ej#1 beam assemblies 1-hr fire rating
TRANSCRIPT
EJ#1
BEAM ASSEMBLIES
1-HR FIRE RATING
Engineering Judgement Report
Client Name: Bremik Construction
Client Address: 1026 SE Stark St, Portland, OR- 97214
Date: 1/19/2018
Engineering Judgement Report
Code Unlimited LLC [2] www.codeul.com
Table of Contents 1 Project Overview ........................................................................................................................................ 3
2 Applicable Codes, Standards, and Guides ................................................................................................. 3
3 Discussion .................................................................................................................................................. 3
3.1 Approach ............................................................................................................................................. 3
4 Proposed design ........................................................................................................................................ 4
5 Assembly Analysis ...................................................................................................................................... 7
5.1 2”x6” Wood Block .............................................................................................................................. 10
6 Summary .................................................................................................................................................. 12
7 Conclusion ............................................................................................................................................... 13
Engineering Judgement Report
Code Unlimited LLC [3] www.codeul.com
1 PROJECT OVERVIEW
Bremik Construction is constructing a new apartment building at 2310 SE Hawthorne Blvd, Portland, OR. The
proposed 4 story mixed-use building includes 59 living units over retail space and 22 parking stalls at the
ground floor. The proposed building is 3-stories of Type VA construction over 1-story Type IA construction with
group R-2 (Residential), S-2 (Storage) and M (Mercantile) occupancies. The building is protected by an
automatic fire sprinkler and a fire alarm systems throughout.
The proposed W-beam assemblies are primary structural members supporting the rated roof in Type VA
construction building. The primary structural members are required to be 1-Hr fire resistance rated per 2014
Oregon Strutural Speciality Code (OSSC) table 601.
Code Unlimited has been asked to provide an analysis for the fire resistance rating of the beam assemblies
found in detail 14/A901 and 9/A960 to ensure they will meet the 1-Hr fire resistance rating per 2014 OSSC.
2 APPLICABLE CODES, STANDARDS, AND GUIDES
2014 Oregon Structural Specialty Code (OSSC) 2015 Technical Report NO. 10 – AWC (American Wood Council)
3 DISCUSSION
3.1 Approach
• The proposed beam assembly has been analyzed in accordance with 2014 OSSC §703.3 Alternative
Methods for Determining Fire Resistance.
• The protection for the proposed assembly has been reviewed for compliance with the requirements of 2014
OSSC §704 Fire Resistance Rating of Structural Members
• There are 2 proposed beam assemblies, each assembly will be analyzed in sections, starting from the bottom
and moving clockwise through left, top and right section of the assembly.
Engineering Judgement Report
Code Unlimited LLC [4] www.codeul.com
4 PROPOSED DESIGN
Assembly#1:
The proposed assembly is composed of W10x60 steel beam located at the 4th floor - roof assembly and
supporting the parapet (see Figure 1 below). The beam is considered as a primary structural member and will
be fire rated on all the exposed sides to meet 1-Hr fire resistance rating per 2014 OSSC table 601.
Engineering Judgement Report
Code Unlimited LLC [5] www.codeul.com
Figure 1: Proposed W10x60 beam assembly at Parapet
Engineering Judgement Report
Code Unlimited LLC [6] www.codeul.com
Assembly #2:
The proposed assembly is composed of a W10x60 steel beam located at the amenity deck of 4th story roof
assembly (see Figure 2 below). The beams are considered as a primary structural members and will be fire
rated on all exposed sides to meet 1-Hr fire resistance rating per 2014 OSSC table 601.
Figure 2: Proposed W10x60 beam assembly at Amenity Deck.
Engineering Judgement Report
Code Unlimited LLC [7] www.codeul.com
5 ASSEMBLY ANALYSIS
The summary of the fire analysis is detailed in the tables below. Table 1 provides analysis to the assembly #1
supporting the parapet. Table 2 provides analysis to the assembly #2 located at the amenity deck of the
building. The SFRM thickness applied to the exposed steel beam will be compared to the UL tested S721
beam assembly.
