ECE 476 Power System Analysis
Review 1
Prof. Tom Overbye
Dept. of Electrical and Computer Engineering
University of Illinois at Urbana-Champaign
![Page 2: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/2.jpg)
Announcements
• HW5 is 3.4, 3.10, 3.14, 3.19, 3.23, 3.60, 2.38, 6.9• It should be done before the first exam, but does not need
to be turned in
• First exam is Tuesday Oct 6 during class• Closed book, closed notes, but you may bring one 8.5 by
11 inch note sheet and standard calculators. • Last name starting with A to 0 in 3017; P to Z in 3013
2
![Page 3: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/3.jpg)
Complex Power
*
cos( ) sin( )
P = Real Power (W, kW, MW)
Q = Reactive Power (var, kvar, Mvar)
S = Complex power (VA, kVA, MVA)
Power Factor (pf) = cos
If current leads voltage then pf is leading
If current
V I V I
V I
S V I j
P jQ
lags voltage then pf is lagging
(Note: S is a complex number but not a phasor)
3
![Page 4: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/4.jpg)
Reactive Compensation
44.94 kV
16.8 MW
6.4 MVR
40.0 kV
16.0 MW
16.0 MVR
16.8 MW 16.0 MW 0.0 MVR 6.4 MVR
16.0 MVR
Key idea of reactive compensation is to supply reactive
power locally. In the previous example this can
be done by adding a 16 Mvar capacitor at the load
Compensated circuit is identical to first example with
just real power load4
![Page 5: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/5.jpg)
Reactive Compensation, cont’d
• Reactive compensation decreased the line flow from 564 Amps to 400 Amps. This has advantages – Lines losses, which are equal to I2 R decrease– Lower current allows utility to use small wires, or
alternatively, supply more load over the same wires– Voltage drop on the line is less
• Reactive compensation is used extensively by utilities
• Capacitors can be used to “correct” a load’s power factor to an arbitrary value.
5
![Page 6: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/6.jpg)
Power Factor Correction Example
1
1desired
new cap
cap
Assume we have 100 kVA load with pf=0.8 lagging,
and would like to correct the pf to 0.95 lagging
80 60 kVA cos 0.8 36.9
PF of 0.95 requires cos 0.95 18.2
S 80 (60 Q )
60 - Qta
80
S j
j
cap
cap
n18.2 60 Q 26.3 kvar
Q 33.7 kvar
6
![Page 7: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/7.jpg)
Balanced 3 -- No Neutral Current
* * * *
(1 0 1 1
3
n a b c
n
an an bn bn cn cn an an
I I I I
VI
Z
S V I V I V I V I
7
![Page 8: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/8.jpg)
Three-Phase - Wye Connection
• There are two ways to connect 3 systems– Wye (Y)– Delta ()
an
bn
cn
Wye Connection Voltages
V
V
V
V
V
V
8
![Page 9: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/9.jpg)
Delta-Wye Transformation
Y
phase
To simplify analysis of balanced 3 systems:
1) Δ-connected loads can be replaced by 1
Y-connected loads with Z3
2) Δ-connected sources can be replaced by
Y-connected sources with V3 30Line
Z
V
9
![Page 10: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/10.jpg)
Per Phase Analysis Procedure
• To do per phase analysis
1. Convert all load/sources to equivalent Y’s
2. Solve phase “a” independent of the other phases
3. Total system power S = 3 Va Ia*
4. If desired, phase “b” and “c” values can be determined by inspection (i.e., ±120° degree phase shifts)
5. If necessary, go back to original circuit to determine line-line values or internal values.
10
![Page 11: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/11.jpg)
Line Resistance
-8
-8
Line resistance per unit length is given by
R = where is the resistivityA
Resistivity of Copper = 1.68 10 Ω-m
Resistivity of Aluminum = 2.65 10 Ω-m
Example: What is the resistance in Ω / mile of a
-8
2
1" diameter solid aluminum wire (at dc)?
