electrical service guidelines for commercial and multi
TRANSCRIPT
Electrical Service Guidelines
for Commercial and
Multi-Residential Installations
Revised August, 2020
New Construction ● 458-5870
Fairbanks ● P O Box 71249, Fairbanks AK 99707 ● 452-1151
1-800-770-GVEA (4832) ● www.gvea.com
“Verify Service Entrance Equipment Meets the Following Criteria”
1. Meter Pole Installations:
a. Pole shall be pressure treated and approved.
b. Pole shall be buried to the proper depth.
c. Pole shall be of sufficient height to meet clearance requirements.
d. Meter pole shall be installed plumb.
e. Pole brand (belly button) shall be exposed for inspection.
f. Conduit mast shall be installed plumb.
g. Service equipment shall be mounted on proper brackets.
h. Pole shall be properly guyed or anchored with approved equipment.
i. Ground wire shall be stapled to pole.
j. Meter shall be mounted to face in the direction specified by GVEA.
2. Service shall be de-energized prior to inspection. Energized or back fed services will not be inspected.
3. Service Equipment shall be placed in a location specified by GVEA.
4. Path for service drop shall be 4’-0" wide and material shall be stacked alongside of clearing by the member.
5. The mast on service equipment that is mounted on the eave side of the building:
a. Shall be 2" minimum size RMC or IMC.
b. Shall be extended through the eaves and properly guyed.
c. Height shall not be other than approved.
6. Install GVEA approved service equipment. See GVEA's Engineering Service Department for approved
equipment list.
7. Inspection card issued by GVEA or City permit shall be posted on the job next to the service equipment.
8. Per NEC 230.7, conductors other than service conductors shall not be installed in the same service raceway
as service conductors.
9. Service conductors shall be installed and terminated by member.
10. Split bolt type connectors to splice conductors are not accepted.
11. Conductor insulation shall be XHHW or RHW for conduit installations or USE for direct burial installations is
required.
12. All access to un-metered conductors shall have sealing provisions for stainless wire bail padlock type seal.
13. All overhead service entrance conductors shall be copper.
14. All mounting hardware shall be corrosion resistant.
15. All lugs shall be mounted by means of a machine screw and a factory-provided tapped hole or a bolt with a
lock washer and nut. Sheet metal screws are not an acceptable means of mounting lugs.
16. Maximum of six individual disconnects allowed per service without main disconnect according to NEC 230.71
& 230.72 provided that the service conductors are rated for the maximum total diversified load of the
disconnects.
17. Multi-meter installations shall be properly identified with approved permanent numbers on the service entrance
equipment. If you have more than one meter on your building, see Meter Identification instructions on page 4.
18. For 7-jaw Y-connected services, the neutral in the meter base shall be connected.
19. Grounding and bonding:
a. Conduits and equipment shall be bonded per GVEA bonding details.
b. Undersized grounding/bonding conductors shall not be accepted.
c. Conduit containing grounding electrode conductor shall be bonded at both ends.
d. Per NEC 110.14(A), terminals for more than one conductor shall be marked.
e. Use of split bolt type connectors is not accepted.
f. Ground rod connection shall be exposed for inspection.
20. Grounding electrode system shall be properly installed to meet NEC requirements. Ground rods shall be
driven 6" below grade into undisturbed earth, out from under the eaves of the building and left open for
inspection (See pages 25 and 26 of this booklet). Cover the ground rod hole in winter to prevent it from filling
with snow.
21. Fuses shall be properly sized and installed. If in doubt whether your fuses are correct for your service, call
GVEA's Engineering Services Department.
22. Equipment (main disconnect, branch breakers, etc.) shall be rated for available fault current per NEC 110.9.
PLEASE DOUBLE CHECK THESE PROBLEM AREAS BEFORE CALLING
GVEA FOR YOUR SERVICE ENTRANCE INSPECTION.
TABLE OF CONTENTS
TITLE.........................................................................................................................................................PAGE
INTRODUCTION................................................................................................................................................................ 3
NEW CONSTRUCTION CONNECTION PHONE NUMBER............................................................................................. 3
SUBMITTAL OF LOAD DATA.......................................................................................................................................... 3
DESIGN CRITERIA FOR MEMBER'S DESIGN CONTRACTOR OR ENGINEER........................................................... 3
SPECIAL WAIVERS FOR SERVICES.............................................................................................................................. 3
METERING STANDARDS
LOCATION OF METERS........................................................................................................................................... 4
METER SEALING...................................................................................................................................................... 4
METER IDENTIFICATION......................................................................................................................................... 4
METER EQUIPMENT................................................................................................................................................ 4
METERING - LESS THAN 600 VOLTS..................................................................................................................... 5
METERING - GREATER THAN 600 VOLTS (PRIMARY METERING)......................................................................7
TAMPERING WITH METERS…................................................................................................................................ 7
UNUSUAL CONDITIONS........................................................................................................................................... 7
CABLE LIMITERS............................................................................................................................................................. 7
UNDERGROUND OBSTRUCTIONS................................................................................................................................. 7
UNDERGROUND CABLE MECHANICAL SUPPORT......................................................................................................7
ELECTRIC GENERATORS
OPTIONAL STANDBY SYSTEMS............................................................................................................................. 7
GENERATION, SMALL POWER PRODUCTION, & SNAP....................................................................................... 7
PLACEMENT OF EQUIPMENT NEAR ELECTRICAL POWER LINES AND CONDUCTORS........................................ 7
PLACEMENT OF ELECTRICAL EQUIPMENT NEAR NATURAL & LIQUID PETROLEUM GAS EQUIPMENT............7
ILLUSTRATIONS
TYPICAL PERMANENT OVERHEAD SERVICE, TYPE A (NOT TO EXCEED 300 AMPS)............................................8
TYPICAL PERMANENT OVERHEAD SERVICE, TYPE B (NOT TO EXCEED 300 AMPS).…………............................ 9
TYPICAL PERMANENT UNDERGROUND SERVICE (OVER 200 AMPS).………….………….……...............................10
TYPICAL PERMANENT OVERHEAD SERVICE (OVER 200 AMPS)..............................................................................11
UNDERGROUND SERVICE (NOT TO EXCEED 300 AMPS)...........................................................................................12
UNDERGROUND SERVICE ON PLYWOOD BACKBOARD........................................................................................... 13
TYPICAL POLE MOUNTED SERVICE (NOT TO EXCEED 300 AMPS)..........................................................................14
300 AMP SINGLE-PHASE SELF-CONTAINED METER.................................................................................................. 15
TEMPORARY CONSTRUCTION SERVICE (CT SERVICE OVER 200 AMPS)...............................................................16
POLE MOUNTED RISER DETAILS FOR SECONDARY URD RISER SERVICE............................................................17
STAND-OFF BRACKET DETAILS FOR SECONDARY URD RISER SERVICE..............................................................18
GUYING TO A STRUCTURE.............................................................................................................................................19
GUYING A POLE............................................................................................................................................................... 20
SHUNT TRIP DETAILS......................................................................................................................................................21
TYPICAL MULTIPLE METERED SERVICE ENTRANCE
SIX UNITS OR LESS..................................................................................................................................................22
MORE THAN SIX UNITS............................................................................................................................................23
© 2020 Golden Valley Electric Association, Inc. Page 1
TABLE OF CONTENTS
TITLE..........................................................................................................................................................PAGE
TYPICAL CT METERED SERVICE (1200 AMPS AND BELOW).....................................................................................24
GROUNDING DETAILS
CT METERED SERVICE WITH MAIN DISCONNECT...............................................................................................25
METER LOCATED ON BUILDING BEING SERVED................................................................................................. 26
POLE OR POST MOUNTED METER........................................................................................................................ 27
MULTIPLE METERED SERVICE WITHOUT MAIN DISCONNECT (W/ ALTERNATE)............................................ 28
NOTES FOR MULTIPLE METERED SERVICE DETAILS......................................................................................... 29
METERING
METER SOCKET FOR CURRENT TRANSFORMER AND CONNECTION DIAGRAM............................................ 30
SELF-CONTAINED METER SOCKETS (100 to 300 AMPS)..................................................................................... 31
CONDUIT DETAILS
FOR TRANSFORMER PADS 14'-0" FROM POLE.................................................................................................... 32
FOR TRANSFORMER PADS MORE THAN 14 '-0" FROM POLE.............................................................................33
TRANSFORMER PAD DETAILS
SINGLE-PHASE TRANSFORMER BOX PAD (FOR TRANSFORMERS 15-167kVA).............................................. 34
SECONDARY PEDESTAL DETAILS......................................................................................................................... 35
THREE-PHASE TRANSFORMER VAULT.................................................................................................................36
THREE-PHASE TRANSFORMER VAULT NOTES................................................................................................... 37
PRIMARY METERING....................................................................................................................................................... 38
TRANSFORMER IMPEDANCE VALUES......................................................................................................................... 39
LOAD AND PRINT INFORMATION REQUIRED BY GVEA............................................................................................. 40
LOAD DATA SUBMISSION FORM “ELECTRICAL LOAD DATA AND ELECTRICAL PRINT”..................................... 41
TYPICAL ELECTRIC SERVICE ONE-LINE DRAWING
SELF-CONTAINED.................................................................................................................................................... 42
CT............................................................................................................................................................................... 43
MULTIPLE METER.....................................................................................................................................................44
A link to the PDF version of this document can be found on the GVEA web page at:
http://www.gvea.com/resources/connect/newconstruction under Construction Guides.
© 2020 Golden Valley Electric Association, Inc. Page 2
ELECTRICAL SERVICE REQUIREMENTS FOR COMMERCIAL
AND MULTI-RESIDENTIAL INSTALLATIONS
INTRODUCTION:
This manual is intended to familiarize the member's contractor and/or
engineer with the requirements for commercial and multi-residential
services. The information in this booklet provides general guidelines for
the installation of service equipment to meet the requirements of GVEA.It is the owner's responsibility to make sure that the service is also
installed to meet all applicable city, borough, and State of Alaska codes,
as well as the National Electrical Code (NEC) and National Electrical
Safety Code (NESC). State law requires that an applicable Electrical
Administrator Licensee supervise work related to commercial and
multi-residential electrical service installations. This booklet
references the current adopted edition of the NEC & NESC.
NEW CONSTRUCTION CONNECTION PHONE NUMBER: 458-5870
Members or Contractors should call GVEA's New Construction Services
office to notify GVEA that they are planning to construct a new service
or for information.
SUBMITTAL OF LOAD DATA:
Commercial loads are often expensive to serve and involve complex
electrical requirements. Golden Valley requires detailed electrical load
data and electrical construction plans prepared by an Alaska State
Registered Electrical Engineer. For services 200A and below we may
accept plans prepared by an Alaska State Licensed Electrical
Contractor. Pre-approval is required unless a PE stamp is provided.
Golden Valley's Engineering Services Department shall review the
submitted load data information for the design and construction of
facilities and utility equipment necessary to accommodate this new
load. A member shall apply for service before any submittal review or
engineering services can take place.
In order to be approved for a connection to Golden Valley's system, the
member's actual installation shall correspond to the reviewed
construction plans and the submitted load data. Changes made to the
submitted design or load data after submission but before
connection must be approved by Golden Valley's Engineering
Services Department. An “Electrical Load Data and Electrical
Print” form is on page 40 of this booklet.
Information and details for services requiring Primary Metering
Equipment (PME) shall also be included in the load data.
DESIGN CRITERIA FOR MEMBER'S DESIGN CONTRACTOR OR
ENGINEER:
The Engineering Services Department at GVEA may be consulted
when the member's design contractor or engineer requires additional
information regarding electrical service requirements.1. All three-phase services shall be four-wire. Three-phase
three-wire services are not allowed.
2. When sizing service transformers and service entrance
conductors, the voltage drop from the distribution line (high side
of the transformer) to the point of service should not exceed
3.33% at peak load.
3. Information about the available fault current from GVEA's system
may be obtained by contacting the Engineering Services
Department. Typical distribution transformer impedance values
are shown on page 38 of this booklet for use in determining short
circuit fault currents. GVEA assumes an infinite bus on the high
side of the transformer for calculating available fault currents for
service applications.
4. All service overcurrent devices installed on GVEA's system shall
have a minimum interrupting rating of 10,000 Amps. The member
shall demonstrate that any overcurrent device used is able to
interrupt the available fault current when it exceeds 10,000 Amps
as per NEC 110.9. Series rated breaker systems shall be
identified as such with markings on the equipment in which it is
contained.
5. Current limiting fuses are an acceptable means to reduce the
available fault current.
6. Current Transformers (CT's) and test switches shall be supplied
by GVEA. CT's shall be installed by the member's Electrical
Contractor and the test switches shall be installed by GVEA.
7. Where the member requires a degree of voltage regulation
greater than the characteristics of the electrical service normally
furnished by GVEA, the member shall be responsible for
obtaining, installing and maintaining the required voltage
regulating equipment.
8. The grounded service conductor may be permitted to be reduced
in size, compared to the phase conductors, under certain
conditions allowed by NEC 220.61. Before any reduced size
grounded service conductor is installed, calculations justifying the
size reduction shall be reviewed and approved by GVEA's
Engineering Services Department.
9. The rules and article references stated in NEC article 230.79
"Rating of Service Disconnecting Means" shall be used to size
service entrance equipment breakers. The rating of the main
breaker shall meet current NEC requirements. The service
entrance equipment in which the main breaker is mounted must
be rated for 100 Amps minimum load and 10,000 Amps minimum
short circuit current. It is the member's responsibility to recalculate
the load when any changes are made to the member's
electrical system and apply for an appropriately sized service.
10.GVEA recommends the use of copper conductors, especially for
underground services. If aluminum conductor is used it shall have
an ampacity equal to or greater than that of the copper conductor
called out in this book. Copper pigtails shall be used
when terminating aluminum conductor in service equipment
(NSi PT series or comparable).
11.Service equipment shall be marked with the maximum
available fault current and the date of calculation, according to
NEC 110.24 requirements.
12.Seal conduit interior space around conductors at first access point
when transitioning between warm and cold areas and from below
to above grade.
13.Conduit runs shall have one set of lateral service conductors per
conduit.
SPECIAL WAIVERS FOR SERVICES:
Any exception to the requirements or construction detail drawings in
this booklet shall be approved in writing by GVEA prior to ordering and
installation of equipment. Requests should be submitted to
GVEA's New Construction Services Department. Methods of
electrical equipment installation other than that outlined in this
booklet are allowed only with written approval prior to installation.
© 2020 Golden Valley Electric Association, Inc. Page 3
METERING STANDARDS:
The following are the minimum requirements or standards for member
metering installations. Metering and service entrance equipment shall
be approved by GVEA prior to installation.
LOCATION OF METERS
Prior to wiring a building or performing any electrical construction for a
new service, the member shall request approval from GVEA for the
location of member's service equipment, including meters.
1. Service equipment shall be located as specified by GVEA's New
Construction Services Department. Alternate service locations
shall be approved by GVEA. Where building occupancy requires
more than one meter, the meters shall be grouped at one readily
accessible location. GVEA approval for other arrangements may
be obtained when capacity requirements make multiple services
desirable and are permitted by the NEC.
2. The meter shall be level, plumb and located outdoors on
the member's structure (building, meter pole, or pedestal). The
meter shall be firmly supported and be in locations free from
vibration, mechanical damage, accumulating ice, or falling ice.The meter shall be accessible for reading, testing, and
replacement.
3. The meter may be installed indoors only with prior approval of
GVEA and only when conditions prohibit outdoor placement.Such meters shall be located as specified by GVEA.
4. GVEA does not permit the installation of member's meter socket
on GVEA facilities, such as distribution transformer enclosures,wood poles, or pad-mount transformers. Meters are not allowed
on mobile structures such as trailers, houseboats, barges,
cranes, skid- mounted electrical generators, dredges, draglines,or mobile pumping equipment, etc.
5. For single installations, the horizontal center line of the meter
shall be between 5'-0” and 6'-0” above the finished grade or
floor immediately in front of the meter. For multiple meter
installations, the horizontal center line of the highest
disconnecting means, circuit breaker, switch, etc., shall be a
maximum of 6'-7” above finished grade or finished floor. The
bottom of the service entrance equipment shall not be less
than 3'-0” above finished grade.
6. Minimum unobstructed wall space for a single meter
is 11”w x 1'-2”h. Installation requiring manual bypass shall
require a 1'-3”w x 2'-1”h wall space. NEC 110.26 should
be reviewed for working space requirements around the
meter.
7. The distance between either vertical edges of a meter enclosure
shall not be less than 1-1/2” from a wall or
obstruction. Additional wall space shall be required for current
transformer services. Also, space requirements increase when
more than one meter is used.
8. If an existing meter has become inaccessible for inspection,
reading, or testing; the member shall, at their expense,
extend wiring to a new and approved meter location.
9. GVEA is not obligated to provide service to a location not
approved by GVEA. A member who installs service entrance
equipment without prior GVEA approval may be required, at the
member's expense, to relocate the service equipment to an
approved location.
10.If roof overhang is less than 2'-0", provide suitable protection for
meter from ice and snow. Protection by overhanging roof
is preferred. An acceptable alternative is a protective hood made
of 18 gauge (minimum) galvanized steel, fastened at the roof
edge or wall, and extending out a minimum of 12" off the front of
the meter enclosure. Installation must meet all relevant code
requirements.
METER SEALING
Meters shall be secured with GVEA supplied screw type
meter retaining rings. 300 Amp meter enclosures must be the
ringless type. Other ringless type meter enclosures may be
approved by GVEA. All cabinets and gutters containing
un-metered wires shall be arranged to enable sealing. This
includes current transformer (CT) cabinets or CT compartments in
switch gear. For example, where fused disconnects are ahead
of multiple meter base installations, the member or electrical
contractor shall provide an operable main switch interlocked with
the fuse access compartment ensuring that the fuses remain
accessible to the member. Sealing devices shall be of the type
that accepts GVEA's standard stainless wire, bail padlock-type
seal. CT circuits running between the CT enclosure and the meter
base shall be enclosed in conduit in all unsealed areas; conduit
elbows with access fittings or covers, unions and junction boxes
shall not be permitted in the CT circuit conduit. Conduits used for
CT circuits shall be of the threaded type. Compression
fittings shall not be accepted.
METER IDENTIFICATION
If more than one meter is installed at one location, all sockets and
entrance equipment shall be clearly and permanently marked
using 1” to 2” high letters to designate the particular apartment or
office served. Rivets or screw type fasteners are preferred for
label mounting. If meters are marked incorrectly, the member
shall be responsible for all costs incurred by GVEA in correcting
the meter identification and chargeable electrical usage.
NOTE: Ink labeling shall not be considered permanent.
METER EQUIPMENT
1. Sockets
Acceptable meter sockets shall be manufactured in
accordance with National Electrical Manufacturing Association
(NEMA) ANSI Standard C12.7-2005, labeled by a Certified
Testing Laboratory and equipped with terminals and meter jaws.
