electric power generation and excitation system

Upload: mansen-nsubuga

Post on 07-Apr-2018

224 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/6/2019 Electric Power Generation and Excitation System

    1/20

    CHAPTER THREE:

    ELECTRIC POWER GENERATION AND THE EXCITATION

    SYSTEM

    2.1 Introduction

    The relationship between magnetism and electrical current was discovered and

    documented by Oerstad in 1819. He found that if an electric current was caused to flow

    through a conductor that a magnetic field was produced around that conductor.

    In 1831, Michael Faraday discovered that if a conductor is moved through a magnetic

    field, an electrical voltage is induced in the conductor.

    The magnitude of this generated voltage is directly proportional to the strength of the

    magnetic field and the rate at which the conductor crosses the magnetic field. The

    induced voltage has a polarity that will oppose the change causing the induction

    Lenzs law.

    This natural phenomenon is known as Generator Action and is described today by

    Faradays Law of Electro Magnetic Induction:

    Vind = /t, where Vind = induced voltage, = change in flux density,

    t = change in time All rotary generators built today use the basic principles of

    Generator Action.

  • 8/6/2019 Electric Power Generation and Excitation System

    2/20

    2.2.0 THE BASIC GENERATOR

    2.2.1 The Elementary Ac Generator

    The elementary ac generator consists of a conductor (or loop of wire) in a magnetic field

    (usually produced by an electromagnet). The two ends of the loop are connected to slip

    rings and they are in contact with two brushes.

    When the loop rotates it cuts magnetic lines of force, first in one direction and then the

    other.

    In the first half turn of rotation, a positive current is produced and in the second half of

    rotation produces a negative current. This completes one cycle of ac generation.

  • 8/6/2019 Electric Power Generation and Excitation System

    3/20

    2.2.2 Development of the Sine Wave

    At the instant the loop is in the vertical position, the loop sides are moving parallel to

    the field and do not cut magnetic lines of force.

    In this instant, there is no voltage induced in the loop. As the loop rotates, sides will cut

    the magnetic lines of force inducing voltage in the loop.

    When the loop is in the horizontal position, maximum voltage is induced. The rotation

    of the coil through 360 degrees results in an ac sine wave output

    2.2.3 Three Phase Voltage

    Three phase voltage is developed using the same principles as the development of

    single phase voltage.

    Three (3) coils are required positioned 120 electrical degrees apart.

  • 8/6/2019 Electric Power Generation and Excitation System

    4/20

    A rotating magnetic field induces voltage in the coils which when aggregated produce

    the familiar three phase voltage pattern.

    2.3.0 TYPES OF GENERATORS

    Essentially, there are two basic types of generators:

    - Asynchronous (Induction) generators

    - Synchronous generators

    2.3.1 Induction Generators

    The induction generator is nothing more than an induction motor driven above its

    synchronous speed by an amount not exceeding the full load slip the unit would have as

    a motor.

  • 8/6/2019 Electric Power Generation and Excitation System

    5/20

    Assuming a full load slip of 3%, a motor with a synchronous speed of 1200 rpm would

    have a full load speed of 1164 rpm. This unit could also be driven by an external prime

    mover at 1236 rpm for use as an induction generator.

    The induction generator requires one additional item before it can produce power it

    requires a source of leading VARs for excitation. The VARs may be supplied by

    capacitors (this requires complex control) or from the utility grid.

    Induction generators are inexpensive and simple machines, however, they offer little

    control over their output. The induction generator requires no separate DC excitation,

    regulator controls, frequency control or governor.

    2.3.2 Synchronous Generators

    Synchronous generators are used because they offer precise control of voltage,

    frequency, VARs and WATTs.

    This control is achieved through the use of voltage regulators and governors.

    A synchronous machine consists of a stationary armature winding (stator) with many

    wires connected in series or parallel to obtain the desired terminal voltage.

    The armature winding is placed into a slotted laminated steel core. A synchronousmachine also consists of a revolving DC field - the rotor.

    A mutual flux developed across the air gap between the rotor and stator causes the

    interaction necessary to produce an EMF. As the magnetic flux developed by the DC

    field poles crosses the air gap of the stator windings, a sinusoidal voltage is developed

    at the generator output terminals. This process is called electromagnetic induction.

    The magnitude of the AC voltage generated is controlled by the amount of DC exciting

    current supplied to the field.

