electrical systems safety
TRANSCRIPT
NUE 505ANUE 505A
Electrical systems safetyElectrical systems safety
Assessment preparationAssessment preparation
22
Protection devicesProtection devices
10-1
1
10
102
103
4.5
Time (sec)
Current (x IRATED)
BMagnetic Section
Thermal Section
Circuit Breaker Types
10-1
1
10
102
103
Time (sec)
Current (x IRATED)7.5
C
Thermal Section
New Magneticoperation
Circuit Breaker Types
10-1
1
10
102
103
Time (sec)
Current (x IRATED)12
D
Thermal Section
New Magneticoperation
Circuit Breaker Types
RCD,sRCD,s
Residual Current Device RCDSafety Switch
LOAD
NA/s
Supply
When the circuit is in good condition.
(No Earth Faults)
(I active = I neutral) = No Flux = No Induced EMF
Supply to the Load is Maintained
IA
IN
RCD with Earth Fault
LOAD
NA/s
Supply
When an Earth Faults occurs.
(I active I neutral) = Flux in Core = Induced EMF
The fault is Isolated
Safety SwitchNA/s
Supply
Not Earthed
A person can receive a shock with a “Safety Switch” installed
Another point to consider: An RCD rated at 40Amps will not trip (like a C/B) if say 52Amps will to flow through the device.
3 RCD 3 LOAD
NL1
Supply
LOAD
L2 L3
3 RCD 1 LOAD
N
Supply
LOAD
A
Max Demand Max Demand CalculationsCalculations
Domestic LightingDomestic Lighting
Max Demand Max Demand CalculationsCalculations
Domestic PowerDomestic Power
Max Demand Max Demand CalculationsCalculations
Domestic AppliancesDomestic Appliances
Max Demand Max Demand CalculationsCalculations
Domestic Multi-phaseDomestic Multi-phase
Max Demand Max Demand CalculationsCalculationsNon-Domestic LightingNon-Domestic Lighting
A Small motel installation contains the following
Max Demand Max Demand CalculationsCalculations
Non-Domestic PowerNon-Domestic Power
A factory has the following loading, calculate the maximum
demand consideration.
Max Demand Max Demand CalculationsCalculationsNon-Domestic AppliancesNon-Domestic Appliances
A factory has the following three-phase loads,what would be the loading for a maximum
demand calculation.
Cable selectionCable selection
Cable selection Cable selection based on voltage based on voltage
dropdrop
Voltage dropVoltage drop
Single-phaseSingle-phase
Voltage dropVoltage drop
Multi-phaseMulti-phase
Conductor size Conductor size based on voltage based on voltage
dropdrop
Overall multi-phase Overall multi-phase voltage drop voltage drop calculationcalculation
Fault loop Fault loop impedanceimpedance
AS/NZ 3000:2000 - 1.7.4.3.3AS/NZ 3000:2000 - 1.7.4.3.3
The The earth system impedanceearth system impedance, and the , and the Trip Trip characteristic of the protective devicecharacteristic of the protective device must be such must be such that if;that if;
A fault of negligible impedance occurs (active to A fault of negligible impedance occurs (active to earth - short circuit) earth - short circuit)
Automatic disconnect of the supply (high enough fault Automatic disconnect of the supply (high enough fault current to operate the protective device)current to operate the protective device)
Within a specified timeWithin a specified time6.3.3.2.1
6.3.3.2.2AmendmentAS/NZS 3000:2000
The Fault Loop
1. The impedance needs to be low enough, to allow a high enough fault current, to operate the protective device, within a given time period. (6.3.3.2.2)
2. The Earth Loop Impedance is matched to the Protective Device Tripping Characteristics.
3 Phase Supply N/L
Earth SystemEarth System There are three ways to determine whether There are three ways to determine whether
fault loop impedance is OK:fault loop impedance is OK: 1.1. Measure fault loop impedance at the Measure fault loop impedance at the
load.load.
