![Page 1: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/1.jpg)
1
EMERGENCYGENERATORS
Bill Lauzon, PEHeather Werner, BS
Lauzon Life Safety Consulting, LLC262-945-4567
Website: Lauzon-LSC.com
JAN ‘15 - LUNCH & LEARN
![Page 2: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/2.jpg)
Lauzon Life Safety Consulting, LLC262-945-4567
Heather Lauzon Werner• Experienced Life Safety Inspector• Current Director of Environment of Care
Lakeview Specialty Hospital & CBRF• Experienced with CMS, Joint Commission & CARF Surveys
JAN ‘15 - LUNCH & LEARN
YOUR PRESENTERS:
![Page 3: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/3.jpg)
3
Bill Lauzon, PE
1973-2006“Facility Engineer”
Tomah – Fargo- Madison Kenosha - Racine
2006-2011DHS-DQA
2011-presentLauzon Life Safety
Consulting, LLCStatewide Consultant
YOUR PRESENTERS:
![Page 4: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/4.jpg)
4
EMERGENCY GENERATORS
![Page 5: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/5.jpg)
5
EMERGENCY GENERATORS
![Page 6: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/6.jpg)
6
1. PRIMARY
2. BACK-UP
CO-GENERATION
EMERGENCY GENERATORS
![Page 7: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/7.jpg)
7
JAN ‘15 - LUNCH & LEARN
![Page 8: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/8.jpg)
8
JAN ‘15 - LUNCH & LEARN
Jan
Generators
Feb
Life Safety Plans
Mar
Waste Streams
Apr
TBD
May
TBD
Jun
TBD
Jul
Marge’s Hot Topic
Aug
TBD
Sep
TBD
Oct
TBD
Nov
TBD
Dec
TBD
TENTATIVE 2015 LUNCH & LEARN CALENDAR
![Page 9: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/9.jpg)
9
JAN ‘15 - LUNCH & LEARN
Jan
Generators
Feb
Life Safety Plans
Mar
Waste Streams
Apr
TBD
May
TBD
Jun
TBD
Jul
Marge’s Hot Topic
Aug
TBD
Sep
TBD
Oct
TBD
Nov
TBD
Dec
TBD
TENTATIVE 2015 LUNCH & LEARN CALENDAR
Topics Under Development:
• NFPA 99 Risk Assessment• Record Keeping• Fire Drills• LSC 2012 Update• Fire Dampers• Energy Conservation
• OSHA’s Health Care Issues• Humidification• Electrical Testing• Infection Control• Interim Life Safety Measures• Others
![Page 10: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/10.jpg)
10
EMERGENCY GENERATORS
Agenda1. REGULATIONS (NFPA 101, 99, 110; TJC, NEC)
2. COMPLIANCE CONFUSIONS
3. INSTALLATION requirements
4. INSPECTIONS requirements
![Page 11: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/11.jpg)
11
EMERGENCY GENERATORS
I wonder if there will many questions
this month?
