Energy and Buildings 102 (2015) 357–369 Contents lists available at ScienceDirect Energy and Buildings j ourna l ho me page: www.elsevier.com/locate/enbuild Model predictive control for indoor thermal comfort and energy optimization using occupant feedback Xiao Chen a , Qian Wang a,, Jelena Srebric b a Department of Mechanical and Nuclear Engineering, The Pennsylvania State University, University Park, PA 16802, United States b Department of Mechanical Engineering, University of Maryland, College Park, MD 20742, United States a r t i c l e i n f o Article history: Received 12 December 2014 Received in revised form 31 May 2015 Accepted 1 June 2015 Available online 5 June 2015 Keywords: Model predictive control (MPC) Dynamic thermal sensation (DTS) Data-driven model Energy consumption Actual mean vote (AMV) Extended Kalman Filter (EKF) a b s t r a c t This study developed two model predictive control (MPC) algorithms, a certainty-equivalence MPC and a chance-constrained MPC, for indoor thermal control to minimize energy consumption while maintaining occupant thermal comfort. It is assumed that occupant perceptions of thermal sensation can be contin- ually collected and fed back to calibrate a dynamic thermal sensation model and to update the MPC. The performance of the proposed MPCs based on Actual Mean Vote (AMV) was compared to an MPC using Fanger’s Predicted Mean Vote (PMV) as the thermal comfort index. Simulation results demonstrated that when the PMV gives an accurate prediction of occupants’ AMV, the proposed MPCs achieve a comparable level of energy consumption and thermal comfort, while it reduces the demand on continually sensing environmental and occupant parameters used by the PMV model. Simulation results also showed that when there is a discrepancy between the PMV and AMV, the proposed MPC controllers based on AMV expect to outperform the PMV based MPC by providing a better outcome in indoor thermal comfort and energy consumption. In addition, the proposed chance-constrained MPC offers an opportunity to adjust the probability of satisfying the thermal comfort constraint to achieve a balance between energy consumption and thermal comfort. © 2015 Elsevier B.V. All rights reserved. 1. Introduction Reducing building energy consumption and providing a bet- ter indoor thermal condition not only improves the environmental quality due to reduced emission rate, but also keeps people more productive at work and away from building health related prob- lems. Current building control algorithms are mainly rule based (if-then-else based rules) and thus the performance of a large num- ber of buildings heavily depends on the experience of building managers. In recent years, various advanced control techniques, such as fuzzy logic control [1,2], agent-based intelligent control [3], neural network control [4], optimal control [5], and model predic- tive control [6–19] have emerged in building control applications. In particular, model predictive control has gained increasing popularity in utilizing passive or active thermal storage to save energy [7–9]. With weather predictions and occupancy schedules, free cooling at night was used in cooling applications and night Corresponding author at: The Pennsylvania State University, 325 Leon- hard Building, University Park, PA 16802, United States. Tel.: +1 814 8658281; fax: +1 814 8659693. E-mail address: [email protected] (Q. Wang). setback was adopted for heating applications [7,8]. Peak-load shif- ting was implemented in MPC to save electricity cost by taking advantage of the time-of-day rate of electricity price [9]. MPC was also applied to determine optimal temperature set-points at the top level of a hierarchical control, for which simple PID or on-off controllers were used for lower-level components such as fans, heating/cooling coils and thermal storage tanks [7]. Alternatively, low level components could be directly managed by a MPC to achieve a higher level of efficiency [11]. While on one hand energy saving is important, on the other hand, occupant thermal comfort plays a key role in the control of Heating, Ventilating and Air Conditioning (HVAC) systems for low- energy buildings. A large number of the existing control algorithms were designed such that the neutral temperature was achieved based on the Fanger’s thermal comfort model. Alternatively, the so- called effective temperature, which is a combination of the indoor temperature and relative humidity, could be used as the index for thermal comfort [10]. Though the existing HVAC control algorithms seldom directly optimize a PMV index (or use it as a constraint), a numerical study demonstrated that using the PMV in defining the thermal comfort constraint in a MPC could reduce energy consump- tion and improve thermal comfort, compared to utilizing a comfort zone from a psychrometric chart [10]. http://dx.doi.org/10.1016/j.enbuild.2015.06.002 0378-7788/© 2015 Elsevier B.V. All rights reserved.

Upload: dangkien

Post on 29-Mar-2018

216 views

Category:

Documents


2 download

TRANSCRIPT

Mo

Xa

b

a

ARRAA

KMDDEAE

1

tqpl(bmsnt

pef

hf

h0

Energy and Buildings 102 (2015) 357–369

Contents lists available at ScienceDirect

Energy and Buildings

j ourna l ho me page: www.elsev ier .com/ locate /enbui ld

odel predictive control for indoor thermal comfort and energyptimization using occupant feedback

iao Chena, Qian Wanga,∗, Jelena Srebricb

Department of Mechanical and Nuclear Engineering, The Pennsylvania State University, University Park, PA 16802, United StatesDepartment of Mechanical Engineering, University of Maryland, College Park, MD 20742, United States

r t i c l e i n f o

rticle history:eceived 12 December 2014eceived in revised form 31 May 2015ccepted 1 June 2015vailable online 5 June 2015

eywords:odel predictive control (MPC)ynamic thermal sensation (DTS)ata-driven model

a b s t r a c t

This study developed two model predictive control (MPC) algorithms, a certainty-equivalence MPC and achance-constrained MPC, for indoor thermal control to minimize energy consumption while maintainingoccupant thermal comfort. It is assumed that occupant perceptions of thermal sensation can be contin-ually collected and fed back to calibrate a dynamic thermal sensation model and to update the MPC. Theperformance of the proposed MPCs based on Actual Mean Vote (AMV) was compared to an MPC usingFanger’s Predicted Mean Vote (PMV) as the thermal comfort index. Simulation results demonstrated thatwhen the PMV gives an accurate prediction of occupants’ AMV, the proposed MPCs achieve a comparablelevel of energy consumption and thermal comfort, while it reduces the demand on continually sensingenvironmental and occupant parameters used by the PMV model. Simulation results also showed that

nergy consumptionctual mean vote (AMV)xtended Kalman Filter (EKF)

when there is a discrepancy between the PMV and AMV, the proposed MPC controllers based on AMVexpect to outperform the PMV based MPC by providing a better outcome in indoor thermal comfortand energy consumption. In addition, the proposed chance-constrained MPC offers an opportunity toadjust the probability of satisfying the thermal comfort constraint to achieve a balance between energyconsumption and thermal comfort.

© 2015 Elsevier B.V. All rights reserved.

. Introduction

Reducing building energy consumption and providing a bet-er indoor thermal condition not only improves the environmentaluality due to reduced emission rate, but also keeps people moreroductive at work and away from building health related prob-

ems. Current building control algorithms are mainly rule basedif-then-else based rules) and thus the performance of a large num-er of buildings heavily depends on the experience of buildinganagers. In recent years, various advanced control techniques,

uch as fuzzy logic control [1,2], agent-based intelligent control [3],eural network control [4], optimal control [5], and model predic-ive control [6–19] have emerged in building control applications.

