CBS Signtex Lighting 220 VFWAvenue, Grasonville, MD 21638 TEL: (410)827-8300 Fax:(410)827-8866 [email protected] www.signtexlighting.com Building Utility Supply (CBS) 120/ 277 VAC AC AC Up To (8) 24V Emergency Lighting Circuits Central Battery 100-1000 Watts for 90 mins. Central Central Battery Battery 100-1000 100-1000 Watts Watts for 90 mins. for 90 mins. Converts ANY type of LED fixture to low voltage emergency operation from central batteries Factory or field installable in the Fire and Electrical Enclosure of UL listed fixtures Compatible with all types of dimming and lighting controls Fully automatic self-test and self- diagnostics is standard for all systems Central batteries allow efficient & easy maintenance that ensures compliance with the Life Safety Code Reduces number of batteries per building by more than 100:1 compared to unit equipment Exit signs, exterior and other fixtures for emergency lighting are included in the system throughout any building Installations with MARS (Monitoring And Reporting System) allow internet communication between all fixtures and battery systems and deliver automatic fault reports via email to any address ELC Emergency Lighting Controller for LED General Lighting Fixtures CBS ELC ELC ELC ELC DESIGNED &MADE IN T H E U S A ELC ELC ELC ELC ELC ELC ELC ELC Warehouse Low Voltage Emergency Circuits ELC ELC ELC ELC Office 10-12 FT CEILING 30-40 FT CEILING EMERGENCY LIGHTING CIRCUIT: LOW VOLTAGE 24 VDC NORMAL LIGHTING BRANCH CIRCUIT 120/ 277 VAC U C US LISTED L ®

Upload: others

Post on 23-Jan-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELC Emergency Lighting Controller for LED General Lighting … · 2018. 5. 14. · LLF = 100 x 30/ (Luminaire Power) % ELC Spec Procedure for LED General Lighting Luminaires run a

CB

S

Signtex Lighting220 VFWA venue, Grasonville, MD 21638 • T EL: (410)827- 8300 Fax: (410)827- 8866

[email protected] www.signtexlighting.com

Building Utility Supply (CBS)120/ 277 VAC

AC ACUp To (8) 24V Emergency Lighting Circuits

CentralBattery

100-1000Watts

for 90 mins.

Central CentralBattery Battery

100-1000 100-1000Watts Watts

for 90 mins. for 90 mins.

Converts ANY type of LED fixture to low voltage emergency operation from central batteries

Factory or field installable in the Fire and Electrical Enclosure of UL listed fixtures

Compatible with all types of dimming and lighting controls

Fully automatic self-test and self-diagnostics is standard for all systems

Central batteries allow efficient & easy maintenance that ensures compliance with the Life Safety Code

Reduces number of batteries per building by more than 100:1 compared to unit equipment

Exit signs, exterior and other fixtures for emergency lighting are included in the system throughout any building

Installations with MARS (Monitoring And Reporting System) allow internet communication between all fixtures and battery systems and deliver automatic fault reports via email to any address

ELC Emergency Lighting Controller forLED General Lighting Fixtures

CBS

ELC ELCELC ELC

D E S I G N E D & M A D E I N

T H E U S A

ELC ELC ELC

ELC

ELC ELCELC

ELC

Warehouse

Low Voltage Emergency Circuits

ELC

ELC

ELC

ELC

Office

10-12 FT CEILING

30-40 FT CEILING

EMERGENCY LIGHTING CIRCUIT: LOW VOLTAGE 24 VDC

NORMAL LIGHTING BRANCH CIRCUIT 120/ 277 VAC

UC US

LISTED

Page 2: ELC Emergency Lighting Controller for LED General Lighting … · 2018. 5. 14. · LLF = 100 x 30/ (Luminaire Power) % ELC Spec Procedure for LED General Lighting Luminaires run a

STEP

1STEP

2STEP

3STEP

4STEP

5STEP

6

SELECT FIXTURE DESIRED FOR EMERGENCY LIGHTING AND DOWNLOAD THE IES PHOTOMETRIC FILE.

Determine LIGHT LOSS FACTOR (LLF) for emergency lighting: (a)For normal power range to 120W, use LLF of 25%.(b)For luminaires with normal power range above 120W: LLF = 100 x 30/ (Luminaire Power) %

ELC Spec Procedurefor LED General Lighting Luminaires

run a photometric calculation for the fixture at specified mounting height and reflectivity criteria, and determine the spacing required to produce 1fc average over the path of egress.

EMERGENCY POWER = LLF (%) x NORMAL POWER

TOTAL POWER = EM POWER x TOTAL EM FIXTURES

Select ELC model PACKAGE TYPE (P1-P4) based on:EMERGENCY POWER (EPR)NORMAL DRIVER OUTPUT VOLTAGEQUANTITY OF NORMAL DRIVERSSPACE AVAILABLE IN DRIVER COMPARTMENT

Signtex Lighting220 VFWA venue, Grasonville, MD 21638 • T EL: (410)827- 8300 Fax: (410)827- 8866

[email protected] www.signtexlighting.com

D E S I G N E D & M A D E I N

T H E U S AUC US

LISTED