* See Pages 30 and 31. ** Shall be approved by GVEA.*** 300A service is single phase only.
TYPE OF
SERVICE
SOCKET
TYPE
NON-CT SERVICE
(100-300 Amps)
CT SERVICE
(ABOVE 200 AMPS)
TERMINALS FIGURE* TERMINALS FIGURE*
120/240V,
1Ø, 3W***
S-BASE 44,6***
6 1
240/480V,
1Ø, 3W**
S-BASE 4 4 6 1
120/208V,
3W**
S-BASE 5 5 --- ---
120/208V,
3Ø, 4W
S-BASE 7 7 13 3
277/480V,
3Ø, 4W
S-BASE 7 7 13 3
120/240V,
3Ø, 4W
S-BASE 7 7 13 2
240/480V,
3Ø, 4W
S-BASE 7 7 13 2
© 2020 Golden Valley Electric Association, Inc. Page 4
The sockets shall have an ampacity rating equal to, or greater than,
any conducting portion of the service entrance equipment including the
entrance panel and the service conductors. This requirement applies to
single-phase, three-phase, and self contained meter bases that are
300 Amps and below. The minimum socket box size for underground
service is 7"w x 1'-2"h for 100 Amp services and 11"w x 1'-2"h for
services above 100 Amps. The minimum socket box size for overhead
service is 7"w x 1'-2"h for 100 Amps and 8"w x 1'-2"h for services
above 100 Amps. Pages 30 and 31 show the type of socket that should
be used for each specific type of service. All CT metering shall require
a test switch in the meter base. GVEA shall supply and install the test
switch.
2. Socket Installation
Meter sockets shall be plumb and securely fastened to the
structure. Unused threaded socket openings, or any other type of
opening not used shall be closed with approved plugs that are
locked in place from the inside of the meter socket. Install sealing
lock nuts or hubs on all conduit penetrations of outdoor cabinets.
All conductors shall be securely fastened to their respective
terminals and shall be arranged in a manner which shall not
interfere with the installation of the meter. Running conductors
behind meter socket is permitted if box is designed for it. Where
the service contains a grounded neutral conductor, the member
shall provide the ground connection between the neutral and the
socket.
3. Service Conductor Identification and Connections
As per NEC 110.15, when a three-phase, four-wire service is
supplied from a delta-connected secondary with the mid point of
one phase grounded to supply lighting and similar loads, the
phase conductor in the service entrance having the higher voltage
to ground (high leg or power leg) shall be identified by the color
orange and shall be located on the RIGHT HAND lug of the meter
base. There are NO EXCEPTIONS! If the neutral conductor is
insulated, it shall be identified as per NEC 200.6.
4. Service Entrance Grounding
Grounding shall comply with GVEA requirements and the NEC.
Refer to the appropriate Grounding Detail on pages 25 through 29.
5. Final Service Connections
GVEA shall make the service connection only after approval of the
inspection authorities. Whenever possible, these authorities
should be given adequate notice regarding the wiring plans to
avoid any unnecessary delay. Energized or back fed services will
not be inspected. The new service must be de-energized prior to
inspection. No meter shall be installed until the member has
submitted a new service application, the member has completed
all requirements for that location, and a Service Entrance Electrical
Inspection card is posted at the service. If the installation is within
the Fairbanks City limits, a city inspection and permit is required.
METERING – LESS THAN 600 VOLTS
1. Socket Installation
A. Service Point
The service point, unless otherwise specified, is the point of
connection between GVEA’s circuit facilities and the member’s
circuit wiring. Typically this would be at the service mast head
on overhead services and at the secondary lugs on padmount
or overhead transformers for underground services.
B. Location of Service Overcurrent Protection
Socket type metering shall be installed on the line side of the
overcurrent protective devices in the service entrance, except
where code requirements indicate otherwise.
C. Switchboard Assemblies
In the case of large loads where the member’s establishment is
open and accessible to GVEA employees during normal
business hours, the metering may, only with prior written
approval by GVEA, be installed on the member’s switchboard.
D. Residential
Meters shall not be placed in any unsafe location, such as
along stairways and above window wells. Carport, porch, or
patio areas shall be avoided due to possible future enclosure
of such area, limiting access to meter reading or testing by
GVEA.
2. Self Contained Metering
A. Ampacity
The member shall provide a self-contained meter socket
installation on each new or remodeled service entrance that
has an ampacity of 200 Amps or less (unless using the optional
single-phase 300A service).
B. Meter Bases
Meter bases shall use the standard S-type socket base.
C. Meter Bypass Provision
Manual bypass provisions are required on 300 Amp meter
bases and are optional on 200 Amp, three-phase, seven jaw
meter bases. Unless specifically approved by GVEA prior to
installation, meter bypass provisions are not allowed on any
other types of meter base installations. Automatic bypasses
shall not be used in any installation.
3. Current Transformer Metering
A. Ampacity
CT’s are required when the service entrance capacity is
greater than 200 Amps (Unless using the optional
single-phase 300A service.). GVEA’s New Construction section
shall be consulted to determine a mutually satisfactory space
and location for the CT’s. For larger service ampacities switch
gear with provisions for built in metering equipment should be
considered.
Where the meter enclosure is located remote from the CT
enclosure, the conduit length between the CT’s and the meter
enclosure shall not exceed 50'-0". No other conductors shall be
in the conduit containing the CT leads.
B. Cabinets – Dimensions and Installations
The dimensions of a CT cabinet, separate from the switchgear
assembly, shall depend on the size and number of
CT’s, service entrance conductors and the location of entrance
and exit conduits into and out of the CT cabinet. The minimum
depth of the cabinet shall be 9” for single-phase and 11” for
three-phase. See page 23 for dimensions.
CT cabinets shall be provided with means to accommodate
GVEA seals (stainless wire bail padlock type). They shall not
contain facilities other than the service conductors and GVEA’s
equipment and shall not be used for the addition of branch
circuits.
© 2020 Golden Valley Electric Association, Inc. Page 5
C. Current Transformers – Installation and Wiring
GVEA shall supply the bar-type CT’s for installation by the
member’s electrical contractor per sizing based on the submitted
load data. CT’s shall be mounted on manufacturer’s CT mounting
bracket, unless the design of the cabinet has brackets already
installed and labeled with short circuit fault current rating. The
number of parallel runs connected to bar-type CT’s should be
limited to 4. GVEA shall wire the secondary terminals before the
CT’s are covered and sealed. Mounting bolts shall have both
ends accessible for future removal. Provisions shall be made so
that the CT and meter sections are readily accessible and can be
sealed by GVEA using stainless wire bail padlock type seals.
The CT cabinet, mounting rack, conduit and conduit fittings
between the CT location and the meter enclosure shall be located
on the member’s structure and shall be furnished and installed by
the member. The conduit shall be not less than 1” in diameter and
shall include a pulling line. The conduit length shall not exceed
50'-0" in length. All meter conductor conduits shall be corrosion
resistant protected intermediate metal conduit (IMC) or rigid metal
conduit (RMC). Hazardous or non-standard installation locations
may require a higher standard of corrosion resistant materials.
The conduit connecting the meter enclosure socket and CT
enclosure shall be installed by the member’s electrical contractor
and run direct without access points such as junction boxes,
unions or elbows with access fittings or covers. Conduits used for
CT circuits shall be of the threaded type. Compression fittings
shall not be accepted. At no time shall branch circuits, or
conduit not related to metering be allowed in the enclosures, nor
shall other compartments in the switch gear be used to carry
metering wire without being in a conduit. Metering wire shall not
be allowed in the service entrance conduit. Separate conduits
shall be used.
D. Current Transformer Bypass Provisions
Bypass provisions for this type of installation shall be
accomplished by a test switch furnished and installed by GVEA.
Standard test switches used by GVEA are:
Single-phase (7 pole) Meter Devices #: 107-1280
Three-phase (10 pole) Meter Devices #: 110-1423
GVEA shall install all secondary wiring between CT’s, test
switches and meters. GVEA shall supply the CT’s, test
switches, and meters.
E. Switchboard Assembly Installations
CT’s may be installed in the member’s switchboard
assembly. CT’s shall be mounted behind a hinged metal
panel. Mounting bolts shall be avoided where both ends of each
bolt are not accessible for future removal. Provision shall be
made so that the CT’s and meter sections are readily accessible
and can be sealed and secured by GVEA. When CT’s are to be
factory installed in the switchboard assembly, the member shall
supply CT’s and submit CT technical data to GVEA for review of
accuracy classification, size, thermal current rating factor, and
burden. GVEA requires an ANSI accuracy rating of 0.3% at a
burden of 0.5 Ohms at 100% rated current. Technical data for
switchgear assemblies with factory installed CT’s shall be
submitted to GVEA’s Engineering Services Department for
approval.
F. Service Disconnect Provisions
Disconnects (breaker or fused) installed for CT metering shall
have padlocking provisions to allow locking of the disconnecting
means in the off position
4. Remote Trip Disconnect
When the main service disconnect is to be installed inside a building,
or within a stand-alone enclosed structure, or otherwise remote from
the meter location, the following guidelines shall be followed to
insure that the service and any emergency power sources may be
disconnected from outside the building. See page 22 for a typical
detail drawing.
A. Push Button Operator
A push button operator shall be provided to serve as the remote
disconnect device. The button shall be suitable for the
environment in which it is installed. For example, if it is located
outside, it shall be weatherproof. If the button is located inside an
enclosure, the enclosure shall be weatherproof. See Shunt Trip
Details, shown on page 22. A service disconnect plaque shall be
provided by the member and shall be fastened in place beneath
the button. The plaque shall be permanently attached to the
structure. If the button is placed inside an enclosure the plaque
shall be mounted on the outside of the enclosure. The plaque
shall be approximately 2” x 5” (H x W), metal or plastic, with
engraved 1/4” lettering which reads:
REMOTE POWER
SERVICE DISCONNECT
B. Location
A push button operator shall be grouped together with the meter
on the outside of the building to be served, mounted at a height
of 5'-0" to 6'-0" feet above final grade. The push button
operator must be in a location that is readily accessible to
fire department personnel.
C. Drawings
Detailed drawings showing the physical locations of the push
button operator and meter shall be submitted to GVEA’s New
Construction Services Department for review.
D. Suggested Material List
The following list of materials is supplied to assist with procuring
equipment for the remote trip station. All of the materials listed
should be available from local suppliers.
1. Push button operator unit – Square D type K, or
similar, push button operator with contact block and
mushroom button.
2. Associated wiring – as required for complete installation.
3. Plaque – available from a variety of local trophy vendors.
4. Enclosure (if necessary) suitable for the environment in
which it is to be mounted.
E. Source of Power for Shunt Trip Circuits
The source of power for a shunt trip circuit shall be the load side
of the main disconnecting means. It shall not be permitted to be
supplied from the load side of any branch circuit breaker nor shall
it be permitted to be supplied from a remote panel or other power
source.
© 2020 Golden Valley Electric Association, Inc. Page 6
METERING – GREATER THAN 600 VOLTS (PRIMARY
METERING)
High voltage instrument transformers shall be required for members
taking service at primary voltage under provisions of GVEA’s
Tariff. Consult GVEA before construction begins to establish a
mutually satisfactory location for the service point, and to clarify
metering installation details. The member shall submit their
preliminary plans for review prior to the purchase of equipment and
the start of construction. Drawings required for review shall include:
1. A plot plan showing desired point of service.
2. Service configuration details (overhead or underground).
3. Service entrance equipment and structures.
4. Arrangement of service substation equipment.
5. One-line diagram.
6. Size and impedance of transformer.
All facilities including the “member's pole” and beyond shall be
furnished, installed, operated, maintained and owned by the
member. Equipment installation shall be in accordance with the
requirements of NEC 230.200 and GVEA.
All facilities prior to the “Member's pole” shall be
furnished, installed, operated, and owned by GVEA. This includes
a 30'-0” span of primary line from the existing primary pole line, a
new pole that contains the primary metering equipment, and the
span of conductor and associated hardware between the “Point of
Service” and the “Member's Pole”.
TAMPERING WITH METERS
Tampering with meters is prohibited by GVEA and is a civil offense
under Alaska Law (AS 42.20.030). In addition to statutory
penalties, a fee shall be charged to anyone who breaks a seal
without authorization or otherwise tampers with GVEA’s facilities. In
flagrant cases, electric utility service shall be
discontinued. Authorization to break a meter seal shall be given by
GVEA’s Operations Department in appropriate cases.
CABLE LIMITERS:
Cable limiters may be used to protect against short circuit currents
in underground service conductors under 600V. If used, cable
limiters shall be of the bolted terminal to bolted terminal type. Tube
or compression rod type cable limiters are not acceptable. The
transformer connections are to be insulated for 600 volts and shall
provide a dead front installation. Where cable limiters are installed
in vaults, adequate space for this equipment and cable terminations
shall be provided.
UNDERGROUND OBSTRUCTIONS:
Location of any customer facilities approved by GVEA does not
take into consideration underground obstructions; it is the owner’s
responsibility to call other utilities for underground locates and to
identify any underground obstructions prior to placing any new
equipment.
UNDERGROUND CABLE MECHANICAL SUPPORT:
Installations using large conductors or using multiple runs of
conductors may produce excessive forces which could cause
damage to the transformer bushing. Installations such as this may
be required to either mechanically support the conductors or to
leave enough conductor slack to prevent damage. Consult GVEA’s
New Construction Services Department prior to installation for a
determination.
ELECTRIC GENERATORS:
OPTIONAL STANDBY SYSTEMS
No member shall, without prior GVEA approval, permanently
connect any electric generator to wiring which is intended to be
energized at any time from GVEA’s system. Proper sectionalizing
and protective equipment shall be installed in conformance with
applicable Federal, State, and Municipal codes and GVEA
requirements.
GVEA offers a publication called “Standby Electric Generators for
Alaskan Residences” which contains advice and installation
illustrations. This publication is available at GVEA’s Member Service
Department and online at:
http://gvea.com/images/pdf/generatorbook.pdf
GVEA recommends that any transfer switch, for the use of
transferring load from utility supply wiring to a member owned
generator, be installed by a licensed electrician in accordance with
the appropriate articles of NEC sections 702 & 705.
COGENERATION, SMALL POWER PRODUCTION, & SNAP
A member may operate an electric generator in parallel with GVEA
provided they have executed a Cogeneration and Small Power
Production Interconnection Agreement with GVEA. Copies of the
Cogeneration and Small Power Production Interconnection
Standards and Procedures, Application for Cogeneration and Small
Power Production Interconnection, and Interconnection Agreement
forms are available upon request from GVEA’s New Construction
Services Department.
PLACEMENT OF EQUIPMENT NEAR ELECTRICAL POWER
LINES AND CONDUCTORS:
GVEA prefers horizontal clearances from overhead conductors to
any equipment or object to be not less than 15'-0".
Alaska State Statute Title 18, Chapter 60, Section 670 (18.60.670)
requires a minimum distance of 10'-0" from power lines or overhead
conductors to equipment or machinery. See this statute for full
details. Wind displacement of conductors should be considered.
Note that this clearance is greater than required by the NESC.
PLACEMENT OF ELECTRICAL EQUIPMENT NEAR NATURAL &
LIQUID PETROLEUM GAS EQUIPMENT:
Electrical equipment (i.e.: service disconnect, electrical meters,
receptacles, etc.) shall be installed not less than 5'-0" from any LPG
tank installation and related regulators, etc. or NG meter and
regulators. If the gas equipment is installed less than 5'-0" to the
electrical equipment, then the electrical equipment shall meet the
requirements of Article 500 and 501 of the NEC. See NEC 230.70(A)
(4) amendment by the City of Fairbanks.
UNUSUAL CONDITIONS
The above standards are a statement of minimum requirements for
most member metering installations. Standards are necessarily
subject to additions and changes as new developments and
progress may dictate. In doubtful or unusual instances, special
consideration will be necessary. GVEA shall be consulted as to any
conditions which may not be set forth herein.
© 2020 Golden Valley Electric Association, Inc. Page 7
Typical Permanent Overhead Service, Type A
(Not To Exceed 300 Amps)
1. In addition to the requirements of NEC 230.9, service drop
conductors shall be a minimum of 3'-0" from any door, opening
window, gable vent, or other building opening. The service drop
conductors may be less than 3'-0" when installed above a gable
vent or non-opening window per the Exception to NEC230.9(A).
2. All service entrance masts that extend above the roof line shall be
a minimum 2" rigid metal conduit (RMC) or intermediate metal
conduit (IMC) and shall be guyed using minimum 1/8" aircraft
cable and approved clamp. See Roof Guy Detail on page 19.
3. If roof overhang is less than 2'-0", provide suitable protection for
meter from ice and snow. Protection by overhanging roof is
preferred. An acceptable alternative is a protective hood made of
18 gauge (minimum) galvanized steel, fastened at the roof edge
or wall, and extending out a minimum of 12" off the front of the
meter enclosure and 6" on each side of the service equipment.
Installation must meet all relevant code requirements.
4. The use of split-bolts is not allowed.
5. Couplings in the conduit shall be below roof line.
6. Telephone drop may not be attached to mast. See NEC 230.28.
7. Members shall provide and maintain a minimum 4'-0" wide
clearing between the service entrance and the GVEA pole.
8. Utility service drop is limited to a maximum 150'-0" span.
Messenger cable is furnished by GVEA.
9. See the Fairbanks City NEC Amendments for additional
requirements for service installations in the Fairbanks City Limits.
10. Conductor insulation shall be type XHHW or RHW.
11. See NEC 230.24 for required clearances over roof. If local city
requirements call for vertical clearance of service drop conductors
to be greater than 3'-0" or a flat roof is classified as accessible,
then the mast assembly and guying will be designed by a qualified
engineer. Mast designs shall be submitted to the GVEA's
Engineering Services Department and the City of Fairbanks
Electrical Inspector for review prior to installation.
12. If the grounding electrode conductor is exposed to physical
damage it shall be run in conduit securely fastened to the
structure. See NEC 250.64(B).
13. Self-contained 300 Amp service is single-phase only. See page
15 for details.
14. Local governing bodies may require specific clearances above
that shown depending on the location of the service drop
conductors. If applicable, specific required service drop clearances
may require longer pole lengths. Contact GVEA's Engineering
Services department for a determination prior to any installation.