In particular, model predictive control has gained increasing

opularity in utilizing passive or active thermal storage to savenergy [7–9]. With weather predictions and occupancy schedules,ree cooling at night was used in cooling applications and night

∗ Corresponding author at: The Pennsylvania State University, 325 Leon-ard Building, University Park, PA 16802, United States. Tel.: +1 814 8658281;

ax: +1 814 8659693.E-mail address: [email protected] (Q. Wang).

ttp://dx.doi.org/10.1016/j.enbuild.2015.06.002378-7788/© 2015 Elsevier B.V. All rights reserved.

setback was adopted for heating applications [7,8]. Peak-load shif-ting was implemented in MPC to save electricity cost by takingadvantage of the time-of-day rate of electricity price [9]. MPC wasalso applied to determine optimal temperature set-points at thetop level of a hierarchical control, for which simple PID or on-offcontrollers were used for lower-level components such as fans,heating/cooling coils and thermal storage tanks [7]. Alternatively,low level components could be directly managed by a MPC toachieve a higher level of efficiency [11].

While on one hand energy saving is important, on the otherhand, occupant thermal comfort plays a key role in the control ofHeating, Ventilating and Air Conditioning (HVAC) systems for low-energy buildings. A large number of the existing control algorithmswere designed such that the neutral temperature was achievedbased on the Fanger’s thermal comfort model. Alternatively, the so-called effective temperature, which is a combination of the indoortemperature and relative humidity, could be used as the index forthermal comfort [10]. Though the existing HVAC control algorithmsseldom directly optimize a PMV index (or use it as a constraint), a

numerical study demonstrated that using the PMV in defining thethermal comfort constraint in a MPC could reduce energy consump-tion and improve thermal comfort, compared to utilizing a comfortzone from a psychrometric chart [10].

358 X. Chen et al. / Energy and Build

Nomenclature

AMV virtual occupants’ actual mean voteAw wall area, m2

percentage of violation in chance constraintCi thermal capacitance of ith node in thermal network

model, J/K-sCLO occupants’ clothing insulationcpa specific heat of air, J/kg-Kcpw specific heat of water vapor, J/kg-Kd offset parametere process noiseGint internal gain, Wh convection coefficient, W/m2-Khin outdoor specific enthalpy of moist air, J/kghout indoor specific enthalpy of moist air, J/kghwe evaporation heat of water at 0 ◦C, J/kgJt cost at time step t in MPC formulationk conduction coefficient, W/m-KKp proportional gainKI integral gainl wall thickness, mM metabolic ratem air mass flow rate, kg/sq slack variable for constraintqvent flow ventilation heat flow, WRij thermal resistance between node i and j, K/WRH relative humidityTa ambient air temperature, KTi temperature of ith node in thermal network model,

KTo outdoor air temperature, KTmr mean radiant temperature, KTN adjacent room temperature, KTS predicted thermal sensation in a generic model�T sampling time, st time stepu control input, WVa air velocity, m/sv measurement noiseWin indoor humidity ratioWout outdoor humidity ratioWs saturation humidity ratiow random noise in AMVx thermal sensation state

Hctirmstmcrccp

d

y observed mean vote of thermal sensation

However, direct incorporation of the PMV in a MPC design forVAC systems could pose practical implementation challenges. Thealculation of PMV involves iteration, which could raise computa-ion concerns, especially for MPC which is known to be computationntensive. Past work tried to approximate the PMV with a neu-al network model [4,12,20] or with a linearized parameterizationodel [21]. In addition, most buildings typically do not have sen-

ors to continually measure humidity, air velocity and mean radiantemperature. Even though for laboratory facilities where the afore-

entioned environmental sensing data are available, occupantlothing insulation and activity levels, which could vary withespect to time and vary among occupants, are seldom monitoredontinually and individually. Assuming a uniform and constant

lothing level for occupants could cause errors in predicting occu-ant thermal sensations [11].

In this study, the MPC problem formulation used a data-riven dynamic thermal sensation (DTS) model developed using

ings 102 (2015) 357–369

occupants’ feedback on thermal perceptions [22]. A distinctive fea-ture of this DTS model lies in that the time-varying offset parameterof the proposed Wiener-logistic model can be estimated throughan extended Kalman Filter (EKF) using real-time occupant votes tocapture the variability of thermal sensation due to environmen-tal or occupant-associated changes. Rather than assuming that a“PMV sensor” exists [10], this study assumed that occupants actas a sensor for indoor thermal comfort and there exists a feedbackchannel for occupants to provide their thermal sensation votes tothe controller. Field studies showed that there could be a discrep-ancy between Fanger’s PMV and occupants’ AMV [23]. Furthermore,occupants’ awareness of opportunities to control their environ-ment could affect their perceptions of thermal comfort [24], andoccupants did often express their wishes to intervene automatedcontrol systems [25]. Though under the current building environ-ment, it might not be practical for an individual occupant to directlycontrol HVAC systems to achieve a personalized thermal environ-ment, it is reasonable to assume that there is a feedback channelfor occupants to communicate their thermal sensation perceptionsto the controller.

Replacing Fanger’s PMV by such a dynamic thermal sensa-tion model in the MPC formulation enables the proposed MPCdesign for HVAC systems to adapt to uncertainties and varia-tions associated with occupants’ thermal perceptions. In addition, achance-constrained MPC was also developed using the DTS model,which provides an opportunity for the controller to adjust the prob-ability level of violation of thermal comfort to achieve a balancebetween energy consumption and thermal comfort.

2. Models

This section presents a data-driven dynamic thermal sensationmodel and a building model, which were used in the performanceevaluation of the proposed MPCs.

2.1. Experiments with human subjects

Chamber experiments with human subjects were approved bythe Institutional Review Board at the Pennsylvania State University(IRB # 41077). The experiments were conducted in a climate cham-ber with its dimension shown in Fig. 1. The chamber was dividedinto two identical rooms and each room has its own HVAC unit. AHOBO U12 data logger was positioned in the middle of each roomto measure air temperature and relative humidity. The mean radi-ant temperature of each room was measured by the BlackGlobeTemperature Sensor for Heat Stress (BlackGlobe) mounted at thesame position as the HOBO U12 data logger. In the experiments, allenvironmental parameters were controlled to be the same for bothrooms of the climate chamber, and both rooms were used at thesame time to provide enough space for all participants. Therefore,the chamber can be viewed as a single virtual room and subjectvotes from the two rooms were not differentiated.

The experiments were conducted in February, with outdoortemperature around 5 ◦C to 7 ◦C, and outdoor humidity level around50%. There were two sessions and each session lasted 2.5 h. In thefirst session, the room temperature was initially set at 21 ◦C for50 min, then raised to 30 ◦C for another 50 min, and reduced backto 21 ◦C again for the rest of the first session. The temperature ofthe second session started at 30 ◦C for 50 min, then reduced to 23 ◦Cfor another 50 min, and back to 30 ◦C for the rest of the session.The available humidifier was not used to mimic the indoor envi-

ronmental conditions typical for buildings without humidification.When the indoor air was heated to 21 ◦C to 30 ◦C, the resulting rel-ative humidity of the chamber varied between 15% and 25%, withan average of 21%. Since the experiments were designed to model

X. Chen et al. / Energy and Buildings 102 (2015) 357–369 359

Fig. 1. Climate chamber layout.

