mm) (132mm) (172mm) (90mm)
Dimensions
Note: Dimensions are approximate
Flat Top Unit – High Sill, Left Hand Piping
Top View
Right End ViewFront View
Top View
Left End View Front View
Page Headline Here Page Headline Here
9
Dimensional Data - Low Sill Unit Size 015-018
Flat Top Unit – Low Sill, Left Hand Piping
Slope Top Unit – Low Sill, Right Hand Piping
Note: Dimensions are approximate
U V W X Y
16¼" 6⅝" 6" 3¼" 22½" (413mm) (168mm) (152mm) (83mm) (572mm)
Unit Size A B J K L M N P Q R S T
015-018 54" 53⅜" 4⅜" 2¾" 4¼" 1" 1¾" 10¼" 13/5" 5¼" 7½" 10¾" (1372mm) (1356mm) (111mm) (70mm) (108mm) (26mm) (45mm) (260mm) (41mm) (134mm) (192mm) (273mm)
Dimensions
Top View
Right End View
Front View
Top View
Left End View Front View
Page Headline Here Page Headline Here
10
Unit Airflow Waterflow Voltage Cooling Heating Size CFM L/S GPM L/S Btuh/hr Watts EER COP Btuh/hr Watts COP
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1 208/230-60-1265/277-60-1208/230-60-1265/277-60-1
Water LoopRated in Accordance with ISO Standard 13256-1 Boiler/Tower
007
009
012
015 018
*
347
275
559
421
*
164
130
264
199
*
2.43
2.90
3.70
4.61
*
0.153
0.183
0.233
0.291
*
9170
11600
14500
16400
*
651
776
964
1223
*
14.1
14.9
15.1
13.4
*
4.1
4.4
4.4
3.9
*
11000
13900
18200
20900
*
686
894
1031
1379
*
4.7
4.6
5.2
4.4
Unit Airflow Waterflow Voltage Cooling Heating Size CFM L/S GPM L/S Btuh/hr Watts EER COP Btuh/hr Watts COP
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1 208/230-60-1265/277-60-1208/230-60-1265/277-60-1
Ground LoopRated in Accordance with ISO Standard 13256-1
007
009
012
015 018
*
347
275
559
421
*
164
130
264
199
*
2.43
2.90
3.70
4.61
*
0.153
0.183
0.233
0.291
*
9730
12300
15400
17300
*
602
700
885
1132
*
16.2
17.5
17.3
15.3
*
4.7
5.1
5.1
4.5
*
7030
9000
10900
13700
*
627
780
940
1189
*
3.3
3.4
3.4
3.4
Unit Airflow Waterflow Voltage Cooling Heating Size CFM L/S GPM L/S Btuh/hr Watts EER COP Btuh/hr Watts COP
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1 208/230-60-1265/277-60-1208/230-60-1265/277-60-1
Ground SourceRated in Accordance with ISO Standard 13256-1
* Not available at time of publication. Please consult your McQuay Representative for specific availability
007
009
012
015 018
*
347
275
559
421
*
164
130
264
199
*
2.43
2.90
3.70
4.61
*
0.153
0.183
0.233
0.291
*
11000
13500
17600
19000
*
465
555
716
928
*
23.8
24.3
24.6
20.4
*
7.0
7.1
7.2
6.0
*
9060
11600
14400
17400
*
657
841
987
1277
*
3.0
4.1
4.3
4.0
Improved Efficiency35% greater efficiency than the minimum required by ASHRAE 90.1, for units l ess t han 17 ,000 B tuh pe r ISO Standard 13256-1 for Boi ler /Tower
ISO Performance Data
Page Headline Here Page Headline HereEngineering Data
Unit Size Voltage-Hz-Phase Electric Heater Fan Total Unit Min. Voltage Min. Circuit Max. Fuse Size
FLA Motor FLA FLA Amps
Unit Size Voltage-Hz-Phase Compressor Fan Total Unit Min. Voltage Min. Circuit Max. Fuse Size
RLA LRA Motor FLA FLA Amps
***
50222250252229283328
***–
15.020.0
-15.020.020.025.020.025.0
007
009
012
015
018
Electrical – Standard Static Motor
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1208/230-60-1265/277-60-1208/230-60-1265/277-60-1
***
10.54.94.612.46.15.57.36.69.67.8
***
0.500.250.230.500.250.230.330.330.330.33
***
8.03.73.59.54.74.25.65.07.46.0
***
8.504.03.710.05.04.45.95.37.76.3
* *
* 104187239104187239187239187239
***
15.06.06.020.010.06.010.010.015.010.0
007
009
012
015
018
Electrical – Standard Static Motor and Optional Electric Heater (Heat Pump Not Running)
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1
115-60-1208/230-60-1265/277-60-1208/230-60-1265/277-60-1208/230-60-1265/277-60-1
***–
11.012.5
–11.012.514.917.114.917.1
***–
10.712.3
–10.712.314.616.814.616.8
***–
0.250.23
–0.250.230.30.30.330.33
***–
187239–
187239187239187239
* * *
–13.715.7
