effect of load-generated transformer noise in a substation
TRANSCRIPT
EUROPEAN TRANSACTIONS ON ELECTRICAL POWEREuro. Trans. Electr. Power 2011; 21:596–607Published online 5 August 2010 in Wiley Online Library (wileyonlinelibrary.com). DOI: 10.1002/etep.464
Effect of load-generated transformer noise in a substation
*CyE-
Co
Sanjay Patil1*,y, George G. Karady2 and Wesley Knuth3
1PJM Interconnection Operations Planning, Norristown, PA, U.S.A.2Department of Electrical Engineering, Arizona State University, Tempe, AZ, U.S.A.
3Salt River Project Apparatus Engineering, Tempe, AZ, U.S.A.
SUMMARY
The objective of the project was to assess the severity of load-generated transformer noise in neighborhoodsof the substation by performing the acoustic noise level dBA measurements around power transformer atdifferent loads and distances. The results showed that 125 Hz frequency noise becomes dominant at�80% ofthe full-load with fans out of operation and varies linearly with the load. The regression equations betweenMVA loading and the average sound pressure level at 2 and 70 m away from the transformer wereestablished. The increase in the average sound pressure level from no-load to full-load was found to be�3.60 dBA. When the fans were on, the increase in the average sound pressure level due to the loadwas negligible, as the fans’ noise was the dominant noise source. It was determined if the fans operate innight, it may cause some complaints from people living near the substation. Copyright # 2010 John Wiley &Sons, Ltd.
key words: transformer noise level; load-generated noise level; 120 Hz noise level; effect of noise level;sound pressure level; sound power level
1. INTRODUCTION
The choice of selecting the transformer depends on various factors, but these days
transformers noise level is becoming an important factor in its selection. The noise level
of the transformers located in the residential areas has become a point of concern for the
utilities [1]. Transformers produce a significant humming noise and the main causes of this
noise level are magnetostriction of the core, electromagnet forces in the winding, and cooling
equipments.
It was generally agreed that the no-load noise produced by the transformer core is the main source
of noise. Because of its severe requirement efforts had been made to reduce the no-load noise of
the transformer and a significant reduction in its level had been achieved [2]. However, the load-
generated noise in the transformer had not given importance in the past decades. It has been
observed that the noise level produced by the transformer increases as the load on the transformer
increases [3]. In the past, transformer manufactures provided only no-load noise emitted by the
transformer, whereas now many manufacturers also provide load-generated noise level of the
transformer.
The objective of the project was to measure the acoustic noise level dBA around several power
transformers at different loads and distances to achieve the following [4]:
� D
orr
m
py
evelop curves depicting the noise versus load in the near and far field.
� A
ssess the severity of load-generated transformer noise in the Salt River Project (SRP)substations.
espondence to: Sanjay Patil, PJM Interconnection Operations Planning, Norristown, PA, U.S.A.
ail: [email protected]
right # 2010 John Wiley & Sons, Ltd.
EFFECT OF LOAD-GENERATED TRANSFORMER NOISE 597
2. TEST SETUP
Figure 1 shows the test site where sound pressure level measurements were taken. It can clearly be seen
that the test substation is located close to the residential area.
The nominal high/low voltage rating of the transformer is 230/70.8 kV, respectively. The MVA
rating of the transformer with respect to OA/FA/FA is 150/200/250 MVA at 458C and 168/224/
280 MVA at 558C, respectively [4].
The length of the prescribed contour of the transformer was measured to be 26 m. The prescribed
contour was selected at 2, 5, 8, and 16 m away from the principle radiating surface of the
transformer as shown in Figure 2. Some of the measurements were also taken 70 m away near the
residential area.
The sound pressure level measurements were taken on different dates and time with
the fans in or out of operation to get maximum exposure of the load, temperature, voltage,
and other factors. The drain valve (DV) was selected as the first position, and at each
successive clockwise position of 1 m (indicated as small boxes in Figure 2), the sound
pressure level measurements were taken facing the sound level meter microphone in front of
the transformer at a height of 2 m as suggested by Refs. [3,5]. The sound pressure level
predictions performed at 5, 8, and 16 m are not discussed in the paper due to document size
limitation.