2.65 10 Ω-m1609 0.084
0.0127m
mR
mile mile
11
![Page 12: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/12.jpg)
Magnetics Review
• Ampere’s circuital law:
e
F = mmf = magnetomtive force (amp-turns)
= magnetic field intensity (amp-turns/meter)
d = Vector differential path length (meters)
= Line integral about closed path (d is tangent to path)
I =
eF d I
H l
H
l
l
Algebraic sum of current linked by
12
![Page 13: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/13.jpg)
Magnetics Review
• Ampere’s circuital law:
e
F = mmf = magnetomtive force (amp-turns)
= magnetic field intensity (amp-turns/meter)
d = Vector differential path length (meters)
= Line integral about closed path (d is tangent to path)
I =
eF d I
H l
H
l
l
Algebraic sum of current linked by
13
![Page 14: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/14.jpg)
Line Inductance Example
Calculate the reactance for a balanced 3, 60Hz
transmission line with a conductor geometry of an
equilateral triangle with D = 5m, r = 1.24cm (Rookconductor) and a length of 5 miles.
0 1 1 1ln( ) ln( ) ln( )
2 'a a b ci i ir D D
a
Since system is assumed
balanced
i b ci i
14
![Page 15: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/15.jpg)
Line Inductance Example, cont’d
a
0a
0
70
3
6
Substituting
i
Hence
1 1ln ln
2 '
ln2 '
4 10 5ln ln
2 ' 2 9.67 10
1.25 10 H/m
b c
a a
a
a
i i
i ir D
Di
r
DL
r
15
![Page 16: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/16.jpg)
Conductor Bundling
To increase the capacity of high voltage transmission
lines it is very common to use a number of
conductors per phase. This is known as conductor
bundling. Typical values are two conductors for
345 kV lines, three for 500 kV and four for 765 kV.
16
![Page 17: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/17.jpg)
Bundled Conductors, cont’d
14
12 13 14
1
12 1
1
14
15 16 17 18 2 3 4
1 19 1
geometric mean radius (GMR) of bundle
( ' ) for our example
( ' ) in general
geometric mean distance (GMD) of
conductor 1 to phase b.
( )
(
b
bb
b
b b b ab
c
R
r d d d
r d d
D
d d d d D D D D
D d d
14
,10 1,11 1,12 2 3 4) c c c acd d D D D D
17
![Page 18: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/18.jpg)
Inductance of Bundle, cont’d
0a 1
But remember each bundle has b conductors
in parallel (4 in this example). So
L / ln2 b
DL b
R
18
![Page 19: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/19.jpg)
Bundle Inductance Example
0.25 M0.25 M
0.25 M
Consider the previous example of the three phases
symmetrically spaced 5 meters apart using wire
with a radius of r = 1.24 cm. Except now assume
each phase has 4 conductors in a square bundle,
spaced 0.25 meters apart. What is the new inductance
per meter?
2 3
13 4
b
70a
1.24 10 m ' 9.67 10 m
R 9.67 10 0.25 0.25 2 0.25
0.12 m (ten times bigger!)
5L ln 7.46 10 H/m
2 0.12
r r
19
![Page 20: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/20.jpg)
Transposition
• To keep system balanced, over the length of a transmission line the conductors are rotated so each phase occupies each position on tower for an equal distance. This is known as transposition.
Aerial or side view of conductor positions over the length
of the transmission line.