![Page 12: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/12.jpg)
12
Agenda
1. REGULATIONS (NFPA 101, 99, 110; TJC, NEC)
2. COMPLIANCE CONFUSIONS
3. INSTALLATION requirements
4. INSPECTIONS
EMERGENCY GENERATORS
![Page 13: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/13.jpg)
13
3 Big AHJs follow the same Code
(but different editions)
GENERATOR REGULATORS
![Page 14: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/14.jpg)
14
3 Big
AHJs
GENERATOR REGULATORS
![Page 15: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/15.jpg)
15
GENERATOR REGULATIONS
![Page 16: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/16.jpg)
16
GENERATOR REGULATIONS
10199 110
![Page 17: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/17.jpg)
17
1. LSC 18.2.9.2 – Emergency Lighting2. LSC 7.9.2.3 – Emergency Lighting3. LSC 18.2.10.2 – Exit Signs4. LSC 18.5.1.2 – Alarm, Comm, Gen Lite5. LSC 18.5.1.3 – Life Support6. 99 3-4.1.1 – Gen Set - Level 1 EES7. 99 3-4.4.1.1 – Gen Maintenance8. 99 3-5.1 – Gen Set – Level 2 EES9. 99 3-6.1 – Gen Set – Level 3 EES10. 110 Emergency Standby Systems
At least 10 Locations
GENERATOR REGULATIONS
New
Existing
![Page 18: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/18.jpg)
18
18.2.9.2: “Buildings equipped with or in which patients require the use of life-support systems shall have EMERGENCY LIGHTING equipment supplied by the life safety branch of the electrical system as described in NFPA 99”
This wording in NOT in Chapter 19
GENERATOR REGULATIONS
![Page 19: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/19.jpg)
19
7.9.2.3: “Emergency generators providing power to EMERGENCY LIGHTING systems shall be installed , tested, and maintained in accordance with NFPA 110”
(ALSO applies to Existing Health Care)
GENERATOR REGULATIONS
![Page 20: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/20.jpg)
20
18.2.10.2: “Buildings equipped with or in which patients require the use of life-support systems shall have ILLUMINATION OF THE REQUIRED EXIT AND DIRECTIONAL SIGNS supplied by the life safety branch of the electrical system as described in NFPA 99” This wording in NOT in Chapter 19
GENERATOR REGULATIONS
![Page 21: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/21.jpg)
21
18.5.1.2: “Power for ALARMS, emergency communication systems, and illumination of generator set locations shall be in accordance with the essential electrical system requirements of NFPA 99”
This wording in NOT in Chapter 19
GENERATOR REGULATIONS
![Page 22: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/22.jpg)
22
18.5.1.3: “Any health care occupancy…that normally uses LIFE-SUPPORT DEVICES shall have electrical systems designed and installed in accordance with NFPA 99”(Exception: “Not apply to a facility that uses life-support equipment for emergency purposes only)
This wording in NOT in Chapter 19
GENERATOR REGULATIONS
![Page 23: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/23.jpg)
23
3-4.1.1: GENERATOR SET• One or more alternative sources
for use when the normal source is interrupted”
• On-Site• Under the Control• Comply with NFPA 110• Exclusive Use• 10 Sec Transfer• Safety Devices & Annunciators• ATS Features
Does NOT apply to Existing HC
GENERATOR REGULATIONS
![Page 24: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/24.jpg)
24
3-4.4.1.1: GENERATOR MAINT.• Maintenance shall be
performed in accordance with NFPA 110
Does NOT apply to Existing HC
GENERATOR REGULATIONS
![Page 25: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/25.jpg)
25
3-5.1: TYPE 2 EES (Nursing H)“The requirements for sources for Type 2 essential electrical systems shall confirm to those listed in 3-4.1”
Does NOT apply to Existing HC
GENERATOR REGULATIONS
![Page 26: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/26.jpg)
26
3-6.1: TYPE 3 EES (Ambulatory)“Generators shall confirm to 3-4.1.1”
Does NOT apply to Existing HC
GENERATOR REGULATIONS
![Page 27: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/27.jpg)
27
NFPA 110: Emergency & Standby Power Systems
• 3 - Generator Requirements• 4 – Switching Requirements• 5 – Install Requirements• 6 – Test Requirements
