www.tridonic.com 1Subject to change without notice.
Data sheet 02/13-881-3
FL ballastsElectronic dimming
Product description
•Processor-controlledballastwithyinside
•HighestpossibleenergyclassCELMAEEI=A1BAT1
•Noise-freeprecisecontrolviaDALIor
DSIsignal,switchDIMorcorridorFUNCTION
•OEM-specificreservedmemoryareas
•ExtendedDALIcommands
•5-yearguarantee
Interfaces
•DALI
•DSI
•switchDIM(withmemoryfunction+selectabledimmingrate)
•corridorFUNCTION(individuallyprogrammable)
Functions
• IntelligentTemperatureGuard(overtemperatureprotection)
• IntelligentVoltageGuard(overvoltageindication
andundervoltageshutdown)
•Optimumfilamentheatinginanydimmersetting
•Disconnectionoffilamentheatingfromadimminglevelofapprox.
90%formaximumenergyefficiency(SMART-Heatingconcept)
•Faderatesbetween50msand90s(min.–max.)
•AutomaticallytriggeredemergencylightingvalueinDCmode,
canbesetbetween1and100%
•ForemergencylightingsystemsasperEN50172
•Automaticstartafterreplacementofdefectivelamps
•Automaticshutdownifthelampisfaulty
•DimmingpossibleinDCmode
•Backwardscompatible
ÈStandards,page3
Wiring diagrams and installation examples,page6
PCA T8 EXCEL one4all lp Y, 36 – 58 WEXCELT8
T8
side fixing features
Technical dataMainsvoltagerange 220–240V
ACvoltagerange 198–264V
DCvoltagerange 176–280V(lampstart≥198VDC)
Mainsfrequency 0/50/60Hz
Overvoltageprotection 320VAC,1h
Typ.powerinputonstandby <0.5W
Protectivehotrestart 0.5sforAC/0.2sforDC
Dimmingrange 1–100%
Lampstartpossiblefrom 1%
Operatingfrequency ~40–100kHz
Typeofprotection IP20
Ordering data
Type Article number Packaging,carton
Packaging,pallet
Weightperpcs.
For luminaires with 1 lamp
PCA 1x36 T8 EXCEL one4all lp Y 22176239 10pc./pcs. 760pc./pcs. 0.244kg
PCA 1x58 T8 EXCEL one4all lp Y 22176235 10pc./pcs. 760pc./pcs. 0.263kg
For luminaires with 2 lamps
PCA 2x36 T8 EXCEL one4all lp Y 22176240 10pc./pcs. 760pc./pcs. 0.277kg
PCA 2x58 T8 EXCEL one4all lp Y 22176237 10pc./pcs. 640pc./pcs. 0.333kgPHASED OUT
www.tridonic.com 2Subject to change without notice.
Data sheet 02/13-881-3
FL ballastsElectronic dimming
Specific technical dataLampwattage
Lamptype
Type Articlenumber
DimensionsLxWxH
HolespacingD
Lamppower2
Circuitpower2
EEI Currentat50Hz230V2
λat50Hz230V
tcpointmax.
Ambienttemperatureta3
For luminaires with 1 lamp1x36W T8 PCA 1x36 T8 EXCEL one4all lp Y 22176239 360x30x21mm 350mm 32W 35.0W A1BAT 0.15A 0.96 75°C -25...60°C
1x58W T8 PCA 1x58 T8 EXCEL one4all lp Y 22176235 360x30x21mm 350mm 50W 53.5W A1BAT 0.23A 0.97 75°C -25...60°C
For luminaires with 2 lamps2x36W T8 PCA 2x36 T8 EXCEL one4all lp Y 22176240 360x30x21mm 350mm 64W 68.5W A1BAT 0.30A 0.98 80°C -25...60°C
2x58W T8 PCA 2x58 T8 EXCEL one4all lp Y 22176237 425x30x21mm 415mm 100W 108.0W A1BAT 0.47A 0.99 80°C -25...50°C1 AccordingtotheEUdirectivesonecodesignrequirements(EC)No.245/2009and(EC)No.347/2010.2 Validat100%dimminglevel.3 0°Ctotamax:unrestricteddimming.-25°Cto0°C:unrestricteddimmingfrom100%to30%.-25°Cto0°C,dimmingbelow30%:malfunctionpossiblebutnodamagetoECG.ThisappliestoACandDCoperation.