Figure 1. Top view of the test site substation.
Figure 2. Field measurement locations in the substation site.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
598 S. PATIL, G. G. KARADY AND W. KNUTH
3. TEST RESULTS
Figure 3 shows the calculated average sound pressure levels from 26 measurements taken around the
transformer at different distances and MVA loadings. Four noise level measurements taken with fans
on (FO) are also shown in figure and are indicated as FO in the x-axis. The x-axis shows the MVA
loading of the transformer and the y-axis shows the calculated average sound pressure levels of the
transformer at different distances.
It can be noticed from Figure 3 that the sound levels decreases as the distance from the
transformer increases. It was expected that when the distance from the transformer doubles, the
sound pressure level would be reduced by 3 dBA in the near field and thereafter at a constant
interval of 6 dBA [6–8]. However, sound pressure level dBA measurements have shown that the
distance attenuation is more or less than expected attenuation when the distance is doubled. This
reveals that the sound pressure level is also dependent on factors other than MVA loading like
temperature, pressure, humidity, reflection, and diffraction due to the objects nearby the test field
etc. The effect of reflection and diffraction was not considered significant as the objects were far
away from the transformer and would have minimal effect on the measurements taken near the
transformer.
The calculated average sound pressure level without fans showed that as the MVA loading increases
the noise level around the transformer remained approximately the same at that particular distance. For
example, consider two measurements, one recorded in the summer with �199 MVA loading and the
other in the winter with �67 MVA loading on the transformer. The sound levels of the transformer are
recorded to be 63.57 and 63.72 dBAwith respect to the MVA loading of the transformer. Even the MVA
loading of the transformer was tripled or reached 70% of its full-load; the average sound pressure level
of the transformer did not change or changed very little. The reason was that the ambient was different
every time the measurement was carried out in the field and this ambient noise was also picked by the
sound level meter along with the sound pressure level of the transformer. The difference between
minimum and maximum average sound pressure level was found to be within 3 dBA at a particular
distance. Recorded sound pressure levels at individual frequencies were used to weaken the ambient
noise level from the overall sound pressure levels of the transformer using the method discussed in
Section 5.
Figure 3. Calculated average sound pressure level of the transformer at different distances and MVAloadings.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
EFFECT OF LOAD-GENERATED TRANSFORMER NOISE 599
It can also be noticed that the noise level recorded with fans is�7–10 dBA higher than the noise level
recorded without fans. Thus the fan noise is the dominant noise source in the transformer.
Another sound level meters are available in the market which records sound level using sound
intensity level technique and have better accuracy as it automatically eliminate the background noise
levels. In this project, sound pressure level method based sound level meter was used to carry out
measurements in the field. It also picked up background noise level in addition to the transformer noise
in the field.
4. MODEL FOR SOUND PRESSURE LEVEL MEASUREMENTS TAKEN AROUND THE
TRANSFORMER
To determine the dependency of noise level 14 factors (high voltage, low voltage, secondary current,
MVA loading, hot spot temperature, oil temperature, ambient temperature, pressure, relative humidity,
solar, wind direction, wind speed, FO/off, and distance) were initially considered. After applying the
linear regression analysis using Minitab, it was determined that only fans and distance are the
significant factors to determine the noise level of the transformer.
The linear regression equation of the model obtained is as follows:
Y ¼ 64:06 þ 8:52FS � 0:66X dBA (1)
The R2 of the model was found to be 0.9347, respectively. Equation (1) gives the relationship
between response (average sound pressure level) and the factors (FO/Off and distance). The
residual of the sound pressure level is close to 0, 54% of the time. Within �1.8 dBA change in the
residual of the sound pressure level, �91% of the data has been recovered. The model only
consists of 2, 5, 8, and 16 m distances. The linear regression equation obtained is limited to these
distances and does not take into account the MVA loading of the transformer. Therefore a
different approach is required to predict the average sound pressure level under different MVA
loadings and distances.