NOTES: See pages 3-7 for general requirements
LEAVE 1'-6" TAIL -SEE WIRE
SIZE TABLE & NOTES 9 & 10
UTILITY SERVICE DROP
-SEE NOTES 7, 8, & 14
SEE NOTE 5
SEALING HUB
LEAVE GROUND ROD
CONNECTION UNCOVERED
FOR INSPECTION
GROUNDING ELECTRODE SYSTEM -SEE PAGE 26
BARE COPPER GROUNDING ELECTRODE CONDUCTOR
SECURED TO STRUCTURE -SEE TABLE BELOW
COPPER CLAD STAPLE EVERY 6" -SEE NOTE 12
RAINTIGHT SERVICE ENTRANCE EQUIPMENT
CONDUIT STRAP
ROOF FLASHING AND SEAL
NO JOINTS ALLOWED -SEE NOTE 5
MAST CLAMP FOR SERVICE DROP SUPPLIED BY GVEA
MAST CLAMP FOR ROOF GUYING SUPPLIED BY MEMBER
SEE ROOF GUYING DETAIL PAGE 19
GUY CABLE
CROSBY CLAMP
GALVANIZED THIMBLE EYEBOLT
14'-0" MIN.
3'-0" MIN.
SEE PAGE 19
FOR MAX.
1'-6" MIN.
SEE NOTE 11
6"
5'-0" MIN.
6'-0" MAX.
1'-6"
MIN.
REVISED 03/2020
FINAL GRADE
WIRE/CONDUIT SIZE TABLE
WIRE SHALL BE COPPER
SERVICE
SIZE
MINIMUM
WIRE SIZE
(XHHW OR
RHW)
MINIMUM
CONDUIT
SIZE (RMC
OR IMC)
MINIMUM
GROUNDING
ELECTRODE
CONDUCTOR
SIZE
MINIMUM
EQUIPMENT
GROUNDING
CONDUCTOR
SIZE
100 Amp
200 Amp
300 Amp
300 kcmil
Copper
#3/0
Copper
#2
Copper
1 1/4"
See note 2
2"
2"
#4
Copper
#4
Copper
#2
Copper
#4
Copper
#6
Copper
#8
Copper
FOR A METER BASE LOCATED UNDER RAFTER TAILS, RISER MUST
EXTEND ABOVE ROOFLINE. SEE NOTES 1 & 2.
1'-0"
SEE NOTE 3
© 2020 Golden Valley Electric Association, Inc. Page 8
Typical Permanent Overhead Service, Type B
(Not To Exceed 300 Amps)
1. In addition to the requirements of NEC 230.9, service
drop conductors shall be a minimum of 3'-0" from any
door, opening window, gable vent, or other building
opening. The service drop conductors may be less than
3'-0" when installed above a gable vent or non-opening
window per the Exception to NEC230.9(A).
2. The use of split-bolts is not allowed.
3. Telephone drop shall be more than 1'-0" (vertical
clearance) below power cable at all points. See NESC
235C1, Exception 3.
4. Members shall provide and maintain a minimum 4'-0"
wide clearing between the service entrance and the
GVEA pole.
5. Utility service drop is limited to a maximum 150'-0" span.
Messenger cable is furnished by GVEA.
6. See the Fairbanks City NEC Amendments for additional
requirements for service installations in the Fairbanks
City Limits.
7. Conductor insulation shall be type XHHW or RHW.
8. If the grounding electrode conductor is exposed to
physical damage it shall be run in conduit securely
fastened to the structure. See NEC 250.64(B).
9. Self-contained 300 Amp service is single-phase only.
See page 15 for details.
GALVANIZED OVAL EYEBOLT 5/8" MIN.
-SEE NOTES 4 & 5
3'-0"
MIN.
LEAVE 1'-6" TAIL -SEE WIRE
SIZE TABLE & NOTES 6 & 7
CONDUIT STRAP
SEALING HUB
RAINTIGHT SERVICE ENTRANCE
EQUIPMENT
BARE GROUNDING ELECTRODE
CONDUCTOR SECURED TO
STRUCTURE -SEE TABLE BELOW
COPPER CLAD STAPLE EVERY 6"
-SEE NOTE 8
GROUND ROD SHALL BE
PLACED A MINIMUM OF 1'-6"
FROM STRUCTURE
LEAVE GROUND ROD CONNECTION
UNCOVERED FOR INSPECTION
GROUNDING ELECTRODE SYSTEM
-SEE PAGE 26
5'-0" MIN.
6'-0" MAX.
14'-0" MIN.
2'-0" MAX.
6"
REVISED 03/2020
FINAL GRADE
WIRE/CONDUIT SIZE TABLE
WIRE SHALL BE COPPER
SERVICE
SIZE
MINIMUM
WIRE SIZE
(XHHW OR
RHW)
MINIMUM
CONDUIT
SIZE (RMC
OR IMC)
MINIMUM
GROUNDING
ELECTRODE
CONDUCTOR
SIZE
MINIMUM
EQUIPMENT
GROUNDING
CONDUCTOR
SIZE
100 Amp
200 Amp
300 Amp
300 kcmil
Copper
#3/0
Copper
#2
Copper
1 1/4"
See note 2
2"
2"
#2
Copper
#4
Copper
#4
Copper
#8
Copper
#6
Copper
#4
Copper
NOTES: See pages 3-7 for general requirements
© 2020 Golden Valley Electric Association, Inc. Page 9
Typical Permanent Underground Service
(Over 200 Amps)
GROUNDING ELECTRODE
CONDUCTOR
-SEE NOTES 4 & 5
SEE NOTE 3
GROUND ROD SHALL BE
PLACED A MINIMUM OF 1'-6"
FROM STRUCTURE
SERVICE EQUIPMENT WITH MAIN
DISCONNECT, CT AND METER
ENCLOSURE -SEE PAGE 25
5'-0" MIN.
6'-0" MAX.
1. It is highly recommended that all conductors
or cables under drivable areas be placed in
conduit. 10'-0" minimum distance from meter
to transformer.
2. The use of split-bolts is not allowed.
3. See the Fairbanks City NEC Amendments for
additional requirements for service
installations in the Fairbanks City Limits.
4. If the grounding electrode conductor is
exposed to physical damage it shall be run in
conduit securely fastened to the structure.
See NEC 250.64(B).
5. Grounding electrode conductors sized per
NEC 250.66 with minimum size to be #4 Cu
in accordance with GVEA requirements. For
specific service entrance, see approved
GVEA load data for minimum permissible
grounding electrode conductor size. See note
18 on page 25 for another grounding
electrode bonding jumper connection option.
Grounding conductors shall be continuous as
per NEC 250.64(C) and protection from
physical damage as per NEC 250.64(B).
6. Optional terminal bus can be added to
connect bonding jumpers from multiple
grounding electrodes. Optional terminal bus
will be effectively bonded to enclosure. A
grounding electrode conductor will connect
the optional bus with the neutral bus and it
shall be sized as per NEC 250.66.
7. Approved copper-clad ground rod, 8'-0" x
5/8" dia. min., with approved connector,
driven into undisturbed earth. Leave exposed
for inspection.
8. Service entrance equipment shall be raintight.
Install sealing lock nuts or hubs on all conduit
penetrations of outdoor enclosures.
9. Sealing locknuts or hubs shall be used on all
conduits that penetrate enclosures in an
exterior installation.
10. The member's contractor shall provide a
tented and heated area for pulling and
terminating conductors for underground
installations when the temperature is less
than +20°F. The heating source will be an
indirect fired system. Contact GVEA's New
Construction section for more information.
11. Service equipment shall be marked with the
available fault current and date calculated
according to NEC 110.24.
12. Conduit runs shall have one set of service
lateral conductors per conduit.
5'-0" MIN.
6'-0" MAX.
LEAVE GROUND ROD
CONNECTION
UNCOVERED FOR
INSPECTION
GROUNDING ELECTRODE
SYSTEM -SEE PAGE 26
MAIN
DISCONNECT
ENCLOSURE
CT
ENCLOSURE
METER
ENCLOSURE
GALVANIZED RIGID
METAL CONDUIT
SIZED PER NEC.
CAUTION TAPE
SERVICE CONDUCTOR
WITH INSULATION TYPE
USE -SEE NOTE 1
1'-6"
MIN.
LEAVE 1'-0" SLACK LOOP
6"
2'-0"
6"
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
FINAL GRADE
FINAL GRADE
© 2020 Golden Valley Electric Association, Inc. Page 10
Typical Permanent Overhead Service
(Over 200 Amps)
SEE NOTE 10
GROUND ROD SHALL BE
PLACED A MINIMUM OF
1'-6" FROM STRUCTURE
1. In addition to the requirements of NEC 230.9, service
drop conductors shall be a minimum of 3'-0" from any
door, opening window, gable vent, or other building
opening. The service drop conductors may be less than
3'-0" when installed above a gable vent or non-opening
window per the Exception to NEC230.9(A).
2. The use of split-bolts is not allowed.
3. Telephone drop shall be more than 1'-0" (vertical
clearance) below power cable at all points. See NESC
235C1, Exception 3.
4. Member shall provide and maintain a minimum 4'-0"
wide clearing for service drop conductors between
service entrance and GVEA pole.
5. Utility service drop is limited to a maximum 150'-0"
span. Messenger cable is furnished by GVEA.
6. See the Fairbanks City NEC Amendments for additional
requirements for service installations in the Fairbanks
City Limits.
7. Conductor insulation shall be type XHHW or RHW.
8. If the grounding electrode conductor is exposed to
physical damage it shall be run in conduit securely
fastened to the structure. See NEC 250.64(B).
9. The maximum ampacity of an overhead service shall
be limited to 300 Amps single phase or 275 Amps three
phase. If a service greater than 300 Amps single phase
or 275 Amps three phase is required then it will be
served by an underground connection.
10. Sealing locknuts or hubs shall be used on all conduits
that penetrate enclosures in an exterior installation.
11. Grounding electrode conductors sized per NEC 250.66
with minimum size to be #4 Cu in accordance with
GVEA requirements. For specific service entrance, see
approved GVEA load data for minimum permissible
grounding electrode conductor size. See note 18 on
page 25 for another grounding electrode bonding
jumper connection option. Grounding conductors shall
be continuous as per NEC 250.64(C) and protection
from physical damage as per NEC 250.64(B).
12. Service equipment shall be marked with the available
fault current and date calculated according to NEC
110.24.
5'-0" MIN.
6'-0" MAX.
LEAVE GROUND ROD
CONNECTION
UNCOVERED FOR
INSPECTION
GROUNDING ELECTRODE
SYSTEM -SEE PAGE 26
GALVANIZED OVAL EYEBOLT 5/8" MIN
-SEE NOTES 1, 4, & 5
METER
ENCLOSURE
CT
ENCLOSURE
MAIN
DISCONNECT
ENCLOSURE
COPPER CLAD STAPLE EVERY 6"
CONDUIT STRAP
LEAVE 1'-6" TAIL
-SEE NOTE 6 & 7
SERVICE EQUIPMENT WITH
MAIN DISCONNECT, CT
AND METER ENCLOSURE
-SEE PAGE 25
3'-0"
MIN.
14'-0" MIN.
2'-0" MAX.
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTES 2 & 11
6"
NOTES: See pages 3-7 for general requirements
FINAL GRADE
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 11
Underground Service
(Not to Exceed 300 Amps)
1. It is highly recommended that all conductors or cables
under drivable areas be placed in conduit. 10'-0"
minimum distance from meter to transformer.
2. The use of split-bolts is not allowed.
3. See the Fairbanks City NEC Amendments for additional
requirements for service installations in the Fairbanks
City Limits.
4. If the grounding electrode conductor is exposed to
physical damage it shall be run in conduit securely
fastened to the structure. See NEC 250.64(B).
5. If grounding requirements of NEC 250.50 cannot be
met, and made electrodes are utilized as the sole type
of grounding electrodes, then the resistance
requirements of NEC 250.53(A)(2) shall be met.
Electrodes may be directly bonded together with
grounding electrode conductor, individually routed to
the neutral bus, or connected to an optional terminal
bus as stated in note 18 on page 25. A ground rod is
required by GVEA even if a metal water pipe or
other electrodes listed in NEC 250.50 are used.
6. Approved copper-clad ground rod, 8'-0" x 5/8" diameter
minimum, with approved connector, driven into
undisturbed earth. Leave exposed for inspection.
7. Sealing locknuts or hubs shall be used on all conduits
that penetrate enclosures in an exterior installation.
8. Self-contained 300 Amp service is single-phase only.
See page 15 for details.
9. Location of any customer facilities approved by GVEA
does not take into consideration underground
obstructions; it is the owner’s responsibility to call other
utilities for underground locates and to identify any
underground obstructions prior to placing any new
equipment.
10. The member's contractor shall provide a tented and
heated area for pulling and terminating conductors for
underground installations when the temperature is less
than +20°F. The heating source will be an indirect fired
system. Contact GVEA's New Construction section for
more information.
LEAVE GROUND ROD CONNECTION
UNCOVERED FOR INSPECTION
GROUND RODS
-SEE NOTES 5 & 6
SERVICE
100 Amp
200 Amp
SIZE
Copper
Copper
MINIMUM
GROUNDING
#4
#4
WIRE/CONDUIT SIZE TABLE
WIRE SIZE
MINIMUM
#2
#3/0
Copper
Copper
CONDUIT SIZE
1 1/4"
2"
MINIMUM
(USE, XHHW,
(RMC OR IMC)
ELECTRODE
CONDUCTOR
SIZE
Copper
Copper
EQUIPMENT
#8
#6
GROUNDING
CONDUCTOR
SIZE
300 Amp
Copper
#2300 kcmil
Copper
2"
Copper
#4
OR RHW)*
* Conductor insulation shall be type XHHW or RHW for
installations in conduit, or type USE for direct burial installations.
MINIMUM
FINAL GRADE
MINIMUM 8"x8" MEMBER-OWNER PRESSURE
TREATED TIMBER RATED FOR DIRECT GROUND
CONTACT OR POLE (TIMBER NOT SHOWN)
5'-0" MIN.
6'-0" MAX.
SERVICE CONDUCTOR WITH INSULATION TYPE
USE TO PAD OR POLE MOUNT TRANSFORMER
OR SECONDARY PEDESTAL -SEE NOTE 1
LEAVE 1'-0" SLACK LOOP TYP.
CAUTION TAPE 6" FROM FINISH GRADE. RUN
THE FULL LENGTH OF THE CONDUCTOR RUN.
2'-0"
GALVANIZED RIGID METAL CONDUIT
STAND-OFF BRACKET IF POLE IS USED.
UNISTRUT MOUNTING IF TIMBER IS
USED. (TIMBER NOT SHOWN)
3'-0" MIN.
1'-6" MIN.
(TYP.)
1'-6"6'-0" MIN.
6"
RAINTIGHT SERVICE ENTRANCE EQUIPMENT
ON POLE HUGGER BRACKETS FOR POLE
MOUNTING AND UNISTRUT MOUNTS FOR
TIMBER MOUNTING.
OPTIONAL CONSTRUCTION OUTLET SHALL BE
RAINTIGHT GFCI
COPPER CLAD STAPLE EVERY 6" -SEE NOTE 4
GROUNDING ELECTRODE CONDUCTOR
GALVANIZED RIGID METAL CONDUIT IF
CONSTRUCTION OUTLET IS OMITTED
MEMBERS FEEDER AND EQUIPMENT GROUNDING
CONDUCTORS IF CONSTRUCTION OUTLET IS OMITTED
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
WIRE SHALL BE COPPER
© 2020 Golden Valley Electric Association, Inc. Page 12
Trench must be inspected by GVEA prior to backfill.
Underground Service on Plywood Backboard
1. It is highly recommended that all conductors or cables
under drivable areas be placed in conduit. 10'-0"
minimum distance from meter to transformer.
2. The use of split-bolts is not allowed.
3. See the Fairbanks City NEC Amendments for additional
requirements for service installations in the Fairbanks
City Limits.
4. If the grounding electrode conductor is exposed to
physical damage it shall be run in conduit securely
fastened to the structure. See NEC 250.64(B).
5. If grounding requirements of NEC 250.50 cannot be met,
and made electrodes are utilized as the sole type of
grounding electrodes, then the resistance requirements
of NEC 250.53(A)(2) shall be met. Electrodes may be
directly bonded together with grounding electrode
conductor, individually routed to the neutral bus, or
connected to an optional terminal bus as stated in note
18 on page 25. A ground rod is required by GVEA
even if a metal water pipe or other electrodes listed
in NEC 250.50 are used.
6. Optional terminal bus can be added to connect bonding
jumpers from multiple grounding electrodes. Optional
terminal bus will be effectively bonded to enclosure. A
grounding electrode conductor will connect the optional
bus with the neutral bus and it shall be sized as per NEC
250.66.
7. Approved copper-clad ground rod, 8'-0" x 5/8" dia.
minimum, with approved connector, driven into
undisturbed earth. Leave exposed for inspection.
8. Service entrance equipment shall be raintight. Install
sealing lock nuts or hubs on all conduit penetrations of
outdoor enclosures.
9. Location of any customer facilities approved by GVEA
does not take into consideration underground
obstructions; it is the owner’s responsibility to call other
utilities for underground locates and to identify any
underground obstructions prior to placing any new
equipment.
10. The member's contractor shall provide a tented and
heated area for pulling and terminating conductors for
underground installations when the temperature is less
than +20°F. The heating source will be an indirect fired
system. Contact GVEA's New Construction section for
more information.
11. Conduit runs shall have one set of service lateral
conductors per conduit.
LEAVE GROUND ROD CONNECTION
UNCOVERED FOR INSPECTION
GROUND RODS
-SEE NOTES 5 & 6
SERVICE
100 Amp
200 Amp
SIZE
Copper
Copper
MINIMUM
GROUNDING
#4
#4
WIRE/CONDUIT SIZE TABLE
#2
#3/0
Copper
Copper
1 1/4"
2"
ELECTRODE
CONDUCTOR
SIZE
Copper
Copper
EQUIPMENT
#8
#6
GROUNDING
CONDUCTOR
SIZE
* Conductor insulation shall be type XHHW or RHW for
installations in conduit, or type USE for direct burial installations.
MINIMUM
FINAL GRADE
MINIMUM 6"x6" MEMBER-OWNER PRESSURE
TREATED TIMBER RATED FOR DIRECT GROUND
CONTACT (TYP OF TWO)
5'-0" MIN.
6'-0" MAX.
SERVICE CONDUCTOR WITH INSULATION TYPE
USE TO PAD OR POLE MOUNT TRANSFORMER
OR SECONDARY PEDESTAL -SEE NOTE 1
LEAVE 1'-0" SLACK LOOP (TYP.)
CAUTION TAPE 6" FROM FINISH GRADE. RUN
THE FULL LENGTH OF THE CONDUCTOR RUN.
2'-0"
3'-0" MIN.
1'-6" MIN.
(TYP.)
1'-6"
MAIN DISCONNECT ENCLOSURE
6"
MEMBERS FEEDER AND EQUIPMENT
GROUNDING CONDUCTORS
SERVICE EQUIPMENT WITH MAIN DISCONNECT
-SEE PAGE 25, CT AND METER ENCLOSURE
SHALL MEET ALL REQUIREMENTS SHOWN
BARE COPPER GROUNDING ELECTRODE
CONDUCTOR -SEE PAGE 25, CT METERED
SERVICE GROUNDING DETAIL
GALVANIZED RIGID METAL CONDUIT,
NUMBER OF RUNS AS REQUIRED
CT ENCLOSURE
METER ENCLOSURE
3/4" PRESSURE TREATED
ALL WEATHER PLYWOOD
6" MAX.
