1 GLOBAL CLIMATE AND ENERGY PROJECT | STANFORD UNIVERSITY Energy Tutorial: Electric Grid 101 GLOBAL CHALLENGES GLOBAL SOLUTIONS GLOBAL OPPORTUNITIES GCEP RESEARCH SYMPOSIUM 2011 | STANFORD, CA Professor Thomas J. Overbye Fox Family Professor of Electrical and Computer Engineering University of Illinois at Urbana-Champaign [email protected]

Upload: vandiep

Post on 30-Jan-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

1

GLOBAL CLIMATE AND ENERGY PROJECT | STANFORD UNIVERSITY

Energy Tutorial:

Electric Grid 101

GLOBAL CHALLENGES – GLOBAL SOLUTIONS – GLOBAL OPPORTUNITIES

GCEP RESEARCH SYMPOSIUM 2011 | STANFORD, CA

Professor Thomas J. Overbye Fox Family Professor of Electrical and Computer Engineering

University of Illinois at Urbana-Champaign

[email protected]

Page 2: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Three Electric System Components

• Generation – source of electric energy

– coal provides over half of the U.S. electric energy

• Load – consumes electric energy

– consumers are in complete control of the switch; utilities must supply enough power to meet load

• Transmission and Distribution – the wires that carry the power from generation to load

– Operating at voltages up to 765 kV (kilovolt), with 500 kV, 345 kV and 230 kV common

2

Page 3: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Major Power Grid Components

3

Page 4: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power and Energy

• Power is the instantaneous transfer of energy; expressed in watts (W), kW, MW, GW

– US installed generation capacity is about 1000 GW

• Energy is the integration of power over time; expressed in units of joules (J = 1 W-sec), kWh (3.6 x 106 J), or btu (1055 J; 1 MBtu=0.292 MWh)

• U.S. electric energy consumption is about 3600 billion kWh (about 13,333 kWh per person; 1.5 kW continuous per person on average)

4

Page 5: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

AC System Analysis

• The power grid is an ac system, operating at close to 60 Hz in North America, 50 Hz in many other places

• Constant frequency ac systems are analyzed using phasor analysis, which expresses a time varying value, such as a voltage or current, as a magnitude and phase angle

– v(t) = Vmax cos( t + v) Vrms v

– Phase angle is always with respect to an arbitrary reference angle

5

Page 6: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

The Advantage of Phasor Analysis

6

0

2 2

Resistor ( ) ( )

( )Inductor ( )

1 1Capacitor ( ) (0)

C

Z = Impedance

R = Resistance

X = Reactance

XZ = =arctan( )

t

v t Ri t V RI

di tv t L V j LI

dt

i t dt v V Ij C

R jX Z

R XR

Device Time Analysis Phasor

Page 7: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Instantaneous Electrical Power

7

max

max

max max

( ) ( ) ( )

v(t) = cos( )

(t) = cos( )

1cos cos [cos( ) cos( )]

2

1( ) [cos( )

2

cos(2 )]

V

I

V I

V I

p t v t i t

V t

i I t

p t V I

t

Power

Page 8: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Average Electrical Power

8

max max

0

max max

1( ) [cos( ) cos(2 )]

2

1( )

1cos( )

2

cos( )

= =

V I V I

T

avg

V I

V I

V I

p t V I t

P p t dtT

V I

V I

Power Factor

Average

P

Angle

ower

Page 9: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Complex Power

9

*

cos( ) sin( )

P = Real Power (W, kW, MW)

Q = Reactive Power (var, kvar, Mvar)

S = Complex power (VA, kVA, MVA)

Power Factor (pf) = cos

If current leads voltage then pf is leading

If current

V I V I

V I

S V I j

P jQ

lags voltage then pf is lagging

Page 10: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Consumption in Devices

10

2Resistor Resistor

2Inductor Inductor L

2

Capacitor Capacitor C

CapaCapacitor

Resistors only consume real power

P

Inductors only consume reactive power

Q

Capacitors only generate reactive power

1Q

Q

C

I R

I X

I X XC

V2

citorC

C

(Note-some define X negative)X

Page 11: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Capacitors for Power Factor Correction