(Compare values against Table B4.1 of (Compare values against Table B4.1 of AS3000)AS3000)
2. Calculate the maximum length allowable 2. Calculate the maximum length allowable for the FSC, and come in for the FSC, and come in under that.under that.
3.3. Measure the A/A-E impedance.Measure the A/A-E impedance.
(Compare it to Table 3.2 AS3017)(Compare it to Table 3.2 AS3017)
Earth SystemEarth System
1 Measure the Fault Loop Impedance…
There are three ways to determine whether fault loop impedance is OK:
Earth SystemEarth System
♦ ZLOOP = ZACTIVE + ZEARTH + Z NEUTRAL + Z TX
♦ All these will limit current and dictate the fault current that will flow.
Load
N/L
16A
MEN Link must be left intact
Earth SystemEarth System
10-1
1
10
102
103
4
Time (sec)
Current (x IRATED)
BMagnetic Section
Thermal Section
Circuit Breaker Types
1x
10-1
1
10
102
103
Time (sec)
Current (x IRATED)
7.5
C
Thermal Section
New Magneticoperation
Circuit Breaker Types
1x
10-1
1
10
102
103
Time (sec)
Current (x IRATED)
12.5
D
Thermal Section
New Magneticoperation
Circuit Breaker Types
1x
Earth SystemEarth System
Load
16A
N/L
MEN Link must be left intact
Earth SystemEarth System
Load
16A
N/L
Active
Earth
MEN Link must be left intact
•Total maximum allowable Fault Loop Impedance = 1.92Ω
• Cold Fault Loop Impedance = 1.92x0.8 = 1.54Ω
• If supply is 240V per phase, then multiply Z by 240/230, or 1.04: Fault Loop Impedance = 1.54 x 1.04
= 1.60Ω
• If RCD protection is used, AS3000, rule 6.3.4.2.1 (2) states that if the RCD operates during the FLI test, the test result is considered satisfactory.
Earth SystemEarth System
1 Measure the Fault Loop Impedance…
There are three ways to determine whether fault loop impedance is OK:
2. Calculate the maximum length allowable for the Final Sub Circuit and come in underthat.
Earth SystemEarth System
Load
16A
N/L
With 80% of voltage drop here in a fault, the FSC must have 80% of the total Fault Loop Impedance.
Where the length and CSA of the mains is not known, we may assume that 80% of the voltage drop under fault conditions will occur in the final sub-circuit (B5.2.1b).
0.8 x VNOM x CSAACTIVE x CSA EARTHLMAX = ITRIP x x (CSAACTIVE + CSA EARTH)
= 22.5 x 10-3 ohm-mm2/metre for Copper = 36 x 10-3 ohm-mm2/metre for Aluminium
• This gives the maximum length allowable for any given circuit.
•Maximum length allowable for any given circuit can be calculated from (B5.2.2):
(Page 237 AS3000)
Earth SystemEarth System
1 Measure the Fault Loop Impedance…
There are three ways to determine whether fault loop impedance is OK:
2. Calculate the maximum length allowable for the Final Sub Circuit and come in underthat.
3. Measure the A/A-E impedance.(Compare it to Table 3.2 AS3017)
AS3017:Testing
andInspectionGuidlines
Notes:1. It is cold resistance.2. It is for FSC only.3. There are still holes…
MAIN SWITCHBOARD
Load
But what if the cable/CB size is not there on that
table?
Say, 300mm2 orange circ. cable supplying a 415V, 350A, 3-phase motor through underground conduit 140mtrs away. C/B is 400A type “C”.
1. CCC of 300mm2 cable = 415A
2. Determine the current required to cause instantaneous operation of the C/B.• 7.5 x 400 = 3000A
3. Determine the (hot) fault loop impedance• 240/3000 = 0.08
4. Total circuit Cold FLZ = 0.08 x .8 = 0.064
5. Final Sub-Circuit FLZ (cold) = 0.064 x 0.8 = 0.0512
Say, 300mm2 orange circ. cable supplying a 415V, 350A, 3-phase motor through underground conduit 140mtrs away…
7. Measure the actual loop impedance.
MAIN SWITCHBOARD
Load
A
V
I 5A
Z = V/I
But what if you are wanting to install the cable, and you want to know if everything is OK?