PHASED OUT
www.tridonic.com 3Subject to change without notice.
Data sheet 02/13-881-3
FL ballastsElectronic dimming
TheballastlumenfactorforACoperation(AC-BLF)doesnotalterfromUn=198VACtoUn=254VAC.TheballastlumenfactorforDCoperation(DC-BLF)onthebasisofanautomaticpowerreductionoftheballasts(defaultvalueis70%)willbesmallerthanAC.ItdoesnotalterintheDCoperatingrange(198–280VDC).
StandardsEN55015EN60929EN61000-3-2EN61347-2-3EN61547SuitableforemergencyinstallationsaccordingtoEN50172
Lamp starting characteristicsWarmstartStartingtime0.5swithACStartingtime0.2swithDCStartatanydimminglevel
AC operationMainsvoltage220–240V50/60Hz198–264V50/60Hzincludingsafetytolerance(±10%)202–254V50/60Hzincludingperformancetolerance(+6%/-8%)
DC operation220–240V0Hz198–280V0Hzcertainlampstart176–280V0HzoperatingrangeUseinemergencylightinginstallationsaccordingtoEN50172orforemergencyluminairesaccordingtoEN61347-2-3appendixJ.
Light output level in DC operationProgrammablefrom0%to100%ProgrammingbyextendedDSIorDALIsignal(16bit).Defaultvalueis70%InDCoperationdimmingmodecanbeactivated.
Emergency unitsThe“PCAT8EXCELone4alllpx”ballastsarecompatiblewithallemergencyunitsfromTridonic.Seethetableinthedatasheet.Alsoall“5-pole”emergencyunitscanbeused.Whenusedwithotheremergencyunitstestsarenecessary.
Temperature rangeUnlimiteddimmingrangefrom0°Ctotamax.-25°Cto0°C:dimmingoperationfrom100%to30%.Ifdimmlevelgoesbelow30%malfunctionpossible,butnoelectronicballastdamage.ThisappliestoACandDCoperation.
Mains currents in DC operation (at 70 % light output)
TypeWattage Mainscurrentat
Un=220VDCMainscurrentatUn=240VDC
PCA 1x36 T8 EXCEL one4all lp X 1x36W 0.13A 0.12APCA 2x36 T8 EXCEL one4all lp X 2x36W 0.26A 0.24APCA 1x58 T8 EXCEL one4all lp X 1x58W 0.19A 0.18APCA 2x58 T8 EXCEL one4all lp X 2x58W 0.40A 0.36A
Harmonic distortion in the mains supply (at 230 V / 50 Hz)Type Wattage THD 3 5 7 9 11
PCA 1x36 T8 EXCEL one4all lp X 1x36W 6.1 4.4 2.2 1.6 1.2 1.2PCA 2x36 T8 EXCEL one4all lp X 2x36W 6.7 3.3 1.3 1.6 2.6 1.6PCA 1x58 T8 EXCEL one4all lp X 1x58W 7.5 5.8 1.2 1.5 1.8 1.2PCA 2x58 T8 EXCEL one4all lp X 2x58W 5.9 4.2 0.7 1.0 1.0 0.6
Ballast lumen factor AC operation (AC-BLF) EN 60929 8.1
TypeWattage AC-BLFat
U=230VACPCA 1x36 T8 EXCEL one4all lp X 1x36W 0.99PCA 2x36 T8 EXCEL one4all lp X 2x36W 0.97PCA 1x58 T8 EXCEL one4all lp X 1x58W 0.98PCA 2x58 T8 EXCEL one4all lp X 2x58W 0.99
PHASED OUT
www.tridonic.com 4Subject to change without notice.
Data sheet 02/13-881-3
FL ballastsElectronic dimming
1) SMART-LSIIlp:articlenumber86458258
DSI PCA T8 EXCEL one4all lpX
switchDIM PCA T8 EXCEL one4all lpX
DALI PCA T8 EXCEL one4all lpX
234
67
DSIDA / D1
DA / D2
234
67L
NDADA
234
67 DA
DADALI
DimmingDimmingcurveisadaptedtotheeyesensitiveness.Dimmingrange1%to100%Digitalcontrolwith:•DSIsignal:8bitManchesterCodeSpeed1%to100%in1.4s
•DALIsignal:16bitManchesterCodeMaximumspeed1%to100%in550ms(adjustablebetween50msand90s)Programmableparameter:MinimumdimminglevelMaximumdimminglevelDefaultminimum=1%Defaultmaximum=100%
Control input (DA/D1, DA/D2)DigitalDALI/DSIsignalorapush-to-makeswitch(switchDIM)canbewiredonthesameterminals(DAandDA).