• Many electric loads are reactive, which means they consume reactive power; i.e., a lagging pf

– Induction motors are a very common example

• Capacitors are commonly used to “correct” the power factor

11

Page 12: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Balanced 3 Phase ( ) Systems

• Bulk power systems are almost exclusively 3

• Single phase is used primarily only in low voltage, low power settings, such as residential and some commercial

• A balanced 3 phase ( ) system has

– three voltage sources with equal magnitude, but with an angle shift of 120

– equal loads on each phase

– equal impedance on the lines connecting the generators to the loads

Page 13: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Advantages of Three Phase

• Can transmit more power for same amount of wire (twice as much as single phase)

• Torque produced by 3 machines is constant

• Three phase machines use less material for the same power rating

• Three phase machines start more easily than single phase machines

13

Page 14: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Three Phase Transmission Lines

14

Page 15: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

The North American Electric Grid

• One of the largest and most complex objects ever created

• Consists of four large 60 Hz ac synchronous subsystems

– Eastern Interconnect, Western Interconnect (WSCC), Texas (ERCOT), Quebec

• Small amounts of power can be transferred between subsystems using AC-DC-AC ties

15

Page 16: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

North America Interconnections

16

Page 17: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

North America Transmission Grid

17

Page 18: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Generation Summary

• Total U.S. Generation consists of more than 10,000 different units with a total capacity of about 800,000 MW

– largest generation “plant” is Grand Coulee (WA) with 7,000 MW of hydro

– next largest are Polo Verde (AZ) with 3,700 MW of nuclear, W.A Parish with 3,600 MW of coal (TX), and Scherer with 3,400 MW of coal in (GA).

18

Page 19: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Electric Load

• The aggregate electric load on the power grid varies continuously, with the customer having almost complete control

– with daily, weekly and seasonal patterns

• Total peak US electric demand is about 710,000 MW, but different areas achieve their peak values at different times

19

Page 20: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Example Yearly Variation in Load

0

5000

10000

15000

20000

250001

518

1035

1552

2069

2586

3103

3620

4137

4654

5171

5688

6205

6722

7239

7756

8273

Hour of Year

MW

Lo

ad

20 Most of the time the load is significantly below its peak value

Page 21: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Daily Load Variation: Very Individual

21

Page 22: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Not All Loads are “Grid Friendly”

• Constant impedance loads are the easiest on the grid; but many loads inject harmonics

22

Switched-Mode Power Supply Current

Source: www.utterpower.com/commercial_grid.htm Source: Fig 2.34 of “Renewable and Efficient

Electric Power Systems” by Masters

Compact fluorescent lamp (CFL)

Page 23: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Transmission and Distribution

• Goal is to move electric power from generation to load with low losses.

• Less losses at high voltages (S=VI* and I2R losses), but more difficult to insulate.

• Typical high voltage transmission voltages are 765, 500, 345, 230, 161, 138 and 69 kV.

• Lower voltage lines are used for distribution (12.4 or 13.8 kV).

• Typical losses are about 3 to 5% in transmission and 10 to 15% in the distribution system. 23

Page 24: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Transmission & Distribution

• Transmission

– networked connections

– power can be supplied from multiple sources

– typically higher voltages, above 100 kV

– mostly overhead, with some underground in urban areas

– Often source of large-scale blackouts

• Distribution

– radial connections

– power moves in one direction only

– typically lower voltages, below 100 kV

– the source of most blackouts, but these are local

– Most new construction is underground, especially in suburban and urban locations 24

Page 25: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Transmission Lines and the Elements

25 Ike in Beaumont, Tx

Quebec Ice Storm

Page 26: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Transmission Lines and Trees

• We like trees, and they grow; but when trees get close to lines bad things can occur.