    If FIXED excitation were applied, the voltage magnitude would be controlled by the

    speed of the rotor (E=4.44fnBA), however, this would necessitate a changing frequency!

  • 8/6/2019 Electric Power Generation and Excitation System

    6/20

    Since the frequency component of the power system is to be held constant, solid state

    voltage regulators or static exciters are commonly used to control the field current and

    thereby accurately control generator terminal voltage.

    The frequency of the voltage developed by the generator depends on the speed of the

    rotor and the number of field poles. For a 60 Hz system, Frequency = speed(rpm)*pole

    pairs/60.

    The synchronous generator units at Nalubaale power station

    2.4.0 GENERATOR PARTS AND FUNCTIONS

    Generator Frame: Provides the structural strength and rigidity for the generator and

    serves as a housing to guide cooling air flow

    Inner End Shield: Is a baffle used to form a path for cooled air

    Generator Fan: Provides continuous circulation of cooling air

    Rotating Field: A magnetic field which induces AC voltage in the stator windings

    Collector Rings: Provide a connection and path for DC power into the rotating field

    windings

  • 8/6/2019 Electric Power Generation and Excitation System

    7/20

    Main Coupling: Is the connection to the drive shaft Generator Coolers: Remove heat

    from the generator cooling air

    Stator Core: Houses the stationary windings and forms a magnetic path necessary for

    induced voltages

    Air Gap: Is the radial clearance between the rotating field and the stator core

    Stator Coil End Turns: Formed when coils leave one slot in a stator core and are returned

    to a different slot

    Terminal Leads: Serve to conduct the three phase voltage and current flow from the

    generator stator to the external system

    An out put stator terminal for one phase

  • 8/6/2019 Electric Power Generation and Excitation System

    8/20

    2.5.0 THE EXCITATION SYSTEM

    In power plant excitation systems has a powerful impact on generator dynamic

    performance and availability, it ensures quality of generator voltage and reactive power,

    i.e. quality of power plant delivered energy to consumers.

    Main functions of the excitation system are to provide variable DC current with short-

    time overload capability, controlling terminal voltage with suitable accuracy, ensurestable operation with network and/or other machines, contribution to transient stability

    subsequent to a fault, communicate with the power plant control system and to keep

    machine within permissible operating range.

  • 8/6/2019 Electric Power Generation and Excitation System

    9/20

    2.5.1.0 Types of Excitation Systems

    Brushless excitation systemsWith rotating exciter machines and Automatic Voltage Regulator (AVR).

    Static excitation systems (SES)This involves feeding rotor directly from thyristor bridges via brushes.

    Among the above types of exciters, Static excitation system plays a very important role

    in modern interconnected power system operation due to its fast acting, good response

    in voltage & reactive power control and satisfactory steady state stability condition.

    For the machines 500 MW & above and fire hazards areas, Brushless Excitation System is

    preferred due to larger requirement of current & plant safety respectively.

    2.5.1.1 Static Excitation System

    In order to maintain system stability in interconnected system network it is necessary to

    have fast acting excitation system for large synchronous machines which means the field

    current must be adjusted extremely fast to the changing operational conditions.

    Besides maintaining the field current and steady state stability the excitation system is

    required to extend the stability limits. It is because of these reasons the static excitation

    system is preferred to conventional excitation systems.

    In this system, the AC power is tapped off from the generator terminal stepped down

    and rectified by fully controlled thyristor Bridges and then fed to the generator field

    thereby controlling the generator voltage output. A high control speed is achieved by

    using an internal free control and power electronic system. Any deviation in the

    generator terminal voltage is sensed by an error detector and causes the voltage

    regulator to advance or retard the firing angle of the thyristors thereby controlling the

    field excitation of the alternator.

    This equipment controls the generator terminal voltage, and hence the reactive load

    flow by adjusting the excitation current. The rotating exciter is dispensed with and

    Transformer & silicon controlled rectifiers (SCRS) are used which directly feed the field

    of the Alternator.

  • 8/6/2019 Electric Power Generation and Excitation System

    10/20

    Static exciter panel

    2.5.1.2 Description of Static Excitation System

    Static Excitation Equipment Consist of;

    i. Excitation (Rectifier) TransformerThe excitation power is taken from generator output and fed through the excitation

    (rectifier) transformer which steps down to the required voltage, for the SCR bridge and

    then fed through the field breaker to the generator field. The rectifier transformer used

    in the SEE should have high reliability as failure of this will cause shutdown of nit/power

    station.

