emergency lighting devices for led applications€¦ · lighting devices for led applications ......
TRANSCRIPT
ELECTRONIC EMERGENCYLIGHTING DEVICESFOR LED APPLICATIONSFor nominal operating periods of 1 hour or 3 hours
Emergency lighting systems spring to life any time normal main lightingsystems fail. Emergency lighting is designed to ensure that staff cansafely leave any rooms and that there is sufficient lighting to illuminaterescue paths/routes as well as to avoid panic situations.
VS emergency lighting devices are designed for use with LED applica-tions and can be operated as part of a combined system with electronicLED drivers.
VS emergency lighting devices test the presence of and the charge lefton batteries during regular cycles and display the existing status via abi-colour LED (self-testing function). This both simplifies battery maintenan-ce and ensures necessary emergency lighting in the event of a mainspower cut. During normal operation, the batteries are recharged withmains power.
Vossloh-Schwabe Deutschland GmbH · Hohe Steinert 8 · 58509 Lüdenscheid · Germany · Phone +49 23 51/10 10 · Fax +49 23 51/10 12 17 · www.vossloh-schwabe.com
A Member of the Panasonic Group
Emergency Lighting Devices for LED Applications
EMERGENCYLIGHTING DEVICESFOR LEDAPPLICATIONS
Emergency LightingModules for 3 HoursOperating Time50, 130 or 220 V voltage outputVS emergency lighting modules are suitable forLED luminaires.Ambient temperature: 5 to 50 °C
Electrical characteristicsPower consumption: 4 VAConstant output: > 3 WWeekly automatic self-diagnosisand daily testing of system statusBattery charge is checked during regulartesting cycles.Optical status display via two-colour LED
Connection detailsMains voltage: 220–240 V ± 10%Mains frequency: 50–60 HzLED emergency light devices must be connectedin line with the installation manual.
Technical notes – Rechargeable batteriesChoice of rechargeable battery depends onthe operating device.Charging time of rechargeable batteries: max. 24 hrs.Rechargeable batteries: nickel-cadmium (NiCd)
Safety featuresProtection class IDegree of protection: IP20SELV (186498)
Type Ref. No. Ref. No. Battery type Nominal operat- Mains current Current Voltage Weight (g)
EL Module Battery ing period (hrs.) at 230 V (mA) output (mA) output (V) EL Module Battery
M5.1 – Dimensions EL module: 210x31.4x21.5 mm
EMCc 180.003 186498 188824 4.8V/4.5Ah 3 22 250–60 12–50 145 490
EMCc 180.004 186499 188824 4.8V/4.5Ah 3 22 150–23 20–130 145 490
EMCc 180.005 186500 188824 4.8V/4.5Ah 3 22 100–13 30–220 145 490
Holders for rechargeable batteriesfor emergency LED lighting modulesIt is recommended to use two holders per rechargeablebattery to ensure optimum hold.Material: PBTFor rechargeable battery type: 4.8V/4.5Ah NiCdRef. No.: 188828
2
The values contained in this data sheet can change due to technical innovations. Any such changes will be made without separate notification.
Vossloh-Schwabe Deutschland GmbH · Hohe Steinert 8 · 58509 Lüdenscheid · Germany · Phone +49 23 51/10 10 · Fax +49 23 51/10 12 17 · www.vossloh-schwabe.com
A Member of the Panasonic Group
Emergency Lighting Devices for LED ApplicationsLE
DEm
erge
ncy
Light
ing
Mod
ules
_GB
–2/
3–
Febr
uary
,201
6
21
,5
210
205,5
31
,4
4,5
M5.1
black
black
450
5.5
redred
green
green
LED
39
6
23.2
36
.21
2.4
Ø37.3
red wire 0.5 mm /AWG20total length = 250 mm
2 JST-EHconnector
red incircuit 2
black incircuit 1
35
35
black wire 0.5 mm /AWG20total length = 250 mm, NiCd
2
240 250
Rechargeable batteries
Emergency LightingModules for 1 HourOperating Time50, 130 or 220 V voltage outputVS emergency lighting modules are suitable forLED luminaires.Ambient temperature: 5 to 50 °C
Electrical characteristicsPower consumption: 3.5 VAConstant output: > 3 WWeekly automatic self-diagnosisand daily testing of system statusBattery charge is checked during regulartesting cycles.Optical status display via two-colour LED
Connection detailsMains voltage: 220–240 V ± 10 %Mains frequency: 50–60 HzLED emergency light devices must be connectedin line with the installation manual.
Technical notes – Rechargeable batteriesChoice of rechargeable battery depends onthe operating device.Charging time of rechargeable batteries: max. 24 hrs.Rechargeable batteries: nickel-cadmium (NiCd)
Safety featuresProtection class IDegree of protection: IP20SELV (186495)
Type Ref. No. Ref. No. Battery type Nominal operat- Mains current Current Voltage Weight (g)
EL Module Battery ing period (hrs.) at 230 V (mA) output (mA) output (V) EL Module Battery
M5.1 – Dimensions (LxWxH): 210x31.4x21.5 mm
EMCc 60.000 186495 188823 4.8V/1.8Ah 1 16 250–60 12–50 145 200
EMCc 60.001 186496 188823 4.8V/1.8Ah 1 16 150–23 20–130 145 200
EMCc 60.002 186497 188823 4.8V/1.8Ah 1 16 100–13 30–220 145 200
Holders for rechargeable batteriesfor emergency LED lighting modulesIt is recommended to use two holders per rechargeablebattery to ensure optimum hold.Material: PCFor rechargeable battery type: 4.8V/1.8Ah NiCdRef. No.: 188827
3
The values contained in this data sheet can change due to technical innovations. Any such changes will be made without separate notification.
Vossloh-Schwabe Deutschland GmbH · Hohe Steinert 8 · 58509 Lüdenscheid · Germany · Phone +49 23 51/10 10 · Fax +49 23 51/10 12 17 · www.vossloh-schwabe.com
A Member of the Panasonic Group
Emergency Lighting Devices for LED ApplicationsLE
DEm
erge
ncy
Light
ing
Mod
ules
_GB
–3/
3–
Febr
uary
,201
6
21
,5
210
205,5
31
,4
4,5
M5.1
black
black
450
5.5
redred
green
green
LED
35
5.5
18
26
.31
3
Ø26.7
red wire 0.5 mm /AWG20total length = 250 mm
2JST-EHconnector
red incircuit 2
black incircuit 1
24
24
black wire 0.5 mm /AWG20total length = 250 mm, NiCd
2
170 250