Apply to Existing HC via LSC 7.9.2.3
GENERATOR REGULATIONS
![Page 28: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/28.jpg)
28
CATEGORICAL WAIVERS
1. Unoccupied Stair Openings 2. Door Locking3. Delayed Egress Locking4. Suite Size & TD5. Sprinkler Testing6. Fire Pump Testing7. OR Humidity8. Fireplaces-Direct Vent
9. Fireplaces-Solid Fuel10. Corridor Kitchens11. Corridor Obstruction12. Combustible Decorations13. Waste Container Size14. Med Gas Alarms15. GENERATOR LOAD BANKING16. Strip Plugs
![Page 29: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/29.jpg)
29
CATEGORICAL WAIVERCHECKLIST
![Page 30: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/30.jpg)
30
CATEGORICAL WAIVERCHECKLIST
2-Hr
1-1/2 Hr Run Time
![Page 31: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/31.jpg)
31
2012 Adoption Impact on GENERATORS
![Page 32: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/32.jpg)
32
1. LSC 18.2.9.2 – Emergency Lighting2. LSC 7.9.2.3 – Emergency Lighting3. LSC 18.2.10.2 – Exit Signs4. LSC 18.5.1.2 – Alarm, Comm, Gen Lite5. LSC 18.5.1.3 – Life Support6. 99 3-4.1.1 – Gen Set - Level 1 EES7. 99 3-4.4.1.1 – Gen Maintenance8. 99 3-5.1 – Gen Set – Level 2 EES9. 99 3-6.1 – Gen Set – Level 3 EES10. 110 Emergency Standby Systems
SameSameSameSameSame
ExpandedExpanded
SameSame
Expanded
In At least 10 Locations
2012 Adoption Impact on GENERATORS
![Page 33: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/33.jpg)
HEALTH CARE CODEChapter 6 – Electrical
Section 6.4.3—Performance Criteria &Testing Covers EES Type 1 performance criteria to assure that the EES is safe and reliable. Includes:
• Maintenance, inspection and testing of the EES alternate power source, including generator testing criteria, test conditions, and testing personnel qualifications
• Specific maintenance, inspection and testing requirements are also required through reference to NFPA 110, Standard for Emergency and Standby Power Systems
• Maintenance & testing of EES circuitry
• Record keeping requirements. 33
![Page 34: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/34.jpg)
34
RECOMMENDATION:
Buy the Handbook
![Page 35: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/35.jpg)
35
If the Past is any Indication:Steps
1. Proposed Rule2. Final Rule Action3. S&C Adopt Ltr4. Effective Date 5. Survey Start
Biggest Question: WHEN will
The 2012 LSC be effective?
Projected2012 LSC Adoption
Apr 2014 (+13 mo) May 2015(+2 mo) Jul 2015(+2 mo) Sep 2015(+6 mo) Mar 2016
2000 LSC AdoptionOct, 2001Nov, 2002Jan, 2003Mar, 2003Sep, 2003
![Page 36: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/36.jpg)
36
3 Big
AHJs
GENERATOR REGULATORS
![Page 37: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/37.jpg)
37
Environment of Care
![Page 38: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/38.jpg)
38
Environment of Care-1Generators
EC.02.05.01 – RISK MANAGEMENT• EP 1 – Installed per Code• EP 2 – Utility Sys Inventory• EP 3 – Maintenance Sys• EP 4 – Frequencies• EP 7 – Drawings• EP 8 – Shut-down Info• EP 9 – Disruption Plans• EP 12 – Repair Service
![Page 39: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/39.jpg)
39
Environment of Care-2Generators
EC.02.05.03 – EMERGENCY SYS• EP 1-9 – Feeds Required Areas
EP.02.05.05 – SYS MAINTENANCE• EP 1-5 – Per Code Requirements
![Page 40: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/40.jpg)
40
Environment of Care-3Generators
EC.02.05.07 – ELECTRICAL MAINT.• EP 4- Monthly Gen Exercise• EP 5 – 30% Load• EP 6 – Monthly ATS Test• EP 7 – 3 Yr, 4 Hr Test (110-2005)• EP 8 – 3 Yr Test @ 30% (110-2005)• EP 9 – Failure Protective Measures• EP 10 – Retest After Repairs
![Page 41: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/41.jpg)
41
Environment of Care-4Generators
EM.02.02.09 – EMERG OP PLAN • EP 2 – Alternate Elect Provision
LS.02.01.20 – MEANS OF EGRESS• EP 32 – All Other Code
Requirements
![Page 42: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/42.jpg)
42
EMERGENCY GENERATORS
Agenda1. REGULATIONS (NFPA 101, 99, 110; TJC, NEC)
2. COMPLIANCE CONFUSIONS3. INSTALLATION requirements
4. INSPECTIONS requirements