    Dry type cast coil transformer is suitable for static excitation applications. The

    transformer is selected such that it supplies rated excitation current at rated voltage

    continuously and is capable of supplying ceiling current at the ceiling excitation for a

    short period of ten seconds.

    Rectifier transformers directly connected to the generator terminals and feeding power

    to the field of the machine via thyristor converters, plays an important role in an

    excitation system and in turn power generation Reliability of this transformer has to be

    ensured in all respects. The selection of the secondary voltage of excitation transformer

    depends upon the field forcing voltage. The primary voltage is the same as that of

    generator terminal voltage.

  • 8/6/2019 Electric Power Generation and Excitation System

    11/20

    Current rating is dependant on the maximum continuous current in the field winding.

    Generally the power rating of the Excitation transformer used in Static Excitation System

    is around 1 % of the rating of generator in MVA.

    These transformers are of class "F" insulation and indoor type. The cooling method of

    the autotransformer is Air Natural (AN).

    Excitation transformer

    ii. SCR Output stageThe SCR output stage consists of a suitable number of bridges connected in parallel.

    Each thyristor bridge comprises of six thyristors, working as a six pulse fully controlled

    bridge. Current carrying capacity of each bridge depends on the rating of individual

    thyristor. Thyristors are designed such that their junction temperature rise is well within

    its specified rating. By changing the firing angle of the thyristors variable output is

    obtained. Each bridge is controlled by one final pulse stage and is cooled by a fan.

    These bridges are equipped with protection devices and failure of one bridge causes

    alarm. If there is a failure of one more thyristor bridges then the excitation current will

    be limited to a predetermined value lesser than the normal current. However, failure of

    the third, bridge results in tripping and rapid de-excitation of the generator. The above

    is applicable for 4 bridges thyristor with (n-1) principle operation.

  • 8/6/2019 Electric Power Generation and Excitation System

    12/20

    The thyristor bridge or power converter

    iii. Excitation Start Up and Field Discharge EquipmentFor the initial build-up of the generator voltage, field-flashing equipment is required.

    The rating of this equipment depends on the no-load excitation requirement and field

    time constant of the generator. From the reliability point of view, provisions for both

    the AC & DC field flashing are provided.

    The field breaker is selected such that it carries the full load excitation current

    continuously and also it breaks the max. field current when the three phase short circuit

    occurs at the generator terminals.

    The field discharge resistor is normally of non-linear type for medium and large capacity

    machines i.e. voltage dependent resistor.

  • 8/6/2019 Electric Power Generation and Excitation System

    13/20

    To protect the field winding of the generator against over voltages, an over voltage

    protection along with a current limiting resistor is used to limit the over voltage across

    the field winding. The OVP operates on the insulation break over Principle. The voltage

    level at which OVP should operate is selected based on insulation level of field winding

    of the generator.

    Field Discharge

    During load condition whenever the Field breaker, opens suddenly there will be a surge

    voltage in the rotor which will damage the rotor winding insulation. To avoid this rotor

    winding is connected to the earth through field discharge Resistor thereby by passing

    the surge voltage to earth and limiting the current to earth. Field discharge greatly

    helps to limit the damages. 'Non-linear field discharge resistance is used which helps in

    faster field suppression/discharge.

    The field discharge resistor

  • 8/6/2019 Electric Power Generation and Excitation System

    14/20

    iv. Regulator & Operational Control Circuits (Control Electronics)Regulator is the heart of the system. This regulates the generator voltage by controlling

    the firing pulses to the thyristors.

    Error detector & amplifierThe Generator terminal voltage is stepped down by a three phase PT. and fed to the

    AVR. The a.c. input thus obtained is rectified, filtered and compared against a highly

    stabilized reference value and the difference is amplified in different stages of

    amplification.

    The AVR is designed with highly stable elements so that variation in ambient

    temperature does not cause any drift or change in the output level. Three CTs sensing

    the output current of the generator feed proportional current across variable resistors in

    the AVR. The voltage thus obtained across the resistors, can be added vectorially eitherfor compounding or for transformer drop compensation. The percentage of

    compensation can be adjusted as the resistors are of variable type.