Table 1Key parameters of the thermal-comfort chamber experiment.

radia

ambi

htastkp

geprdwtAvett

2

msf

x

y

dx

Occupant clothing insulation Occupant activity level Chamber mean

0.71 1 Closely follows

ow the changes of ambient temperature would affect occupants’hermal sensation, other inputs such as air velocity and occupants’ctivity level and clothing insulation were kept almost constantince (1) it would otherwise explode the number of experimen-al conditions, and (2) air temperature is typically the only controlnob for low-energy buildings. Key environmental and occupantarameters of the chamber experiments are summarized in Table 1.

There were a total of 13 participants, including college andraduate students, who completed both sessions of the chamberxperiments. The weight, height, age and gender of each partici-ant were recorded to estimate each individual’s basal metabolicate. Clothing level of each subject was also recorded with detailedescription. During the experiments, participants were allowed toork on laptops, read, and write in their sitting positions, and thus

he activity level of each participant was considered sedentary.ll participants were asked to write down their thermal sensationotes according to the ASHRAE 7-point thermal sensation scalesvery 5 min during a 20 min time period immediately after the ini-ial change of air temperature set-point, and then every 10 min forhe rest of the session time.

.2. A data-driven dynamic thermal sensation model

Based on the chamber experiments, a data-driven dynamic ther-al sensation model was derived to describe occupants’ thermal

ensation variations due to changes of indoor air temperature asollows:

(t + 1) = 0.798 · x(t) + 0.0610 · x(t − 1) + Ta(t) − 0.883 · Ta(t − 1)

+ e(t) (1)

(t) = 3.033 + d(t) + v(t) (2)

exp[−0.558 · (x(t) − 7.931) + 8.166] + 1

This state-space model has a Wiener structure with a linearynamic Eq. (1) and a logistic nonlinear output Eq. (2), where

denotes the thermal sensation state, Ta denotes the ambient

nt temperature Chamber average RH Chamber average air velocity

ent temperature 21% 0.135 m/s

air temperature input with the unit of Celsius, and y denotesthe observed/actual mean vote of thermal sensation. The processnoise and measurement noise are denoted by e and v, respectively.The sampling time of the discrete time dynamic model is 5 min.The logistic output function in (2) has a constant regressor mean(r = 7.931), output coefficient (a = 3.033), dilation (b = 0.558), trans-lation (c = −8.166), but with a time varying offset parameter d(t).The constant model coefficients in (1–2) and a nominal value forthe offset parameter d = −0.994 were obtained by running a nonlin-ear least-squares algorithm over data collected from the chamberexperiments.

In (1), the air temperature Ta is modeled as the sole control input.We assume that the aggregate effect of other significant factorssuch as relative humidity, air velocity, mean radiant temperatureand occupant-related factors is captured by the offset parameterd(t) in (2). Additional thermal or non-thermal factors are consideredas process and sensor noise.

When indoor environmental conditions or occupant clothingand activity level deviate from the nominal condition conducted inthe chamber experiments, a new offset parameter d is re-estimatedusing EKF [26] to effectively correct the model prediction of ther-mal sensation. Essentially, the offset parameter d is modeled as a(discrete time) Wiener process as follows:

d(k + 1) = d(k) + ed(k)

where the parameter process noise ed is assumed to have zero meanand nonzero variance Qd. Define an augmented state variable xA(k)consisting of the original state variable x(k − 1), x(k), and the time-

varying offset parameter d(k), xA(k) =[

x(k − 1) x(k) d(k)]T

.Then an EKF is applied to estimate the augmented state variable, i.e.,

estimating the thermal sensation state and the time-varying offsetparameter d simultaneously (see the Appendix). This dynamic ther-mal sensation model was presented before in the authors’ paper[22].

3 Buildings 102 (2015) 357–369

2

a[amTtt

amrcfadtsitstthifOac[cetptamtOr

fsttttab

lEmfdtbcs(

R

C2dT2 = T1 − T2 + TO − T2 (7)

60 X. Chen et al. / Energy and

.3. Building thermal transport model

The thermal transport model for the chamber was derived using commonly used RC thermal network based on heat balance27,28]. For a RC thermal network, each wall or zone is abstracted as

node. Each node is then modeled as a thermal capacitance (ther-al mass) with its temperature representing the state of the node.

he network is formed by connecting all nodes with thermal resis-ors. The capacitances and resistances can be estimated based onhe geometry and material properties of the building under study.

It is important to notice that the thermal network model is simple representation of actual building environment and itsechanical system. Building network models are widely used and

ecently improved for their capabilities to accurately predict energyonsumption in buildings [29]. These models are popular not onlyor their capabilities to accurately predict energy consumption inctual buildings, but also for their simplicity, allowing testing ofifferent control algorithms prior to their deployment and furtheresting in more complicated scenarios [30]. In the present study,everal important assumptions are made for the network modelncluding negligible internal radiative fluxes, which are applicableo spaces without windows and radiative cooling/heating systems,uch as chilled ceiling or heating radiators [22]. Therefore, thehermal network model treats the conductive and convective heatransfer as well as thermal storage, but it neglects the radiativeeat transfer. It is important to notice that this assumption also

mplies that the mean radiant temperature, used in thermal com-ort models, is equal to the air temperature in the studied space.ur experimental study showed that this assumption is correct for

space with well-insulated walls, without windows or radiativeooling/heating systems, such as the studied chamber environment22]. Furthermore, the thermal network model assumes no recir-ulation of the air supplied to the space, so the total amount ofnergy required for cooling or heating the studied space is overes-imated, but the actual trends and relative differences are followingerformance in actual spaces. Overall, the simplifications used inhe thermal network model result in heat flux values that devi-te from actual systems, but represent correct trends and orders ofagnitude, so they provide a good representation of an actual sys-

em to test the differences in performance of controls algorithms.ur future study will account for a realistic mechanical system

epresentation, such as EnergyPlus software [31].Fig. 2 shows the RC thermal network for a single-room chamber,

or which the roof and floor are ignored. There are 5 nodes in theystem. Node 1 represents the room air and other nodes representhe four single-layered walls of the room. Let Ti(i = 1, · · · , 5) denotehe temperature of the node i = 1, · · · , 5, respectively. Let TO denotehe outdoor temperature. Without loss of generality, it is assumedhat wall 2 faces outside and the rest of the walls are connected todjacent rooms (not shown in the figure) with temperature denotedy TN.

The capacitance of each node, Ci (i = 1, . . ., 5), depends on theumped mass of the node and specific heat of the wall material.ach lumped thermal resistance between each pair of nodes is esti-ated based on different ways of heat transfer given as follows: (1)

or conduction within the wall, Rcond = (lwall)/(2kAw), where lwall

enotes the thickness of the wall, k is the conduction coefficient ofhe wall material, and Aw is the area of the wall; (2) for convectionetween a wall surface and air, Rconv = 1/hAw , where h denotes theonvection coefficient. In this study, all walls are assumed to be theame, and thus the thermal resistance between each pair of nodesi, j), Rij, is assumed to be the same and it is computed as follows,

ij = Rcond + Rconv = l

2kAw+ 1

hAw(3)

Fig. 2. Single room thermal network model.