1. Size of earth: 120mm2 (from AS3000 table 5.1)
2. Find Impedance actual of A-E loop on FSC.
Say, 300mm2 orange circ. cable supplying a 415V, 350A, 3-phase motor through underground conduit 140mtrs away…
Z
R
XL
Note that including XL of the cable only comes into play above 120mm2
But what if you are wanting to install the cable, and you want to know if everything is OK?
1. Size of earth: 120mm2 (from AS3000 table 5.1)
2. Find Impedance actual of A-E loop on FSC.
Say, 300mm2 orange circ. cable supplying a 415V, 350A, 3-phase motor through underground conduit 140mtrs away…
Active: XL = 0.0732/km (Table 30, AS3008)= 0.010248 for 140mtrs
R@750C = 0.0778/km (Table 35, AS3008)R@200C = 0.0778 x 0.8 x 0.14 = 0.0087136 for 140mtrs
•Earth: XL = 0.0743/km = 0.010402 for 140mtrs
R@750C = 0.188/km R@200C = 0.188 x 0.8 /km =0.1504R for 140mtrs = 0.021056
Say, 300mm2 orange circ. cable supplying a 415V, 350A, 3-phase motor through underground conduit 140mtrs away…
• Active XL = 0.010248 R = 0.0087136
• Earth XL = 0.010402 R = 0.021056
Say, 300mm2 orange circ. cable supplying a 415V, 350A, 3-phase motor through underground conduit 140mtrs away…
RA + RE = 0.0298
XA + XE = 0.02065Z = 0.0362
RACTIVEREARTH
XACTIVE
XEARTH
4. Is Loop Z < Maximum Allowable Z?
Z = 0.0362 Z = 0.0512
Last Step…:
• Remember that a type C breaker trips at 7.5 times its rating? This figure is only an approximation. It can be anywhere between 5 and 10 times its rating…
• Remember too, that we took the FSC as having 0.8 of the total circuit impedance? This is an approximation too.
Remember the last question?
Q: Why do we want a low resistance earth wire?To CREATE a high enough fault current to trip the protective device.
To ensure that we do create a high enough fault current, fault loop impedance must be low enough.
AS3017:Testing
andInspectionGuidlines
A Simplified CircuitWe need to look at a complete loop (circuit)
3 Phase Supply
The current path includes the:
Supply Transformer, Distribution System, Mains, Protection Device, Final Sub-Circuit including the Load
N/L
B5.1 Maximum Circuit Length
• This process is used to calculate the maximum circuit length (FSC) taking into consideration:– The rating and type of Protection device– The CSA of the Active conductor– The CSA of the Earthing conductor– The route length of the Final sub-circuit.
• A variation of this process may be used to determine an exact value of the FSC’s impedance, and prove the earth continuity.
3 Phase Supply
There will always be more than 80% of the Nominal Voltage AS/NZ3000:2000 B5.2.1 b
Zext Zint
Zint = 0.8 Uo
Ia
B5.2.1
Isolation, Isolation, disconnection disconnection
and and reconnection reconnection proceduresprocedures
Safe Isolation 1. Assess the need for isolation
2. Notify others
3. Determine how to isolate the circuit
4. Test the supply is present & test meter
5. Isolate the supply. (switch, fuse, C/B etc)
6. Attach danger tags or locks
7. Test that you have isolated the correct circuit
8. Test your meter again
MEN MEN ConnectionConnection
Recent studies have shown that 95% of electricians do not fully understand the MEN system.
This figure comes from the Electrical Contractors Association of Queensland who were conducting training sessions throughout Queensland during 1998.
They asked electricians to draw a MEN system and explain it. Only 5% could!!!