    Grid - control unitThe output of the AVR is fed to a grid control unit, it gets its synchronous a.c. reference

    through a filter circuit and generates six double, pulses spaced 600 electrical apart

    whose position depends on the output of the AVR, i.e. the pulse position varies

    continuously as a function of the control voltage. Two relays are provided, by energizing

    which, the pulses can be either blocked completely or shifted to inverter mode of

    operation

    Pulse - amplifierThe pulse output of the ""Grid control unit "' is amplified further at an intermediate

    stage amplification. This is also known as pulse intermediate stage. The unit has a d.c.

    power supply, which operates from a three phase 38OV supply and delivers

    +15V,1 l5V,+5V, and a coarse stabilized voltage VL. A built in relay is provided which

    can be used for blocking the 6 pulse channels. In a two channel system (like Auto and

    Manual), the change over is effected by energising/ de-energizing the relay.

    Pulse final stageThis unit receives input pulses from the pulse amplifier and transmits them through

    pulse transformers to the gates of the thyristors. A built in power supply provides the

    required d.c. supply to the final pulse and amplifier. Each Thyristor bridge has its own

  • 8/6/2019 Electric Power Generation and Excitation System

    15/20

    final pulse stage. Therefore, even if a thyristor bridge fails with its final pulse stage, the

    remaining thyristors bridges can continue to cater to full load requirement of the

    machine and thereby ensure (n-1) operation.

    Manual control channelA separate manual control channel is provided where the controlling d.c. signal in taken

    from a stabilized d.c. voltage through a motor operated potentiometer. The d.c. signal

    is fed to a separate grid control unit whose output pulses after being amplified at an

    intermediate stage can be fed to the final pulse stage. When one channel is working,

    generating the required pulses, the other remains blocked. Therefore a changeover from

    ""Auto" to "Manual' control or vice versa is effected by blocking or releasing the pulses

    of the corresponding intermediate stage.

    "A pulse supervision unit detects spurious pulses or loss of pulses at the pulses bus bar

    and transfers control from Automatic Channel to manual channel.

    Follow-up unitTo ensure a smooth changeover from 'Auto"' to Manual" control, it is necessary that the

    position of the pulses on both channels should be identical. A pulse comparison unit

    detects any difference in the position of the pulses and with the help of a follow-

    up unit actuates the motor operated potentiometer on the "'Manual"' Channel to turn in

    a direction so as to eliminate the difference.

    However, while transferring control from "Manual"' to "Auto" mode any difference in thetwo control levels can be visually checked on a balance meter and adjusted to obtain

    null before change over.

    Limit controllersWhen a generator is running in parallel with the power network, it is essential to

    maintain it in sychronism without exceeding the rating of the machine and also without

    the protection system tripping. Only automatic Regulator cannot ensure this. It is

    necessary to influence the voltage regulator by suitable means to limit the over

    excitation and under excitation. This not only improves the security of the paralleloperation but makes operation of the system easier. However limiters do not replace

    the protection system but only prevent the protection system from tripping

    unnecessarily under extreme transient conditions.

    The AVR also has a built-in frequency dependent circuit so that when the machine is

    running below the rated frequency from the regulated voltage should be proportional

  • 8/6/2019 Electric Power Generation and Excitation System

    16/20

    to frequency. With the help of a potentiometer provided in the AVR, the circuit can be

    made to respond proportionally to voltage above a certain frequency and proportional

    to a voltage below the certain frequency. The range of adjustment of this cut off

    frequency lies between 40 and 60 Hz.

    The static excitation system is equipped with three limiters which act in conjunction with

    the AVR. These limiters are as under;

    -Rotor current limiter

    The unit basically comprises an actual value converter a limiter with adjustable PID

    characteristics a reference value; dv/dt sensor and a signalisation unit. The field current

    is measured on the a.c. input side of the thyristor converter and is converted into

    proportional d.c. voitages. The signal is compared with an adjustable reference value,

    amplified, and with necessary time lapse fed to the voltage regulator input.Rotor current limiter avoids thermal overloading of the rotor winding and is provided to

    protect the generator rotor against excessively long duration over loads. The ceiling

    excitation is limited to a predetermined limit and is allowed to flow for a time which is

    dependant upon the rate of rise of field current before being limited to the thermal limit

    value.

    -Rotor angle limiter

    This unit limits the angle between the voltage of the network centre and the rotor

    voltage or it limits the angle between the generator voltage and the rotor voltage. Itcomprises an actual value converter, a limiting amplifier with adjustable PID

    characteristics and a reference value unit. The limiting regulator operates as soon as the

    d.c. value exceeds the reference value. For its operation the Unit is given separate power

    supply from a d.c. power pack.