Figure 3: UL S721 Assembly
Engineering Judgement Report
Code Unlimited LLC [8] www.codeul.com
Table 1: Summary of Fire Resistance (Assembly #1)
Location on Beam
Protection Element
Bottom #1 • (2) layers of 5/8” Type X gypsum board • 80 minutes (40 minutes for each layer
of 5/8” Type X gyp board per table 722.6.2(1)
Total (60 min minimum) 80 min (Exceeds min protection)
Left Side Lower #2
• 7/16” thick SFRM applied on the exposed steel beam and steel bolt. (See summary section 6)
• 2x wood member bolted to the web flange
• 60 minutes (see Figure 3)
• 60 minutes (per char rate analysis-see section 5.1)
Total (60 min minimum) 60 min (Equivalent protection)
Left Side Upper #3
• 2”x6” sacrificial wood member • 60 minutes (per char rate analysis –
see section 5.1)
Total (60 min minimum) 60 min (Equivalent protection)
Top #4 • (2) 2”x6” wood block • 120 minutes (60 minutes for each
2”x6” wood member per char rate analysis see section 5.1)
Total (60 min minimum) 120 min (Exceeds minimum)
Right Side Lower #5
• 7/16” thick SFRM applied on the exposed steel beam and steel bolt. (See summary section 6)
• 2x wood member bolted to the web flange
• 60 minutes (see Figure 3)
• 60 minutes (per char rate analysis-see section 5.2)
Total (60 min minimum) 60 min (Equivalent protection)
Fire-Resistance Rating
1-hour 1-hour (minimum)
Engineering Judgement Report
Code Unlimited LLC [9] www.codeul.com
Table 2: Summary of Fire Resistance (Assembly #2)
Location on Beam
Protection Element
Bottom #1 • (2) layers of 5/8” Type X gypsum board • 80 minutes (40 minutes for each layer
of 5/8” Type X gyp board per table 722.6.2(1)
Total (60 min minimum) 80 min (Exceeds min protection)
Left Side Lower #2
• 7/16” thick SFRM applied on the exposed steel beam and steel bolt. (See summary section 6)
• 2x wood member bolted to the web flange
• 60 minutes (see Figure 3)
• 60 minutes (per char rate analysis-see section 5.1)
Total (60 min minimum) 60 min (Equivalent protection)
Left Side Upper #3
• 2”x6” sacrificial wood member • 60 minutes (per char rate analysis –
see section 5.1)
Total (60 min minimum) 60 min (Equivalent protection)
Top #4 • 2”x6” sacrificial wood member • 60 minutes (per char rate analysis –
see section 5.1)
Total (60 min minimum) 60 min (Equivalent protection)
Right Side Upper #5
• 2”x6” sacrificial wood member • 60 minutes (per char rate analysis –
see section 5.1)
Total (60 min minimum) 60 min (Equivalent protection)
Right Side Lower #6
• 7/16” thick SFRM applied on the exposed steel beam and steel bolt. (See summary section 6)
• 2x wood member bolted to the web flange
• 60 minutes (see Figure 3)
• 60 minutes (per char rate analysis-see section 5.2)
Total (60 min minimum) 60 min (Equivalent protection)
Fire-Resistance Rating
1-hour 1-hour (minimum)
Engineering Judgement Report
Code Unlimited LLC [10] www.codeul.com
5.1 2”x6” Wood Block
The minimum wood thickness used as a protective material is 1.5” (actual thickness). The fire resistance of the
wood is permitted by OSSC Section 722.1 to be calculated using Chapter 16 of ANSI/AF&PA National Design
Specification for Wood Construction (NDS). The NDS specifies an effective char layer depth of 1.8” where 1-
hour of fire resistance is required based on equation 16.2-1 shown in Figure 4. Table 16.2.1A of the NDS is
reproduced below in Figure 5.
Figure 4: Equation 16.2-1 in the NDS
Figure 5: Table 16.2.1A of the NDS
Engineering Judgement Report
Code Unlimited LLC [11] www.codeul.com
Figure 6: NDS TR-10 Fig 3-8
NDS Calculation
Per Figure 5 and Figure 6, calculation for minimum wood cover (NDS TR-10 Fig 3-8).
Minimum Wood Cover Depth > achar /1.2. At 1 Hr = 1.8/1.2 = 1.5” minimum (60 Minutes).
As calculated above, 1.5” minimum actual wood thickness is necessary for 1-hour of fire resistance over steel
beam. The proposed 2”x6” thick wood will meet the minimum of 1-hour fire protection.
Engineering Judgement Report
Code Unlimited LLC [12] www.codeul.com
6 SUMMARY
We evaluated each face of the proposed protection for the W10x60 beam assembly to meet the equivalent
encapsulated 1-Hr fire resistance rating requirement per 2014 OSSC. The bottom of the steel beam is to be
protected with two layers of 5/8” Type X gypsum board. Each layer of 5/8” Type X gypsum board provides
minimum 40 minutes of protection to the assembly. From the component additive method, 2-layers of 5/8”
Type X gyp board provides 80 minutes of protection. The web flange of the proposed beams are protected with
blocking or (2x) sacrificial wood members on both sides and bolted through the beam with steel bolts. The
wood members provide a minimum of 60 minutes protection to the web flange per char rate analysis.
The edges of the steel flange and the exposed steel bolts are protected with SFRM (Spray Applied Fire
Resistive Material). The SFRM thickness is calculated based on the comparison to UL tested S721 design
assembly for W6x16 beam. The proposed beam W10x60 flange and steel bolts have greater W/D ratio (W/D -
1.22 & 1.73) (Weight to Heated Perimeter) compared to the tested W6x16 assembly (W/D 0.684). The tested
assembly requires application of 7/16” thick SFRM to meet 1-Hr fire rating. The application of 7/16” thick SFRM
to the exposed flanges and the steel bolts exceeds the minimum required fire resistance to the assembly.
The other sections of the proposed beam will be protected with minimum layer of 2”x6” sacrificial wood block.
The 2”x6” wood block provides 60 minutes of fire protection to the assembly per the char rate analysis detailed
in the section above. With this added protection, the proposed beam assemblies will meet the equivalent
minimum required 1-Hr fire resistance rating per 2014 OSSC.
Engineering Judgement Report
Code Unlimited LLC [13] www.codeul.com
7 CONCLUSION
We have evaluated the protection per 2014 OSSC section 703.3. All sides of the proposed beam assemblies
are protected equivalent to an encased structural member by minimum 2” nominal thick wood members, SFRM
coating or a combination of both. The material will remain in place and provide the required protection from fire
for all sides of the beam. The NDS calculation confirms that 1.5” will be the minimum cover for 1-Hr of fire
resistance, while the component additive method from OSSC confirms adequate fire resistance with (2) layers
of Type X gypsum board.
As shown above, the steel beam assembly is provided with a minimum fire protection of 1-Hr. By providing fire
resistance on all the sides for the length of the beam, the proposed beam assembly will have protection
equivalent to the required 1-Hr fire resistance rated encasement per 2014 OSSC section 704.3
Franklin Callfas
Principal/Fire Protection Engineer
Code Unlimited