26

Before “Trimming” After “Trimming”

Page 27: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Transfer in Transmission Lines

• Below is the full (and more complicated) power flow derivation for a short transmission line

27

V1 V2 + +

- -

I1 I1 Transmission

Line with

Impedance Z S12 S21

1

** 1 2

12 1 1 1

1 1 2 2 2

21 1 2

12 12

with , Z

Z Z

V VS V I V

Z

V V V V Z Z

V V VS

Z Z

Page 28: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Approximate Power Transfer

• For high voltage lines, the reactance (X term) dominates so Z has an angle of close to 90

28

21 1 2

12 12 12

12 12

1 212 12

If we assume a line is lossless with impedance jX and

are just interested in real power transfer then:

90 90

Since - cos(90 ) sin , we get

sin

Hence the maximu

V V VP jQ

Z Z

V VP

X

1 212

m power transfer is

Max V VP

X

Power Transfer is primarily due to

a phase angle difference!

Page 29: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Transformers

• Transformers provide an easily means for changing ac voltage levels

– Power flow through transformers is bi-directional

• Heating is a major concern that can quickly lead to loss of transformer life (and occasionally explosions!)

• High voltage transformers (say 230 kV and up) are large, heavy, and difficult to replace

29

Page 30: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

A 230/115 kV Transformer

30

Page 31: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Residential Distribution Transformers

• Residential single phase electric service uses a center tapped transformer to provide 240/120 volt service; a separate ground is used for safety

31

Page 32: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power System Time Frames

32

Lightning Propagation

Switching Surges

Stator Transients and

Subsynchronous Resonance

Transient Stability

Governor and Load

Frequency Control

Boiler and Long-Term

Dynamics; power flow

10-7 10-5 10-3 0.1 10 103 105

Time (Seconds)

Page 33: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power System Operations

• The next several slides use a power system simulation package, PowerWorld Simulator, to demonstrate the operation of the electric grid over a time period of minutes to hours (quasi-steady state)

33

Page 34: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

One-line Diagram

• Most power systems are balanced three phase systems.

• A balanced three phase system can be modeled as a single (or one) line.

• One-lines show the major power system components, such as generators, loads, transmission lines.

• Components join together at a bus.

34

Page 35: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

A Substation “Bus”

35

Page 36: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Metro Chicago Electric Grid

36

Page 37: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Example Three Bus Power System

37

Bus 2 Bus 1

Bus 3Home Area

204 MW

102 MVR

150 MW

150 MW

37 MVR

116 MVR

102 MW

51 MVR

1.00 PU

-20 MW

4 MVR

20 MW

-4 MVR

-34 MW

10 MVR

34 MW

-10 MVR

14 MW

-4 MVR

-14 MW

4 MVR

1.00 PU

1.00 PU

106 MW

0 MVR

100 MWAGC ON

AVR ON

AGC ON

AVR ON

Load with

green

arrows

indicating

amount

of MW

flow

Used

to control

output of

generator Direction of arrow is used to indicate

direction of real power (MW) flow

Note the

power

balance at

each bus

Page 38: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Balance Constraints

• Power flow refers to how the power is moving through the system.

• At all times in the simulation the total power flowing into any bus MUST be zero!

• This is know as Kirchhoff’s law. And it can not be repealed or modified.

• Power is lost in the transmission system.

38

Page 39: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Basic Power Control

• Opening a circuit breaker causes the power flow to instantaneously (nearly) change.

• No other way to directly control power flow in a transmission line.

• By changing generation we can indirectly change this flow.

39

Page 40: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Transmission Line Limits

• Power flow in transmission line is limited by heating considerations.

• Losses (I^2 R) can heat up the line, causing it to sag.

• Each line has a limit; Simulator does not allow you to continually exceed this limit. Many utilities use winter/summer limits.

40

Page 41: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Overloaded Transmission Line

41

Page 42: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Interconnected Operation

• Power systems are interconnected across large distances. Most of North America east of the Rockies is one system, with most of Texas and Quebec being major exceptions

• Individual entities (e.g., a utility) only own or operate a small portion of the system, referred to an balancing authority area (previously operating area).

42

Page 43: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Balancing Authority Areas

• Transmission lines that join two areas are known as tie-lines.

• The net power out of an area is the sum of the flow on its tie-lines.

• The flow out of an area is equal to total gen - total load - total losses

= tie-flow

43

Page 44: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Area Control Error (ACE)

• The area control error is the difference between the actual flow out of an area, and the scheduled flow.

• Ideally the ACE should always be zero.

• Because the load is constantly changing, each utility must constantly change its generation to “chase” the ACE.

