Electric Shock Drowning … The Invisible Killer – Marina Electrical Safety – Part II

Page 2: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

2 2

Overview – Topics to Cover

• What is an Electric Shock Drowning?

• Basics of Marina Electrical Systems and Causes of an Electric

Shock Drowning

• NEC 555.3 – Ground-Fault Protection

• Where can protection be located?

• What can be done to lessen the chances of an Electric Shock

Drowning?

• General Marina Rules

• Ground Fault Circuit Breakers

• Ground Fault Monitoring

• Single Point Monitoring

• Multiple Point Monitoring

• NFPA 303-5.20 – Maintenance of Electrical Wiring and

Equipment

Page 3: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

3 3

Instructor Bio – Michel Rivas

• Product Engineer – Marina Electrical Design

• B.S. in Electrical Engineering

• Concentration in Power Systems and Distribution

• Working with Eaton MP&L for 2 strong years

• Oversees more than 700 electrical designs a year

• Experienced in power pedestals and distribution, and

electrical safety and efficiency

Page 4: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

4 4

Electric Shock Drowning and the Causes

Page 5: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

5 5

What is Electric Shock Drowning?

• Electric Shock Drowning occurs when faulty wiring on a boat or in

a marina causes underwater metals to become energized.

• Examples of underwater metals that could become

energized:

• Boat Props

• Dock Frames

• This creates an electrical field in the water.

• The magnitude and intensity of the electrical field is determined

by how much current is being leaked into the water.

Page 6: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

6 6

What is Electric Shock Drowning?

• A swimmer enters the electrical field and completes the electrical

circuit to ground.

• The swimmer becomes a target for the electrical current

leakage because the human body is a better conductor of

electricity than fresh water

• Fresh water is close to 70 times more resistive than salt

water. This makes electric current leakage in fresh water

marinas a major concern.

• Depending on the amount of current in the water and a

swimmers location relative to the electrical field, a person

may experience effects ranging from a slight tingle, to

complete loss of muscle control, to ventricular fibrillation.

Page 7: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

7 7

Dangers of Electrical Leakage – Freshwater vs. Saltwater

Page 8: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

8 8

Dangers of Electrical Leakage – Freshwater vs. Saltwater

Page 9: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

9 9

Underwater Electrical Field

50mA of Leakage

20mA of Leakage

5mA of Leakage

Page 10: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

10 10

Electric Shock Drowning Medical Facts

• Current

• not Voltage

• Light Bulb

• 100 mA

Current Effects

1 mA to 8 mA Tingle, sensation of shock, not

painful, muscle control not lost

8 mA to 15 mA Painful shock, muscle control

not lost

15 mA to 20 mA Pain shock, muscle control is

lost, paralysis / inability to swim

occurs, labored breathing

50 mA to 100 mA Ventricular Fibrillation possible

100 mA to 200 mA Ventricular Fibrillation occurs

200+ mA Burn marks may appear, chest

muscles clamp heart

Page 11: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

11 11

Basics of the Electrical System

Line 1 (Black) – current carrying conductor

Line 2 (Red) – current carrying conductor

Neutral (White) – returns current to complete circuit

Ground (Green) – offers current another path to

complete circuit if short or overload occurs

Page 12: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

12 12

Basics of the Electrical System

Page 13: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

13 13

Perfect Electrical Circuit

• Example:

• 30 amps out on

line to the

receptacle

• 29.5 amps

returned via the

neutral

• Grounding

conductor picks

up the remaining

0.5 amps before

it can leak into

the water

Page 14: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

14 14

Inadequate Electrical Circuit

• Example:

• 30 amps out on

line to the

receptacle

• 29.0 amps

returned via the

neutral

• Faulty ground only

picks up 0.5

amps

• 0.5 amps are leaked

into water,

presenting a

potential problem.

Page 15: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

15 15

Brief Review – Two Keys to Remember

• Two things are required for Electric

Shock Drowning:

1. An electrical fault to ground – either

in the marina or on a boat

2. An incomplete circuit caused by a

faulty or nonexistent circuit

back to the dock’s grounding

system.