5. EVALUATION OF SOUND PRESSURE LEVEL MEASUREMENTS TAKEN AROUND
THE TRANSFORMER
Recorded sound pressure levels at different frequencies were used to evaluate the relation
between MVA loading and the average sound pressure level of the transformer and to assess the
severity of the problem. Using these frequency components, the ambient noise level in the
recorded sound pressure level was diminished to predict the overall sound pressure level of
the transformer.
The average sound pressure levels recorded at 31.5, 63, 125, 250, 500, 1000, and 2000 Hz without
and with fans at distance of 2 m are shown in Figures 4 and 5, respectively. The x-axis gives the
MVA loading and the y-axis gives the calculated average sound pressure levels at individual
frequencies.
By comparing Figures 4 and 5, it can be noticed that even when the fans were on, the lower
frequencies did not show any increase in the sound levels, that is, they did not contribute to it. In other
words, only high frequencies contribute to the fans noise of the transformer.
It can also be noticed from Figure 4 that only 125 Hz sound pressure level has shown linear
increase as the MVA load increases and other frequencies are dependent on the other factors. The
increase in the 125 Hz level is from 50.70 to 59.89 dBA, which is a significant increase. The 125 Hz
is almost the dominant noise source of the transformer compared to the other frequencies. It can be
predicted that with a little increase in the MVA loading, the 125 Hz sound pressure level would
increase and so will the overall sound pressure level of the transformer. This reveals that the load
frequency component is adding to the no-load noise and would increase the overall noise level
emitted by the transformer.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
Figure 4. Average sound pressure levels at individual frequencies without fans at 2 m.
Figure 5. Average sound pressure level at individual frequencies with fans at 2 m.
600 S. PATIL, G. G. KARADY AND W. KNUTH
The 125 Hz sound pressure level theoretically should increase linearly as the load increases. The
prediction of the 125 Hz component at a distance of 2 m with load was done in MS Excel by both linear
and second order polynomial regression analysis and is shown in Figure 6. Both linear and polynomial
regression analyses showed a possible increase in the load component frequency and were initially
considered to test the validity.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
Figure 6. Regression analysis of average sound pressure level-125 Hz at 2 m.
EFFECT OF LOAD-GENERATED TRANSFORMER NOISE 601
5.1. Determination of average no-load and load-generated sound pressure level of the
transformer without fans at 2m
To predict the average no-load and load-generated sound pressure level without fans at 2 m, the
125 Hz frequency was varied and the other frequencies were chosen to be the minimum, obtained
from the measurements taken around the transformer without fans. At first the sound pressure levels
for all the frequencies, except the 125 Hz frequency were converted to sound power levels using
Ref. [9].
The average no-load sound pressure level for 125 Hz frequency was interpolated to be 48.20
and 43.00 dBA for linear regression and polynomial regression, respectively, from Figure 6.
The average full-load sound pressure level for 125 Hz frequency was interpolated to be 62.67
and 69.00 dBA for linear regression and polynomial regression, respectively, from Figure 6. The
predicted 125 Hz sound pressure level at low-load for polynomial regression was not used as
its contribution is less compared to the other frequencies and will not affect the calculation
of overall sound pressure level of the transformer. Thus the 125 Hz frequency value was varied
from 48.00 to 62.67 dBA for the linear regression prediction and from 48.00 to 69.00 dBA for
the polynomial regression prediction at step rate of 1 dBA. At each step increase, the corresponding
MVA loading of the transformer was interpolated and the 125 Hz sound power levels were
obtained using Ref. [9].
The variable 125 Hz sound power levels were then added to the other frequencies sound power levels
obtained earlier and the total sound power level of the transformer for individual interpolated MVA
loadings were acquired. The total sound power levels were then converted back to sound pressure
levels at different MVA loadings using Ref. [9] and are shown in Figure 7 for only linear regression
analysis.