The air change rate is set at 1ACH. The heat exchange due toventilation can be calculated as,

qvent flow = m(hout − hin) = m{

[cpa · To + Wout(cpw · To + hwe)]

−[cpa · T1 + Win(cpw · T1 + hwe)]}

(4)

where qvent flow denotes the ventilation heat flow, m denotes theair mass flow rate and can be calculated based on the volume ofthe room and the air change rate, hout denotes the outdoor spe-cific enthalpy of moist air, hin denotes the indoor specific enthalpyof moist air, cpa denotes the specific heat of air, cpw denotes thespecific heat of water vapor, To denotes the outdoor temperature,T1 denotes the indoor temperature (temperature of node 1), Wout

denotes the outdoor humidity ratio, Win denotes the indoor humid-ity ratio, and hwe denotes the evaporation heat of water at 0 ◦C. It isimportant to note that this model assumes no recirculation, so theentire airflow rate represents outdoor airflow into the space. This isan assumption introduced to simplify the thermal network model.

Humidity ratio W can be calculated as,

W = RH · Ws

1 + (1 − RH)Ws/0.6220(5)

where RH denotes relative humidity, Ws denotes saturation humid-ity ratio, which can be looked up for specific air temperatures. By(5), the indoor and outdoor humidity ratio Win and Wout can becomputed respectively.

Let Gint denote the internal gain. Then based on energy conser-vation, the temperature of each node, Ti, i = 1, · · · , 5, satisfies thefollowing state-space model,

C1dT1

dt= T2 − T1

R21+ T3 − T1

R31+ T4 − T1

R41+ T5 − T1

R51+ qvent flow

+ Gint + u (6)

dt R21 R2O

C3dT3

dt= T1 − T3

R31+ TN − T3

R3N(8)

X. Chen et al. / Energy and Build

Table 2Chamber parameters used in the building model.

Room(air) Walls

Density (kg/m3) 1.16 2000Specific heat Cp (J/kg-K) 1007 935Conduction coefficient k (W/m-K) 0.744Convection coefficient h (W/m2-K) 5Length (m) 6Width (m) 6Height (m) 3

C

C

w(

i2spf

T

T

wioT

A

3

twtejb(irt(tm

Air mass flow rate (kg/s) 0.139Thickness (m) 0.15

4dT4

dt= T1 − T4

R41+ TN − T4

R4N(9)

5dT5

dt= T1 − T5

R51+ TN − T5

R5N(10)

here the control input u denotes the heating (u > 0) or coolingu < 0) flow.

Define T =[

T1 T2 · · · T5]T

(in Kelvin). Consider a constantnternal gain Gint = 500 W and a neighboring room temperature of5 ◦C. By discretization of the continuous time model with a 15 minampling time, the resulting discrete-time building thermal trans-ort model can be written in the following compact state-spaceorm,

(t + 1) = AT(t) + B1TO(t) + B2TN(t) + B3[u(t) + Gint + qvent flow(t)]

(11)

a(t + 1) = CT(t + 1) − 273.15 (12)

here the unit of the room air temperature Ta is Celsius, and numer-cal values of the matrices A, B1, B2, B3 and C can be calculated basedn the geometry and material properties of the chamber given inable 2 and their values are given as follows:

=

⎡⎢⎢⎢⎢⎣

0.1843 0.2026 0.2026 0.2026 0.2026

0.0051 0.9802 0.0014 0.0014 0.0014

0.0051 0.0014 0.9802 0.0014 0.0014

0.0051 0.0014 0.0014 0.9802 0.0014

0.0051 0.0014 0.0014 0.0014 0.9802

⎤⎥⎥⎥⎥⎦ ,

BT1 =

[0.0014 0.0106 0 0 0

],

BT2 =

[0.0041 0 0.0106 0.0106 0.0106

],

BT3 =

[0.0034 0 0 0 0

]C =

[1 0 0 0 0

]. Control formulation

Two types of MPC designs using the dynamic thermal sensa-ion model (1–2) were developed to minimize energy consumptionhile maintaining occupant thermal comfort. At each time instant

, the MPC solves a finite-horizon constrained minimization ofnergy consumption to determine the optimal heating/cooling tra-ectory based on the prediction of indoor conditions (from theuilding model) and prediction of occupants’ actual mean votefrom the DTS model). Only the first step of the control trajectorys implemented at the current time instant t and the procedure isepeated at the next time instant. For the simulations conducted in

his study, outdoor weather conditions were assumed to be knownhistorical data were used), based on which prediction of indoor airemperature was computed using the building thermal transport

odel (10–11). Due to the considered process noise and sensor

ings 102 (2015) 357–369 361

noise in the DTS model (1–2), the observed occupants’ AMV isassumed to be a random variable.

In the first MPC, the thermal comfort constraint is specifiedin terms of the DTS model prediction for AMV and the controllerassumes that the prediction is correct under certainty equivalence,i.e., the disturbance/noise is assumed to take its expected value.This MPC is referred to as Certainty Equivalence MPC, denoted asCEMPC-DTS. In the second MPC, a stochastic thermal comfort con-straint is defined, which requires that the probability of AMV withina specified bound is larger than a preset number. This MPC isreferred to as Chance-Constrained MPC, denoted as CCMPC-DTS. Adeterministic approximation of the chance constraint was adoptedin this paper, which leads to a tighter bound on thermal comfortthan that used in CEMPC.

Performance of the CEMPC-DTS and CCMPC-DTS were com-pared to a MPC using Fanger’s PMV as the thermal comfort index(denoted as MPC-PMV) and a rule-based PI control (denoted asRuleBased-PI) that represents the current control practice for HVACsystems. Control formulations of the three MPC designs are givenin Section 3.1 and details on the RuleBased-PI are given in Section3.2.

3.1. MPC formulations

The general MPC formulation is described as follows.Cost:

minUt

Jt:=∑N

k=1[u(t + k|t)]

2

+ �∑N

k=1[q(t + k|t)] (13)

This cost function is subject to the following models for buildingthermal transport and thermal sensation for building occupants.

Building thermal transport model:

T(t + k + 1|t) = AT(t + k|t) + B1TO(t + k|t) + B2TN(t + k|t)

+ B3[u(t + k|t) + Gint(t + k|t) + qvent flow(t + k|t)] (14)

Ta(t + k + 1|t) = CT(t + k + 1|t) − 273.15 (15)

Thermal sensation model:

TS(t + k|t) = f (Ta(t + k|t), Ta(t + k − 1|t), . . .) (16)

Constraint on thermal comfort:

ymin − q(t + k|t) ≤ TS(t + k|t) ≤ ymax + q(t + k|t) (17)

q(t + k|t) ≥ 0 (18)

Constraint on cooling and heating power:

umin ≤ u(t + k|t) ≤ umax (19)

where Ut = [u(t + 1|t), · · · , u(t + N|t)] denotes the control input trajec-tory along the prediction horizon, and N denotes the length of theprediction horizon. The cost function Jt is defined as the L2 normof the control input u(t + k|t) plus the L1 norm of the slack variableq(t + k|t) for satisfying the thermal comfort constraint. A very largenumber � is chosen to heavily penalize the violation of thermalcomfort. TS represents thermal sensation in a generic model (16),which will be substituted by different thermal comfort models inthe subsequent subsections. A soft constraint (17) is consideredfor maintaining the thermal sensation within the bounds ymin and

ymax using the slack variable q to avoid infeasibility in solving theresulting MPC. The control input is subject to constraint (19) withthe maximum cooling power denoted by umin (umin < 0) and themaximum heating power denoted by umax (umax > 0).