20
![Page 21: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/21.jpg)
Inductance of Transposed Line
13
m 12 13 23
0 0a
70
Define the geometric mean distance (GMD)
D
Then for a balanced 3 system ( - - )
1 1ln ln ln
2 ' 2 '
Hence
ln 2 10 ln H/m2 ' '
a b c
ma a a
m
m ma
d d d
I I I
DI I I
r D r
D DL
r r
21
![Page 22: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/22.jpg)
Inductance with Bundling
b
0a
70
If the line is bundled with a geometric mean
radius, R , then
ln2
ln 2 10 ln H/m2
ma
b
m ma
b b
DI
R
D DL
R R
![Page 23: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/23.jpg)
Line Conductors, cont’d
• Total conductor area is given in circular mils. One circular mil is the area of a circle with a diameter of 0.001 = 0.00052 square inches
• Example: what is the area of a solid, 1” diameter circular wire? Answer: 1000 kcmil (kilo circular mils)
• Because conductors are stranded, the equivalent radius must be provided by the manufacturer. In tables this value is known as the GMR and is usually expressed in feet.
23
![Page 24: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/24.jpg)
Review of Electric Fields
eA
2
To develop a model for line capacitance we
first need to review some electric field concepts.
Gauss's law:
d = q (integrate over closed surface)
where
= electric flux density, coulombs/m
d = differential
D a
D
a
2
e
area da, with normal to surface
A = total closed surface area, m
q = total charge in coulombs enclosed
24
![Page 25: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/25.jpg)
Gauss’s Law Example
•Similar to Ampere’s Circuital law, Gauss’s Law is most useful for cases with symmetry.•Example: Calculate D about an infinitely long wire that has a charge density of q coulombs/meter.
Since D comes
radially out inte-
grate over the
cylinder bounding
the wireeA
d 2 q
where radially directed unit vector2
D Rh qh
qR
r r
D a
D a a
25
![Page 26: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/26.jpg)
Line Capacitance, cont’d
aa a
To eliminate mutual capacitance we'll again
assume we have a uniformly transposed line.
For the previous three conductor example:
q 2ince q = C
ln
a
a
V V
S V CDVr
26
![Page 27: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/27.jpg)
Bundled Conductor Capacitance
1
1cb 12
Similar to what we did for determining line
inductance when there are n bundled conductors,
we use the original capacitance equation just
substituting an equivalent r
Note fo
adius
r t
( )
he
Rn
nrd d
b
capacitance equation we use r rather
than r' which was used for R in the inductance
equation
27
![Page 28: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/28.jpg)
Line Capacitance, cont’d
1
m
13
m
1cb 12
-12o
For the case of uniformly transposed lines we
use the same GMR, D , as before.
2
ln
where
D
R ( ) (note r NOT r')
ε in air 8.854 10 F/m
n
mcb
ab ac bc
n
CD
R
d d d
rd d
28
![Page 29: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/29.jpg)
Line Capacitance Example
•Calculate the per phase capacitance and susceptance of a balanced 3, 60 Hz, transmission line with horizontal phase spacing of 10m using three conductor bundling with a spacing between conductors in the bundle of 0.3m. Assume the line is uniformly transposed and the conductors have a 1cm radius.
29
![Page 30: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/30.jpg)
Line Capacitance Example, cont’d
13
13
m
1211
c 11
8
(0.01 0.3 0.3) 0.0963 m
D (10 10 20) 12.6 m
2 8.854 101.141 10 F/m
12.6ln
0.09631 1
X2 60 1.141 10 F/m
2.33 10 -m (not / m)
cbR
C
C
30
![Page 31: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/31.jpg)
Transmission Line Equivalent Circuit
•Our current model of a transmission line is shown below
For operation at frequency , let z = r + j L
and y = g +j C (with g usually equal 0)
Units on
z and y are
per unit
length!