44

Page 45: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Automatic Generation Control

• Most utilities use automatic generation control (AGC) to automatically change their generation to keep their ACE close to zero.

• Usually the utility control center calculates ACE based upon tie-line flows; then the AGC module sends control signals out to the generators every couple seconds.

45

Page 46: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Three Bus Case on AGC

Bus 2 Bus 1

Bus 3Home Area

266 MW

133 MVR

150 MW

250 MW

34 MVR

166 MVR

133 MW

67 MVR

1.00 PU

-40 MW

8 MVR

40 MW

-8 MVR

-77 MW

25 MVR

78 MW

-21 MVR

39 MW

-11 MVR

-39 MW

12 MVR

1.00 PU

1.00 PU

101 MW

5 MVR

100 MWAGC ON

AVR ON

AGC ON

AVR ON

46

Net tie flow is

close to zero

Generation

is automatically changed

to match change in load

Page 47: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Transactions

• Power transactions are contracts between areas to do power transactions.

• Contracts can be for any amount of time at any price for any amount of power.

• Scheduled power transactions are implemented by modifying the area ACE: ACE = Pactual,tie-flow - Psched

47

Page 48: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

100 MW Transaction

Bus 2 Bus 1

Bus 3Home Area

Scheduled Transactions

225 MW

113 MVR

150 MW

291 MW

8 MVR

138 MVR

113 MW

56 MVR

1.00 PU

8 MW

-2 MVR

-8 MW

2 MVR

-84 MW

27 MVR

85 MW

-23 MVR

93 MW

-25 MVR

-92 MW

30 MVR

1.00 PU

1.00 PU

0 MW

32 MVR

100 MWAGC ON

AVR ON

AGC ON

AVR ON

100.0 MW

48

Scheduled

100 MW

Transaction from Left to Right

Net tie-line

flow is now

100 MW

Page 49: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Multi-Area Operation

• If Areas have direct interconnections, then they may directly transact up to the capacity of their tie-lines.

• Actual power flows through the entire network according to the impedance of the transmission lines.

• Flow through other areas is known as “parallel path” or “loop flows.”

49

Page 50: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Seven Bus Case: One-line

50

Top Area Cost

Left Area Cost Right Area Cost

1

2

3 4

5

6 7

106 MW

168 MW

200 MW 201 MW

110 MW

40 MVR

80 MW 30 MVR

130 MW

40 MVR

40 MW

20 MVR

1.00 PU

1.01 PU

1.04 PU1.04 PU

1.04 PU

0.99 PU1.05 PU

62 MW

-61 MW

44 MW -42 MW -31 MW 31 MW

38 MW

-37 MW

79 MW -77 MW

-32 MW

32 MW

-14 MW

-39 MW

40 MW-20 MW 20 MW

40 MW

-40 MW

94 MW

200 MW

0 MVR200 MW

0 MVR

20 MW -20 MW

AGC ON

AGC ON

AGC ON

AGC ON

AGC ON

8029 $/MWH

4715 $/MWH 4189 $/MWH

Case Hourly Cost

16933 $/MWH

System Has Three “Areas”

Page 51: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Seven Bus Case: Area View

Area Losses

Area Losses Area Losses

Top

Left Right

-40.1 MW

0.0 MW

0.0 MW

0.0 MW

40.1 MW

40.1 MW

7.09 MW

0.33 MW 0.65 MW

51

System has

40 MW of

“Loop Flow”

Actual

flow

between

areas

Scheduled

flow

Loop flow can result in higher losses

Page 52: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Loop Flow in Eastern Interconnect

52

Contours

show lines

that would

carry at

least 2%

of a power

transfer

from

Wisconsin

to TVA

Page 53: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Reactive Power

• Reactive power is supplied by

– generators, capacitors, transmission lines

• Reactive power is consumed by

– loads

– transmission lines/transformers (high losses)

• Reactive power must be supplied locally.

• Reactive must satisfy Kirchhoff’s law - total reactive power into a bus MUST be zero.

53

Page 54: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Voltage Magnitude

• Power systems must supply electric power within a narrow voltage range, typically with 5% of a nominal value.