(TYP.)
6'-0" MIN.
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
WIRE SHALL BE COPPER
© 2020 Golden Valley Electric Association, Inc. Page 13
MINIMUM
CONDUIT
SIZE (RMC
OR IMC)
MINIMUM
WIRE SIZE
(USE, XHHW,
OR RHW)*
Trench must be inspected by GVEA prior to backfill.
Typical Pole Mounted Service
(Not to Exceed 300 Amps)
1. If service drop exceeds 50'-0", pole shall be guyed. Service
drop shall not exceed 150'-0". See guying details on page 20.
2. Telephone drop shall be more than 1'-0" (vertical clearance)
below power cable at all points. See NESC 235C1, Exception
3.
3. Use of split bolts is not allowed.
4. Members shall provide and maintain a minimum 4'-0" wide
clearing between the service entrance and the GVEA pole.
5. A bare copper conductor shall be connected to the neutral,
service enclosure at disconnect, and to the well or ground rod.
See table below for size.
6. Approved copper-clad ground rod, 8'-0" x 5/8" dia. minimum,
with approved connector, driven into undisturbed earth. Leave
exposed for inspection.
7. Per NEC 250.53(A) two ground rods must be installed if they
are utilized as the sole type of grounding electrodes. One
ground rod may be installed if the resistance requirements of
NEC 250.53(A)(2) are met. Electrodes shall be directly
bonded together with grounding electrode conductor. See
page 27 for service grounding detail.
8. Temporary construction service is not to be used for
energizing permanent wiring systems. Construction service is
approved for construction power only. Service will be
disconnected 12 months after connect or if permanent wiring is
energized.
9. Conductor insulation shall be type XHHW or RHW.
10. Meter poles shall be fully pressure treated. Cedar poles are
not accepted. Minimum pole length shall be 25'-0", buried at a
depth of 5'-0". Poles 30'-0" and longer must be buried 10% of
pole length plus 2'-0". The fill around the pole must be tamped
firm so that the pole will not lean when it is climbed. Pole brand
(belly button) must be visible after equipment is mounted.
11. For services above 200 amps see page 16 for CT service or
page 15 for 300A self-contained service or contact GVEA's
Engineering Department for information on temporary
construction.
12. Meter poles are to be placed a minimum of 20'-0" from primary
lines.
13. If the grounding electrode conductor is exposed to physical
damage it shall be run in conduit securely fastened to the pole.
See NEC 250.64(B).
14. Service entrance equipment shall be raintight. Install sealing
lock nuts or hubs on all conduit penetrations of outdoor
enclosures.
15. Self-contained 300 Amp service is single-phase only. See
page 15 for details.
16. The maximum ampacity of an overhead service shall be limited
to 300 Amps single phase or 275 Amps three phase. If a
service greater than 300 Amps single phase or 275 Amps
three phase is required then it will be served by an
underground connection.
17. Local governing bodies may require specific clearances above
that shown depending on the location of the service drop
conductors. If applicable, specific required service drop
clearances may require longer pole lengths. Contact GVEA's
Engineering Services department for a determination prior to
any installation.
LEAVE GROUND
ROD CONNECTION
UNCOVERED FOR
INSPECTION
GROUND RODS
-SEE NOTES 6 & 7
SERVICE
100 Amp
200 Amp
SIZE
Copper
Copper
MINIMUM
GROUNDING
#4
#4
WIRE/CONDUIT SIZE TABLE
WIRE SIZE
MINIMUM
#2
#3/0
Copper
Copper
CONDUIT SIZE
1 1/4"
2"
MINIMUM
(USE, XHHW,
(RMC OR IMC)
ELECTRODE
CONDUCTOR
SIZE
Copper
Copper
EQUIPMENT
#8
#6
GROUNDING
CONDUCTOR
SIZE
300 Amp
Copper
#2300 kcmil
Copper
2"
Copper
#4
OR RHW)*
MINIMUM
5'-0" MIN.
6'-0" MAX.
5'-0"
MIN.
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTE 5
WIRE SHALL BE COPPER
5'-0"
MAX.
POLE BRAND MUST
BE EXPOSED FOR
INSPECTION
MEMBER-OWNED
PRESSURE
TREATED POLE
ANGLE THIMBLE EYEBOLT
AND GALVANIZED SQUARE
WASHER
1'-6"
MIN.
6'-0" MIN.
6"
25'-0"
MIN.
COPPER CLAD STAPLES EVERY 6"
-SEE NOTE 3
OPTIONAL CONSTRUCTION
OUTLET SHALL BE
RAINTIGHT GFCI
SERVICE ASSEMBLY 100
AMP MIN.
STAND-OFF BRACKETS
MAINTAIN 6" CLEARANCE
BETWEEN CONDUIT AND
POLE
CONDUIT AND POLE MUST
BE INSTALLED PLUMB TO
GROUND
LEAVE 1'-6" TAIL -SEE WIRE
SIZE TABLE & NOTE 9
2'-0"
MAX.
UTILITY SERVICE
DROP -SEE NOTES
1, 4, 12, & 17
6" MIN
1'-0" MAX.
GALVANIZED OVAL EYENUT
AND GALVANIZED SQUARE
WASHER
6"
MIN.
NOTES: See pages 3-7 for general requirementsREVISED 08/2020
© 2020 Golden Valley Electric Association, Inc. Page 14
FINAL GRADE
GUY CABLE 1/4" MIN.
GALVANIZED STEEL
OR ALUMINUM CLAD
CABLE -SEE NOTE 1
PERFORMED GRIP
OR 3 BOLT CLAMP
1
L
2
L
N
2
L
L
1
N
1
L
2
L
N
E
G
C
UNDERGROUND OR OVERHEAD SERVICE
WATER PIPE, SEE NOTES 2 & 5
GROUND ROD
GROUND RING
BUILDING STEEL
CONCRETE ENCASED ELECTRODE
300 Amp Single-Phase Self-Contained Meter
REVISED 03/19
1. Service entrance location shall be approved by GVEA
and shall be located as close as possible to existing
GVEA facilities.
2. Conduit for service cable shall be sized per NEC but
shall not be less than 2".
3. Member's service equipment shall conform to the NEC
and State and Municipal Codes and shall be inspected
and approved prior to connection of service by GVEA.
4. Standard 300 Amp service rated breaker is an
acceptable main disconnect.
5. Meter socket shall conform to requirements on pages 4
and 5 for 100-200 Amp services with these exceptions:
-Socket rated for 300 Amps or greater
-Bypass lever required
-Upper right hand jaw shall be reduced or have
anti-inversion clip installed to prevent insertion of
200A meter.
-Meter enclosure to be the ringless type to
accommodate the required meter bypass lever.
6. The maximum ampacity of service shall be limited to
300 Amps, based on NEC calculated load. If a service
greater than 300 Amps is required, this optional service
will not be allowed.
7. No deviation from this standard shall be allowed unless
approved in writing by GVEA's Engineering Services
Department prior to installation.
8. Sealing lock nuts or hubs shall be installed on conduit
penetrations of outdoor enclosures.
SERVICE
SIZE
MINIMUM
GROUNDING
WIRE/CONDUIT SIZE TABLE
ELECTRODE
CONDUCTOR
SIZE
EQUIPMENT
GROUNDING
CONDUCTOR
SIZE
300 Amp
Copper
#2
300 kcmil Copper
See note 4 & 6
2"
Copper
#4
MINIMUM
8'-0" x 5/8" DIA. MIN. COPPER CLAD
GROUND ROD TYP.
WIRE SHALL BE COPPER
GROUNDING ELECTRODE SYSTEM,
SEE NOTES 1 & 3 ON PAGE 26
SEE NOTE 8 ON PAGE 25
CONTINUOUS GROUNDING ELECTRODE
CONDUCTOR TO GROUND ROD,
SEE NOTE 6 ON PAGE 26
IRREVERSIBLE COMPRESSION CONNECTOR
GROUNDING ELECTRODE
CONDUCTOR MIN. #2 AWG
COPPER, SEE NOTES 8 & 9
ON PAGE 25
4-WIRE FEEDER TO
DISTRIBUTION PANEL
GROUNDING BLOCK SHALL
BE PERMANENTLY BONDED
TO ENCLOSURE
COMBINATION RAINTIGHT
METER AND SERVICE
ENCLOSE, SEE NOTE 6 & 7
SERVICE ASSEMBLY
METER BYPASS LEVER,
SEE NOTE 5
FROM GVEA POWER SYSTEM
MAIN BREAKER OR DISCONNECT
AND FUSES, SEE NOTE 4
NOTES: See pages 3-7 for general requirements
FROM GVEA POWER SYSTEM
© 2020 Golden Valley Electric Association, Inc. Page 15
MINIMUM
CONDUIT
SIZE (RMC
OR IMC)
MINIMUM
WIRE SIZE
(XHHW OR
RHW)
Temporary Construction Service
(CT Service Over 200 Amps)
1. If service drop exceeds 50'-0", pole shall be
guyed. Service drop shall not exceed 150'-0".
See guying details on page 20.
2. Telephone drop shall be more than 1'-0" (vertical
clearance) below power cable at all points. See
NESC 235C1, Exception 3.
3. Use of split bolts is not allowed.
4. Members shall provide and maintain a minimum
4'-0" wide clearing between the service entrance
and the GVEA pole.
5. Approved copper-clad ground rod, 8'-0" x 5/8" dia.
min., with approved connector, driven into
undisturbed earth. Leave exposed for inspection.
6. Per NEC 250.53(A) two ground rods must be
installed if they are utilized as the sole type of
grounding electrodes. One ground rod may be
installed if the resistance requirements of NEC
250.53(A)(2) are met. Electrodes shall be directly
bonded together with grounding electrode
conductor. See page 25 for CT metered service
grounding detail.
7. Temporary construction service is not to be used
for energizing permanent wiring systems.
Construction service is approved for construction
power only. Service will be disconnected 12
months after connect or if permanent wiring is
energized.
8. Conductor insulation shall be type XHHW or
RHW.
9. Meter poles shall be fully pressure treated. Cedar
poles are not accepted. Minimum pole length shall
be 25'-0", buried at a depth of 5'-0". Poles 30'-0"
and longer must be buried 10% of pole length plus
2'-0". The fill around the pole must be tamped firm
so that the pole will not lean when it is climbed.
Pole brand (belly button) must be visible after
equipment is mounted.
10. If the grounding electrode conductor is exposed to
physical damage it shall be run in conduit
securely fastened to the pole. See NEC
250.64(B).
11. Meter poles are to be placed a minimum of 20'-0"
from primary lines.
12. The maximum ampacity of an overhead service
shall be limited to 300 Amps single phase or 275
Amps three phase. If a service greater than 300
Amps single phase or 275 Amps three phase is
required then it will be served by an underground
connection.
13. Service entrance equipment shall be rain tight.
Install sealing lock nuts or hubs on all conduit
penetrations of outdoor enclosures.
14. Local governing bodies may require specific
clearances above that shown depending on the
location of the service drop conductors. If
applicable, specific required service drop
clearances may require longer pole lengths.
Contact GVEA's Engineering Services department
for a determination prior to any installation.
MAIN DISCONNECT
ENCLOSURE
ANGLE THIMBLE EYEBOLT
AND GALVANIZED
SQUARE WASHER
FINAL GRADE
RMC
CT ENCLOSURE
COPPER CLAD STAPLES
EVERY 6" -SEE NOTE 10
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTE
9 ON PAGE 25
POLE BRAND MUST BE
EXPOSED FOR INSPECTION
STAND-OFF BRACKETS -SEE
NOTE 1 & DETAILS ON PAGE 18
MEMBER-OWNED
PRESSURE TREATED POLE
LEAVE 1'-6" TAIL, CONDUCTORS
SIZED PER LOAD, SEE NOTE 8
GALVANIZED OVAL EYENUT AND
GALVANIZED SQUARE WASHER
UTILITY SERVICE DROP,
SEE NOTES 1, 4, 11, & 14
6" MIN.
6" MIN.
1'-0" MAX.
2'-0" MAX.
25'-0"
MIN.
LEAVE GROUND
ROD CONNECTION
UNCOVERED FOR
INSPECTION
GROUND RODS
-SEE NOTES 5 & 6
6'-0" MIN.
1'-6"
MIN.
6" 6"
5'-0"
MIN.
5'-0" MIN.
TO
6'-0" MAX.
NOTES: See pages 3-7 for general requirements
FRONT VIEW
SIDE VIEW
© 2020 Golden Valley Electric Association, Inc. Page 16
REVISED 08/2020
METER ENCLOSURE
SERVICE EQUIPMENT
WITH MAIN DISCONNECT,
CT, AND METER
ENCLOSURE ON
UNISTRUT SHALL MEET
ALL REQUIREMENTS
SHOWN ON PAGE 25.
MAINTAIN CLEARANCE OF
6" BETWEEN CONDUIT AND
POLE
PREFORMED GRIP OR 3
BOLT CLAMP
GUY CABLE MIN 1/4"
GALVANIZED STEEL
OR ALUMINUM CLAD
CABLE -SEE NOTE 1
CONDUIT AND POLE MUST
BE INSTALLED PLUMB TO
GROUND
PLAN VIEW
SIDE VIEW
Pole Mounted Riser Details For Secondary URD Riser Service
CONDUIT INSTALLATION
SEE NOTE 2 ON PAGE 18
GROUNDING CLAMPS TO BE
PROVIDED BY MEMBER. BOND
CONDUITS TO POLE GROUND.
RIGID SWEEP. PVC SWEEPS
WILL NOT BE ACCEPTED.
IRREVERSIBLE COMPRESSION
CONNECTOR
8'-0" MIN.
SEE NOTE 3
ON PAGE 18
3'-0" MIN.
18" MIN.
6"
TRANSFORMERS ABOVE
TRANSFORMER BANK
CENTERLINE
12"-18"
PROVIDE SUFFICIENT LENGTH
OF SECONDARY CONDUCTOR
TO REACH TRANSFORMER LUGS
SIDE VIEW
18" MIN.
6"
TRANSFORMER LOCATION
ABOVE MAY VARY
ROTATE 45° FROM TRANSFORMER OR
CENTERLINE OF TRANSFORMER BANK.
PLACE STAND-OFF BRACKET IN EITHER
QUADRANT ON THE SAME SIDE OF POLE
AS THE TRANSFORMER. SEE NOTE 1
AND DETAILS ON PAGE 18.
6" MIN. SEE NOTE 1 ON PAGE 18
3'-0" MIN.
12"-18"
CLIMBING ZONE.
NO EQUIPMENT
PLACED IN THIS
AREA WITHOUT
APPROVAL FROM
GVEA.
CLIMBING ZONE.
NO EQUIPMENT
PLACED IN THIS
AREA WITHOUT
APPROVAL FROM
GVEA.
PLAN VIEW
SINGLE-PHASE SERVICE
THREE-PHASE SERVICE
6" MIN. SEE NOTE 1 ON PAGE 18
8'-0" MIN.
SEE NOTE 3
ON PAGE 18
IRREVERSIBLE COMPRESSION
CONNECTOR
GROUND ROD AND POLE
GROUND CONDUCTOR
PROVIDED BY GVEA
LEAVE TRENCH OPEN
FOR INSPECTION
REVISED 03/2020
GROUND ROD AND POLE
GROUND CONDUCTOR
PROVIDED BY GVEA
© 2020 Golden Valley Electric Association, Inc. Page 17
DETAIL 3
2 ea. 4" CONDUITS ON ONE SIDE OF
THE STAND-OFF BRACKET
1 ea. 4" AND 1 ea. 2" CONDUITS ON ONE
SIDE OF THE STAND-OFF BRACKET
DETAIL 1
2 ea. 4" CONDUITS ON TWO SIDES OF
THE STAND-OFF BRACKET
DETAIL 4
1 ea. 4" AND 1 ea. 2" CONDUITS ON TWO
SIDES OF THE STAND-OFF BRACKET
DETAIL 2
Stand-Off Bracket Details For Secondary URD Riser
REVISED 03/19
1. 6" minimum between pole and conduit is required. Conduit
installations with less than 6" clearance will not be accepted. Only
one set of stand-off brackets will be allowed on a pole.
Contact GVEA's New Construction office for information about
adding new services to a pole with existing risers.
2. All conduit shall be stubbed out of ground 3'-0" for inspection.
Conduits out of plumb will not be accepted.
3. The initial section of conduit shall have two brackets. Subsequent
conduit sections require only one bracket. Standoff brackets on
supporting structures shall be arranged such that there is not less
than 8'-0" between either the lowest bracket, the ground, or other
accessible surface as specified in NESC 217.A.2.C.
4. Minimum sized stand-off bracket shall be 15". Stand-off bracket
details number 1 through 4 shows the maximum number of
conduits and conduit sizes allowed on 15" and 18" stand-off
brackets.
5. If the number of conduits exceed that shown in details 1 through
4, contact GVEA's New Construction Department for a solution.
The maximum size pole mounted three-phase transformer bank is
225 kVA.
6. GVEA has the option to replace pole mounted transformer(s) with
pad-mounted transformer if design constraints require it.
7. Items on this sheet shall be furnished by member's electrical
contractor. GVEA will install materials above the 3'-0" level.
NOTES: See pages 3-7 for general requirements
18" STAND-OFF
BRACKET
18" STAND-OFF
BRACKET
15" STAND-OFF
BRACKET
15" STAND-OFF
BRACKET
6" MIN.
-SEE NOTE 1
4.5" O.D.
1.5"
2.5" O.D.
6" MIN.
-SEE NOTE 1
4.5" O.D.
1.5"
2.5" O.D.
6" MIN.
-SEE NOTE 1
4.5" O.D.
2"
4.5" O.D.
6" MIN.
-SEE NOTE 1
4.5" O.D.
2"
4.5" O.D.
#2AWG - 3/0 AWG
-Contractor to dig trench & install materials, including first 3'-0" of
riser on primary pole for inspection by GVEA. Trench must be
inspected prior to backfill.
-Contractor shall provide sufficient amount of conduit (RMC or
IMC) to reach base of transformer, secondary conductors,
standoff brackets, pipe clamps, ground clamps, lag bolts, rigid
sweeps, and weather head.
-Leave wire coiled at base of pole.
-GVEA linemen will install remainder of riser and wire.
4/0AWG and Larger
-Contractor to dig trench & install materials, including first 3'-0" of
riser on primary pole with jet line pulled in. Trench must be
inspected prior to backfill.
-Contractor shall provide sufficient amount of conduit (RMC or
IMC) to reach base of transformer, secondary conductors,
standoff brackets, pipe clamps, ground clamps, lag bolts, rigid
sweeps, and weather head.
-If run is more than 75'-0" contractor will provide wire on individual
reels and reel stands.