3 Build

3(

utsGt(

x

d

y

T

5t

3

s

P

wic[

y

wDi˝

62 X. Chen et al. / Energy and

.1.1. Certainty equivalence MPC based on DTS modelCEMPC-DTS)

In CEMPC-DTS, the thermal sensation equation (16) is computedsing the DTS model expressed in (1–2) under the assumption thathe noise e(t) and v(t) take their respective expected values. In thistudy, the process noise e(t) and sensing noise v(t) are assumed to beaussian with zero mean, i.e., E[e(t)] = 0 and E[v(t)] = 0. As a result,

he following thermal sensation prediction is used to substitute16) in CEMPC-DTS:

ˆ(t + k + 1|t) = 0.798 · x(t + k|t) + 0.0610 · x(t + k − 1|t)

+ Ta(t + k|t) − 0.883 · Ta(t + k − 1|t) (20)

ˆ(t + k|t) = d(t + k − 1|t) (21)

ˆ(t + k|t) = 3.033exp[−0.558 · (x(t + k|t) − 7.931) + 8.166] + 1

+ d(t + k|t) (22)

S(t + k|t) = y(t + k|t) (23)

Note that the coefficient values in (20)–(22) correspond to a min sampling time and re-discretization using a 15 min samplingime was conducted in the controller simulation.

.1.2. Chance constrained MPC based on DTS model (CCMPC-DTS)CCMPC-DTS considers the following probabilistic (chance) con-

traint for thermal comfort:

rob{ymin ≤ TS(t + k|t) ≤ ymax} ≥ 1 − (24)

here denotes a predefined small percentage. Assuming a Gauss-an distributed process/sensor noise with zero mean, the chanceonstraint (24) can be approximated by a deterministic constraint32] as follows:

min + �y ≤ y(t + k|t) ≤ ymax − �y (25)

y = ˇ˝1/2 (26)

here y(t + k|t) denotes the prediction for AMV given by theTS model (20–22), =

√2erf −1(1 − 2˛) with erf−1 denoting the

nverse of the standard error function erf (x) = (2)/(√

�)∫ x

0e−u2

du, corresponds to the measurement prediction covariance in (A.11)

Fig. 3. Block diagram for D

ings 102 (2015) 357–369

(which is a scalar here due to the single output variable) and it canbe computed using EKF.

By further softening the constraint using the slack variable q inCCMPC-DTS, thermal constraint (17) is replaced by

(ymin + �y) − q(t + k|t) ≤ y(t + k|t) ≤ (ymax − �y) + q(t + k|t) (27)

Compared to the constraint used in CEMPC-DTS, the constraintin CCMPC-DTS offers two advantages: (1) a tunable probability ofconstraint violation ˛, and (2) a tighter thermal comfort bound toimprove thermal comfort.

3.1.3. MPC based on PMV model (MPC-PMV)In the MPC-PMV formulation, Fanger’s PMV model is used to

implement (16) for TS(t + k|t),TS(t + k|t) = PMV(Ta(t + k|t), Tmr, RH, Va, CLO, M) (28)

where the air temperature prediction Ta(t + k|t) is obtained from thebuilding model (14) and (15), the mean radiant temperature Tmr isassumed to be the same as the air temperature, and the relativehumidity RH, air velocity Va, occupants’ clothing insulation levelCLO and metabolic rate (activity level) M at time (t+k) are assumedto be known.

3.2. RuleBased-PI control

In this control strategy, the thermal comfort constraint isdefined by specifying heating and cooling set points, denoted bySPheating and SPcooling respectively, with a buffer to prevent shortcycling. The actual values of these set points are chosen by build-ing managers and they vary by seasons and climate regions. If theindoor temperature is low (Ta < SPheating − buffer), a PI control isapplied to increase the indoor temperature to the heating set pointSPheating. If the indoor temperature is high (Ta > SPcooling + buffer), a PIcontrol is applied to cool the indoor air temperature to the coolingset point SPcooling. The PI control with a low-pass filter used in thispaper is given as follows:

u−(k) = Kp · err(k) + KI · �T ·∑k

i=0err(i) (29)

u(k) = 0.1 · u−(k) + 0.9 · u(k − 1) (30)

where err denotes the error between the heating set point SPheating(or cooling set point SPcooling) and indoor air temperature Ta, Kp andKI are proportional and integral gain, respectively, and �T is thesampling time.

TS model based MPC.

X. Chen et al. / Energy and Buildings 102 (2015) 357–369 363

4

4

Ctt

A

wbiWPu[o

cIatetAthott

fttrtihts

oebb(pb

Fig. 5. Clothing insulation level used in simulation.

Fig. 6. Outdoor weather. (a) Top: 3 day outdoor temperature history in March.

Fig. 4. Indoor relative humidity used in simulation.

. Simulation results

.1. Simulation platform

Performance of the two DTS-based MPC, CEMPC-DTS andCMPC-DTS, was compared to the MPC-PMV and Rule-based PIhrough simulations. Here, the occupants’ AMV is simulated usinghe PMV plus a random white noise w,

MV(k) = PMV(k) + w(k) (31)

here the random noise w is assumed to follow a Gaussian distri-ution. When w has a zero mean E[w] = 0, we assume that the PMV

s an accurate model to describe the occupants’ AMV without bias.hen w has a nonzero mean, i.e., E[w] /= 0, we assume that the

MV is biased in evaluating AMV, noting that PMV was reported tonderestimate or overestimate thermal sensation in field surveys22,23]. In the remaining of this paper, the output of the virtualccupant model (31) is referred to as virtual occupants’ feedback.

Fig. 3 shows the block diagram for the DTS model based MPController (either CEMPC-DTS or CCMPC-DTS) used in simulations.t is assumed that occupants’ feedback on thermal sensation isvailable to be used by the MPC design. At each time step ofhe simulation, the observed occupants’ AMV is first passed to anxtended Kalman Filter to estimate the state variable x(t + k|t) andhe offset parameter d(t + k|t) simultaneously (details given in theppendix). These two parameters are then fed into the DTS model

o generate the prediction of AMV y(t + k|t) along the optimizationorizon. By solving the corresponding MPC optimization (CEMPCr CCMPC), the optimal heating or cooling flow is determined andhen fed into the building model to compute the resulting roomemperature.

For the MPC-PMV controller, there is neither an “EKF” block noreedback of occupants’ thermal sensation to the MPC-PMV con-rol. Among the six input variables to the PMV model, the room airemperature is predicted by the building model (13–14), the meanadiant temperature is set to be the same as the air temperature,he air velocity and occupant activity level are set to the values usedn a chamber experiment [22] (see Table 1), and the indoor relativeumidity and clothing insulation levels are designed to start fromhe nominal values given in Table 1 and then follow the trajectorieshown in Fig. 4 and Fig. 5, respectively.

The simulation time step �T is set to be 15 min. The MPCptimization horizon is chosen to be N = 20 sampling intervalsquivalent to 5 h. The bounds on thermal sensation are set toe ymin = −0.5 and ymax = 0.5. The control input is constrainedy umin = −5000 (for 5 kW max cooling power) and umax = 5000

for 5 kW max heating power) respectively. In the RuleBased-PI,arameters are set to be SPheating = 24 Celsius, SPcooling = 26 Celsius,uffer = 1 Celsius, Kp = 2000 and KI = 100.

Bottom: 3 day outdoor temperature history in September. (b) Top: 3 day outdoorrelative humidity history in March. Bottom: 3 day outdoor relative humidity historyin September.