Page 16: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

16 16

NEC 555.3 – Ground-Fault Protection

Page 17: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

17 17

NEC 555.3 – Ground Fault Protection

• New to the 2011 National Electrical Code

• “The main overcurrent protective device that feeds the marina

shall have ground fault protection not exceeding 100mA.

Ground-protection of each individual circuit breaker or

feeder circuit shall be permitted as a suitable alternative.”

• Overcurrent protection device – the device that disrupts power

to a circuit or piece of electrical equipment in the event of

an electrical problem. Examples include circuit breakers

and fuses. Circuit breakers are the most common form of

ground-fault protection devices.

• There is a similar code that applies to floating buildings also

requiring no less than 100mA protection for floating

buildings – NEC 553.4.

Page 18: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

18 18

Where can 100mA Ground-Fault Protection be Located?

Page 19: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

19 19

Protection at the Utility Entrance

• Circuit breaker protection

can be located where

the incoming power

enters the facility from

the utility company.

• While this is a very

economical solution,

it may be difficult to

pinpoint the exact

cause or causes of

the current leakage.

• Leakage grouping will

also be a drawback

for this solution.

Page 20: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

20 20

Protection at the Head of Each Dock

• Circuit breaker protection can be

located at the head of each

dock within a disconnect or

distribution panel.

• Comparatively, this is also an

economical solution.

• Identifying the cause or causes of

the leakage depends on how

the system is wired.

• The effects of leakage grouping will

depend on the number of

boats powered by each piece

of equipment.

Page 21: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

21 21

Protection on Each Dock

• Circuit breaker protection can be

located on each dock within a

distribution panel or through a

ground fault monitoring

system with shunt trip circuit

breakers.

• While this is a more costly solution, it

is relatively easy to identify

the cause or causes of the

leakage.

• The effects of leakage grouping will

again depend on the number

of boats powered by each

piece of equipment.

Page 22: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

22 22

Protection in Each Power Pedestal

• Circuit breaker protection can be

located in each power

pedestal through ground-fault

circuit breakers.

• This is a very costly solution, but is

very easy to identify the

cause of current leakage. If

the circuit breaker trips, the

boat or piece of equipment

plugged in is experiencing a

problem.

• Leakage grouping is mitigated

with this solution as each

circuit breaker is monitored

individually.

Page 23: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

24 24

Leakage Grouping

Page 24: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

25 25

Leakage Grouping - Example

BOAT A

4mA

LEAKAGE

BOAT B

5mA

LEAKAGE

BOAT C

6mA

LEAKAGE

Page 25: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

26 26

15mA of Current Produced by the Three Boats

Current Effects

1 mA to 8 mA Tingle, sensation of shock, not

painful, muscle control not lost

8 mA to 15 mA Painful shock, muscle control

not lost

15 mA to 20 mA Pain shock, muscle control is

lost, paralysis / inability to swim

occurs, labored breathing

50 mA to 100 mA Ventricular Fibrillation possible

100 mA to 200 mA Ventricular Fibrillation occurs

200+ mA Burn marks may appear, chest

muscles clamp heart

Page 26: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

27 27

Loop Feed System

Multiple pedestals looped together on a single circuit

Page 27: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

28 28

Loop Feed System (cont.)

Design Characteristic Effect of Wiring Method

Number of Vessels or

Equipment on Each Circuit

High – multiple vessels of pieces

of equipment are looped together

on one circuit.

Leakage Grouping Effect High – more devices powered by

a single circuit produce a high

likelihood of leakage grouping.

Ease of Detecting the

Cause or Causes of

Leakage Sources

Difficult – pinpointing the device

or devices producing the leakage

can be problematic due to the

number of devices on each

circuit.

Page 28: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

29 29

“Homerun” System

L1 N L2 G

(A) (N) (B) (G)

L1 N L2 G

(A) (N) (B) (G)

LINE 1

LINE 2

CIRCUIT BREAKERIN DISTRIBUTION

PANEL

LINE 1

LINE 2

CIRCUIT BREAKERIN DISTRIBUTION

PANEL

TYPICAL "HOMERUN" WIRING SYSTEM - THREE PEDESTALS

L1 N L2 G

(A) (N) (B) (G)

PEDESTAL #1 PEDESTAL #2 PEDESTAL #3

LINE 1

LINE 2

CIRCUIT BREAKERIN DISTRIBUTION

PANEL

Individual circuit for each boat.