-GVEA will pull wire with Contractor assistance.
-GVEA will provide pulling equipment to include pulling harness,
large diameter traveler and bull rope.
Secondary Riser Build
© 2020 Golden Valley Electric Association, Inc. Page 18
Guying To A Structure
REVISED 03/19
1. All service conduit extending above the roof shall be
minimum 2" rigid conduit and shall be guyed. Roof guy
line shall be minimum 1/8" stainless steel wire (aircraft
cable) with approved crosby clamps. Quantity/Length
determined by installation requirements.
2. No other attachments are permitted on the mast.
3. For mast heights greater then 5'-0" the mast assembly
and guying shall be designed by a qualified engineer.
Mast designs shall be submitted to GVEA's
Engineering Services Department and the City of
Fairbanks Electrical Inspector, if required, for review
prior to installation.
45° OR MORE
VERTICAL STRUCTURE
EYEBOLT MOUNTING DETAIL
INCORRECT INSTALLATION
THE OVAL EYE BOLT MOUNTED
TO ONLY ONE SUPPORT
BOARD SHALL NOT BE
ACCEPTED! THIS IS TYPICAL
FOR ALL INSTALLATIONS
REGARDLESS OF VERTICAL,
HORIZONTAL, OR OTHER
INSTALLED ORIENTATION.
ROOF GUY DETAIL B - 3 GUYS
ONLY WITH PRIOR GVEA APPROVAL
FOR MAST HEIGHT OF 3'-6" TO 5'-0"
HORIZONTAL STRUCTURE
EYEBOLT MOUNTING DETAIL
ROOF GUY DETAIL A - 1 GUY
3'-6" MAXIMUM MAST HEIGHT
NOTES: See pages 3-7 for general requirements
GVEA SERVICE
DROP CONDUCTORS
(TO GVEA POLE AND
TRANSFORMER)
TOP VIEW
ELEVATION TOP VIEW
MAST CLAMPS
MAST
THIMBLE EYEBOLT
CROSBY CLAMP
GUY CABLES
MAST CLAMPS
GUY CABLE
CROSBY CLAMP
THIMBLE EYEBOLT
LEAVE 1'-6"
TAILS
3'-0" MIN.
3'-6" MAX.
MAST -SEE
NOTE 2
ROOF FLASHING
AND SEAL
CONDUIT STRAPS
MAST
MAST CLAMPS
GVEA SERVICE DROP
CONDUCTORS (TO GVEA
POLE AND TRANSFORMER)
THIMBLE EYEBOLT
CROSBY CLAMP
GUY CABLE
EXISTING WALL
STUDS
INSULATION
WASHER &
SQUARE NUT
DEAD AIR SPACE
INTERIOR
SHEETROCK
WALLBOARD
WASHER & SEAL
OVAL EYE BOLT
EXTERIOR SHEATHING
2" x 6" BOARDS LENGTH
AS REQUIRED
INSULATION
WASHER & SQUARE
NUT
WASHER & SEAL
THIMBLE EYEBOLT
INTERIOR SHEETROCK
WALLBOARD
DEAD AIR SPACE
EXISTING ROOF
JOISTS OR TRUSS
ROOF FLASHING
AND SEAL
2" x 6" BOARDS
LENGTH AS
REQUIRED
MAST CLAMP FOR ROOF
GUYING SUPPLIED BY
MEMBER
MAST CLAMP FOR
ROOF SERVICE FROM
SUPPLIED BY GVEA
CROSBY CLAMP
GUY CABLE
VE
RT
IC
AL
180°
180°
30°
30°
© 2020 Golden Valley Electric Association, Inc. Page 19
Guying A Pole
180°
GUY CABLE SHALL BE
IN LINE WITH SERVICE
DROP
POLE
UTILITY SERVICE DROP (TO
GVEA POLE & TRANSFORMER)
OVAL EYENUT
GALVANIZED SQUARE
WASHER
ANGLE THIMBLE EYEBOLT
PREFORMED GRIP
GUY CABLE MIN. 1/4"
GALVANIZED STEEL
OR ALUMINUM CLAD
CABLE
SCREW ANCHOR SHALL BE INSTALLED
A MINIMUM OF 15'-0" FROM METER POLE
(MEASURED AT FINAL GRADE).
REVISED 03/2020
TOP VIEW
SIDE VIEW
POLE GUY DETAIL
SCREW ANCHOR DETAIL
FINAL GRADE
5'-0" MIN.
6" MAX.
6"
MIN.
© 2020 Golden Valley Electric Association, Inc. Page 20
REMOTE POWER
SERVICE DISCONNECT
ST
CCS
TRANSFORMER
L1 L2 L3
PB
OCP
EXTERIOR INTERIOR
LOAD
UTILITY
CIRCUITS
ST
CCS
TRANSFORMER
L1 L2 N
PB
OCP
EXTERIOR INTERIOR
LOAD
UTILITY
CIRCUITS
L3
Shunt Trip Details
REVISED 03/19
1. CCS: Contact Clearing Switch (opens when circuit breaker is shunt
tripped).
OCP: Overcurrent Protection, Shunt Trip Circuit (rated for available
fault current and source voltage). Installed as close to source as
practical.
PB: Push Button Switch, push-pull, normally open, Square D K type
with mushroom push button (or equal)
ST: Shunt Trip Coil, coil voltage rated for source voltage. Sourced from
load side of Main Disconnecting Means (main circuit breaker).
2. Verify additional requirements and coordinate lockable enclosures
housing the push button operator with the Fire Department having
jurisdiction and serving the facility. The push button operator must be
in a location that is readily accessible to fire department
personnel.
3. The push button operator shall be grouped together with meter on the
outside of the building to be served and mounted at a height of 5'-0" to
6'-0" above final grade.
4. The push button operator shall be suitable for the environment in which
it is installed.
5. A second shunt trip circuit shall be installed adjacent to the service
disconnect shunt trip to shutdown and disconnect any emergency
power sources. This plaque shall read "GENERATOR DISCONNECT"
or "EMERGENCY POWER DISCONNECT".
6. Conduit between Main Disconnecting Means and Shunt Trip Push
Button Operator shall be RMC or IMC.
7. Conductor insulation shall be XHHW or RHW.
8. An engineered design for the shunt trip circuit is required. The design
shall specify the OCP rating, shunt trip conductor size, pushbutton
rating, shunt trip unit, etc.
9. The shunt trip circuit shall be tested on a regular basis to ensure the
Main Disconnecting Means can be remotely tripped.
10. See Page 6, Section 4 for other details.
JUNCTION BOX OR ENCLOSURE.
PLAQUE MOUNTED ON OUTSIDE
OF ENCLOSURE IF PUSH BUTTON
HOUSED INSIDE OF ENCLOSURE.
2" x 5" (H x W) METAL OR
PLASTIC PLAQUE WITH
ENGRAVED 1/4" LETTERING.
SHUNT TRIP UNIT HOUSING
REMOTE PUSH BUTTON OPERATOR AND
PLACARD EXAMPLE INSTALLATION
EXAMPLE LINE TO LINE CONNECTION SCHEMATIC EXAMPLE LINE TO NEUTRAL CONNECTION SCHEMATIC
EXTERNALLY MOUNTED
PUSH BUTTON
MAIN DISCONNECTING MEANS
(MAIN CIRCUIT BREAKER)
EXTERNALLY
MOUNTED
PUSH BUTTON
SHUNT TRIP UNIT HOUSING
MAIN DISCONNECTING MEANS
(MAIN CIRCUIT BREAKER)
EXTERNALLY
MOUNTED
PUSH BUTTON
NOTES: See pages 3-7 for general requirements
© 2020 Golden Valley Electric Association, Inc. Page 21
12
3
4
5 6
1
2
N
L
L
Typical Multiple Meter Service Entrance
(Six Units or Less)
METER SOCKET. METERS INSTALLED BY GVEA
1. Service entrance location shall be approved by GVEA
and shall be located as close as possible to existing
GVEA facilities.
2. Conduit for service cable shall be sized per NEC but
shall not be less than 2". Conduit runs shall have one
set of service lateral conductors per conduit.
3. Member's service equipment shall conform to the NEC
and State and Municipal Codes and shall be inspected
and approved prior to connection of service by GVEA.
4. Any deviation from this standard shall be approved in
writing by GVEA's Engineering Services Department.
5. Conductor insulation shall be type USE for direct burial
installations or type XHHW or RHW for installations in
conduit.
6. If the grounding electrode conductor is exposed to
physical damage it shall be run in conduit securely
fastened to the structure. See NEC 250.64(B).
7. The bottom of the service entrance equipment shall not
be less than 3'-0" above finished grade or finished floor.
Choose equipment size to maintain this minimum
distance and a maximum height of 6'-7" to the horizontal
centerline of the highest breaker or handle of the
disconnecting means.
8. Install sealing lock nuts or hubs on all conduit
penetrations of outdoor enclosures.
9. If conductors are 3/0AWG or smaller, direct burial is
acceptable.
TYPICAL SERVICE BREAKER RATED FOR
AVAILABLE FAULT CURRENT (MIN. 10,000 AIC)
ALL METER BASES SHALL BE IDENTIFIED
WITH PERMANENT LABELING (PERMANENT
MARKER NOT ALLOWED) -SEE PAGE 4
SERVICE ENTRANCE BUSING
IF CONCENTRIC KNOCKOUT IS USED
GROUND BONDING BUSHING TO
ENCLOSURE WITH A BONDING JUMPER.
RIGID METAL CONDUIT
CONDUIT CLAMP
GALVANIZED RIGID METAL ELBOW
6'-7" MAX.
NEMA TYPE 3R RAIN
RESISTANT GROUPED
METERING ENCLOSURE
3'-0" MIN.
SEE NOTE 7
COPPER CLAD STAPLED
EVERY 6"
GROUNDING ELECTRODE
CONDUCTOR #4 COPPER
MINIMUM SIZE -SEE NOTE
6 & GROUNDING DETAIL
ON PAGE 26
2'-0" MIN.
CABINET SHALL BE ABLE TO BE SEALED BY GVEA
TO APPROVED GROUND
-SEE GROUNDING
DETAIL ON PAGE 27
FINAL GRADE
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 22
12
34
5
6
7 8
L
L
N
1
2
Typical Multiple Meter Service Entrance
(More than Six Units)
REVISED 03/19
METER SOCKET
METER INSTALLED BY GVEA
1. Service entrance location shall be approved by GVEA
and shall be located as close as possible to existing
GVEA facilities.
2. Conduit for service cable shall be sized per NEC but
shall not be less than 2". Conduit runs shall have one
set of service lateral conductors per conduit.
3. Member's service equipment shall conform to the NEC
and State and Municipal Codes and shall be inspected
and approved prior to connection of service by GVEA.
4. Where fused disconnects are provided, a separate fuse
access door shall be provided, interlocked with the main
switch, to permit fuse replacement by owner without
breaking the main service cabinet seals. (An internal
barrier suitable for sealing is not acceptable).
5. Any deviation from this standard shall be approved in
writing by GVEA's Engineering Services Department.
6. Conductor insulation shall be type USE for direct burial
installations or type XHHW or RHW for installations in
conduit.
7. The bottom of the service entrance equipment shall not
be less than 3'-0" above finished grade or finished floor.
Choose equipment size to maintain this minimum
distance and a maximum height of 6'-7" to the horizontal
centerline of the highest breaker or handle of the
disconnecting means.
8. Install sealing lock nuts or hubs on conduit penetrations
of outdoor enclosures.
9. Service with 6 or more meters is required to have a main
breaker service disconnect.
10. If conductors are 3/0AWG or smaller, direct burial is
acceptable.
TYPICAL SERVICE BREAKER
RATED FOR AVAILABLE FAULT
CURRENT (MIN. 10,000 AIC)
ALL METER BASES SHALL BE
IDENTIFIED WITH PERMANENT
LABELING (PERMANENT MARKER
NOT ALLOWED) -SEE PAGE 4
IF CONCENTRIC KNOCKOUT IS USED
GROUND BONDING BUSHING TO
ENCLOSURE WITH A BONDING JUMPER.
GALVANIZED METAL CONDUIT
CONDUIT CLAMP
GALVANIZED RIGID METAL
ELBOW
NEMA TYPE 3R RAIN RESISTANT
MODULAR METERING ENCLOSURE
COPPER CLAD STAPLED EVERY 6"
GROUNDING ELECTRODE CONDUCTOR
#4 COPPER MINIMUM SIZE -SEE
GROUNDING DETAIL ON PAGE 26
FINAL GRADE
INTERNAL BUS BARS TO BE RATED
FOR AVAILABLE FAULT CURRENT
TO APPROVED GROUND
-SEE GROUNDING
DETAIL ON PAGE 26
2'-0" MIN.
MAIN BREAKER OR FUSED DISCONNECT
RATED FOR AVAILABLE FAULT
CURRENT (MIN. 10,000 AIC)
CABINET SHALL BE ABLE TO BE SEALED
BY GVEA
MAX. 4 METERS VERTICAL
6'-7" MAX.
3'-0" MIN.
SEE NOTE 7
NOTES: See pages 3-7 for general requirements
© 2020 Golden Valley Electric Association, Inc. Page 23
Typical CT Metered Service
(1200 Amps and Below)
1. Conductors shall be connected to the CT mounting bracket
using appropriate UL approved compression connectors or
mechanical lugs, suitable for the conductor material type.
Aluminum conductors shall not be directly connected using
mechanical lugs.
2. This drawing is not intended to show grounding details. See
page 25 and 27 for Grounding Details.
3. Conduit for meter conductors shall be at least 1 inch diameter
and no longer than 50'-0". Conduit shall be RMC or IMC. No
Compression Fittings shall be accepted. All conduit used for CT
circuits shall be of the threaded type.
4. Mount CT's to the cabinet using factory accessory or brackets
installed at factory, with allowable short circuit fault current
rating marked on accessory or cabinet. Both ends of all
mounting bolts shall be accessible for future removal. Mount so
as to allow NEC required space to train both source and load
conductors. CT's shall be mounted at right angles to enclosure
panels with polarity marks facing source side.
5. CT cabinet cover shall have two handles or similar lifting device
or be hinged.
6. CT cabinet, meter enclosure, and main disconnects shall be
grouped together on the outside of building. All enclosures shall
be rain resistant (NEMA 3R). Inside locations are not permitted
without approval prior to installation.
7. On service above 1200 Amps, switch gear installation is
preferred. Submit CT information to GVEA for approval.
8. GVEA shall install CT secondary wiring and test switch.
9. This area for GVEA supplied test switch. See page 6, "Current
Transformer Bypass Provisions."
10. Conductor insulation shall be type USE for direct burial
installations or type XHHW or RHW for installations in conduit.
11. The member's contractor shall provide a tented and heated
area for pulling and terminating conductors for underground
installations when the temperature is less than +20°F. The
heating source will be an indirect fired system. Contact
GVEA's New Construction section for more information.
12. Equipment grounding conductor (EGC) to distribution panel(s)
required. See NEC 250.32(B).
13. Sealing locknuts or hubs shall be used on all conduits that
penetrate enclosures in an exterior installation.
14. Service equipment shall be marked with the available fault
current and date calculated according to 2014 NEC 110.24.
15. Use Burndy Hystack or equivalent when landing multiple sets
of conductors. Using nuts to separate conductors will not be
accepted.
METER INSTALLED
BY GVEA
STANDING SURFACE (floor, etc.)
SOURCE
CURRENT TRANSFORMER CABINET
(Min. Size W x H x D)
1200 and Below
Above 1200
SERVICE ENTRANCE
CONDUCTOR AMPACITY
Consult Utility
LOAD
CURRENT TRANSFORMER CABINET
SERVICE DISCONNECT SWITCH
Install CT with polarity
dot toward SOURCE.
SEE NOTE 9
SEE NOTE 2
SEE NOTES
1, 4, & 7
METER
ENCLOSURE
3Ø - 3'-0" x 3'-0" x 11"
1Ø - 2'-0" x 2'-8" x 9"
SEE NOTE 13
FUSE
CT
SEE NOTE 8
SEE NOTE 12
SEE
NOTES
3 & 13
11" MIN.
9 1/2"
MIN.
5'-0" MIN.
6'-0" MAX.
1.5"
MIN.
3"
MIN.
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 24
Grounding Details
(CT Metered Service with Main Disconnect)
1. All service enclosures shall be NEMA 3R outdoor type. Hubs are to be
of the sealable type. Hubs exposed to weather shall be rated weather
tight.
2. All CT and meter enclosures shall be sealable and have locknuts,
hubs and hub covers that are not removable from exterior of can.
3. This conduit shall be continuous. No junction boxes, unions, or
conduit bodies are permitted.
4. These conduits shall be Rigid Metal Conduit (RMC) or Intermediate
Metal Conduit (IMC) and sized in accordance with NEC 344.22 for
RMC and 342.22 for IMC. No compression fittings shall be accepted.
Sealing locknuts shall be installed on conduits penetrating outdoor
enclosures.
5. Conduit size between CT and meter enclosure shall be a minimum of
1" diameter and not longer than 50'-0". Conduit shall be RMC or IM C.
6. Supply side equipment bonding jumper shall be sized per NEC
250.102(C) with the exception that the minimum size allowed by
GVEA shall be #4 Cu. Equipment bonding jumper shall be run
continuous throughout service equipment.
7. Bond grounding electrode conductor to metal water pipe and other
available grounding electrodes as required by NEC 250.50
"Grounding Electrode System".
8. If grounding requirements of NEC 250.50 cannot be met, and made
electrodes are utilized as the sole type of grounding electrodes, then
the resistance requirements of NEC 250.53(A)(2) shall be met.
Electrodes may be directly bonded together with grounding electrode
conductor, individually routed to the neutral bus, or connected to an
optional terminal bus as stated in note 18. A ground rod is required
by GVEA even if a metal water pipe or other electrodes listed in
NEC 250.50 are used.
9. Grounding electrode conductors sized per NEC 250.66 with minimum
size to be #4 Cu in accordance with GVEA requirements. For specific
service entrance, see approved GVEA load data for minimum
permissible grounding electrode conductor size. See note 18 for
another grounding electrode bonding jumper connection option.
Grounding conductors shall be continuous as per NEC 250.64(C) and
protection from physical damage as per NEC 250.64(B).
10. Use #4 Cu conductor to bond CT meter enclosure. CT meter bonding
conductor shall be continuous between bonding points.
11. All neutral buses shall be effectively bonded to enclosures in
accordance with NEC 250.92. Install separate grounding lug in
enclosure if neutral bus is not directly bonded to enclosure. Factory
supplied neutral bus bonding means are subject to approval.
12. Per NEC 250.12 and 250.96, paint shall be removed from surfaces in
contact with grounding fittings. Exposed metal at ground points shall
be protected with conductive corrosion inhibitor.
13. Supply-side bonding jumpers and CT meter bonding conductor shall
be routed through the conduit. Each end of the conduit shall be
bonded as required by GVEA.