The predicted average no-load Lp noload and full-load Lp load sound pressure level using linear
regression was found to be 61.51 and 65.12 dBA, respectively. The predicted average no-load and full-
load sound pressure level for polynomial regressions was found to be 61.51 and 69.68 dBA,
respectively. Note the no-load sound pressure levels achieved for linear and polynomial regression
analysis are same because the no-load sound pressure level at 125 Hz was varied starting at 48.00 dBA
for polynomial regression analysis.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
Figure 7. Regression analysis of the predicted average sound pressure level without fans at a distance of 2 mfor different MVA loadings.
602 S. PATIL, G. G. KARADY AND W. KNUTH
Using method described in Ref. [5], the average load-generated sound pressure level at \approx 78%
rated value of the transformer can be used to calculate the average full-load generated sound pressure
level and was found to be:
Lp load ¼ 65:15 dBA (2)
The average full-load sound pressure level at a distance of 2 m obtained from the linear regression
prediction is 65.12 dBA, which is close to as obtained by Equation (2). It revealed that the 125 Hz
sound pressure level of the transformer is proportional to the MVA loading and exhibits a linear
relationship.
The increase in the average sound pressure level from no-load to full-load at a distance of 2 m was
3.61 dBA, which can be significant in highly urbanized area.
The third order polynomial regression line was also drawn and an equation was obtained using MS
Excel for the predicted average sound pressure level at 2 m without fans and is shown in Figure 7. The
R2 for the third order polynomial regression was found to be 1. Within 0.00 to + 0.03 dBA change in the
residual of the predicted average sound pressure level all the data was recovered.
The predicted average sound pressure level without fans Y2 load at a distance of 2 m from the
transformer can be obtained by inputting the load values in Equation (3):
Y2 load ¼ ð61:51 þ 1 � 10�7L3 þ 8 � 10�6L2 þ 29 � 10�4LÞ dBA (3)
5.2. Determination of average no-load and load-generated sound pressure level of the transformer
with fans at 2m
The variation in the sound pressure levels from no-load to full-load with fans can also be predicted by
using the recorded frequencies of the transformer. The average sound pressure levels at 31.5 and 63 Hz
were kept the same as described in Section 5.1 as fan noise does not contribute to the lower frequencies
sound levels. The sound pressure levels with FO at frequencies 250 Hz and onwards have been chosen
minimum from the measurements performed around the transformer with FO. The value of the 125 Hz
sound pressure level had been predicted for only linear regression using the Figure 6. The same method
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
Figure 8. Regression analysis of the predicted average sound pressure level with fans at a distance of 2 m fordifferent MVA loadings.
EFFECT OF LOAD-GENERATED TRANSFORMER NOISE 603
was used as described in Section 5.1 to obtain predicted average sound pressure level with fans at a
distance of 2 m for different MVA loadings and is shown in Figure 8.
The R2 for the third order polynomial regression was found to be 0.9996. The residual of the
predicted average sound pressure level was found to be within the range of �0.11 to 0.00 dBA using the
equation obtained from the third order polynomial regression:
Y2 fan load ¼ ð70:60 þ 3 � 10�8L3 � 4 � 10�6L2 þ 6 � 10�4LÞ dBA (4)
The regression Equation (4) can be used to determine the predicted average sound pressure level
with fans Y2 fan load at a distance of 2 m from the transformer.
The predicted average no-load and full-load sound pressure level with fans was found to be
70.60 and 71.22 at a distance of 2 m, respectively. The increase in the sound pressure level
from no-load to full-load is small because higher frequencies have more contribution to
the overall sound pressure level of the transformer than 125 Hz or lower frequencies. The increase
in the predicted no-load and full-load average sound pressure level due to fans is 9.09
(Y2 fan load � Y2 load at L¼ 0) and 6.10 (Y2 fan load � Y2 load at L¼ 280) dBA at a distance of 2 m,
respectively. Therefore, it can be concluded that the fans noise is the dominating noise source
in the transformer.
5.3. Determination of average no-load and load-generated sound pressure level of the
transformer with and without fans at 70m
The predicted average sound pressure level in the near field can be used to predict the transformer noise
level in the far field at different MVA loadings as described in Refs. [3,5]. The transformer has been
considered as a point source. The measured height and perimeter of the transformer is 4.78 and 26 m.