![Page 43: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/43.jpg)
43
GENERATORCompliance Confusions
Often Confused Conditions
1 - NEW vs EXISTING• LSC Chapter 18 is Different than Chapter 19• NFPA 99 Applies to New Installation • NFPA 70, Art 715 Applies to New Installation
![Page 44: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/44.jpg)
44
1- NEW vs EXISTING
DQA: Likes to enforce the NEW CONSTRUCTION CODE THAT WAS IN EFFECT
when the facility was built or remodeled
RATHER THANthe existing code (chapter 19)
• TJC does not• CMS does not
![Page 45: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/45.jpg)
45
2 – FUEL SOURCE
• On-Site Storage (Diesel) vs Reliable Service (NG)• 30% Exception for Diesel only
GENERATORCompliance Confusions
![Page 46: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/46.jpg)
46
3 – CODE EDITION
• 2000 LSC vs newer editions• NFPA 110 – 1999 edition vs 2005 edition (TJC)• NFPA 70 (NEC) – 2011, 2008, 2005 by Wis
GENERATORCompliance Confusions
![Page 47: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/47.jpg)
47
4 – LEVEL vs TYPE
GENERATORCompliance Confusions
• NFPA 110 – LEVEL = Stringency of Performance1 – Failure has serious life consequences2 - Failure less critical
• NFPA 99 – TYPE = Kind of Essential Elect Sys1 – Life Support 2 – No Life Support3 - Ambulatory
![Page 48: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/48.jpg)
48
5 – EPS, EES vs EPSS• EPS = Emergency Power Supply
(generator/ancillary equip, NFPA 110)• EES = Essential Electrical Sys
(the Alternate source of power & all distribution equipment, NFPA 99)
• EPSS = Emerg Power Supply System (the Alternate source of power & all distribution equipment-NFPA 110)
Often Confused Conditions
GENERATORCompliance Confusions
![Page 49: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/49.jpg)
49
Often Confused Conditions
GENERATORCompliance Confusions
EES/EPSS
EPS
![Page 50: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/50.jpg)
50
EMERGENCY GENERATORS
Agenda1. REGULATIONS (NFPA 101, 99, 110; TJC, NEC)
2. COMPLIANCE CONFUSIONS
3. INSTALLATION requirements
4. INSPECTIONS requirements
![Page 51: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/51.jpg)
51
GENERATORINSTALLATION
110: Emergency & Standby Power Systems
Chapters:• 3 - Generator Requirements• 4 – Switching Requirements• 5 – Install Requirements• 6 – Test Requirements
Apply to Existing HC via LSC 7.9.2.3
![Page 52: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/52.jpg)
52
3-1 - Level 1 – Energy Source
On Site Fuel Storage required if probability of interruption is high
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSTALLATION
![Page 53: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/53.jpg)
53
NATURAL GAS FUEL SOURCECMS Region 5 Release (5/29/2009)
“If a facility uses a natural gas generator to provide backup power to LSC required systems (i.e., emergency lights, exit lights, fire alarm system, etc.), the facility may obtain a letter from its natural gas vendor to demonstrate the fuel source is reliable and to meet the requirements for an on-site backup power source.
The letter of reliability from the vendor regarding the fuel supply must contain all of the following:1. A statement of reasonable reliability of the natural gas delivery 2. A brief description that supports the statement regarding the
reliability 3. A statement that there is a low probability of interruption of the
natural gas 4. A brief description that supports the statement regarding the
low probability of interruption 5. The signature of technical personnel from the natural gas
vendor “
![Page 54: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/54.jpg)
54
SAMPLE Natural Gas Provider Letter
![Page 55: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/55.jpg)
55
SAMPLE Natural Gas Provider Letter
![Page 56: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/56.jpg)
56
3-5.4.5 – TYPE OF BATTERY“ Starting batteries for Level 1 installations shall NOT be of the maintenance-free variety”
110: EMERGENCY & STANDBY POWER SYSTEMS
* 3-5.4.5 – (Appendix A)“It is recommended that lead-acid starting batteries be replaced every 24 to 30 months.”