31
![Page 32: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/32.jpg)
Derivation of V, I Relationships
We can then derive the following relationships:
( )
( ) ( )
dV I z dx
dI V dV y dx V y dx
dV x dI xz I yV
dx dx
32
![Page 33: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/33.jpg)
Setting up a Second Order Equation
2
2
2
2
( ) ( )
We can rewrite these two, first order differential
equations as a single second order equation
( ) ( )
( )0
dV x dI xz I yV
dx dx
d V x dI xz zyVdxdx
d V xzyV
dx
33
![Page 34: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/34.jpg)
V, I Relationships, cont’d
2 2
Define the propagation constant as
where
the attenuation constant
the phase constant
Use the Laplace Transform to solve. System
has a characteristic equation
( ) ( )( ) 0
yz j
s s s
34
![Page 35: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/35.jpg)
Determining Line Voltage, cont’d
1 2
1 2
1
1 2
2
c
( ) cosh( ) sinh( )
(0) cosh(0) sinh(0)
Since cosh(0) 1 & sinh(0) 0
( )sinh( ) cosh( )
( ) cosh( ) sinh( )
where Z characteristic
R
R
R RR
R R c
V x K x K x
V V K K
K V
dV xzI K x K x
dx
zI I z zK I
yyz
V x V x I Z x
zy
impedance
35
![Page 36: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/36.jpg)
Lossless Transmission Lines
c
c
c
For a lossless line the characteristic impedance, Z ,
is known as the surge impedance.
Z (a real value)
If a lossless line is terminated in impedance
Z
Then so we get...
R
R
R c R
jwl ljwc c
VI
I Z V
36
![Page 37: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/37.jpg)
Lossless Transmission Lines
2
( ) cosh sinh
( ) cosh sinh
( )( )
V(x)Define as the surge impedance load (SIL).
Since the line is lossless this implies
( )
( )
R R
R R
c
c
R
R
V x V x V x
I x I x I x
V xZ
I x
Z
V x V
I x I
If P > SIL then line consumes
vars; otherwise line generates vars.
37
![Page 38: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/38.jpg)
Transmission Matrix Model, cont’d
S
S
VWith
I
Use voltage/current relationships to solve for A,B,C,D
cosh sinh
cosh sinh
cosh sinh
1sinh cosh
R
R
S R c R
RS R
c
c
c
VA B
IC D
V V l Z I l
VI I l l
Z
l Z lA B
l lC DZ
T
38
![Page 39: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/39.jpg)
Equivalent Circuit Model
The common representation is the equivalent circuit
Next we’ll use the T matrix values to derive the
parameters Z' and Y'.
39
![Page 40: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/40.jpg)
Equivalent Circuit Parameters
'' 2
' '1 '
2
' '2 2
' ' ' '' 1 1
4 2
' '1 '
2' ' ' '
' 1 14 2
S RR R
S R R
S S R R
S R R
S R
S R
V V YV I
ZZ Y
V V Z I
Y YI V V I
Z Y Z YI Y V I
Z YZ
V V
Z Y Z YI IY
40
![Page 41: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/41.jpg)
Three Line Models
(longer than 200 miles)
tanhsinh ' 2use ' ,2 2
2 (between 50 and 200 miles)
use and 2
(less than 50 miles)
use (i.e., assume Y is zero)
ll Y Y
Z Zll
YZ
Z
Long Line Model
Medium Line Model
Short Line Model
41
![Page 42: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/42.jpg)
Power Transfer in Lossless Lines
21 1 2
12 12 12
12 12
1 212 12
If we assume a line is lossless with impedance jX and
are just interested in real power transfer then:
90 90
Since - cos(90 ) sin , we get
sin
Hence the maximu
V V VP jQ
Z Z
V VP
X
1 212
m power transfer is
Max V VP
X
42
![Page 43: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/43.jpg)
Ideal Transformer
• First we review the voltage/current relationships for an ideal transformer– no real power losses– magnetic core has infinite permeability– no leakage flux
• We’ll define the “primary” side of the transformer as the side that usually takes power, and the secondary as the side that usually delivers power.– primary is usually the side with the higher voltage, but
may be the low voltage side on a generator step-up transformer.