14. It is the member's responsibility to phase mark paralleled conductors
in an easily visible manner. High leg of delta services shall be
identified ORANGE per NEC 110.15.
15. Threadless couplings and connectors are not allowed for bonding
service equipment. OZ Gedney Type CHM-T or similar UL listed with
piercing screw approved for bonding are acceptable for bonding
conduit to enclosures and may be substituted for conduit bonding
bushings. Standard locknuts, sealing locknuts, or grounding
wedges are not acceptable for bonding at service equipment.
16. Compression or screw-type connectors are acceptable means of
splicing conductors. Split bolt type are not allowed.
17. Service equipment shall be marked to identify it as being suitable for
use as service equipment.
18. Optional terminal bus can be added to connect bonding jumpers from
multiple grounding electrodes. Optional terminal bus shall be
effectively bonded to enclosure. A grounding electrode conductor
shall connect the optional bus with the neutral bus and it shall be
sized as per NEC 250.66.
19. Equipment grounding conductor (EGC) to distribution panel(s)
required. See NEC 250.32(B).
20. Service equipment shall be marked with the available fault current
and date calculated according to NEC 110.24.
METER ENCLOSURE
WITH SOLID TOP
AND NO HOLE FOR
HUB ATTACHMENT
GROUND ELECTRODE
CONDUCTOR -SEE NOTE 9
(with parallel entrance conductors)(with separate meter enclosure)
TO APPROVED GROUND
SEE GROUNDING DETAIL
ON PAGE 26
TO APPROVED GROUND
SEE GROUNDING DETAIL
ON PAGE 26
METER
ENCLOSURE
CT ENCLOSURE
DISCONNECT
ENCLOSURE
METER
ENCLOSURE
CT ENCLOSURE
DISCONNECT
ENCLOSURE
5'-0" MIN.
6'-0" MAX.
METER ENCLOSURE WITH
SOLID TOP AND NO HOLE
FOR HUB ATTACHMENT
OVERHEAD SOURCE
SEE NOTES 3, 4, & 14
SEE NOTE 2
SEE NOTE 4
SEE NOTE 12
5'-0" MIN.
6'-0" MAX.
SEE NOTES 3, 4, & 5
BONDING JUMPER
SEE NOTE 15
SEE NOTES 3, 4, & 15
SEE NOTE 10
UNDERGROUND SOURCE
SEE NOTE 12
SEE NOTES
13 & 15 TYP.
EQUIPMENT BONDING
JUMPER -SEE NOTE 6
MAX. HEIGHT
TO CENTER OF
HANDLE 6'-7"
TO LOAD
BONDING
JUMPER
NEUTRAL BUS
-SEE NOTE 11 & 12
SEE NOTE
12 & 18
SEE NOTE 12
SEE NOTE 10
SEE NOTE 12
SEE NOTES
3, 4, & 5
SEE NOTE 2
SEE NOTE 4
OVERHEAD SOURCE -SEE NOTES 3, 4, & 14
EQUIPMENT
BONDING
JUMPER
-SEE NOTE 6
BUSHING LUGS
-SEE NOTE 13 &
15 TYP.
SEE NOTE 12
SEE NOTES
12 & 18
NEUTRAL BUS
-SEE NOTES 11 & 12
MAX. HEIGHT
TO CENTER OF
HANDLE 6'-7"
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTE 9
UNDERGROUND SOURCE
SEE NOTES 3, 4, & 15
GROUNDING ELECTRODE
SYSTEM -SEE NOTES 7 & 8
GROUNDING ELECTRODE
SYSTEM -SEE NOTES 7 & 8
TO LOAD
FINAL GRADE
NOTES: See pages 3-7 for general requirements
UNDERGROUND OR OVERHEAD SERVICE UNDERGROUND OR OVERHEAD SERVICE
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 25
1
L
2
L
N
2
L
L
1
N
E
G
C
WATER PIPE -SEE NOTES 2 & 6
GROUND ROD(S)
GROUND RING
BUILDING STEEL
CONCRETE ENCASED ELECTRODE
Grounding Details
(Meter Located on Building Being Served)
1. Bond grounding electrode conductor to metal water pipe
and other available grounding electrodes as required by
NEC 250.50 "Grounding Electrode System".
2. The grounding connection to a metal water pipe shall be
within 5'-0" of the point where the water pipe enters the
structure. A water pipe that is used for grounding shall be
buried in the earth for a minimum of 10'-0" of it's length.
3. All possible grounding configurations could not be shown.
All grounding shall comply with article 250 of the NEC. It
is recommended to bond the grounding electrode
jumpers to a grounding bus in the enclosure or to the
grounding electrode conductor. Pipe connections may
become corroded and compromise the integrity of the
grounding system.
4. Threadless couplings and connectors are not allowed for
bonding service equipment. OZ Gedney Type CHM-T or
similar UL listed with piercing screw approved for bonding
are acceptable for bonding conduit to enclosures and
may be substituted for conduit bonding bushings.
Standard locknuts, sealing locknuts, or grounding
wedges are not acceptable for bonding at service
equipment.
5. Conductor insulation shall be type USE for direct burial
installations or type XHHW or RHW for installations in
conduit.
6. Self-contained 300 Amp service is single-phase only.
See page 15 for details.
7. In the absence of a metallic water pipe in direct contact
with the earth a well casing may be used as a grounding
electrode in place of the water pipe provided that the well
casing meets all the requirements of NEC 250.52(A)(1)
for direct earth contact of 10'-0".
8. If the grounding electrode system consists of only one
ground rod or set of ground rods as required by NEC
250.53(A)(2), the grounding electrode conductor shall be
sized as per NEC Table 250.66. When additional
grounding electrodes are employed the sole grounding
electrode conductor to the ground rod can be reduced in
size to a minimum #4 AWG Cu conductor.
ADDITIONAL 8'-0" x 5/8" DIAMETER MIN. COPPER
CLAD GROUND ROD (IF FIRST ROD IS ONLY
GROUNDING ELECTRODE -SEE NEC 250.53(A)(2))
GROUNDING ELECTRODE SYSTEM
-SEE NOTES 1 & 3 ON PAGE 26
-SEE NOTE 8 ON PAGE 25
CONTINUOUS GROUNDING ELECTRODE
CONDUCTOR TO GROUND ROD -SEE NOTE 7
IRREVERSIBLE
COMPRESSION
CONNECTOR
GROUNDING ELECTRODE CONDUCTOR
MIN. #4 OR #2 AWG COPPER
-SEE NOTES 8 & 9 ON PAGE 25
4-WIRE FEEDER TO DISTRIBUTION PANEL
GROUNDING BLOCK SHALL BE PERMANENTLY
BONDED TO ENCLOSURE
COMBINATION RAINTIGHT
METER AND SERVICE ENCLOSE
SERVICE ASSEMBLY
MAIN BREAKER OR DISCONNECT AND FUSES
-SEE NOTE 4
SERVICE
100 Amp
200 Amp
SIZE
Copper
Copper
MINIMUM
GROUNDING
#4
#4
WIRE/CONDUIT SIZE TABLE
#2
#3/0
Copper
Copper
1 1/4"
2"
ELECTRODE
CONDUCTOR
SIZE
Copper
Copper
EQUIPMENT
#8
#6
GROUNDING
CONDUCTOR
SIZE
300 Amp
Copper
#2300 kcmil
Copper
2"
Copper
#4
MINIMUM
8'-0" x 5/8" DIAMETER MIN. COPPER CLAD GROUND
ROD TYP.
SEALING LOCK NUT & BONDING BUSHING
6'-0"
MIN.
NOTES: See pages 3-7 for general requirements
FROM GVEA POWER SYSTEM
WIRE SHALL BE COPPER
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 26
MINIMUM
CONDUIT
SIZE (RMC
OR IMC)
MINIMUM
WIRE SIZE
(USE, XHHW,
OR RHW)*
L
N
1
2
L
G
N
L
1
L
2
G
L
2
1
L
N
EGC
EGC
Grounding Details
(Pole or Post Mounted Meter)
1. Bond grounding electrode conductor to metal water pipe
and other available grounding electrodes as required by
NEC 250.50 "Grounding Electrode System".
2. The grounding connection to a metal water pipe shall be
within 5'-0" of the point where the water pipe enters the
structure. A water pipe that is used for grounding shall be
buried in the earth for a minimum of 10'-0" of it's length.
3. All possible grounding configurations could not be shown.
All grounding shall comply with article 250 of the NEC. It
is recommended to bond the grounding electrode jumpers
to a grounding bus in the enclosure or to the grounding
electrode conductor. Pipe connections may become
corroded and compromise the integrity of the grounding
system.
4. Threadless couplings and connectors are not allowed for
bonding service equipment. OZ Gedney Type CHM-T or
similar UL listed with piercing screw approved for bonding
are acceptable for bonding conduit to enclosures and may
be substituted for conduit bonding bushings. Standard
locknuts, sealing locknuts, or grounding wedges are
not acceptable for bonding at service equipment.
5. Conductor insulation shall be type USE for direct burial
installations or type XHHW or RHW for installations in
conduit.
6. Self-contained 300 Amp service is single-phase only.
See page 15 for details.
7. In the absence of a metallic water pipe in direct contact
with the earth a well casing may be used as a grounding
electrode in place of the water pipe provided that the well
casing meets all the requirements of NEC 250.52(A)(1)
for direct earth contact of 10'-0".
8. If the grounding electrode system consists of only one
ground rod or set of ground rods as required by NEC
250.53(A)(2), the grounding electrode conductor shall be
sized as per NEC Table 250.66. When additional
grounding electrodes are employed the sole grounding
electrode conductor to the ground rod can be reduced in
size to a minimum #4 AWG Cu conductor.
ADDITIONAL 8'-0" x 5/8" DIA. MIN.
COPPER CLAD GROUND ROD (IF
FIRST ROD IS ONLY GROUNDING
ELECTRODE -SEE NEC 250.53(A)(2))
GROUNDING ELECTRODE SYSTEM
-SEE NOTES 1 & 3
-SEE NOTE 8 ON PAGE 25
CONTINUOUS GROUNDING
ELECTRODE CONDUCTOR
TO GROUND ROD
-SEE NOTE 7
IRREVERSIBLE
COMPRESSION
CONNECTOR
GROUNDING ELECTRODE CONDUCTOR
MIN. #4 OR #2 AWG COPPER -SEE TABLE
BELOW AND NOTES 8 & 9 ON PAGE 25
4-WIRE FEEDER TO DISTRIBUTION
PANEL
ISOLATED NEUTRAL BUS BAR
COMBINATION RAINTIGHT METER
AND SERVICE ENCLOSE
LOCK NUT & BONDING BUSHING
GROUNDING BLOCK SHALL
BE PERMANENTLY BONDED
TO ENCLOSURE
FROM GVEA
POWER SYSTEM
WATER PIPE -SEE NOTES 2 & 6
CONCRETE ENCASED ELECTRODE
GROUND RING
BUILDING STEEL
8'-0" x 5/8" DIA. MIN.
COPPER CLAD
GROUND ROD TYP.
SEALING LOCK NUT & BONDING
BUSHING
6'-0"
MIN.
GROUND ROD CLAMP
SERVICE DISCONNECT EQUIPMENT
SHALL BE LOCATED WHERE
CONDUCTORS ENTER THE BUILDING
CIRCUIT BREAKER OR SWITCH
AND FUSES
MAIN BREAKER
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTE 9
ON PAGE 25
CONDUCTORS IN
CONDUIT OR
DIRECT BURY
NOTES: See pages 3-7 for general requirements
SERVICE
100 Amp
200 Amp
SIZE
Copper
Copper
MINIMUM
GROUNDING
#4
#4
WIRE/CONDUIT SIZE TABLE
WIRE SIZE
MINIMUM
#2
#3/0
Copper
Copper
1 1/4"
2"
(USE, XHHW,
ELECTRODE
CONDUCTOR
SIZE
Copper
Copper
EQUIPMENT
#8
#6
GROUNDING
CONDUCTOR
SIZE
300 Amp
Copper
#2300 kcmil
Copper
2"
Copper
#4
OR RHW)*
MINIMUM
WIRE SHALL BE COPPER
REVISED 03/2020
GROUND ROD
© 2020 Golden Valley Electric Association, Inc. Page 27
MINIMUM
CONDUIT
SIZE (RMC
OR IMC)
SERVICE ENTRANCE BUSWAY
FINAL GRADE
TO APPROVED GROUND
SEE GROUNDING
DETAIL ON PAGE 26
FINAL GRADE
SERVICE ENTRANCE WIREWAY
TO APPROVED GROUND
SEE GROUNDING DETAIL
ON PAGE 26
Grounding Details
(Multiple Metered Service without Main Disconnect)
REVISED 03/19
(Multiple Metered Service without Main Disconnect, Alternate)
GROUNDING ELECTRODE SYSTEM
-SEE NOTES 7 & 8
NEUTRAL BUS NEUTRAL BUS NEUTRAL BUS
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTE 9
GROUNDING ELECTRODE SYSTEM
-SEE NOTES 7 & 8
MAIN BONDING JUMPER
5'-0" MIN.
6'-0" MAX.
MAX. HEIGHT
TO CENTER OF
HANDLE 6'-7"
EQUIPMENT BONDING JUMPER
-SEE NOTES 16 & 23 TYP.
UNGROUNDED SOURCE
SEE NOTES
4, 5, & 6 TYP.
EQUIPMENT
BONDING
JUMPER -SEE
NOTE 12
SEE NOTE 15
TYP.
GROUNDED SERVICE
CONDUCTOR (NEUTRAL)
-SEE NOTE 10
NEUTRAL BUS
-SEE NOTES 14 & 15
SEE NOTE 22 SEE NOTE 22
SEE NOTE 22
SEE NOTE 22
SEE NOTES 4,
5, 6, & 16 TYP.
EQUIPMENT BONDING
JUMPER -SEE NOTE 12
SEE NOTE
15 TYP.
GROUNDED SERVICE
CONDUCTOR (NEUTRAL)
-SEE NOTE 11 TYP.
SEE NOTES
1 & 2
GROUNDED SERVICE
CONDUCTOR
(NEUTRAL) -SEE
NOTE 11 TYP.
SEE NOTES 1 & 2
SEE NOTE 3 TYP.
MAX. HEIGHT
TO CENTER OF
HANDLE 6'-7"
5'-0" MIN.
6'-0" MAX.
MAIN BONDING
JUMPER
SEE NOTES 4,
5, 6, & 16 TYP.
GROUNDING ELECTRODE
CONDUCTOR -SEE NOTE 9
EQUIPMENT BONDING JUMPER
-SEE NOTES 13 & 16 TYP.
UNGROUNDED SOURCE
SEE NOTES 4, 5,
& 6 TYP.
NEUTRAL BUS
-SEE NOTES
14 & 15 TYP.
SEE NOTE 15
TYP.
NEUTRAL BUS -SEE NOTE 14 & 15
GROUNDED SERVICE
CONDUCTOR
(NEUTRAL)
-SEE NOTE 10
EQUIPMENT
BONDING JUMPER
-SEE NOTE 12
NOTES FOLLOW ON PAGE 29
© 2020 Golden Valley Electric Association, Inc. Page 28
Grounding Details
Notes for Multiple Metered Service Details
1. All service enclosures shall be NEMA 3R outdoor type.
Hubs exposed to weather shall be rated weather tight.
2. All equipment before meter shall be sealable. Hubs and
hub covers shall not be removable from exterior of can.
3. Compression or screw type connectors are an acceptable
means of connecting conductors to bus bar.
4. This conduit shall be continuous. No junction boxes or
conduit bodies are permitted.
5. These conduits shall be Rigid Metal Conduit (RMC) or
Intermediate Metal Conduit (IMC) and sized in
accordance with NEC 344.22 for RMC and 342.22 for
IMC. No compression fittings shall be accepted. Sealing
locknuts shall be installed on conduits penetrating outdoor
enclosures.
6. Threadless couplings and connectors are not allowed for
bonding service equipment. OZ Gedney Type CHM-T or
similar UL listed with piercing screw approved for bonding
are acceptable for bonding conduit to enclosures and may
be substituted for conduit bonding bushings. Standard
locknuts, sealing locknuts, or grounding wedges are
not acceptable for bonding at service equipment.
7. Bond grounding electrode conductor to metal water pipe
and other available grounding electrodes as required by
NEC 250.50 "Grounding Electrode System".
8. If grounding requirements of NEC 250.50 cannot be met,
and made electrodes are utilized as the sole type of
grounding electrodes, then the resistance requirements of
NEC 250.53(A)(2) shall be met. Electrodes may be
directly bonded together with grounding electrode
conductor or individually routed to the neutral bus. A
ground rod is required by GVEA even if a metal water
pipe or other electrodes listed in NEC 250.50 are used.
9. Grounding electrode conductor sized in accordance to
NEC 250.66 with minimum size to be #4 Cu in
accordance with GVEA requirements. For specific service
entrance, see approved GVEA load data for minimum
permissible grounding electrode conductor size. #4 Cu
may be used when made electrodes are the sole type of
grounding electrodes. Grounding conductors shall be
continuous as per NEC 250.64(C) and protection from
physical damage as per NEC 250.64(B).
10. Grounded service conductor sized in accordance to
maximum diversified service demand and NEC 250.24(C)
with minimum size to be #4 Cu according to GVEA
requirements. Grounded service conductor shall be
continuous from service point throughout service
equipment to the neutral bus connection point.
11. Individual grounded service conductors sized in
accordance to individual diversified service demand and
NEC 250.24(C) with minimum size to be #4 Cu according
to GVEA requirements. Individual grounded service
conductors shall be continuous from the busway neutral
bus throughout service equipment to the equipment
neutral bus.
12. Equipment bonding jumper sized in accordance to NEC
250.28(D) with minimum size to be #4 Cu according to
GVEA requirements. Equipment bonding jumper to be
continuous throughout service equipment.
13. Individual equipment bonding jumpers sized in
accordance to individual disconnect ungrounded
conductor sizes and to NEC 250.28(D) with minimum size
to be #4 Cu according to GVEA requirements. Bonding
jumpers to be continuous throughout service equipment
with the exception of the individual disconnect taps.
14. Neutral bus to be effectively bonded to enclosure in
accordance with NEC 250.96. Install separate grounding
lug in enclosure if neutral bus is not directly bonded to
enclosure. Factory supplied neutral bus bonding means
are subject to approval.
15. Per NEC 250.12 and 250.96, paint shall be removed from
surfaces in contact with grounding fittings. Exposed metal
at ground points shall be protected with conductive
corrosion inhibitor.
16. Equipment bonding jumper shall be routed through
the conduit, and each end of the conduit shall be
bonded.
17. It is the member's responsibility to phase mark paralleled
conductors in an easily visible manner. High leg of delta
services shall be identified ORANGE per NEC 110.15.