GENERATORINSTALLATION
![Page 57: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/57.jpg)
57
3-5.5 – CONTROL FUNCTIONS: Control panel shall have:
• Auto remote start capability• Run-Off-Auto switch• Shutdowns• Alarms• Controls• Remote Stop switch
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSTALLATION
![Page 58: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/58.jpg)
58
3-5.6 – REMOTE CONTROL & ALARMS:• Remote, common audible alarm• Powered by storage battery• 20 specified indicators/functions
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSTALLATION
![Page 59: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/59.jpg)
59
5-2 – EPS LOCATION:• Separate room (level 1), 2-hr enclosure• EPSS not in room with normal power• Minimize flood potential
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSTALLATION
5-3 – EPS LIGHTING• Battery powered emergency lite
![Page 60: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/60.jpg)
60
5-13 – ACCEPTANCE:• Full load test for 2 hrs• Cycle Crank test• Documentation to AHJ
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSTALLATION
![Page 61: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/61.jpg)
61
Agenda1. REGULATIONS (NFPA 101, 99, 110; TJC, NEC)
2. COMPLIANCE CONFUSIONS
3. INSTALLATION requirements
4. INSPECTIONS
EMERGENCY GENERATORS
![Page 62: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/62.jpg)
62
6-1.1: “The routine maintenance and operational testing program shall be based on the MANUFACTURER’S RECOMMENDATIONS, instruction manuals, and the minimum requirements of this chapter and the authority having jurisdiction.”
Usually not a Document Review issue because most use a mfgr rep for
annual maintenance.
110: EMERGENCY & STANDBY POWER SYSTEMS
EMERGENCY GENERATORS
![Page 63: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/63.jpg)
63
6-2 – Manuals, Tools & Parts• Manuals near Level 1 sys• High mortality Parts on-site
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSPECTIONS
![Page 64: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/64.jpg)
64
6-3 – EPSS Maintenance Program• Written schedule• Written record• Transfer switch program• Batteries inspected every 7 days, (including
electrolyte levels)
EPSS = Emerg Power Supply System
(the Alternate source of power & all distribution equipment-NFPA 110)
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSPECTIONS
![Page 65: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/65.jpg)
65
GENERATORINSPECTIONS
![Page 66: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/66.jpg)
66
ALL Inspection documents must show:
1. WHO did the inspection? (have documentation of qualifications; if using Initials, a conversion to names)
2. WHAT was inspected? (If multiple devices, list each one w/location)
3. WHEN was the inspection performed?
4. HOW was the inspection performed? (describe method used & criteria for pass/fail)
5. DEFICIENCIES were corrected? (Document Who, What, When of correction)
Joint Commission:EC.02.03.05, EP25
CMS:Instructions to Surveyors
![Page 67: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/67.jpg)
67
6-4.1 – Weekly Inspection
• Includes all appurtenant components
110: EMERGENCY & STANDBY POWER SYSTEMS
XX
XX
GENERATORINSPECTIONS
![Page 68: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/68.jpg)
68
Zero in on GENERATOR INSPECTIONS
![Page 69: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/69.jpg)
69
Generator Inspection - WEEKLY
XX
XX
XX
X
Compare the FORM
(left)
The Code REQUIREMENTS
(right)Against
![Page 70: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/70.jpg)
70
Generator Inspection - WEEKLYWeekly exercise is not required
![Page 71: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/71.jpg)
71
Generator Inspection - WEEKLY
XXXX
XX
Compare the FORM
(left)
The Code REQUIREMENTS
(right)Against
![Page 72: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/72.jpg)
72
Generator Inspection - WEEKLY
XX
![Page 73: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/73.jpg)
73
Recommended
WEEKLY
FormPDF Available for FREE at:Website: Lauzon-LSC.com
Code Central Members can download the excel version
that is editable
![Page 74: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/74.jpg)
74
6-4.2 – Monthly Exercise• 30 Minute, Under Load• Load measured by:
• 30% of Nameplate rating, or• Min exhaust gas temperature, or• Annual 2 hr load bank (diesel only)
(25%-30m, 25%-30m, 75%-60m)
110: EMERGENCY & STANDBY POWER SYSTEMS
GENERATORINSPECTIONS
![Page 75: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/75.jpg)
75
110: EMERGENCY & STANDBY POWER SYSTEMS
6-4.4 – Time Delays• Min 5 min restore to normal• Min 5 min shut-down
GENERATORINSPECTIONS
![Page 76: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/76.jpg)
76
110: EMERGENCY & STANDBY POWER SYSTEMS
6-4.5 – Auto Transfer Switches• Operate Monthly
GENERATORINSPECTIONS
![Page 77: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/77.jpg)
77
Generator Exercise - MONTHLY
Shows the Who & When but not any of the DETAILS of the Exercising
Compare the FORM
(left)
The Code REQUIREMENTS
(right)Against
![Page 78: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/78.jpg)
78
Generator Exercise - MONTHLY
What does it take to ‘earn’ an
“OK”?