Most common in areas that

require on-shore meter reading

Page 29: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

30 30

“Homerun System” (cont.)

Design Characteristic Effect of Wiring Method

Number of Vessels or

Equipment on Each Circuit

Low – each boat or piece of

equipment is on an individual

circuit.

Leakage Grouping Effect Low - each device is powered by

a single circuit breaker.

Ease of Detecting the

Cause or Causes of

Leakage Sources

Easy – if a circuit breaker trips,

the piece of equipment it is

protecting is experiencing a

problem.

Page 30: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

31 31

What Can Be Done to Lessen the Chances of an Electrical Shock Drowning?

Page 31: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

32 32

General Rules – No Swimming in the Marina

• Do not allow swimming in your marina.

• Post signs prohibiting swimming in the marina.

Page 32: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

33 33

General Rules – Designated In-Water Work Times

• Set aside a window of time where people can work on boats in

the water when the electricity will be turned off.

• Post dates and / or times.

• Inform customers and workers no power will be available on the

docks.

• Customers need to be aware their power will be turned off

during these “working windows.”

• Contractors will need to be aware that no electricity will be

available for power tools.

Page 33: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

34 34

General Rules – Electrical Work

• Electrical work should only be completed by certified electricians.

• Marina work should comply with all NEC and NFPA codes.

• Routine maintenance and inspections should be performed

at least annually per NFPA 5.20 “Maintenance of Electrical

Wiring and Equipment.”

• Document inspections and maintenance for liability

purposes.

• Boat owners should have all electrical work completed by

ABYC certified electricians.

• Boat owners should also document inspections and

maintenance for liability purposes.

Page 34: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

35 35

Equipment – Ground Fault Circuit Breakers

• Installing ground fault circuit breakers in all pedestals can be

expensive and lead to “customer renovations.”

• “Nuisance tripping” can occur.

• Customer renovations – customers frustrated by circuit

breakers that constantly trip bypass protection devices.

• It is important to educate boat owners of the potential

hazards associated with work performed by untrained

professionals.

• Nuisance tripping – common phrase used by customers to

deflect blame for faulty boat wiring and / or repairs.

• If a circuit breaker is in good working condition and trips,

there is a problem present.

Page 35: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

36 36

Equipment – Ground Fault Circuit Breakers

• Different Types of Ground Fault Circuit Breakers

• 5mA – People Protection

• 30mA – Equipment Protection

• REMINDER: Current NEC Code requires 100mA protection

somewhere within the electrical system for all new

installations.

• REMINDER: 15mA can cause serious injury

Current Effects

15 mA to 20 mA Pain shock, muscle control is

lost, paralysis / inability to swim

occurs, labored breathing

Page 36: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

38 38

Equipment – Ground Fault Monitors

• Install a ground fault monitoring system in the marina.

• Usually consist of a control module and current transformer(s).

• Wires are run through the current transformer(s) and the

electrical cycle is measured.

• Multiple models

• Single Source Monitoring

• One monitor for one major power source

• Multiple Source Monitoring

• One monitor for multiple power sources

Page 37: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

39 39

Ground Fault Monitors

Page 38: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

40 40

Ground Fault Monitors – Integral CT Model

Page 39: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

41 41

Ground Fault Monitors – Single Source Monitoring

Page 40: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

42 42

Ground Fault Monitors – Single Source Monitoring

Design Characteristic Effect of Monitoring Method

Cost Low – Single CT units are

relatively inexpensive and can be

added to existing equipment.

Leakage Grouping Effect High – more devices monitored

by a single CT produce a high

likelihood of leakage grouping.

Ease of Detecting the

Cause or Causes of

Leakage Sources

Difficult – pinpointing the device

or devices producing the leakage

can be problematic due to the

number of devices on one

monitor

Page 41: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

43 43

Ground Fault Monitors – Multiple Source Monitoring

Page 42: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

44 44

Ground Fault Monitors – Multiple Source Monitoring

Design Characteristic Effect of Monitoring Method

Cost High – Multiple CT units can be

expensive due to the number of

CTs required for monitoring.

Leakage Grouping Effect

Low - each circuit is monitored by

a single CT. Fewer vessels

monitored on one CT limits the

grouping effect.