–13.715.718.621.418.621.4
Unit Size *007 009 012 015 018 Fan Wheel - D x W (In.) 4⅜ x 27¼ 4⅜ x 27¼ 4⅜ x 27¼ 4⅜ x 35⅜ 4⅜ x 35⅜ Fan Motor Horsepower 1/30 1/30 1/30 1/18 1/18
Coil Face Area (Sq. Ft.) 1.67 1.67 1.67 2.22 2.22 Coil Rows 2 2 3 2 3 Refrigerant Charge (Oz.) 17.6 19.2 22 29.9 32
Low Sill (1) 23¾W x 8¾D (1) 31¾W x 8¾D
Filter, (Qty.) Size (In.) High Sill (1) 29¼W x 9¾D (1) 37¼W x 9¾D
Water Connections, Female NPT (In.) 5/8 O.D. 5/8 O.D. 5/8 O.D. 5/8 O.D. 5/8 O.D. Condensate Connections, Female NPT (In.) 3/4 I.D. 3/4 I.D. 3/4 I.D. 3/4 I.D. 3/4 I.D.
Weight, Operating (Lbs.) 144 146 166 171
Weight, Shipping (Lbs.) 164 166 196 201
Unit Physical Data
* Not available at time of publication. Please consult your McQuay Representative for specific availability.
11
Open Loop “Well Water”“Open Loop” well water systems use ground water to remove or add heat to the interior water loop. The key benefit of an open loop system is the constant water temperature, usually 50°F to 60°F, which provides efficient operation at a low first cost. Open Loop applications are commonly used in coastal areas where soil characteristics allow reinjection wells to return the water back to the aquifer. Reinjection wells must be approved by the U.S. Environmental Protection Agency.
(800) 432-1342www.mcquay.com
A global leader in system solutions for air conditioning, heating, ventilating and refrigeration.
© 2009 McQuay International A/SP 31-258 (4/09)
Water Source Heat Pump Geothermal Systems
Water source heat pump systems are one of the most efficient systems available for heating and cooling buildings. High efficiency, self-contained McQuay Enfinity units can be placed in virtually any location within a building. Each unit responds only to the heating or cooling load of the individual zone it serves. This provides excellent comfort levels for occupants, better control of energy use for building owners and lower seasonal operating costs.
Boiler/Tower LoopA “Boiler/Tower” application uses a simple two pipe water circulating system that adds heat, removes heat or transfers rejected heat to other units throughout the building. The water temperature for heating is usually provided by a natural gas or electric boiler located in a mechanical room. The condens-ing water temperature is provided by a cool-ing tower that dissipates waste heat. This application can be the lowest cost of the loop options available.
Geothermal Closed LoopVertical loops (shown) are installed by drilling vertical bore holes into the earth and inserting a plastic polyethylene supply/return pipe into the holes. Horizontal loops are installed in trenches approximately 5 feet below the ground surface. Both vertical and horizontal loops extract the Earth’s natural heat and reject it back.
Surface Water or Lake LoopA “Surface Water” or “Lake” (shown) closed loop system is a geothermal loop that is directly installed in a lake or body of water that is near the building. In many cases, the body of water is constructed on the building site to meet run-off or aesthetic require-ments. The size and the depth of the lake is critical, and commercial design services should be used to certify that a given body of water is sufficient for building loads.
McQuay International delivers engineered, flexible solutions for commercial, industrial and institutional HVAC requirements with reliable products, knowledgeable applications expertise and responsive sup-port. McQuay products and services are provided through a worldwide network of dedicated sales and service offices.
™ ® The following are trade names or registered trademarks of their respective companies: LonTalk and LonMark from Echelon Corporation, BACnet from ASHRAE and Enfinity from McQuay International.
Products Manufactured in an ISO Certified Facility.