Digital signal DALI/DSIThecontrolinputisnon-polarandprotectedagainstaccidentalconnectionwithamainsvoltageupto264V.ThecontrolsignalisnotSELV.Controlcablehastobeinstalledinaccordancetotherequirementsoflowvoltageinstallations.Differentfunctionsdependingoneachmodule.
SMART interfaceAnadditionalinterfaceforthedirectconnectionoftheSMART-LSIIlp1)lightsensor.Thesensorregistersactualambientlightandmaintainstheindividuallydefinedluxlevel.AftereverymainsresettheSMARTinterfaceauto-maticallychecksforaninstalledsensor.WiththesensorinstalledthePCAT8EXCELone4alllpxautomaticallyrunsintheconstantluxlevelmode.ON/OFFswitchviamains,switchDIMorDALI/DSIsignal.DALI/DSIsignal=0switchesoff,DALI/DSIsignal≥1switcheson.WithrelativeDALIdimmingcommands(e.g.up,downetc.)orswitchDIMsignalsitispossibletochangethecontrolledlightleveltemporarily.TemporarilymeansthatafteraswitchingcycleOFF/ONcommandtheballastwillstartatthepresetvaluedeterminedbytheSMART-LSIIlp.Theinstallationofthetwowirebusisaccordingtotheappropriatelowvoltageregulations.
switchDIMIntegratedswitchDIMfunctionallowsadirectconnectionofapushtomakeswitchfordimmingandswitching.Briefpush(<0.6s)switchesballastONandOFF.Theballastsswitch-ONatlightlevelsetatswitch-OFF.Whenthepushtomakeswitchisheld,PCAballastsaredimmed.AfterrepushthePCAisdimmedintheoppositedirection.TheswitchDIMfadetimeissetto3sfrommin.tomax.inthefactorysettings.Witha20spushtothepushtomakeswitchthisfadetimecanbechangedto6s.InthisinstancetheswitchDIMapplicationwillbesynchronizedto50%lightlevelafter10sandafter20sthelightlevelrisesto100%withthenewfadetime.Ateverysynchronizsation(10skeystroke)thedevicewillresetto3s(factorysetting)IninstallationswithPCAswithdifferentdimminglevelsoroppositedimmingdirections(e.g.afterasystemextension),allPCAscanbesynchronizedto50%dimminglevelbya10spush.Useofpushtomakeswitchwithindicatorlampisnotpermitted.switchDIMandcorridorFUNCTIONareverysimpletoolsforcontrollingballastswithconventionalmomentary-actionswitchesormotionsensors.Toensurecorrectoperationasinusoidalmainsvoltagewithafrequencyof50Hzor60Hzisrequiredatthecontrolinput.Specialattentionmustbepaidtoachievingclearzerocrossings.SeriousmainsfaultsmayimpairtheoperationofswitchDIMandcorridorFUNCTION.
225
255
DALI200
175
150
125
100
75
50
25
0
1009080706050403020100
digitaldimmingvalue
relativelightinglevelin%
100
90
80
70
60
50
40
30
20
10
0
100 90 80 70 60 50 40 30 20 15 10 5 4 3 2 1
Energy saving PCA T8 EXCEL one4all lp Ymainspowerin%
dimminglevelin%
Dimmingcharacteristicsasseenbythehumaneye
DSI
Dimming characteristics PCA T8 EXCEL one4all lp Y
Loading of automatic circuit breakersAutomaticcircuitbreakertype C10 C13 C16 C20 B10 B13 B16 B20
InstallationØ 1.5mm2 1.5mm2 1.5mm2 2.5mm2 1.5mm2 1.5mm2 1.5mm2 2.5mm2
PCA 1x36 T8 EXCEL one4all lp X 30 50 74 80 15 25 37 40
PCA 2x36 T8 EXCEL one4all lp X 16 24 34 38 8 12 17 19
PCA 1x58 T8 EXCEL one4all lp X 22 34 48 52 11 17 24 26
PCA 2x58 T8 EXCEL one4all lp X 16 24 32 36 8 12 16 18
Continuousoperation:tocalculatetheprotectivesafteyswitchseemaincurrent,page2
Backwards compatibilityWithasimplekeycombinationaPCAT8EXCELone4alllpxcanberesetasanormalPCAEXCELlpfromthepreviousgeneration.Synchronisationsimplyhastotakeplacethreetimeswithinoneminute(3x10s).Toactivatethe“x”settingsagain,synchronisationhastotakeplacefourtimeswithinoneminute.