Ease of Detecting the

Cause or Causes of

Leakage Sources

Easy – if an alarm is triggered,

the piece of equipment it is

monitoring is experiencing a

problem.

Page 43: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

45 45

First Aid for Electric Shock Victims

• If possible turn off all power sources that may come in contact

with the water. Area should be deemed safe before any

action is taken.

• Extreme caution should be taken when removing victim from the

water.

• Call 911 immediately

• Begin artificial ventilation - victim with pulse, but not breathing

• OR

• CPR - victim without pulse and not breathing

• use (AED) Artificial Electrical Defibrillator if available

Page 44: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

46 46

Signs of Electric Shock Drowning or Potential for Electrical Shock Drowning

• Often leaves no bodily clues to suggest anything but “simple

drowning” due to alcohol intoxication or heart attack.

• No signs of burning due to the victim being submerged in

water – no signs of electrocution.

• Often classified as electrical shock due to “evidence of great

distress, multiple deaths…”

• Signs of a Potential Problem:

• Tingling sensation reported by anyone swimming in the

marina.

• Excessive damage to metal boat parts in the water – props,

etc…

Page 45: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

47 47

NFPA 303-5.20 – Maintenance of Electrical Wiring and

Equipment

Page 46: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

48 48

NFPA 303-5.20 – Maintenance of Electrical Wiring and

Equipment

• “An inspection of all electrical wiring,

ground connections, conduit,

hangers, supports, connections,

outlets, appliances, devices, and

portable cables installed or used in a

marina, boatyard, boat basin, or similar

establishment shall be made at regular

intervals to ensure a complete inspection

at least annually.”

Page 47: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

49 49

NFPA 303-5.20 – Maintenance of Electrical Wiring and

Equipment (cont.)

• “The inspection required in 5.20.1 shall

include a test of the ground integrity

and polarity.”

• “The use of grounding-type portable electrical

equipment that is not properly and

adequately grounded” shall be identified

and removed from use or repaired.

Page 48: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

50 50

Inspections – Signs of Potential Problems

Page 49: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

51 51

Inspections – Signs of Potential Problems

Page 50: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

52 52

Inspections – Signs of Potential Problems

Page 51: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

53 53

Inspections – Signs of Potential Problems

Page 52: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

54 54

Inspections – Signs of Potential Problems

Page 53: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

55 55

Inspections – Signs of Potential Problems

Page 54: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

56 56

Inspections – Signs of Potential Problems

Page 55: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

57 57

Inspections – Signs of Potential Problems

Page 56: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

58 58

Inspections – Signs of Potential Problems

Page 57: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

59 59

Inspections – Signs of Potential Problems

Page 58: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

60 60

Inspections – Signs of Potential Problems

Page 59: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

61 61

Inspections – Signs of Potential Problems

Page 60: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

62 62

Inspections – Signs of Potential Problems

Page 61: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

63 63

Inspections – Signs of Potential Problems

Page 62: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

64 64

Inspections – Signs of Potential Problems

Page 63: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

65 65

Inspections – Signs of Potential Problems

Page 64: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

66 66

Inspections – Signs of Potential Problems

Page 65: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

67 67

Inspections – Signs of Potential Problems

Page 66: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

68 68

Inspections – Signs of Potential Problems

Page 67: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

69 69

Inspections – Signs of Potential Problems

Page 68: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

70 70

Inspections – Signs of Potential Problems

Page 69: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

71 71

Inspections – Signs of Potential Problems

Page 70: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

72 72

Inspections – Signs of Potential Problems

Page 71: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

73 73

Inspections – Signs of Potential Problems

Page 72: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

74 74

Inspections – Signs of Potential Problems

Page 73: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

75 75

Inspections – Signs of Potential Problems

Page 74: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

76 76

Inspections – Signs of Potential Problems

Page 75: Electric Shock Drowning … The Invisible Killer Marina ...cdnmedia.endeavorsuite.com/images/organizations... · Killer – Marina Electrical Safety – Part II . 2 2 Overview –

77 77

Review

Michel Rivas

Eaton – Marina Power & Lighting

(757) 258-6324 Phone

(757) 258-8805 Fax

[email protected]

www.marinapower.com