    It generates a d.c. signal proportional to the load or rotor angle from the stator current

    and voltage by means of a simple analog circuit. The device takes over as soon as the

    set limit angle is exceeded. By increasing the excitation and ignoring opposite control

    signals the unit is prevented from failing out of step.

    -Stator current limiter

    This unit functions in conjunction with an integrator unit which provides the necessary

    dead time and the gradient, which can be adjusted by potentiometers. The regulator

    consists essentially of a measuring converter, two comparators, two PID regulators and a

    d.c. power pack. A discriminator in the circuit differentiates between inductive and

  • 8/6/2019 Electric Power Generation and Excitation System

    17/20

    capacitive current. The positive and negative signals processed by two separate

    amplifiers are brought to the output stage and only that output which has to take care

    of the limitation is made effective.

    Stator current limiter avoids thermal over loading of the stator windings. Stator current

    limiter is provided to protect the generator against long duration of large statorcurrents. For excessive inductive current it acts over the AVR after a certain time lag and

    decreases the excitation current to limit the inductive current to the limit value. But for

    excessive capacitive current it acts on the AVR without time delay to increase the

    Excitation and thereby reduce the capacitive loading. This is necessary as there is a risk

    for the machine failing out of step during under excited mode of operation.

    -Slip stabilizing units

    The slip stabilizing unit is used for the suppression of rotor oscillations of the alternator

    through the additional influence of excitation. The slip as well as acceleration signals

    needed for the stabilization are derived from active power delivered by the alternator.

    Both the signals, which are correspondingly amplified and summed up, influence

    the excitation of the synchronous machine through AVR in a manner as to suppress the

    Rotor oscillations.

    2.5.1.3 Merit of Static Excitation System

    Performance

    1) Faster Response in voltage & Reactive Power Control

    2) Higher Accuracies of Voltage control

    3) Faster discharge of field energy with inversion of thyristor bridge output

    4) Provision of limiters & stabilizing equipment help to improve dynamic & transient

    stability

    5) Largely independent of variation in the excitation supply voltage & frequency

    Operational Maintenance

    1) Redundancies in different Circuits increase reliability and availability

    2) Adequate monitoring facilities aid fault finding & reduce down time

  • 8/6/2019 Electric Power Generation and Excitation System

    18/20

    3) Absence of rotating parts enables less maintenance

    4) Lower SCR value for larger generators (Reduces weight/compact in size & cost)

    General

    1) Up rating of the machine can be done by adding additional power circuits/adding

    more redundancies

    2) Location of the equipment can be planned independent of the machine

    thereby increasing the flexibility in the plant layout

    3) Retrofitting of Static Excitation Equipment for old slow acting exciter

    4) Length of the machine shorter when compare to other excitation equipment

    2.5.1.4 Power Supply

    The voltage regulating equipment needs an a.c. supply 38OV 3 Phase for its power

    supply units which is derived from the secondary side of the rectifier transformer

    through an auxiliary transformer. This voltage is reduced to different levels required for

    the power packs by means of multi-winding transformers.

    A separate transformer supplies the synchronous voltage 3x38OV for the filter circuit ofeach channel and the voltage relay. During testing and pre-commissioning activities

    when generator voltage is not available, the station auxiliary supply 3 Phase 415V can be

    temporarily connected through an. auxiliary step down transformer for testing purpose

    with the help of a regulator test/service switch.

    The supply for the, thyristor Bridge fan is taken from an independent transformer which

    gets it input supply from the secondary of the excitation transformer. The control &

    protection relays need 48V & 24VDC which are delivered from the station battery by

    means of the DC/DC converters, which are internally protected against overload.

  • 8/6/2019 Electric Power Generation and Excitation System

    19/20

    2.5.1.5 PROTECTIONS

    The following protections are provided in the Static Excitation Equipment;

    1) Rectifier transformer over current instantaneous and delayed.

    2) Rectifier transformer over Temperature

    3) Rotor Over-Voltage

    4) Rotor earth fault.

    5) Fuse failure monitoring circuit for thyristors

    6) Loss of control voltage (48V & 24V)

    7) dv/dt protection of SCR by snubber net works

    8) Cooling System failure for thyristors

  • 8/6/2019 Electric Power Generation and Excitation System

    20/20