The distance from the transformer to the far field (near residential area) has been measured to be around
70 m.
Using predicted average sound pressure levels at 2 m from Figures 7 and 8, the predicted average
sound pressure level in the far field has been calculated at different MVA loads without and with fans as
shown in Figures 9 and 10, respectively [3,5]. The third order polynomial regression line and equation
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
Figure 9. Regression analysis of the predicted average sound pressure level without fans at a distance of70 m for different MVA loadings.
Figure 10. Regression analysis of the predicted average sound pressure level with fans at a distance of 70 mfor different MVA loadings.
604 S. PATIL, G. G. KARADY AND W. KNUTH
obtained has also been shown in the figures. The R2 for the third order polynomial regression was found
to be 1 and 0.9996, respectively. The residual of the sound pressure level was found to be within the
range of �0.01 to + 0.01 and �0.11 to + 0.00 dBA using the third order polynomial regression
equation, respectively.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
EFFECT OF LOAD-GENERATED TRANSFORMER NOISE 605
The predicted average sound pressure level of the transformer without fans Y70 load and with fans
Y70 fan load at a distance of 70 m from the transformer can be calculated by inputting the load values in
obtained Equation (5) and Equation (6), respectively:
Y70 load ¼ ð39:09 þ 1 � 10�7L3 þ 8 � 10�6L2 þ 28 � 10�4LÞ dBA (5)
Y70 fan load ¼ ð48:17 þ 3 � 10�8L3 � 4 � 10�6L2 þ 6 � 10�4LÞ dBA (6)
The predicted average no-load LpAR noload and full-load LpAR load sound pressure level in the far field
without fans in operation was found to be 39.09 and 42.70, respectively.
The predicted average no-load LpAR fan noload and full-load LpAR fan load sound pressure level in the
far field (70 m) with fans in operation was found to be 48.18 and 48.80 dBA, respectively.
6. ASSESSMENT OF THE DISTURBING EFFECT OF THE NOISE
In general, the response to the noise level at a point may vary from person to person. However
limits are usually set by cities for the maximum allowable noise levels in residential, industrial,
and commercial areas. The maximum limit may also vary from city to city, depending on the
condition of the surrounding areas. According to the City of Tempe Code, the noise level near
residential area should not exceed 45 and 55 dBA from 2200 to 0700 hours and 0700 to
2200 hours, respectively [10].
Table I. The expected sound pressure level in the far field and complaint levels.
MVA loading Fans Predicted average sound pressure levels Day complaint levels Night complaint levels
0 Off 39.09 No No0 On 48.18 No Low280 Off 42.70 No No280 On 48.80 No Low
Figure 11. Predicted average sound pressure levels around the transformer at different distances and MVAloadings.
Copyright # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
606 S. PATIL, G. G. KARADY AND W. KNUTH
The assessment of the predicted average sound pressure levels at a distance of 70 m should be
checked with the city ordinance limits. Table I shows the predicted average sound pressure levels under
different conditions and the expected complaint levels from the residents.
When the transformer is under no-load and full-load condition without fans, the predicted average
sound pressure level in the far field is below the city ordinance limits during the day and the night.
Under the no-load and full-load condition with FO, the predicted average sound pressure level is not a
problem during the day time; however during the night, the sound pressure level under the no-load and
full-load conditions is higher by 3.18 and 3.80 dBA, respectively, from the city ordinance limits.
Therefore, the sound pressure level generated by the transformer may cause some complaints from the
residents near the substations.
Using method described in Section 5, the predicted average sound pressure levels of the
transformer at different distances and MVA loadings was calculated and is shown in Figure 11.
In addition to the MVA loading values during which the data was recorded in the field
around the transformer, MVA loading values were extended to full-load of the transformer.
By comparing Figures 2 and 11 it can be clearly seen that the distortion in the sound
pressure has been weakened by using the method described in the paper. The predicted
average sound pressure level shows distinguish variation in figure with the distance and MVA
loading change.
The above method only takes the effect of distance attenuation of the sound pressure level.
