electrical room doors and other civil requirements

15
1. Standard requirements for doors 2. Model doors finalized for sonadih 3. Photos of doors from other plants 4. Civil requirements for substation cable cellar room 5. Cable Cut out requirements 6. Anti panic bar details Contents

Upload: sivaramkv

Post on 16-Nov-2014

1.162 views

Category:

Documents


0 download

DESCRIPTION

Requirement of substation building design

TRANSCRIPT

Page 1: Electrical Room Doors and Other Civil Requirements

1. Standard requirements for doors

2. Model doors finalized for sonadih

3. Photos of doors from other plants

4. Civil requirements for substation cable cellar room

5. Cable Cut out requirements

6. Anti panic bar details

Contents

Page 2: Electrical Room Doors and Other Civil Requirements

1. Standards requirement for doors- General

Page 3: Electrical Room Doors and Other Civil Requirements

Extract from Indian Electricity rules – 1956 amended up to 2000.

Hence only metal doors of fire rating – 2 hours are accepted. The same is as per NFPA 70 E new fire guidelines of Lafarge

2. Standards requirement for doors– Specific Electrical

Page 4: Electrical Room Doors and Other Civil Requirements

Specific other requirements

Recommendation – The same should be followed for Jojobera

2. Model doors finalized for Sonadih

Page 5: Electrical Room Doors and Other Civil Requirements

Model – D7 Approved for main entrance for sonadih – Same recommended

Photo – old Now anti panic bar fixed and swing outwards

2. Model doors finalized for Sonadih – Main entrance

Page 6: Electrical Room Doors and Other Civil Requirements

Model – D8a Approved for equipment entrance sonadih – Same recommended

2. Model doors finalized for Sonadih – Equipment entrance

Page 7: Electrical Room Doors and Other Civil Requirements

Transformer room door with a small door for inspection and interlocking – Height to be adjusted according to approved heights- same recommended

2. Model doors finalized for Sonadih – Dist Transformer

Page 8: Electrical Room Doors and Other Civil Requirements

3. Photos of doors – from other plants

Cellar Room door Equipment Entrance door

Main Entrance door

Here all the doors are wooden only metallic doors of 2 hour fire rating are accepted

Page 9: Electrical Room Doors and Other Civil Requirements

Cable cellar with supports where cellar height is >2 meter beam bottom

Advantage – Panel alignment does not depend on civil finishing

4. Civil Requirements for cable cellar rooms

Page 10: Electrical Room Doors and Other Civil Requirements

Cut out extension job – to ensure min 250 mm gap

Requirement – Cut out details should be correctly assessed

5. Cable cut out requirements

Page 11: Electrical Room Doors and Other Civil Requirements

Anti panic bar Inspection on 13.10.2008 at Kolkata – and accepted for Both sonadih and mejia projects

5. Anti panic bar details

Page 12: Electrical Room Doors and Other Civil Requirements

Anti panic bar Inspection on 13.10.2008 at Kolkata

1. One no anti panic bar is brought for inspection at Kolkata.

2. The anti panic bar is of Godrej make which is a reputed concern.

3. The anti-panic bar is also fire rated – 1.5 hour .

4. Party will submit the type test report & equipment wise test report.

5. With conditions 3 & 4 the anti panic bar is approved.

Some photographs are attached in next slides

Page 13: Electrical Room Doors and Other Civil Requirements

Anti panic bar Inspection on 13.10.2008 at Kolkata

Make Godrej – a reputed concern Name plate

Page 14: Electrical Room Doors and Other Civil Requirements

Anti panic bar Inspection on 13.10.2008 at Kolkata

Panic bar – Back side

Panic bar – Front side

Page 15: Electrical Room Doors and Other Civil Requirements

Anti panic bar Inspection on 13.10.2008 at Kolkata

Panic bar – not actuated condition Panic bar – actuated condition