18. Service equipment shall be marked to identify it as being
suitable for use as service equipment.
19. Use of split bolts is not allowed.
20. Equipment grounding conductor (EGC) to distribution
panel(s) is required. See NEC 250.32(B).
21. Compression or screw type connectors are an acceptable
means of tapping the individual equipment bonding
jumpers. Size of equipment bonding jumpers shall
conform to NEC 250.28(D).
22. Compression or screw type connectors are an acceptable
means of tapping the grounded service conductor
(neutral).
23. Individual equipment bonding jumpers sized in
accordance to individual disconnect ungrounded
conductor sizes and to NEC 250.28(D) with minimum size
to be #4 Cu according to GVEA requirements. Individual
equipment bonding jumpers to be continuous from tap
throughout service equipment.
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 29
1
2
3
1
23
BKOR
1 32
N
2
1
R W BR W
1 2
OR
1
WBKBU R W
2 3 1N
N
3
2
1
Y W BR W
2 3 3
BKOR BU
21
W R W Y
N 1 2
N
2
3
1
WBRW
3
Metering
Meter Socket for Current Transformer
and Connection Diagram
(Dot indicates location of
polarity mark on instrument
transformers relative to the
supply system.)
1. Potential transformers are required for
service voltages above 480V.
2. Meter base enclosure for any of the
above metering configurations shall
include provisions for a GVEA provided
test switch.
3. GVEA shall provide the CT's for the
member's contractor to mount for
services of 1200 Amps or less. For
services over 1200 Amps, CT's shall be
provided by the manufacturer with the
switchgear. GVEA shall provide and
install the test switch and wire the CT's,
test switches, and meter base.
4. As required by NEC 110.15 the phase
conductor in the service entrance having
the higher voltage to ground shall be
identified by the color ORANGE, and be
located on the right hand lug of the
meter base. (4-wire delta only)
5. If grounding requirements of NEC
250.50 cannot be met, and made
electrodes are utilized as the sole type
of grounding electrodes, then the
resistance requirements of NEC
250.53(A)(2) shall be met. Electrodes
may be directly bonded together with
grounding electrode conductor,
individually routed to the neutral bus, or
connected to an optional terminal bus as
stated in note 6. A ground rod is
required by GVEA even if a metal
water pipe or other electrodes listed
in NEC 250.50 are used.
6. Optional terminal bus can be added to
connect bonding jumpers from multiple
grounding electrodes. Optional terminal
bus shall be effectively bonded to
enclosure. A grounding electrode
conductor shall connect the optional bus
with the neutral bus and it shall be sized
as per NEC 250.66.
LEGEND:
CURRENT TRANSFORMER
THREE-PHASE SUPPLY SYSTEM
DELTA
WYE
TEST
SWITCH
TEST
SWITCH
TEST
SWITCH
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
13 Terminal
3 Current Transformers
4 Wire WYE
277/480V, 3Ø, 4W
120/208V, 3Ø, 4W
TYPE OF SERVICE
TERMINAL
TYPE OF SERVICE
TERMINAL
120/240V, 3Ø, 4W
240/480V, 3Ø, 4W
4 Wire DELTA, see note 4
3 Current Transformers
13 Terminal6 Terminal
2 Current Transformers
3 Wire
240/480V, 1Ø, 3W
120/240V, 1Ø, 3W
TYPE OF SERVICE
TERMINAL
FIGURE 3FIGURE 2FIGURE 1
© 2020 Golden Valley Electric Association, Inc. Page 30
1. Manual bypass sockets are not allowed
unless specifically approved by GVEA
prior to installation.
2. As required by NEC 110.15 the phase
conductor in the service entrance
having the higher voltage to ground
shall be identified by the color
ORANGE, and be located on the right
hand lug of the meter base (4-wire
delta only).
3. If grounding requirements of NEC
250.50 cannot be met, and made
electrodes are utilized as the sole type
of grounding electrodes, then the
resistance requirements of NEC
250.53(A)(2) shall be met. Electrodes
may be directly bonded together with
grounding electrode conductor,
individually routed to the neutral bus,
or connected to an optional terminal
bus as stated in note 4. A ground rod
is required by GVEA even if a metal
water pipe or other electrodes listed
in NEC 250.50 are used.
4. Optional terminal bus can be added to
connect bonding jumpers from multiple
grounding electrodes. Optional terminal
bus shall be effectively bonded to
enclosure. A grounding electrode
conductor shall connect the optional
bus with the neutral bus and it shall be
sized as per NEC 250.66.
5. Socket for 300A self-contained meter
shall conform to all requirements of the
4 terminal meter socket. In addition, it
shall be rated for 300A, have a bypass
lever, and the upper right hand jaw
must be reduced or have an
anti-inversion clip installed to prevent
the insertion of a 200A meter. The
meter enclosure must be the ringless
type to accommodate the required
meter bypass lever.
6. Meter bypass provisions are optional
on 200 Amp, three-phase, seven jaw
meter bases.
FIGURE 5
FIGURE 6
REDUCED OR
CLIP INSTALLED
-SEE NOTE 5
FIGURE 7
5 TERMINAL
TYPE OF SERVICE
· 120/208V, 3W Network
· 240V, 3Ø, 3W, Delta
· 480V, 3Ø, 3W, Delta
4 TERMINAL
TYPE OF SERVICE
· 120/240V, 1Ø, 3W
· 240/480V, 1Ø, 3W
4 TERMINAL (300 Amp)
TYPE OF SERVICE
· 120/240V, 1Ø, 3W, 300A
7 TERMINAL
TYPE OF SERVICE
· 120/208V, 4W, Wye
· 277/480V, 3Ø, 4W, Wye
· 120/240V, 3Ø, 4W, Delta
See note 2
· 240/480V, 3Ø, 4W, Delta
See note 2
· See note 6 for optional
bypass provisions
METER BYPASS
LEVER -SEE
NOTE 5
Metering
Self-Contained Meter Sockets (100 to 300 Amps)
FIGURE 4
REVISED 03/2020
NOTES: See pages 3-7 for general requirements
© 2020 Golden Valley Electric Association, Inc. Page 31
6
"
m
i
n
.
1. Most items on this page will be furnished by GVEA. An approved
Overhead Line Contractor, determined and contracted by GVEA,
shall perform all work shown. An applicable Electrical
Administrator License is required to perform supporting work not
shown on this document. See page titled 'Three-Phase
Transformer Vault Notes' for more detailed information.
2. Use additional couplings and nipples as required for 3'-6" conduit
depth and positioning.
3. Install pull line in primary conduits and cap both ends.
4. Finished top elevation of pad shall be 6" above final grade and not
subject to seasonal flooding.
5. Any conduit entering the side of the vault shall utilize precast
knock-outs.
6. Use 2" conduit for single phase installation. Use 4" conduit for
three phase installation. Conduits installed which are not plumb
shall not be accepted.
7. Slope all underground conduits 1/4" per 10'-0" minimum towards
vault.
8. All sweeps, elbows (above or below grade), and conduit above
grade shall be galvanized rigid metal conduit. PVC conduit shall
NOT be accepted in primary runs. Conduit runs of HDPE shall be
of the same manufacturer. The contractor is responsible for
removing all ridges created inside the HDPE joints. All materials
shall be listed for use.
9. Install first 3'-0" conduit stick on pole for inspection. Conduits
which are not plumb shall not be accepted.
10. Bollards are required to protect the transformer if placed near
vehicular traffic areas.
11. The member's contractor shall provide a tented and heated area
for pulling and terminating conductors for underground
installations when the temperature is less than +20°F. The heating
source will be an indirect fired system. Contact GVEA's New
Construction section for more information.
12. GVEA shall terminate all transformer secondary connections.
13. Engineering approval is required for more than 5 secondary runs.
Primary Riser Conduit Details
For Transformer Pads 14'-0" From Pole
(Length and routing to be approved by GVEA)
SEE PAGE 34 FOR SINGLE-PHASE
BOX PAD DETAIL. SEE PAGE 36
FOR THREE-PHASE, VAULT
DETAIL, AND FILL MATERIAL
SPECIFICATIONS
FINAL GRADE
CLIMBING ZONE.
NO EQUIPMENT
PLACED IN THIS AREA.
LEAVE TRENCH OPEN FOR INSPECTION
TYPE OF
INSTALLATION
1 Phase
3 Phase
THREADED MALLEABLE UNILETS
Appleton Electric Co. (or Equal) Catalog No.
C 200-M (2")
C 400-M (4")
6"
GALVANIZED RIGID CONDUIT PIPE CAP
-SEE NOTES 3 & 6
CAP ENDS OF CONDUIT
-SEE NOTES 3 & 6
SEE PAGE 34 FOR SINGLE-PHASE
BOX PAD DETAIL AND PAGE 36
FOR THREE-PHASE PAD DETAIL
6"-12"
GALVANIZED RIGID METAL OR HDPE
(ELECTRICAL CONDUIT LISTED TO UL 651A)
CONDUIT SLOPED TO DRAIN TO VAULT
-SEE NOTES 6, 7, & 8
ONE SET OF STAND-OFF BRACKETS PER
POLE, SIZED AS REQUIRED AND NOT PLACED
IN THE CLIMBING ZONE. STAND-OFF
BRACKETS TO BE ROTATED 45° FROM
CENTERLINE -SEE PAGE 18 FOR DETAILS
GALVANIZED RIGID
METAL ELBOW
-SEE NOTE 8
GROUND ROD AND
POLE GROUND
CONDUCTOR
PROVIDED BY GVEA
6"
GALVANIZED RIGID METAL
CONDUIT, 10'-0" LENGTHS
-SEE NOTES 6, 8, & 9
IRREVERSIBLE COMPRESSION
CONNECTOR
STAND-OFF BRACKETS SIZED
AS REQUIRED -SEE PAGE 18
FOR DETAILS
GALVANIZED RIGID METAL
CONDUIT AND PIPE CAP
-SEE NOTES 3 & 6
GROUNDING BUSHING PROVIDED
BY MEMBER. BOND CONDUIT TO
POLE GROUND.
3'-0"
CAUTION TAPE 6" FROM FINAL
GRADE. RUN THE FULL
LENGTH OF THE CONDUIT RUN.
3'-6" MIN.
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 32
6
"
m
i
n
.
1. Most items on this page will be furnished by GVEA. An approved
Overhead Line Contractor, determined and contracted by GVEA,
shall perform all work shown. An applicable Electrical Administrator
License is required to perform supporting work not shown on this
document. See page titled 'Three-Phase Transformer Vault Notes'
for more detailed information.
2. Use additional couplings and nipples as required for 3'-6" conduit
depth and positioning.
3. Install pull line in primary conduits and cap both ends.
4. Finished top elevation of pad shall be 6" minimum above final grade
and not subject to seasonal flooding.
5. Any conduit entering the side of the vault shall have the bottom
outside edge of the conduit a minimum of 6" above the vault floor.
6. Drainage conduit shall be installed at the lowest point of the conduit
run, using a 1'-0" deep pea gravel sump. At drainage point,
installation shall have either HDPE with sufficient number of 1/4in
holes or Unilet with cover removed; both shall be wrapped in
GeoTech wrap. This installation shall be inspected by GVEA before
backfilling.
7. Use 2" conduit for single phase installation. Use 4" conduit for three
phase installation. Conduits installed which are not plumb shall not
be accepted.
8. Slope all underground conduits 1/4" per 10'-0" minimum towards
drainage point or vault.
9. All sweeps, elbows (above or below grade), and conduit above
grade shall be galvanized rigid metal conduit. PVC conduit shall
NOT be accepted in primary runs. Conduit runs of HDPE shall be
of the same manufacturer. The contractor is responsible for
removing all ridges created inside the HDPE joints. All materials
shall be listed for use.
10. Conduit shall be stubbed out of ground 3'-0" for inspection.
Conduits which are not plumb shall not be accepted.
11. Bollards are required to protect the transformer if placed near
vehicular traffic areas.
12. The member's contractor shall provide a tented and heated area for
pulling and terminating conductors for underground installations
when the temperature is less than +20°F. The heating source will
be an indirect fired system. Contact GVEA's New Construction
section for more information.
13. GVEA shall terminate all transformer secondary connections.
14. Engineering approval is required for more than 5 secondary runs.
Primary Riser Conduit Details
For Transformer Pads More Than 14'-0" From Pole
(Length and routing to be approved by GVEA)
SEE PAGE 34 FOR SINGLE-PHASE
BOX PAD DETAIL. SEE PAGE 36
FOR THREE-PHASE, VAULT
DETAIL, AND FILL MATERIAL
SPECIFICATIONS
LEAVE TRENCH OPEN
FOR INSPECTION
CLIMBING ZONE.
NO EQUIPMENT
PLACED IN THIS AREA.
6"FINAL GRADE
GALVANIZED RIGID CONDUIT
PIPE CAPS -SEE NOTES 3 & 7
CAP ENDS OF CONDUIT -SEE NOTES 3 & 6
SEE PAGE 34 FOR SINGLE-PHASE BOX PAD DETAIL
AND PAGE 36 FOR THREE-PHASE PAD DETAIL
6"-12"
PEA GRAVEL
ONE SET OF STAND-OFF BRACKETS
PER POLE, SIZED AS REQUIRED AND
NOT PLACED IN THE CLIMBING ZONE.
STAND-OFF BRACKETS TO BE
ROTATED 45° FROM CENTERLINE
-SEE PAGE 18 FOR DETAILS
GALVANIZED RIGID
METAL ELBOW
-SEE NOTE 8
GROUND ROD AND
POLE GROUND
CONDUCTOR
PROVIDED BY GVEA
6"
GALVANIZED RIGID METAL
CONDUIT -SEE NOTES 7,
9, & 10
IRREVERSIBLE COMPRESSION
CONNECTOR
STAND-OFF BRACKETS SIZED
AS REQUIRED -SEE PAGE 18
FOR DETAILS
GALVANIZED RIGID METAL
CONDUIT AND PIPE CAPS
-SEE NOTES 3 & 7
GROUNDING BUSHINGS
PROVIDED BY MEMBER. BOND
CONDUIT TO POLE GROUND.
CAUTION TAPE 6" TO 1'-0"
FROM FINAL GRADE. RUN
THE FULL LENGTH OF
THE CONDUIT RUN.
3'-6" MIN.
1'-0"
DRAINING CONDUIT
-SEE NOTE 6
-SEE TABLE BELOW
GALVANIZED RIGID METAL OR HDPE (ELECTRICAL
CONDUIT LISTED TO UL 651A) CONDUIT SLOPED TO
DRAIN TO VAULT. -SEE NOTES 7, 8, & 9
DRAINING CONDUIT
-SEE NOTE 6
-SEE TABLE BELOW
3'-0"
NOTES: See pages 3-7 for general requirements
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 33
TYPE OF
INSTALLATION
1 Phase
3 Phase
THREADED MALLEABLE UNILETS
Appleton Electric Co. (or Equal) Catalog No.
C 200-M (2")
C 400-M (4")
1. An applicable Electrical Administrator License is required
for all work associated with the installation of
Single-Phase Transformer Box Pads.
2. All gravel is contractor furnished, delivered, and installed.
Gravel shall be 3/4" minus D1. Use mechanical
compactor and proper construction techniques for
compaction of gravel base.
3. All neutral conductors and non-current carrying parts shall
be interconnected and grounded.
4. Transformer installation shall be entirely dead front. All
energized primary and secondary parts and termination
are to be insulated.
5. Provide sufficient length #4 bare Cu loop for grounding all
necessary equipment.
6. GVEA supplied Box Pad shall have means for fastening
transformer.
7. #4 bare copper ground pigtail for comm/tv/phone where
required. Length as required to connect comm/tv/phone
equipment.
8. Use of split-bolts is not allowed.
9. Conduit types other than RMC may be used with prior
GVEA written approval.
10. Bollards are required to protect the transformer if placed
near vehicular traffic areas.
11. The member's contractor shall provide a tented and
heated area for pulling and terminating conductors for
underground installations when the temperature is less
than +20°F. The heating source will be an indirect fired
system. Contact GVEA's New Construction section for
more information.
12. GVEA supplied transformers require a minimum
separation to combustible construction of 25'-0". An
engineered solution is required if the transformer is placed
within 25'-0" of a structure. Reference NFPA 850 current
edition.
13. It is the owner's responsibility to identify underground
obstructions and initiate underground locates prior to
placing any new equipment. Location of customer
facilities approved by GVEA does not take into
consideration underground obstructions.
14. GVEA shall terminate all transformer secondary
connections.
15. Engineering approval is required for more than 5
secondary runs.
Single-Phase Transformer Box Pad Details
(For Transformers 15-167 kVA)
SEE NOTE 5
PRIMARY CONDUIT
DEPTH AS SPECIFIED
SLOPE 1/4" PER
FOOT MIN. TYP.
SECONDARY CONDUIT
DEPTH AS SPECIFIED
PRIMARY CONDUIT
10'-0" x 5/8" DIA. MIN. COPPER
CLAD GROUND ROD DRIVEN
10" FROM BOTTOM OF
EXCAVATION TYP.
SECONDARY CONDUIT
3/4" MINUS D1 FILL WITH
95% COMPACTION
4" MIN.
TYP.
SEE NOTE 7
TRANSFORMER TRANSFORMER
UNDISTURBED COMMON
FILL UNDER PAD TYP.
95% COMPACTION
OF ALL DISTURBED
COMMON BACK
FILL TYP.
TRANSFORMER BOX PAD
SIZED TO TRANSFORMER.
BOX PAD SUPPLIED BY
GVEA AND INSTALLED BY
CONTRACTOR. -SEE NOTE 5
2'-8" MIN.
3'-0" MAX.
4"
6" MIN.
SEE NOTE 5
6" MIN.
REVISED 03/2020
FRONT
SIDE VIEWFRONT VIEW
NOTES: See pages 3-7 for general requirements
FRONT
6" MIN.
© 2020 Golden Valley Electric Association, Inc. Page 34
1. An applicable Electrical Administrator License is
required for all work associated with the installation of
Secondary Pedestals.
2. All gravel is contractor furnished, delivered, and
installed. Gravel shall be 3/4" minus D1. Use mechanical
compactor and proper construction techniques for
compaction of gravel base.
3. All neutral conductors and non-current carrying parts
shall be interconnected and grounded.
4. Provide sufficient length #4 bare Cu conductor loop for
grounding all necessary equipment.
5. Use of split-bolts is not allowed.
6. Conduit types other than RMC may be used with prior
GVEA written approval.
7. Bollards are required to protect the transformer if placed
near vehicular traffic areas.
8. The member's contractor shall provide a tented and
heated area for pulling and terminating conductors for
underground installations when the temperature is less
than +20°F. The heating source will be an indirect fired
system. Contact GVEA's New Construction section for
more information.
9. GVEA shall terminate all transformer secondary
connections.
10. Engineering approval is required for more than 5
secondary runs.