4.2. Environmental and occupant parameters

To evaluate the control performance, simulations in this studyused two different sets of outdoor weather conditions shown

364 X. Chen et al. / Energy and Buildings 102 (2015) 357–369

Fig. 7. Controlled indoor air temperature. (a) Representative Scenario I (March,E

iaffhdbftbaofidiw[(

tGe

Fig. 8. Control input. (a) Representative Scenario I (March, E[w] = 0), control input

[w] = 0). (b) Representative Scenario II (March, E[w] = −0.2).

n Fig. 6. In Fig. 6, the subplots show the outdoor temperaturend relative humidity history data collected at State College, PAor 3 days from 03/09/2013 to 03/11/2013 in March and 3 daysrom 09/10/2013 to 09/12/2013 in September. The indoor relativeumidity trajectory used in the simulations (shown in Fig. 4) isesigned to start at a nominal value of 21% in the first day followedy a sinusoidal curve ranging from 21% to 80% with a period of 24 hor two days. This indoor relative humidity parameter is designedo follow such a trajectory so that the proposed controllers cane tested in very low and very high humidity conditions within

relative short simulation time period. The average clothing levelf occupants is plotted in Fig. 5, which is set to CLO = 0.71 for therst two days, raised to CLO = 0.85 at the beginning of the thirday and then maintained at this value for the rest of the day. The

nitial values of the relative humidity and average clothing levelere chosen from operating conditions of the chamber experiment

22] conducted to obtain nominal coefficients of the DTS model1–2).

To generate the virtual occupant feedback on thermal sensa-ion, the noise w that is added to the PMV in (31) is chosen to be aaussian noise with a standard deviation of 0.08 with three differ-nt mean values: (1) E[w] = 0, used to simulate the scenario where

corresponds to heating power. (b) Representative Scenario II (March, E[w] = −0.2),control input corresponds to cooling power.

there is no discrepancy between the PMV and AMV; (2) E[w] = 0.2,used to simulate the scenario where the PMV underestimates theAMV, and (3) E[w] = −0.2, used to simulate the scenario where thePMV overestimates the AMV.

4.3. Performance metrics

Three metrics are used to evaluate the control performance. Thefirst one is total Energy Consumption (E), which computes the inte-gration of control input (heating/cooling power) over time. Thesecond one is Violation Ratio (VR), which is defined as the ratio ofthe time during which the AMV generated by the Virtual Occupantsfalls outside the thermal sensation bounds over the total simulationtime (3 days). This metric indicates how frequently the constrainton thermal comfort is violated, but it does not provide informa-tion on how far the AMV is away from the specified bounds whenthe constraint is violated. The third metric, Integration of Violation

(IOV), computes the area between the thermal sensation bound (0.5or −0.5 depending on cooling or heating application) and the AMVsthat fall outside the bound.

X. Chen et al. / Energy and Buildings 102 (2015) 357–369 365

cenar

4

eoeaanEs

Fig. 9. Actual mean vote (AMV) from virtual occupants. (a) Representative S

.4. Results and discussions

Considering two sets of weather conditions, three differentxpected values for the Gaussian noise w in simulating virtualccupants, and four controllers, there are a total of 24 cases beingvaluated. Table 3 summarizes the performance statistics, whichre averages of 20 simulation runs for each case. Simulation plots

re presented in Figs. 7–10 for two representative scenarios: Sce-ario I corresponds to E[w] = 0, and Scenario II corresponds to[w] = −0.2, both for the time period in March. Due to the limitedpace, simulation plots for other cases are omitted here.

io I (March, E[w] = 0). (b) Representative Scenario II (March, E[w] = −0.2).

4.4.1. RuleBased-PI versus MPCTable 3 shows that when E[w] = 0, all three MPC algorithms use

less amount of energy than the RuleBased-PI while providing bet-ter thermal comfort (lower IOV). When E[w] /= 0, at least one of thethree MPC algorithms consumes less energy with lower (or com-parable) IOV than the RuleBased-PI. Figs. 7 and 8 shed some lighton the underlying cause for energy savings with improved thermal

comfort for MPC designs. The room temperature profiles given inFig. 7 show that the RuleBased-PI tries to regulate the room temper-ature to the heating set point at 24 ◦C, irrespective of the changesin relative humidity and occupant clothing levels. In contrast, room

366 X. Chen et al. / Energy and Buildings 102 (2015) 357–369

FRE

ttiotdaFMtf

4

istTFpc

ig. 10. Time-varying offset parameter of the DTS model estimated by EKF. (a)epresentative Scenario I (March, E[w] = 0). (b) Representative Scenario II (March,[w] = −0.2).

emperatures controlled by the three MPC designs are adjustedo adapt to the changes in RH and clothing levels. For example,n the second day the room temperatures controlled by MPCs arebserved to follow a roughly flipped pattern of the humidity curveo maintain the same level of thermal sensation. In the third day,ue to the increased clothing insulation level, indoor temperaturesre reduced to a lower value to save energy consumption (see alsoig. 8 for control input trajectories). Fig. 9 shows that for all threePC designs, AMV is closely regulated to be constant except the

imes when changes of RH and clothing level occur, but the AMVor the RuleBased-PI varies a lot.

.4.2. MPC-PMV versus CEMPC-DTSScenario I (March, E[w] = 0) represents the case where the PMV

s assumed to be an accurate prediction for occupants’ AMV. Fig. 7(a)hows that the difference between the two air temperature trajec-ories controlled by the MPC-PMV and CEMPC-DTS is very limited.

he control input trajectories of the two controllers (shown inig. 8(a)) are also very close to each other except for the shorteriods when the changes in RH and clothing level occur. These dis-repancies are mainly due to the learning error of the DTS model.

Fig. 11. Pareto frontier of energy consumption versus thermal comfort violation. (a)March, E[w] = 0; (b) September, E[w] = 0.

Statistics from Table 3 also confirm this observation, with theCEMPC-DTS having a slightly higher energy consumption or IOVthan the MPC-PMV.

Scenario II (March, E[w] = −0.2) represents the case where PMVoverestimates the AMV, i.e., the occupants feel colder than pre-dicted by the PMV. As a result, the room temperature of theCEMPC-DTS is controlled at a higher value (close to 1 ◦C higher) withmore energy consumption than the MPC-PMV (shown by Fig. 7(b)and Fig. 8(b)) to regulate the AMV at −0.5 (shown by Fig. 9(b)).Without feedback from occupants, the AMV resulted from the MPC-PMV is lower than the thermal comfort threshold of −0.5 scale.

When E[w] = 0.2 during the 3 day period in March (figures notshown due to the limited space), occupants feel warmer than pre-dicted and thus less heating power is needed to save energy. Case 7of Table 3 shows that the CEMPC-DTS has cut the energy consump-tion more aggressively than desired and thus leads to a higher IOVthan the MPC-PMV. This indicates that a better balance betweenthe energy saving and thermal comfort is needed, which has beeninvestigated in the design of the CCMPC-DTS.

The cases for the September time period show similar trends asthe March time period, as indicated by statistics from Table 3. WhenE[w] = 0, the CEMPC-DTS has a similar level of energy consump-tion, VR and IOV to the MPC-PMV. When E[w] = 0.2, occupants feel

X. Chen et al. / Energy and Buildings 102 (2015) 357–369 367

Table 3Performance statistics (average of 20 simulation runs).