PHASED OUT
www.tridonic.com 5Subject to change without notice.
Data sheet 02/13-881-3
FL ballastsElectronic dimming
Wiring adviceTheleadlengthisdependentonthecapacitanceofthecable.
Installation instructions
Wiring type and cross sectionThewiringcanbesolidcablewithacrosssectionof0.5to0.75mm²forpushterminaland0.5mm²forIDCterminal.Forthepush-wireconnectionyouhavetostriptheinsulation(8–9mm).
Loosenwirethroughtwistingandpulling
Intelligent Temperature GuardTheintelligenttemperatureguardprotectsthePCAT8EXCELone4alllpxfromthermalover-heatingbyreducingtheoutputpowerorswitchingoffincaseofoperationabovethethermallimitsoftheluminaireorballast.Dependingontheluminairedesign,theITGoperatesatabout5to10°CaboveTctemperature.
Intelligent Voltage GuardIntelligentVoltageGuardisthenameofthenewelec-tronicmonitorfromTridonic.ThisinnovativefeatureofthePCAfamilyofcontrolgearfromTridonicimmediatelyshowsifthemainsvoltagerisesabovecertainthresholds.Measurescanthenbetakenquicklytopreventdamagetothecontrolgear.• Ifthemainsvoltagerisesaboveapprox.305V(volt-agedependsontheballasttype),thelampstartsflashingonandoff.
•Thissignal“demands”disconnectionofthepowersupplytothelightingsystem. plugADDRESSING – simple handling, comissioning
and wiringThenewplug&playsolutionsimplifieshandling.ByattachingdifferentcoloredmarkedplugstotheSMART-Interface,groupaddressesareassignedtothePCAT8EXCELone4alllpx.Thissupersedesasingleaddressingandthedevicescanbeputintooperationwithoutanyadditionalprogramming.Anothersignificantadvantageofthisconceptisincaseofexchangeandnolimitsto64DALIaddresses.IdealforRGBapplicationsandcost-effectivesystemsolutionswithsimplecontrollers.Simple–Quick–Plug&Play!
corridorFUNCTIONThecorridorFUNCTIONcanbeprogrammedintwodifferentways.ToprogramthecorridorFUNCTIONbymeansofsoft-wareaDALI-USBinterfaceisneededincombinationwithaDALIPS.ThesoftwarecanbetheconfigTOOL,thepcaCONFIGURATORorthecorridorFUNCTIONCONFIGURATOR.ToactivatethecorridorFUNCTIONwithoutusingsoftwareavoltageof230VsimplyhastobeappliedforfiveminutesattheswitchDIMconnection.TheunitwillthenswitchautomaticallytothecorridorFUNCTION.Note:IfthecorridorFUNCTIONiswronglyactivatedinaswitchDIMsystem(forexampleaswitchisusedinsteadofpushbutton),thereistheoptionofinstallingapushbuttonanddeactivatingthecorridorFUNCTIONmodebyfiveshortpushesofthebuttonwithinthreeseconds.ThecorridorFUNCTIONV2offerstheaddedbenefitofasecondandthirdpreprogrammedprofile,whichcanbeactivatedbythecorridorFUNCTION plugs.ItisalsopossibletocombinethecorridorFUNCTIONwiththeSMART-LSIIlplightsensor.Applicationandfunctionallityofprofilesseeusermanual.
Operating voltageType Wattage Uout
PCA 1x36 T8 EXCEL one4all lp X 1x36W 250VPCA 2x36 T8 EXCEL one4all lp X 2x36W 350VPCA 1x58 T8 EXCEL one4all lp X 1x58W 250VPCA 2x58 T8 EXCEL one4all lp X 2x58W 350V
Withstandardsolidwire0.5/0.75mm²thecapacitanceoftheleadis30–80pF/m.Thisvalueisinfluencedbythewaythewiringismade.Lampconnectionshouldbemadewithsymmetricalwiring.Hotleads(9,10,15,16)andcoldleads(11,12,13,14)shouldbeseparatedasmuchaspossible.Whenusingtwoormoredimmableballastsinoneluminairewithseparatedimmingcontrols,thelampleadsmustbekeptseparate.