11. Location of any customer facilities approved by GVEA
does not take into consideration underground
obstructions. It is the owner’s responsibility to call other
utilities for underground locates and to identify any
underground obstructions prior to placing any new
equipment.
Secondary Pedestal Details
SEE NOTE 4
SLOPE 1/4" PER
FOOT MIN. TYP.
LAND ALL GROUNDED SERVICE
CONDUCTORS ON TERMINAL
BLOCK -SEE NOTE 3
GVEA SUPPLIED,
CONTRACTOR INSTALLED
SECONDARY PEDESTAL
10'-0" X 5/8" DIA. MIN. COPPER
CLAD GROUND ROD DRIVEN
10" FROM BOTTOM OF
EXCAVATION TYP.
95% COMPACTION
OF ALL DISTURBED
COMMON BACK
FILL TYP.
3/4" MINUS D1
FILL WITH 95%
COMPACTION
SECONDARY CONDUITS
TO LOADS AS NEEDED
95% COMPACTION
OF ALL DISTURBED
COMMON BACK
FILL TYP.
FROM SECONDARY
SIDE OF PAD MOUNT
TRANSFORMER
UNDISTURBED COMMON
FILL UNDER PAD TYP.
1'-6"
3'-0"
APPROX.
6" MIN.
4" MIN.
TYP.
REVISED 03/2020
FRONT
FRONT VIEW SIDE VIEW
NOTES: See pages 3-7 for general requirements
6"
© 2020 Golden Valley Electric Association, Inc. Page 35
FINAL GRADE
1. Conduits may enter the vault
enclosure from the bottom
depending on depth. See note
6 on page 37.
Three-Phase Transformer Vault Details
ALTERNATE SECONDARY CONDUIT
ENTRY
ALTERNATE PRIMARY
CONDUIT ENTRY
REVISED 03/2020
FRONT VIEW
PLAN VIEW
10'-0" X 5/8" DIA. MIN. COPPER CLAD
GROUND ROD DRIVEN 10" FROM
BOTTOM OF EXCAVATION TYP.
SECONDARY CONDUITS SHALL BE
INSTALLED PERPENDICULAR TO
VAULT WALL
PRIMARY CONDUITS TO ENTER THE
VAULT FROM THE FRONT HALF OF
THE TRANSFORMER VAULT
1 PRIMARY CONDUIT FOR PADS
14'-0" OR LESS FROM POLE
2 PRIMARY CONDUITS FOR PADS
GREATER THAN 14'-0" FROM POLE
3/4" MINUS D1, 95%
COMPACTED 6" LIFTS
PRIMARY CONDUITS
SECONDARY CONDUITS
95% COMPACTION OF
ALL DISTURBED
COMMON BACK FILL TYP.
DEPTH AS
SPECIFIED
FOR PRIMARY
CABLES
DEPTH AS
SPECIFIED FOR
SECONDARY
CABLES
6"
6"-12"
6"-12"
1'-0" MIN.
10'-0"
7'-0"
NOTES: See pages 3-7 for general
requirements
5'-0"
© 2020 Golden Valley Electric Association, Inc. Page 36
1. All gravel is contractor furnished, delivered, and
installed. The gravel pad shall be 3/4" minus D1. All
back filled material underneath the gravel pad shall be
structural fill. Use a mechanical compactor and proper
construction techniques for compaction of gravel base.
No disturbed common back fill shall be allowed.
2. All neutral conductors and non-current carrying parts
shall be interconnected and grounded. Provide
sufficient length #4 bare Cu pigtail for grounding all
necessary equipment.
3. Transformer installation shall be entirely dead front. All
energized primary and secondary parts and
terminations shall be insulated.
4. Vault enclosure sized to transformer shall be furnished
by GVEA for installation.
5. Use of split-bolts is not allowed.
6. If any conduit enters the vault from the bottom, the
outside edge of the conduit shall be a minimum of 6"
above the vault floor. Conduit types other than RMC
may be used with prior GVEA written approval.
7. An applicable Electrical Administrator License is
required to perform all work associated with the
installation of transformer vault.
8. Installation of transformer vault and primary shall be
done by a GVEA approved contractor.
9. Transformer wiring and grounding details can be found
in GVEA's URD specifications book.
10. Where cable limiters are installed, adequate space for
this equipment and cable terminations shall be
provided. See page 7.
11. In vehicular traffic areas, bollards shall be required.
12. The member's contractor shall provide a tented and
heated area for terminating conductors for
underground installations when the temperature is less
than +20°F. The heating source will be an indirect fired
system. Contact GVEA's New Construction section for
more information.
13. GVEA supplied transformers require a minimum
separation to combustible construction of 25'-0". An
engineered solution is required if the transformer is
placed within 25'-0" of a structure. Reference NFPA
850 current edition.
14. It is the owner's responsibility to identify underground
obstructions and initiate underground locates prior to
placing any new equipment. Location of customer
facilities approved by GVEA does not take into
consideration underground obstructions.
Three-Phase Transformer Vault Notes
REVISED 03/2020
GVEA Responsibility
- GVEA shall furnish vault, transformer, and primary
conductors, conduit, & termination bracket.
- GVEA shall terminate all transformer secondary
connections.
- GVEA will provide bollards, where necessary.
Contractor Responsibility
-Contractor shall initiate all locates.
-Contractor will install vault, transformer, primary
conductors, conduit, and overhead termination
bracket.
-All vault installations shall have two compaction tests
on base layer under vault completed by a third-party
testing facility. Certified test results shall be submitted
to GVEA meeting 95% compaction.
-Contractor will terminate primary connections.
-Contractor will install secondary conduit, conductors
and associated hardware, unilets (or other means of
drainage), D1 gravel, and other materials not
supplied by GVEA.
-Bollards shall be installed in vehicle traffic areas.
General
-If the transformer is over 14'-0" from the primary pole,
GVEA will provide primary materials at no charge.
-If the transformer is over 14'-0" from the primary pole,
GVEA will provide primary materials at the current
rate beyond 14'-0" and to the transformer.
Note
- Primary and Secondary wire in vault shall be racked.
Installation Obligations
NOTES: See pages 3-7 for general requirements
© 2020 Golden Valley Electric Association, Inc. Page 37
Primary Metering
1. Member's fused disconnect may be used as an air break
isolating switch. Fuse size to be specified by GVEA to
coordinate with GVEA equipment.
2. Fuse sized to protect GVEA system and coordinate with
member's fuse. See note 1.
EXISTING GVEA PRIMARY POLE LINE
NOTES: See pages 3-7 for general requirements
REVISED 03/19
FOR GENERAL ARRANGEMENT INFORMATION ONLY
FINAL GRADE
GVEA'S DISCONNECT
-SEE NOTE 2
PRIMARY LINE
GVEA POLE
MEMBER'S FUSED
DISCONNECT
-SEE NOTE 1
PRIMARY
METERING
EQUIPMENT
30'-0"
GVEA OWNED
MEMBER
OWNED
POINT OF
SERVICE
MEMBER'S POLE
TO MEMBER'S
PRIMARY
50'-0"
GVEA OWNED
© 2020 Golden Valley Electric Association, Inc. Page 38
The table below shows the assumed % impedance and phase angle for distribution transformers
on the transformer base. Where fault current involves only one-half of the low voltage windings,
the % impedance values, based on full rated kVA, are 1.5 and 1.2 times the full winding %R and
%X respectively. An infinite bus is assumed on high side of the transformer.
Transformer Impedance Values
(For use in fault current calculations)
© 2020 Golden Valley Electric Association, Inc. Page 39
Single Phase Padmount or Overhead Transformer or Three Phase Overhead Bank
Transformer Size
[kVA/phase]
5
10
15
25
37.5
50
75
100
150
167
250
333
500
% Impedance*
[%Z]
2.1
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.7
1.7
1.7
1.7
1.7
Phase Angle
[Degrees]
30
30
40
45
45
52.5
52.5
60
60
60
60
60
60
% R+jX
[% Z]
1.819+j1.050
1.386+j0.800
1.226+j1.028
1.131+j1.131
1.131+j1.131
0.974+j1.269
0.974+j1.269
0.800+j1.386
0.850+j1.472
0.850+j1.472
0.850+j1.472
0.850+j1.472
0.850+j1.472
Three Phase Padmount Transformer
Transformer Size
[kVA/phase]
45
75
112.5
150
225
300
500
750
1000
1500
2000
% Impedance*
[%Z]
1.6
1.6
1.6
1.6
1.6
1.6
1.53**
5.18**
5.18**
5.18**
5.18**
Phase Angle
[Degrees]
40
45
45
52.55
52.55
60
60
60
60
60
60
% R+jX
[% Z]
1.226+j1.028
1.131+j1.131
1.131+j1.131
0.974+j1.269
0.974+j1.269
0.800+j1.386
0.765+j1.325
2.590+j4.486
2.590+j4.486
2.590+j4.486
2.590+j4.486
* % Impedance is based on RUS Guide 61-14.
** % Impedance is based on minimum values for three-phase distribution transformers as listed in section 7.1 of
ANSI C57.12.34-2004 and tolerances for impedance as defined in section 9.2 of ANSI C57.12.00-2006.
Site Plan
Site plan shall include property lines; location of structure to be served by utility with respect to the
property lines; location of service entrance equipment; location of GVEA transformer pole that is to
serve your structure; distance between GVEA transformer pole and your service entrance equipment.
Connected Load
This is the total connected load in kilovolt-amps (kVA) computed per the current addition of the
National Electric Code.
Motors and Starters: GVEA conducts a motor starting study for motors 10 horsepower and larger. If
the load contains motor(s) rated 10 horsepower or larger, then the following
data is required for each motor:
· Rated horsepower
· NEC locked-rotor indicating code letter
· Voltage
· Indicate whether single phase or three phase
· Indicate motor starting method (full voltage, reduced voltage [auto
transformer], or drive)
· Indicate motor starting and running sequence for multiple motors
Diversified Demand
If the load is a dwelling type load, then the demand (in kilowatts) shall be the load computed per the
current edition of the National Electric Code. It shall include a calculation for the individual dwelling
units as well as the total load on the service equipment.
For other type loads, the demand (in kilowatts) shall be a knowledgeable estimate by a registered
electrical engineer of the maximum load over a 15-minute time interval.
Load and Print Information Required by GVEA
© 2020 Golden Valley Electric Association, Inc. Page 40
Electrical Print
Include a one-line diagram AND riser diagram of service equipment from service entrance conductors
through the main disconnect and describing all physical details of installation. Refer to Electrical
Service One-Line (Relevant to your service, located on pages 42, 43, 44).
· Conductors and conduits – type, insulation, size, and number
· Over-current Device(s) and Equipment AIC rating
· Meter(s) – including numbering system
· Equipment Bonding and Grounding – per NEC and GVEA Electrical Service Entrance
Requirements
· Sealing Provisions – All access to unmetered conductors or bussing shall have
provisions for installing split/lock seals in accordance with GVEA Service Security
Equipment Sealing program. All meter retaining rings shall be the screw type. More
detailed information is available on request.
Revised 3/2020
WO#
© 2020 Golden Valley Electric Association, Inc. Page 41
Golden Valley Electric Association, Inc.
Cover Sheet
Electrical Load Data and Electrical Print
Application Name: Telephone:
Business Name: Telephone:
Mailing Address:
New Service Location:
Architect/Engineer: Telephone:
Electrical Contractor: Telephone:
Mailing Address: License #:
Service Requested:Volts: Phase: Amps: Configuration (Y or Δ)
The Association has adopted the National Electrical Code (NEC) as the minimum standard acceptable for
electrical installations it serves. The member should be aware that in addition to NEC requirements there
may be more stringent requirements imposed by the Association.
Golden Valley requires a detailed electrical print and detailed listing of the electrical load by a registered
electrical engineer or licensed electrical contractor on all multi-residential, commercial and industrial services.
Please ensure all applicable information required on the list below is attached to this cover sheet.
Checklist of Required Information
Site Plan
Connected Load
Motors and Starters
Diversified Demand
Electrical Print
Electrical Service One-Line (Relevant to your
service, located on pages 42, 43, 44)
Conductors and Conduits
Over-Current Device(s)
Meter(s) (to include numbering system)
Equipment Bonding and Grounding
Sealing Provisions
Reduced Neutral Calculations
When you have submitted the required information, Golden Valley will prepare a “Service Entrance Equipment
Requirement” sheet. A copy of this sheet will be sent to the applicant. DO NOT ORDER equipment prior to
receiving this “Service Entrance Equipment Requirement” sheet.
Load and Print Data Submitted by: Date:
Load and Print Data Received by: Date:
GVEA USE ONLY
Notes:
TO MEMBER EQUIPMENT
SERVICE
DISCONNECT
METER
ENCLOSURE
TO GVEA TRANSFORMER
TO GVEA TRANSFORMER
WATER PIPE
GROUND ROD
GROUND RING
BUILDING STEEL
CONCRETE ENCASED ELECTRODE
[AMPS]
Overcurrent Device Rating
Three Phase: DeltaWye
FuseCircuit Breaker
Concrete Encased Electrode:
Overcurrent Device Interrupt Rating [AIC]
Additional Ground Rod if necessary per NEC250.53(A)(2):
Member Name
Service Location
Date
Prepared By
WO #
Service Lateral Conductors (Underground Service)
Number of Conduit Runs
Conduit Size
Conduit Type:
Phase Conductor Size
Neutral Conductor Size
Conductor Length
Conductor Insulation:
RMC IMC
[IN]
HDPE
[AWG]
[AWG]
[FT]
XHHW RHW USE
Grounding Electrode Conductor
Grounding Electrode System (Check all that apply)
Service Entrance Conductors (Overhead Service)
Service Entrance Size
Number of Conduit Runs
Conduit Size
[IN]
IMCRMC
Conduit Type:
Phase Conductor Size
Neutral Conductor Size
Conductor Insulation:
Service Drop Conductor Length
Service Entrance Conductor Length
XHHW
[AWG]
[AWG]
RHW
[FT]
[FT]
Rating
Single Phase:
Overcurrent Device:
[AMPS]
[VOLTS]
Network:
Voltage
Configuration:
Conductor Size
[AWG]
Ground Rod:
Water System:
Building Steel:
Well Casing:
Ground Ring:
Cu Al
Conductor Material:
· For 100A, 200A, and 300A Non-CT Services
· Provide all applicable information with Load Data cover sheet
· Add details for additional equipment as necessary
· Refer to the GVEA "Electrical Service Requirements for Commercial and Multi-Residential Installations"
Booklet and the current NEC for electric service construction requirements
Self-Contained Service One-Line
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc. Page 42
CT CABINET SERVICE
DISCONNECT
METER
ENCLOSURE
Member Name
Service Location
Date
Prepared By
WO #
GROUND RING
BUILDING STEEL
CONCRETE ENCASED ELECTRODE
WATER PIPE
GROUND ROD
TO GVEA TRANSFORMER
[AMPS]
Overcurrent Device Rating
Three Phase: DeltaWye
FuseCircuit Breaker
Overcurrent Device Interrupt Rating [AIC]
Concrete Encased Electrode:
Additional Ground Rod if necessary per NEC250.53(A)(2):
Grounding Electrode System (Check all that apply)
Service Entrance Conductors (Overhead Service)
Service Entrance Size
Number of Conduit Runs
Conduit Size
[IN]
IMCRMC
Conduit Type:
Phase Conductor Size
Neutral Conductor Size
Conductor Insulation:
Service Drop Conductor Length
Service Entrance Conductor Length
XHHW
[AWG]
[AWG]
RHW
[FT]
[FT]
Rating
Single Phase:
Overcurrent Device:
[AMPS]
[VOLTS]
Network:
Voltage
Configuration:
Ground Rod:
Water System:
Building Steel:
Well Casing:
Ground Ring:
Grounding Electrode Conductor
Conductor Size
[AWG]
TO MEMBER
EQUIPMENT
TO GVEA TRANSFORMER
Service Lateral Conductors (Underground Service)
Number of Conduit Runs
Conduit Size
Conduit Type:
Phase Conductor Size
Neutral Conductor Size
Conductor Length
Conductor Insulation:
RMC IMC
[IN]
HDPE
[AWG]
[AWG]
[FT]
XHHW RHW USE
Cu Al
Conductor Material:
CT Service One-Line
· Provide all applicable information with Load Data cover sheet
· Add details for additional equipment as necessary
· Refer to the GVEA "Electrical Service Requirements for Commercial and Multi-Residential Installations"
Booklet and the current NEC for electric service construction requirements
Page 43
REVISED 03/2020
© 2020 Golden Valley Electric Association, Inc.
Member Name
Service Location
Date
Prepared By
WO #
GROUND RING
BUILDING STEEL
CONCRETE ENCASED ELECTRODE
WATER PIPE
GROUND ROD
Concrete Encased Electrode:
Additional Ground Rod if necessary per NEC250.53(A)(2):
Grounding Electrode System (Check all that apply)
Service Entrance Conductors (Overhead Service)
Number of Conduit Runs
Conduit Size
[IN]
IMCRMC
Conduit Type:
Phase Conductor Size
Neutral Conductor Size
Conductor Insulation:
Service Drop Conductor Length
Service Entrance Conductor Length
XHHW
[AWG]
[AWG]
RHW
[FT]
[FT]
Ground Rod:
Water System:
Building Steel:
Well Casing:
Ground Ring:
Grounding Electrode Conductor
Conductor Size
[AWG]
Unit Overcurrent Device Ratings
Delta Wye
FuseCircuit Breaker
TO GVEA TRANSFORMER
TO MEMBER EQUIPMENT
3
5
8
12
4
6
7
Meter 1
Meter 2
Meter 3
Meter 4
Meter 5
Meter 6
Meter 7
Meter 8
Main Service Disconnect Overcurrent Device
(Required for more than six disconnects):
Main Service
Disconnect
Main Service
Disconnect Rating
TO GVEA TRANSFORMER
Overcurrent Device
Interrupt Rating [AIC]
Service Entrance Size
Rating
[AMPS]
[VOLTS]
Voltage
Single Phase: Network:
Three Phase:
Configuration:
Main Service Disconnect
[AMPS]
[AMPS]
[AMPS]
[AMPS]
[AMPS]
[AMPS]
[AMPS]
[AMPS]
[AMPS]
Service Lateral Conductors (Underground Service)
Number of Conduit Runs
Conduit Size
Conduit Type:
Phase Conductor Size
Neutral Conductor Size
Conductor Length
Conductor Insulation:
RMC IMC
[IN]
HDPE
[AWG]
[AWG]
[FT]
XHHW RHW USE
Cu Al
Conductor Material:
Multiple Meter Service One-Line
REVISED 03/2020
· Provide all applicable information with Load Data cover sheet
· Add details for additional equipment as necessary
· Refer to the GVEA "Electrical Service Requirements for Commercial and Multi-Residential Installations"
Booklet and the current NEC for electric service construction requirements
Page 44© 2020 Golden Valley Electric Association, Inc.