Case Number WeatherCondition

Expected Value of Noise inVirtual Occupant

Controller Energy(E): J Violation Ratio(VR): % Integration ofViolation(IOV)

1 March E[w] = 0 RuleBased-PI 2.38e8 37.10 13.402 MPC-PMV 2.07e8 49.39 8.993 CEMPC-DTS 2.19e8 51.84 12.174 CCMPC-DTS 2.38e8 15.71 2.665 E[w] = 0.2 RuleBased-PI 2.38e8 7.53 1.966 MPC-PMV 2.07e8 0.62 0.0547 CEMPC-DTS 1.84e8 49.74 10.658 CCMPC-DTS 2.04e8 12.12 1.659 E[w] = −0.2 RuleBased-PI 2.38e8 61.09 43.0010 MPC-PMV 2.07e8 99.08 57.3711 CEMPC-DTS 2.56e8 51.93 14.5312 CCMPC-DTS 2.74e8 18.35 4.2513 September E[w] = 0 RuleBased-PI 1.96e8 41.16 22.8214 MPC-PMV 1.82e8 49.27 9.1215 CEMPC-DTS 1.70e8 49.39 13.8116 CCMPC-DTS 1.86e8 19.44 3.6017 E[w] = 0.2 RuleBased-PI 1.96e8 71.48 55.3218 MPC-PMV 1.82e8 99.13 57.3719 CEMPC-DTS 2.03e8 53.65 14.4320 CCMPC-DTS 2.25e8 20.23 3.6221 E[w] = −0.2 RuleBased-PI 1.96e8 15.78 6.91

MPCCEMCCM

h(stt

pftvc

4

oMmavCbtttchM

4t

viFwaCfts

22

23

24

otter than predicted by the PMV and thus demand more coolingmore energy consumption) to satisfy the thermal comfort con-traint (reduced IOV). When E[w] = −0.2, occupants feel coolerhan predicted by the PMV and thus less cooling power is neededo save energy.

For the completeness of information, Fig. 10 plots the offsetarameter of the DTS model estimated by an EKF using occupants’eedback on thermal sensation. The variation of the offset parame-er at the beginning of the first day is due to model calibration. Itsariations at the second and third day show a clear adaptation tohanges of the relative humidity and occupant clothing level.

.4.3. CEMPC-DTS versus CCMPC-DTSTable 3 shows that the thermal comfort violation ratio VR is

ften high for the deterministic control approaches (Rulebased-PI,PC-PMV and CEMPC-DTS), even when E[w] = 0. This implies thatean-vote based deterministic (or certainty-equivalent) controls

re likely not able to meet the thermal comfort constraint if theariance of occupant perceptions of thermal sensation is large. TheCMPC-DTS provides an opportunity to directly specify the proba-ility that thermal comfort constraint will be satisfied. In addition,he tighter bound on thermal comfort imposed by the determinis-ic approximation of the chance constraint helps to improve thehermal comfort level, though at the expense of a larger energyonsumption. Table 3 shows that when E[w] = 0, the CCMPC-DTSas the highest amount of energy consumption among all threePC controllers, but with a significantly lower VR and IOV.

.4.4. Tuning to achieve a balance between energy saving andhermal comfort

To investigate the tradeoff between energy saving and comfortiolation, the probability of thermal constraint violation is var-ed in the CCMPC-DTS to generate the Pareto frontier, as shown inig. 11, for energy consumption versus thermal comfort violationhen E[w] = 0. It is also shown in Fig. 11 that the RuleBased-PI

lways stay upper right to the Pareto frontier, indicating that the

CMPC-DTS can reduce energy usage while improve thermal com-

ort at the same time compared to the RuleBased-PI. Correspondingo similar level of thermal comfort, the difference in energy con-umption between the MPC-PMV and the CCMPC-DTS is around 5%

-PMV 1.82e8 0.52 0.0291PC-DTS 1.37e8 42.05 11.17PC-DTS 1.53e8 17.43 3.26

- 8%. This difference is due to the noise variance used in simulatingvirtual occupants’ feedback.

5. Conclusion and future work

In this study, two model predictive control strategies using adata-driven dynamic thermal sensation model were developed ascomplementary design tools to the PMV-based MPC control foroptimizing indoor thermal comfort and energy saving. The pro-posed chance-constrained MPC was designed to allow specifyingthe probability of violation of thermal comfort constraint, in orderto achieve a balance between energy saving and thermal comfort.Simulation results demonstrated that an MPC based on occupantfeedback can be expected to produce better thermal comfort andenergy outcomes than an MPC based on a theoretical thermal com-fort proxy such as PMV.

This study assumes that there is a feedback channel for occu-pants to communicate their thermal perceptions to the controlsystem, which is lacking in the current building control systems.Experimental testing and evaluation of the proposed DTS basedMPC design algorithms in a chamber environment will be con-ducted in the future work.

Acknowledgements

This project is funded by NSF grant EFRI-1038264/EFRI-1452045. The chamber experiment was approved by the IRB at PennState University (IRB #41077). We would like to thank Dr. MoshoodFadeyi, Dr. Mohammad Heidarinejad, Dr. Yang-Seon Kim and Dr.Mingjie Zhao for their help with the chamber experiment and theirvaluable comments. We also would like to thank the anonymousreviewers for their insightful reviews.

Appendix A. An extended Kalman Filter for estimatingthermal sensation state and time-varying offset parametersimultaneously

Consider the dynamic thermal sensation model (1–2),

x(k + 1) = f1x(k) + f2x(k − 1) + g1Ta(k) + g2Ta(k − 1) + e(k) (A.1)

3 Build

y

waip

d

wa

id

x

tl

w

G

F

h

w

whca

f

x

P

g

y

[

[

[

[

[

[

[

[

[

[

68 X. Chen et al. / Energy and

(k) = a

exp [−c − b · (x(k) − r)] + 1+ d + v(k) (A.2)

here the model coefficients f1, f2, g1, g2, a, b, c, r are constantnd defined accordingly. We assume that the offset parameter ds slowly time-varying and modeled as a (discrete time) wienerrocess as follows:

(k + 1) = d(k) + ed(k) (A.3)

here the parameter process noise ed is assumed to have zero meannd nonzero variance Qd.

Define an augmented state variable xA(k) consisting of the orig-nal state variable x(k), x(k − 1), and the time-varying parameter(k),

A =[

xA1

xA2

], xA1 =

[x1

A1

x2A1

]�

[x(k)

x(k − 1)

], xA2 (k) � d(k) (A.4)

Then the original thermal sensation model (A.1) and (A.2)ogether with the parameter model (A.3) can be rewritten as fol-ows,

xA(k + 1) = FxA(k) + G ◦ Ta(k) + ε(k)

y(k) = h(xA(k)) + v(k)(A.5)

here,

◦ Ta(k) =[

g1Ta(k) + g2Ta(k − 1) 0 0]T

,

ε(k) =[

e(k) 0 ed(k)]T

=

⎡⎣ f1 f2 0

1 0 0

0 0 1

⎤⎦ (A.6)

and the output nonlinear function satisfies,

(xA(k)) = a

exp(−c − b(x1A1

(k) − r)) + 1+ xA2 (k)

The process noise ε(k) and sensor noise v(k) are assumed to behite noise and satisfy the following,

E[ε(k)] = 0, E[ε(k)εT (k′)] = Q (k)ıkk′

E[v(k)] = 0, E[v(k)vT (k′)] = R(k)ıkk′(A.7)

It is assumed that the initial estimate xA(0|0) is uncorrelatedith the process noise and sensor noise sequences. Assume that oneas the estimate xA(k|k) = E[xA(k)|Zk] at time k, with the associateovariance matrix P(k|k), where Zk denotes the statistics obtainedt time k.

