Efficiency Improvement on Steam Power

Plants at Flexible Load ConditionsThorsten StrunkEEC Conf., New Delhi, 30. November 2018

Page 2: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 2 SIEMENS AG – POWER GENERATION SERVICE

Today’s and tomorrow’s Load Requirements

Energy from Renewables has feed-in priority in the grid

source: Spliethoff: et. al, CIT 2011

Scenario 2020 Tomorrow (Scenario 20XX)

Energy market of tomorrow requires flexible fossil fired power plants

Situation 2011

Nuclear Hard Coal Gas

2011 Base Load Base - Intermediate Load Intermediate Load

2020 Intermediate Load Intermediate Load Peak load

Nuclear Hard Coal Gas

2011 Base Load Base - Intermediate Load Intermediate Load

Nuclear Hard Coal Gas

2011 Base Load Base - Intermediate Load Intermediate Load

2020 Intermediate Load Intermediate Load Peak load

20XX Phase out ? ?

Conventional

Wind

photovoltaics

Page 3: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 3 SIEMENS AG – POWER GENERATION SERVICE

Conventional Power Plants need to be able to supply full power

demand in times of non-availability of renewable energy

India Demand Scenario for 2022

Page 4: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 4 SIEMENS AG – POWER GENERATION SERVICE

Market requirements:

Changed operational regimes require highly flexible products

Power

Base

Load

Time

Primary

Frequency

Response

Fast

Start-up

Secondary

Frequency

Response

Peak

Power &

Off-

Frequency

Part-loadFast shut-

down

Prepared for

start-up

Fast start-

up

Flex Operation Line Standard Operation Line

Page 5: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 5 SIEMENS AG – POWER GENERATION SERVICE

Increased flexibility leads to two main issues for Steam

Power Plants

• High stress in component

• Increased wear and tear

• Reduced Reliability & Availability

• Increased maintenance cost

Increased number of starts & load changes

• Low efficiency in Part Load

• Lower number of generated MW

• Lower income

Decreasing number of

generated Power

1

3

2

4

Steam Turbine Modernization can increase Part Load Efficiency and provide higher stress resistance

Page 6: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 6 SIEMENS AG – POWER GENERATION SERVICE

Steam Turbine configuration for 500MW

coal-fired power plants (KWU-design)

4 valves and inlets 2x10m²

Turbine initially designed for fixed pressure operation !

≈ 167 bar / 538 °C

HP IP LP

Page 7: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 7 SIEMENS AG – POWER GENERATION SERVICE

8400

8500

8600

8700

8800

8900

9000

9100

9200

9300

9400

40% 50% 60% 70% 80% 90% 100% 110%

Hal

f-n

et

He

at-R

ate

[kJ

/kW

h]

(SPA

T co

nsi

de

d (

vari

able

sp

ee

d)

Load of ST (relative to rated load)

fixed pressure mode 538°C

Ageing 240month

Full Arc HP at Fixed Pressure Operation

Heat Rate loss of approx. 200 ckal/kwh at 40% load

Turbine in “new

and clean” condition

2200

2100

2000

2150

2050

2250 Heat-Rate vs. Load

VWO

Page 8: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 8 SIEMENS AG – POWER GENERATION SERVICE

Water-Steam-Cycle

- Full load

IP LPHP G

1250 MWth

h ≈ 40%

Thermal Energy to

Water-Steam-Cycle

500 MWel

750 MWth

Thermal Energy to

Atmosphere

Page 9: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 9 SIEMENS AG – POWER GENERATION SERVICE

Water-Steam-Cycle

- Part Load (40%) with Fixed Pressure Operation

IP LPHP G

540 MWth

h ≈ 36,3%

Thermal Energy to

Water-Steam-Cycle

196 MWel

344 MWth

Thermal Energy to

Atmosphere

Large “exergetic

losses” occur due

to throttling in HP

control valves

≈ 21 MW

Page 10: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 10 SIEMENS AG – POWER GENERATION SERVICE