• For example, wall outlet should supply 120 volts, with an acceptable range from 114 to 126 volts.

• Voltage regulation performed mostly by generators, LTC transformers and capacitors.

54

Page 55: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

How the Grid can Fail August 14th, 2003

55

Page 56: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Pricing Electricity and LMPs

• Cost to supply electricity to bus is called the locational marginal price (LMP)

• Presently some electric markets post LMPs on the web

• In an ideal electricity market with no transmission limitations the LMPs are equal

• Transmission constraints can segment a market, resulting in differing LMP

• Determination of LMPs requires the solution on an Optimal Power Flow (OPF)

56

Page 57: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Three Bus LMP Example: Constraint Ignored

57

Line from Bus 1 to Bus 3 is over-loaded; all

buses have same marginal cost

Gen 1’s

cost

is $10

per

MWh

Gen 2’s

cost

is $12

per

MWh

Bus 2 Bus 1

Bus 3

Total Cost

0 MW

0 MW

180 MWMW

10.00 $/MWh

60 MW 60 MW

60 MW

60 MW

120 MW

120 MW

10.00 $/MWh

10.00 $/MWh

180 MW120%

120%

0 MWMW

1800 $/hr

Page 58: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

58

Three Bus LMP Example: Constraint Considered

Bus 2 Bus 1

Bus 3

Total Cost

60 MW

0 MW

180 MWMW

12.00 $/MWh

20 MW 20 MW

80 MW

80 MW

100 MW

100 MW

10.00 $/MWh

14.01 $/MWh

120 MW 80% 100%

80% 100%

0 MWMW

1921 $/hr

Line from 1 to 3 is no longer overloaded, but now

the marginal cost of electricity at 3 is $14 / MWh

Page 59: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

MISO LMPS from 9/30/11 at 10:55am

59

Source:https://www.midwestiso.org/MarketsOperations/RealTimeMarketData/Page

s/LMPContourMap.aspx

Page 60: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Grid Reliability

• Practically all blackouts are due to localized problems in the distribution system

– distribution system has a radial design, so any break in the circuit will blackout those downstream

– such blackouts have no impact on the reliability of the interconnected transmission system

• Of course large blackouts, like 8/14/03, can occur

60

Page 61: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Grid Reliability

• Reliable operations requires

– no transmission lines/transformers are overloaded

– bus voltages are within limits

– must be able to withstand loss of any single device

– must not lose stability during a short-circuit

– system frequency must be very close to 60 Hz (usually about 0.02 Hz)

61

Page 62: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Frequency Control

• Steady-state operation only occurs when the total generation exactly matches the total load plus the total losses

– too much generation causes the system frequency to increase

– too little generation causes the system frequency to decrease (e.g., loss of a generator)

• AGC is used to control system frequency

62

Page 63: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Freq. Response to 2600 MW Loss

63

Page 64: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power System Protection

• A number of different automatic devices are used to protect the power grid

– several different types of relays sense short-circuits, opening the associated lines or transformers

– under/over voltage relays protect against voltage problems

– under/over frequency relays protect against frequency excursions (59.7 Hz or 60.3 Hz)

64

Page 65: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power Systems are Adaptable

• The power grid can sustain a loss of several lines/generators without a major system-wide collapse (probably)

– Northridge 1994 earthquake removed several major lines, splitting the Western Grid in half, and causing under-frequency load-shedding. But the grid remained intact

• Most vulnerable when the loads are highest

65

Page 66: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Power System Vulnerabilities

• Power system operations have evolved to deal with a number of different problems

– weather including lightning, wind, tornados, hurricanes and icing

– earthquakes

– equipment failures

– random acts of violence

66

Page 67: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

Utility Control Centers

• The power grid is controlled by local control centers, using a SCADA (supervisory control and data acquisition) system and usually a more advanced EMS (energy management system)

• The grid can operate open-loop, and in an emergency can be manually controlled

• Cyber-security is an important issue as more controls are network accessible

67

Page 68: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close

ISO New England Control Center

68

Page 69: Energy Tutorial: Electric Grid 101 - Stanford University · PDF fileEnergy Tutorial: Electric Grid 101 ... AC System Analysis •The power grid is an ac system, operating at close