![Page 79: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/79.jpg)
79
Generator Exercise - MONTHLY
Total Run TimeMust be at least 35 Min; .5-Hr is not enough
Need to confirm 30% calc, since nameplate
isn’t shown
Compare the FORM
(left)
The Code REQUIREMENTS
(right)Against
![Page 80: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/80.jpg)
80
Generator Exercise - MONTHLYTotal Run TimeMust be at least 35 Min; .5-Hr is not enough
Need to confirm 30% calc, since nameplate isn’t shown & checks are easy to duplicate
![Page 81: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/81.jpg)
81
Generator Exercise - MONTHLYSatisfactory as a summary sheet, but specific monthly data is required
![Page 82: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/82.jpg)
82
Generator Exercise - MONTHLY
Total Run TimeMust be at least 35 Min; .5-Hr is not enough
Show the # Seconds
Show the # Actual Amps & FLA
30 min under load + cool down (per mfgr)
![Page 83: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/83.jpg)
83
Generator Exercise - MONTHLY
Less Complicated Calc:Target = >.3 x FLAAvg Amps > Target
![Page 84: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/84.jpg)
84
Recommended
MONTHLY
FormPDF Available for FREE at:Website: Lauzon-LSC.com
Code Central Members can download the excel version
that is editable
![Page 85: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/85.jpg)
85
Recommended
MONTHLY
Form
PDF Available for FREE at:Website: Lauzon-LSC.com
Code Central Members can download the excel version that is
editable
![Page 86: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/86.jpg)
86
TOP PORTION
![Page 87: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/87.jpg)
87
CENTER PORTIONCriteria for Pass
![Page 88: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/88.jpg)
88
BOTTOM PORTION
![Page 89: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/89.jpg)
89
Load Bank Test
XX
![Page 90: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/90.jpg)
90
110: EMERGENCY & STANDBY POWER SYSTEMS
6-4.6 – EPSS Circuit Breakers (Level 1 sys)• Operate Annually with EPS Off• Operate Semi-Annual if Med & Hi-voltage• Test every 2 yr if Med & Hi-voltage
GENERATORINSPECTIONS
![Page 91: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/91.jpg)
91
6-4.6 – EPSS Circuit Breakers (Level 1 sys)• Operate Annually with EPS Off• Operate Semi-Annual if Med & Hi-voltage• Test every 2 yr if Med & Hi-voltage
![Page 92: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/92.jpg)
92
WHAT WE COVERED1. REGULATIONS (NFPA 101, 99, 110; TJC, NEC)
2. COMPLIANCE CONSIDERATIONS
3. INSTALLATION requirements
4. INSPECTIONS
EMERGENCY GENERATORS
![Page 93: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/93.jpg)
93
EMERGENCY GENERATORS
![Page 94: EMERGENCY GENERATORS - WHEA · Steps 1. Proposed Rule 2. Final Rule Action 3. S&C Adopt Ltr 4. Effective Date 5. Survey Start Biggest Question: WHENwill The 2012 LSC be effective?](https://reader035.vdocuments.site/reader035/viewer/2022071019/5fd329b4fe267e590051b398/html5/thumbnails/94.jpg)
94
EMERGENCYGENERATORS
Bill Lauzon, PEHeather Werner, BS
Lauzon Life Safety Consulting, LLC262-945-4567
Website: Lauzon-LSC.com
JAN ‘15 - LUNCH & LEARN