MEN System
MENConnection
ConsumerMains MAIN SWITCHBOARD
Circuit ProtectiveDevices
Earth LinkNeutral Link
Main Switch
MENConnection
Circuit ProtectiveDevices
ConsumerMains MAIN SWITCHBOARD
Neutral Link
Main Switch
So why do we earth the neutral at the board?
Load
Direct Earthing System16A
Q: Will the fuse blow?
0.3
0.2
23
FAULT
RTOTAL= 23.5 IFAULT = V/R= 240/23.5 10A
Load
MEN Earthing System
0.3
0.2
16A
RTOTAL= 1 Q: Will the fuse blow?
0.5
IFAULT = V/R= 240/1= 240A
23
N/L
FAULT
RRETURN = 0.5//23 0.5
Q: Why do we want a low resistance earth wire?
To CREATE a high enough fault current to trip the protective device.
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
Earth LinkNeutral Link
NORMALLOAD CURRENT
Typical Earth stake to Earth
resistance = 30 - 2k
Main Switch
ConsumerMains
Load
Low R
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
Earth LinkNeutral Link
FAULT CURRENTMain Switch
Load
A Low Resistance earth CREATES
A high fault current.
Low R
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
ConsumerMains
Earth LinkNeutral Link
What are the values given by AS3000on earth resistance?
Main Switch
Load
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
ConsumerMains
Earth LinkNeutral Link
2 maximum2 maximum
Main Switch
Load
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
ConsumerMains
Earth LinkNeutral Link
Main Switch
< 0.5(6.3.3.2.2)
“The resistance of the protective earthing conductors shall be
low enough to permit the passage of current
necessary to operate the overcurrent protective device”
(6.3.3.2.2)
Load
133133
Why TestWhy Test
134134
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
Earth LinkNeutral Link
LoadOPEN CIRCUIT
MENConnectio
n
135135
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
Earth LinkNeutral Link
NORMALLOAD
CURRENT
Everything operates OK!!!
Load
136136
THEREFORE FAULT CURRENT WILL BE
VERY LOW
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
Main
Sw
itch
Earth LinkNeutral Link
FAULT CURRENT
ButRESISTANCE TO
EARTH IS USUALLY HIGH.
Load
137137
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
Main
Sw
itch
Earth LinkNeutral Link
FAULT CURRENT
AND PROTECTION WILL NOT TRIP.
Load
138138
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
Main
Sw
itch
Earth LinkNeutral Link
FAULT CURRENT
NOTE THAT IF ACTIVE IS SHORTED TO EARTH,ALL EARTHS ARE LIVE!!!
Load
139139
MAIN SWITCHBOARD
MENConnection
Circuit ProtectiveDevices
Main
Sw
itch
Earth LinkNeutral Link
FAULT CURRENT
NOTE ALSO THAT UNDER NORMAL CONDITIONSEVERYTHING ELSE WILL STILL WORK OK!!!
Load
140140
Open CircuitMEN
Connection
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Neutral Link
Sub Mains
Sub Mains
Neutral Link
DISTRIBUTION BOARD 3
CircuitProtective
Devices
Earthing Bar
DISTRIBUTION BOARD 2
Circuit ProtectiveDevices
Neutral Link
Earthing Bar
Main Earthing
Conductor
Sub Mains
Circuit ProtectiveDevices
Neutral Link
Earthing Bar
DISTRIBUTION BOARD 1
Main Switch
What happens on Distribution Boards when the MSB MEN link open-circuits?
AS30005.6.6b(iv)
141141
What happens when What happens when incoming Active and incoming Active and
Neutral are swapped?Neutral are swapped?