DimmableballastsfromTridonichavetobeearthed.
Ballast Terminal Maximum capacitance allowed
Type Cold Hot Cold Hot
PCA 1xx T8 EXCEL one4all lp X 11,12 9,10 200pF 100pF
PCA 2xx T8 EXCEL one4all lp X 11,12,13,14 9,10,15,16 200pF 100pF
8–9mm
wirepreparation:0.5–0.75mm²
PHASED OUT
www.tridonic.com 6Subject to change without notice.
Data sheet 02/13-881-3
FL ballastsElectronic dimming
RFI•Connectiontothelampsofthehotleadsmustbekeptasshortaspossible
•Mainsleadsshouldbekeptapartfromlampleads(ideally5–10cmdistance)
•Donotrunmainsleadsadjacenttotheelectronicballast
•Twistthelampleads•Keepthedistanceoflampleadsfromthemetalworkaslargeaspossible
•Mainswiringtobetwistedwhenthroughwiring•Keepthemainsleadsinsidetheluminaireasshortaspossible
General adviseElectronicballastsarevirtuallynoisefree.Magneticfieldsgeneratedduringtheignitioncyclecancausesomebackgroundnoisebutonlyforafewmilliseconds.
For further technical information please visit www.tridonic.com
ProgrammingWithappropriatesoftwareandaUSBinterfacedifferentfunctionscanbeactivatedandvariousparameterscanbeconfiguredinthenewPCAT5EXCELone4alllpx.AllthatisneededisaDALI-USBandthesoftware.
configTOOLFullversionforprogrammingallthefunctionsandparameters.
pcaCONFIGURATORForprogrammingthecorridorFUNCTION,deviceconfiguration(fadetime,ePowerOnLevel,etc.)DClevel,compatibilitysettings,andstartupdateandforresetting.MaximumamountofballastseeDALI/DSIspecifica-tion.
corridorFUNCTION CONFIGURATORForactivatinganddeactivatingthecorridorFUNCTIONandforproject-specificprogrammingofthePCAT5EXCELone4alllpxunits.MaximumamountofballastseeDALI/DSIspecifica-tion.
Wiring diagram for programming
PCA T8 EXCEL one4all lp X 1x36–58 W PCA T8 EXCEL one4all lp X 2x36–58 W
* * control signal
* leads 9, 10: keep wires short, max. 1.0 m leads 11, 12: max. 2.0 m; ballast must be earthed* * digital signal (DSI), DALI or switchDIM
DA/D2
DA/D1
234
67
1211109
LN
PC and the“configTOOL”
USBSCI
DALIPS
1211109
16151413
DADA
PELN
234
67
PELN
1211109
16151413
DADA
PELN
234
67
max. 64 ECGs (DALI)
1211109
16151413
DADA
PELN
234
67
* * control signal
* leads 9, 10, 15, 16: keep wires short, max. 1.0 m leads 11, 12, 13, 14: max. 2.0 m; ballast must be earthed* * digital signal (DSI), DALI or switchDIM
DA/D2
DA/D1
234
67
141516
131211109
DimmableballastsfromTridonichavetobeearthed.
Operation on DC voltageOurballastsareconstruedtooperateDCvoltageandpulsedDCvoltage.TooperateballastswithpulsedDCvoltagethepolarityisabsolutemandatory.
234
67
D1
D2
+–
Isolation and electric strength testing of luminairesElectronicdevicescanbedamagedbyhighvoltage.Thishastobeconsideredduringtheroutinetestingoftheluminairesinproduction.
AccordingtoIEC60598-1AnnexQ(informativeonly!)orENEC303-AnnexA,eachluminaireshouldbesub-mittedtoanisolationtestwith500VDCfor1second.Thistestvoltageshouldbeconnectedbetweentheinterconnectedphaseandneutralterminalsandtheearthterminal.Theisolationresistancemustbeatleast2MΩ.
Asanalternative,IEC60598-1AnnexQdescribesatestoftheelectricalstrengthwith1500VAC(or1.414x1500VDC).Toavoiddamagetotheelectronicdevicesthistestmustnotbeconducted.
PHASED OUT