The sound pressure level at a distance is not only dependent on the MVA loading, distance, and
fans, but also on the propagation path of the sound. Factors like temperature, wind direction,
wind speed, relative humidity, pressure, and refraction and diffraction from the objects nearby
the transformer were not included in the calculation method. The sound pressure level in the far
field may vary from the predicted average sound pressure level if the above factors were taken
into account.
7. CONCLUSIONS
The results achieved from the research should be fairly applicable to the other substations with similar
transformer and surroundings. The conclusions drawn from the research performed on the test
transformer are as follows:
Co
� T
py
he evaluation of frequency components proved that the 125 Hz frequency component varies
linearly with the load.
� T
he regression equations had been established to predict the average sound pressure level at adistance of 2 m (near field) and 70 m (far or near residential field) with and without fans for
different MVA loadings on the test transformer.
� T
he results revealed that the increase in overall sound pressure level from no-load to full-load is\approx 3.60 dBA without FO the test transformer. However when the fans are on, the increase in
overall sound pressure level from no-load to full-load is \approx 0.60 dBA as the fan noise is the
dominant noise source in the transformer.
� T
he no-load and load-generated sound pressure levels without fans are below the city ordinancelimit and there should be no complaints from the neighborhood. Also if the fans are on during the
day time, the sound pressure level is under the city ordinance limit. However if the fans turns on in
the night, the sound pressure level of the transformer will exceed the city ordinance limit and low
complaints can be expected.
� T
he results did not include the effect of atmospheric conditions. The model built for 30 m awayfrom the transformer revealed that the sound pressure level can be varied by 8 dBA, if the
atmospheric condition were considered [4]. Therefore the sound pressure level at 70 m away from
the transformer can also vary and may cause more complaints. The precise variation of sound
pressure level with the distance considering the atmospheric conditions near residential area has
not been investigated.
right # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep
EFFECT OF LOAD-GENERATED TRANSFORMER NOISE 607
8. LIST OF SYMBOLS AND ABBREVIATIONS
ASU A
Copyrigh
rizona State University
dBA a
-weighted sound pressure levelFS f
ans status (on or off)L lo
ad (MVA)SRP S
alt River ProjectSPL s
ound pressure levelX d
istance (m)ACKNOWLEDGEMENTS
I wish to thank Salt River Project, for funding this research work. Special thanks to Yan Ma for her wisdom andvaluable time, my family, and fellow students for their encouragement.
REFERENCES
1. Glover JD, Sarma MS. Power System Analysis and Design, 3rd edn. Brooks Cole Thomson Learning: Pacific Grove,
CA, 2002; 72–73.
2. Reijnders H. The sound level of a transformer in operation. Smit Transformatoren bv, Tech. Rep., October, 1993; 1–
11.
3. Power transformers Part 10: determination of sound levels, IEC 60076-10-:2001(E), May, 2001.
4. Patil S. Investigation of transformer noise dependence of load, M.S. Thesis, Department of Electrical Engineering,
Arizona State University, Tempe, AZ, December, 2006.
5. IEEE standard test code for liquid-immersed distribution, power, and regulating transformers, IEEE Standard
C57.12.90-1999, June, 1999.
6. Dunsbee J, Milner M. Transformer Noise: Modern Power Transformer Practice, Feinberg R (ed). Wiley: New York,
NY, 1979; 187–208.
7. Specth TR. Transformer sound level. Westinghouse Power Advanced Development Section, Tech. Rep., M 7177,
October, 1967; 1–6.
8. Fink DG, Beaty HW. Standard Handbook of Electrical Engineering, Vol. 10, 15th edn. McGraw-Hill: New York, NY,
2006; 33–37.
9. Specth TR. Octave band sound level of transformers. Westinghouse Power Transformer Division, Tech. Rep., M
7218, December, 1970; 1–11.
10. Ordinance No. 2000. 01, City of Tempe, 2000. Available Online: www.tempe.gov/codecompliance/pdf/
ord.2000.01.pdf.
t # 2010 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2011; 21:596–607
DOI: 10.1002/etep