142142
MAIN SWITCHBOARD
MENConnectio
n
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
A N
LIVEN UP: -Earth stake-Water pipes-Taps-Sink-Cases of appliances
Load
143143
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Neutral Link
Sub Mains
Sub Mains
`Neutral Link
DISTRIBUTION BOARD 3
CircuitProtective
Devices
Earthing Bar
DISTRIBUTION BOARD 2
Circuit ProtectiveDevices
Neutral Link
Earthing Bar
Main Earthing
Conductor
Sub Mains
Circuit ProtectiveDevices
Neutral Link
Earthing Bar
DISTRIBUTION BOARD 1
Main Switch
What happens on Distribution Boards when Main Active and Main Neutral
are swapped?
NA
144144
What happens when What happens when the Main Neutralthe Main Neutral
goes Open Circuit?goes Open Circuit?
145145
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral LinkOPEN CIRCUITNeutral
Load
146146
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
LOAD CURRENT
Load
147147
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
LOAD CURRENT
Load
148148
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
Lo load Resistance
Hi stake - earthResistance:30 - 2k
High Voltage
Low Voltage
High Voltage on Earth System
Load
Voltages...
149149
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
Lo load Resistance
Hi stake - earthResistance:30 - 2k
High Voltage
Low Voltage
High Voltage on Earth System
Livens:-Taps,-Sinks-Water pipes-Metal cases of appliances
Load
Voltages...
150150
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
AllLoads
Q: What causes “tingles” on taps?
151151
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
AllLoads
Q: What causes “tingles” on taps?
VDN=4V
152152
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
AllLoads
Q: What causes “tingles” on taps?
4V
0V
TEST EQUIPMENT TEST EQUIPMENT REQUIRED REQUIRED (AS3017 1.6.2)(AS3017 1.6.2)
• High Voltage Insulation Resistance Tester• Low reading ohmmeter (0.5-5) • Voltage Present Indicator• Trailing lead (of known resistance).• Fault Loop Impedance tester• RCD Tester
TEST EQUIPMENT TEST EQUIPMENT REQUIRED REQUIRED (AS3017 1.6.2)(AS3017 1.6.2)
• Test for dead device.– Category 1: electronic– Category 2: Single Phase boards– Category 3: Three Phase DB / MSB– Category 4: Three Phase power lines
TESTSTESTS
• Visual• Earth Continuity• Insulation Test• Polarity• Correct circuit connections• Fault Loop Impedance check• RCD test
1. General
2. Consumer Mains
3. Switchboards
4. Wiring Systems
5. Electrical Equipment
6. Earthing
Step 1: Visual Examination
158
General RequirementsClause No. What to look for
2.9.6 No exposed live parts. E.g. no
excessive removal of insulation at terminations, terminal covers in place etc.Double insulation maintained where required. E.g. no single insulation in ceiling above light fittings, no more than 100mm single insulation in wall
behind accessories, insulating shrouds installed where required.1.9
All equipment is approved/compliant with Australian Standards and in good condition. E.g. no unsafe/damaged or non-compliant equipment installed.
159
Consumer MainsClause No. What to look for
3.4.1 Consumers Mains should be able to carry the maximum demand current of the installation with some capacity to spare. As a guide: 16mm2 (or parallel 6mm2) for overhead mains, 10mm2 for underground mains.
160
SwitchboardClause No. What to look for
Switchboard is in a suitable location. E.g. At appropriate height2.4 Correct over-current protection is installed. E.g. Correct circuit breaker ratings for each sub-circuit conductor and fault level at switchboard.
Main switch/es is/are appropriate for installation. E.g. current raringNeutral bars/links marked for identification. E.g. Main N/L, RCD N/L
Switchboard wiring correctly fixed. E.g. to hinged panel and at back of board to minimise flexing at terminations.Consistency of switchboard layout and marking. E.g. Correct marking of main switch/es, circuit breakers and corresponding neutral link connections.
161
Wiring SystemsClause No. What to look for
Correct conductor sizes. E.g. adequate current carrying capacity for circuit/load, 2.5mm2 minimum for socket outlets etc.Adequate support and fixing of cables where required. E.g. surface wiring.