Water-Steam-Cycle

- Part Load (40%) with Sliding Pressure Operation

IP LPHP G

540 MWth

h ≈ 37,0%

Thermal Energy to

Water-Steam-Cycle

200 MWel

340 MWth

Thermal Energy to

Atmosphere

Reduced Average

Temperature of

Heat Supply

results in large

“exergetic losses”

≈ 17 MW

→ difference in exergetic losses: 4 “green” MW*

* compared to fixed pressure mode

Page 11: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 11 SIEMENS AG – POWER GENERATION SERVICE

38,3%

38,8%

39,3%

39,8%

40,3%

40,8%

41,3%

41,8%

42,3%

42,8%8400

8500

8600

8700

8800

8900

9000

9100

9200

9300

9400

40% 50% 60% 70% 80% 90% 100% 110%

Hal

f-n

et

He

at-R

ate

[kJ

/kW

h]

(SPA

T co

nsi

de

d (

vari

able

sp

ee

d)

Load of ST (relative to rated load)

fixed pressure mode 538°C

Ageing 240month

sliding pressure mode 538°C

Heat-Rate vs. Load (Fixed-pressure vs. Sliding pressure)

≈ 4 „green“ MW*

* Additional Power output due to better performance

Turbine in “new

and clean” condition

2200

2100

2000

2150

2050

2250

Page 12: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 12 SIEMENS AG – POWER GENERATION SERVICE

HP Steam Turbine with Control Stage

Drum blades(reaction)

Stationary Nozzles

Rotating blade ring (impulse)

Wheel Chamber

full load part load

Valve

closed

Valve operation Full Arc vs. Control Stage

Page 13: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 13 SIEMENS AG – POWER GENERATION SERVICE

38,3%

38,8%

39,3%

39,8%

40,3%

40,8%

41,3%

41,8%

42,3%

42,8%8400

8500

8600

8700

8800

8900

9000

9100

9200

9300

9400

40% 50% 60% 70% 80% 90% 100% 110%

Hal

f-n

et

He

at-R

ate

[kJ

/kW

h]

(SPA

T co

nsi

de

d (

vari

able

sp

ee

d)

Load of ST (relative to rated load)

fixed pressure mode 538°C

Ageing 240month

sliding pressure mode 538°C

Control stage + 3DS blades 538°C

Heat-Rate vs. Load (incl. Control Stage)

2200

2100

2000

2150

2050

2250

Valve point (open: x/4valves)

x=4x=3x=2

x=1

≈ 𝟑𝐃𝐒

Page 14: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 14 SIEMENS AG – POWER GENERATION SERVICE

HP Stage Bypass Valve

→ Variation of swallowing

capacity of the turbine

Stage Bypass Valve

(„Overload Valve“)

Page 15: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 15 SIEMENS AG – POWER GENERATION SERVICE

38,3%

38,8%

39,3%

39,8%

40,3%

40,8%

41,3%

41,8%

42,3%

42,8%8400

8500

8600

8700

8800

8900

9000

9100

9200

9300

9400

40% 50% 60% 70% 80% 90% 100% 110%

Hal

f-n

et

He

at-R

ate

[kJ

/kW

h]

(SPA

T co

nsi

de

d (

vari

able

sp

ee

d)

Load of ST (relative to rated load)

fixed pressure mode 538°C

Ageing 240month

sliding pressure mode 538°C

OLV 538°C

Heat-Rate vs. Load (incl. Stage Bypass)

2200

2100

2000

2150

2050

2250

≈ 𝟑𝐃𝐒

Page 16: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 16 SIEMENS AG – POWER GENERATION SERVICE

38,3%

38,8%

39,3%

39,8%

40,3%

40,8%

41,3%

41,8%

42,3%

42,8%8400

8500

8600

8700

8800

8900

9000

9100

9200

9300

9400

40% 50% 60% 70% 80% 90% 100% 110%

Hal

f-n

et

He

at-R

ate

[kJ

/kW

h]

(SPA

T co

nsi

de

d (

vari

able

sp

ee

d)

Load of ST (relative to rated load)

fixed pressure mode 538°C

Ageing 240month

sliding pressure mode 538°C

Control stage + 3DS blades 538°C

OLV 538°C

Heat-Rate vs. Load (incl. Stage Bypass & Control Stage)