The predicted state at time (k + 1) based on time k is obtained asollows,

ˆA(k + 1|k) = FxA(k|k) + G ◦ Ta(k) (A.8)

The state prediction covariance is updated as

(k + 1|k) = FP(k|k)FT + Q (k) (A.9)

The predicted measurement for the 2nd-order Kalman Filter isiven by,

ˆ(k + 1|k) = h(xA(k + 1|k)) + 12

tr[hxAxA (k + 1)P(k + 1|k)

](A.10)

[

[

[

ings 102 (2015) 357–369

and the measurement prediction covariance matrix is updatedas

S(k + 1) = hxA (k + 1)P(k + 1)hTxA

(k + 1)

+ 12

tr[hxAxA (k + 1)P(k + 1|k)hxAxA (k + 1)P(k + 1|k)

]+ R(k + 1)

(A.11)

where hxA and hxAxA denote the Jacobian and Hessian of the nonlin-ear function h, respectively,

hxA (k + 1) =[∇xA h(xA)

]T∣∣∣ xA = xA(k + 1|k)

hxAxA (k + 1) =[∇xA∇T

xAh(xA)

]∣∣ xA = xA(k + 1|k)(A.12)

References

[1] A.I. Dounis, D.E. Manolakis, Design of a fuzzy system for living spacethermal-comfort regulation, Appl. Energy 69 (2001) 119–144.

[2] J. Singh, N. Singh, J.K. Sharma, Fuzzy modeling and control of HVAC systems –a review, J. Sci. Ind. Res. 65 (2006) 470–476.

[3] K. Dalamagkidis, D. Kolokotsa, K. Kalaitzakis, G.S. Stavrakakis, Reinforcementlearning for energy conservation and comfort in buildings, Build. Environ. 42(2006) 2686–2698.

[4] J. Liang, R. Du, Thermal comfort control based on neural network for HVACapplication, in: Proceedings of IEEE Conference on Control Applications,Toronto, Canada, 2005.

[5] J.E. Braun, Load control using building thermal mass, J. Solar Energy Eng. 125(2003) 292–301.

[6] M. Zaheer-uddin, G.R. Zheng, Optimal control of time scheduled heatingventilation and air conditioning processes in building, Energy Convers.Manage. 41 (2000) 49–60.

[7] Y. Ma, A. Kelman, A. Daly, F. Borrelli, Predictive control for energy efficientbuildings with thermal storage: modeling, simulation, and experiments, IEEEControl Syst. Mag. 32 (2012) 44–64.

[8] M. Kummert, P. Andre, Simulation of a model-based optimal controller forheating systems under realistic hypothesis, in: Proceedings of the 9th IBPSAConference, Montreal, Canada, 2005.

[9] G.P. Henze, D.E. Kalz, S. Liu, C. Felsmann, Experimental analysis ofmodel-based predictive optimal control for active and passive buildingthermal storage inventory, HVAC R Res. 11 (2005) 189–213.

10] R.Z. Freire, G.H. Oliveira, N. Mendes, Predictive controllers for thermal comfortoptimization and energy savings, Energy Build. 40 (2008) 1353–1365.

11] M. Castilla, J.D. Alvarez, M. Berenguel, F. Rodríguez, J.L. Guzmán, M. Pérez, Acomparison of thermal comfort predictive control strategies, Energy Build. 43(2011) 2737–2746.

12] P.M. Ferrira, A.E. Ruano, S. Silva, E.Z.E. Conceicao, Neural networks basedpredictive control for thermal comfort and energy savings in public buildings,Energy Build. 55 (2012) 238–251.

13] F. Oldewurtel, C.N. Jones, M. Morari, A tractable approximation of chanceconstrained stochastic MPC based on affine disturbance feedback, in:Proceedings of 47th IEEE Conference on Decision and Control, Cancun,Mexico, 2008.

14] F. Oldewurtel, A. Parisio, C.N. Jones, D. Gyalistras, M. Gwerder, V. Stauch, B.Lehmann, M. Morari, Use of model predictive control and weather forecastsfor energy efficient building climate control, Energy Build. 45 (2012) 15–27.

15] Y. Ma, F. Borrelli, Fast stochastic predictive control for building temperatureregulation, in: Proceedings of American Control Conference, Montreal,Canada, 2012.

16] X. Zhang, G. Sturzenegger, D. Sturzenegger, M. Morari, Scenario-based MPCfor energy-efficient building climate control under weather and occupancyuncertainty, in: Proceedings of European Control Conference, Zurich,Switzerland, 2013.

17] X. Xu, S. Wang, G. Huang, Robust MPC for temperature control ofair-conditioning systems concerning on constraints and multitypeuncertainties, Build. Serv. Eng. Res. Technol. 31 (2010) 39–55.

18] M. Maasoumy, A. Sangiovanni-Vincentelli, Optimal control of building hvacsystems in the presence of imperfect predictions, in: Proceedings of 5thAnnual Dynamic Systems and Control Conference joint with the 11th Motionand Vibration Conference, Fort Lauderdale, FL, 2012.

19] J. Siroky, F. Oldewurtel, J. Cigler, S. Privara, Experimental analysis of modelpredictive control for an energy efficient building heating system, Appl.Energy 88 (2011) 3079–3087.

20] S. Atthajariyakul, T. Leephakpreeda, Neural computing thermal comfort indexfor HVAC systems, Energy Convers. Manage. 46 (2005) 2553–2565.

21] C.C. Federspiel, H. Asada, User-adaptable comfort control for HVAC systems, J.Dyn. Syst. Meas. Control 116 (1994) 474–486.

22] X. Chen, Q. Wang, J. Srebric, A data-driven state-space model of indoorthermal sensation using occupant feedback for low-energy buildings, EnergyBuild. 91 (2015) 187–198.

Build

[

[

[

[

[

[

[

[30] S. Goyal, P. Barooah, A method for model-reduction of non-linear thermal

X. Chen et al. / Energy and

23] J. Van Hoof, Forty years of Fanger’s model of thermal comfort: comfort for all?Indoor Air 18 (2008) 182–201.

24] J. Toftum, Central automatic control or distributed occupant control for betterindoor environment quality in the future, Build. Environ. 45 (2010) 23–28.

25] S. Barlow, D. Fiala, Occupant comfort in UK offices—how adaptive comforttheories might influence future low energy office refurbishment strategies,Energy Build. 39 (2007) 837–846.

26] Y. Bar-Shalom, X. Li, T. Kirubarajan, Estimation with Application to Trackingand Navigation, John Wiley & Sons, New York, 2001.

27] G. Fraisse, C. Viardot, O. Lafabrie, G. Achard, Development of a simplified andaccurate building model based on electrical analogy, Energy Build. 34 (2002)1017–1031.

[

[

ings 102 (2015) 357–369 369

28] B. Bueno, L. Norford, G. Pigeon, R. Britter, A resistance-capacitance networkmodel for the analysis of the interactions between the energy performance ofbuildings and the urban climate, Build. Environ. 54 (2012) 116–125.