Wiring fixed or passing through holes within 50mm of underside of floor is protected by RCD or mechanical protection.Wiring fixed or passing through holes within 50mm of ceiling material or ceiling fixing support is protected of by RCD or mechanical protection.
162
Wiring fixed or passing through holes within 50mm of underside of roof material is protected by RCD or mechanical protection.Wiring fixed or passing through holes within 50mm of surface of wall is protected by RCD or mechanical protection if outside nominated ‘zones’.
Wiring in location where it is ‘deemed likely to be disturbed is fixed to prevent undue sagging.Single insulated wiring is enclosed in conduit/trunking or junction box, except for switchboard wiring and in wall cavities for up to 100mm behind accessories at which the wiring is terminated.
Connection and terminations are correctly made. E.g. stranded conductors twisted, single conductors doubled back, no excess insulation removed, damaged insulation reinstated, no undue mechanical stress on any connection.
163
Electrical EquipmentClause No. What to look for
4.3.11 Stove circuit has a ‘functional switch’ installed in appropriate location.Equipment and accessories installed in accordance with safe and sound practice. E.g. accessible for operation, adequately fixed and supported.
Equipment is suitable for the conditions to which it is likely to be exposed. E.g. weatherproof fittings on external walls.
164
EarthingClause No. What to look for
MEN link correctly installed.MEN link is correct size.
2.9.4.4 MEN link terminated at extremity of Main Neutral Link and Main Neutral terminated in next adjacent terminal or both clearly marked.Correct location of Earth Electrode. i.e. outside, exposed to the weather.
Correct termination and protection of Main Earth at electrode.Correct size of Main Earth and Protective Earthing Conductors.
Correct size Equipotential Bonding Conductor.5.5.4.2 Earth conductors protected against ‘becoming displaced, damaged or cut’ as appropriate to ‘expected conditions’.
All earth conductor terminations comply with clause 3.7.Correct use of 1 or 2 screw terminal connections as required.
Initial Procedures
• Open all Main Switches.
• Turn C/B’s off / remove fuse wedges.
• Disconnect the Main Neutral, and Main Earth from the Neutral link.
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth Link
Neutral Link
Light
• From Main Earth to Earth Electrode: <0.5• Make sure all FSC earth resistance values
are under the value of table 3.2 of AS 3017.
• OR• Make sure all FSC are under the maximum
length allowable and have good continuity…
STEP 2: Earth Continuity
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth Link
Neutral Link
Light
Known resistance
STEP 3: Insulation Resistance
• Test between Main Earth and• 1. Main Active with main switch ON.• 2. Main Neutral
• Result: >1M
1. Consumer Mains:
Disconnect any service bonding conductor:
STEP 3: Insulation Resistance
• Test between Main Earth at Switchboard and:
• The Active Conductors of circuits which require testing:>1M
• The Neutral Conductors of circuits which require testing: >1M
2. Final Subcircuits:
With all C/B’s ON or fuse wedges IN, and all switches in the installation ON:
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
Light
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Main
Sw
itch
ConsumerMains
Earth LinkNeutral Link
Light
Switched Active
STEP 3: Insulation Resistance
• Where heater elements are tested: >10k
• Checks:• 1. Polarity of mains or submains.• 2. C/B’s and single pole switches operate
in Active.
• 3. Polarity socket outlets
STEP 4: Polarity Tests
STEP 5: Correct Circuit Connections
• Check that under normal operation earths do not carry current.
• There is no interconnection of conductors between different circuits.
MEN Connection
MAIN SWITCHBOARD
Circuit ProtectiveDevices
Neutral Link
Sub Mains
Sub Mains
`Neutral Link
DISTRIBUTION BOARD 3
CircuitProtective
Devices
Earthing Bar
DISTRIBUTION BOARD 2
Circuit ProtectiveDevices
Neutral Link
Earthing Bar
Sub Mains
Circuit ProtectiveDevices
Neutral Link
Earthing Bar
DISTRIBUTION BOARD 1
Main Switch
AN
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222