2200

2100

2000

2150

2050

2250

Valve point (open: x/4valves)

x=4x=3x=2

x=1

≈ 𝟑𝐃𝐒

Page 17: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 17 SIEMENS AG – POWER GENERATION SERVICE

Additional “green” power (sliding pressure and Control Stage)

can save up to 55.000 tons CO2 emission / year

-6,0 MW

-4,0 MW

-2,0 MW

0,0 MW

2,0 MW

4,0 MW

6,0 MW

8,0 MW

10,0 MW

40% 50% 60% 70% 80% 90% 100% 110%

Po

we

r d

iffe

ren

ce r

ela

tive

to

fix

ed

pre

ssu

re

mo

de

-as

de

sign

ed

["g

ree

n"

MW

]

Load of ST (relative to rated load)

Benefit of control stage +3DS blades

Benefit of sliding

Ageing 240month

> 6 MW > 3 MWFixed pressure /

“new and clean” condition

Page 18: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 18 SIEMENS AG – POWER GENERATION SERVICE

Scenario: Control Stage

Focus: Europe

Source: VGB 2015

Costs of additional

gained „green“

Electricity much

lower compared to

new power plants

0,8

Page 19: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 19 SIEMENS AG – POWER GENERATION SERVICE

Lower technical minimum is better than two shift operation

Comparison of life consumption based on cold, warm and hot start

Start Life Consumption IEC 45 VGB R105M

Cold Start 23 – 75 hours 100 200

Warm Start 15 -17 hours 700 400

Hot Start 10 -12 hours 3000 1600

Load Change 3 hours -

140%

155%

170%

100%

120%

140%

160%

180%

210 MW 500 MW 660 MW

Incremental O&M costs

Base Load Technical Minimum 2 shift

Page 20: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 20 SIEMENS AG – POWER GENERATION SERVICE

Transient Operation (Ramp Up / Ramp Down)

increased temperature gradient results increased life consumption

Crack depth: 50%

wall thickness

Main steam valve

Page 21: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 21 SIEMENS AG – POWER GENERATION SERVICE

Power on Demand

Reduction of Wall Thickness to Improve Start Up & Cycling

Capabilities

Example: Reduced Casing thickness & reduced thermal piston loading by HP bypass cooling

Significant improvement in LCF

coolingsteammixed steam

main steam

0

20

40

60

80

100

Lo

ad

in

%

Time

Design with internal bypass

cooling

Design without internal bypass

cooling

Page 22: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 22 SIEMENS AG – POWER GENERATION SERVICE

Primary Frequency Control

- Situation in Germany

PRL „Primary Control Power“ → to be activated within 30 seconds

Demand ≈ 600MW

(for Germany)

For allocating (positive and negative) Power for Primary Frequency Control specific prices

of 2000 – 2500 € per MW and week are paid.

Cost for Primary Control Power

(weekly e-auction)

Mio €

Page 23: Efficiency Improvement on Steam Power Plants at Flexible ......coal-fired power plants (KWU-design) ... • The return of investment for the Steam Turbine modernization is lower than

Restricted © Siemens AG 2018

2018-11-22Page 23 SIEMENS AG – POWER GENERATION SERVICE

HP Steam Turbine Solution

• The Heat Rate increases in part load operation which results in higher CO2 emission and coal

consumption

• Boiler Sliding Pressure Operation reduces the losses, however to the disadvantage of controllability.

• HP with Control Stage provides the lowest heat rate losses and maintains controllability.

• HP Modernization is required to implement the Control Stage

• With a HP Modernization the aging will be reversed and additional efficiency improvement can be

gained by using state of the art blading and sealing technology.

• HP design update can reduce the stresses in cycling operations.

• The return of investment for the Steam Turbine modernization is lower than all other Cost of

Electricity measures.

• Condensate throttling allows for fast load ramp rates.

• ST Mods and Flex-Power ServicesTM solution (e.g. I&C) can provide additional improvement in

Flexibility and Efficiency