43
![Page 44: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/44.jpg)
Ideal Transformer Relationships
1 1 2 2
1 21 1 2 2
1 2 1 1
1 2 2 2
Assume we have flux in magnetic material. Then
= turns ratio
m
m m
m m
m
N N
d d d dv N v N
dt dt dt dtd v v v N
adt N N v N
44
![Page 45: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/45.jpg)
Current/Voltage Relationships
'1 1 2 2
1 2 1 2'
1 2 12
1 2
1 2
If is infinite then 0 . Hence
1or
Then
0
10
N i N i
i N i NN i N ai
av v
i ia
45
![Page 46: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/46.jpg)
Transformer Equivalent Circuit
Using the previous relationships, we can derive an
equivalent circuit model for the real transformer
' 2 '2 2 1 2
' 2 '2 2 1 2
This model is further simplified by referring all
impedances to the primary side
r e
e
a r r r r
x a x x x x
46
![Page 47: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/47.jpg)
Simplified Equivalent Circuit
47
![Page 48: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/48.jpg)
Calculation of Model Parameters
• The parameters of the model are determined based upon – nameplate data: gives the rated voltages and power– open circuit test: rated voltage is applied to primary with
secondary open; measure the primary current and losses (the test may also be done applying the voltage to the secondary, calculating the values, then referring the values back to the primary side).
– short circuit test: with secondary shorted, apply voltage to primary to get rated current to flow; measure voltage and losses.
48
![Page 49: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/49.jpg)
Per Unit Calculations
• A key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually have to refer
impedances to the different sides of the transformers
• This problem is avoided by a normalization of all variables.
• This normalization is known as per unit analysis.
actual quantityquantity in per unit
base value of quantity
49
![Page 50: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/50.jpg)
Per Unit Conversion Procedure, 1f
1. Pick a 1 VA base for the entire system, SB
2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unitNote, per unit conversion on affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
50
![Page 51: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/51.jpg)
Per Unit Example
Solve for the current, load voltage and load power
in the circuit shown below using per unit analysis
with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV.
Original Circuit51
![Page 52: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/52.jpg)
Three Phase Per Unit
1. Pick a 3 VA base for the entire system,
2. Pick a voltage base for each different voltage level, VB. Voltages are line to line.
3. Calculate the impedance base
Procedure is very similar to 1 except we use a 3 VA base, and use line to line voltage bases
3BS
2 2 2, , ,3 1 1
( 3 )
3B LL B LN B LN
BB B B
V V VZ
S S S
Exactly the same impedance bases as with single phase!
52
![Page 53: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/53.jpg)
Three Phase Per Unit, cont'd
4. Calculate the current base, IB
5. Convert actual values to per unit
3 1 13 1B B
, , ,
3I I
3 3 3B B B
B LL B LN B LN
S S S
V V V
Exactly the same current bases as with single phase!
53
![Page 54: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/54.jpg)
Three Phase Transformers
• There are 4 different ways to connect 3 transformers
Y-Y D-D
Usually 3 transformers are constructed so all windings
share a common core54
![Page 55: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/55.jpg)
3f Transformer Interconnections
D-Y Y-D
55
![Page 56: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/56.jpg)
Load Models
• Ultimate goal is to supply loads with electricity at constant frequency and voltage
• Electrical characteristics of individual loads matter, but usually they can only be estimated– actual loads are constantly changing, consisting of a large
number of individual devices– only limited network observability of load characteristics
• Aggregate models are typically used for analysis• Two common models
– constant power: Si = Pi + jQi
– constant impedance: Si = |V|2 / Zi
56
![Page 57: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/57.jpg)
Bus Admittance Matrix or Ybus
• First step in solving the power flow is to create what is known as the bus admittance matrix, often call the Ybus.
• The Ybus gives the relationships between all the bus current injections, I, and all the bus voltages, V,
I = Ybus V
• The Ybus is developed by applying KCL at each bus in the system to relate the bus current injections, the bus voltages, and the branch impedances and admittances
57
![Page 58: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/58.jpg)
Ybus Example
Determine the bus admittance matrix for the network
shown below, assuming the current injection at each
bus i is Ii = IGi - IDi where IGi is the current injection into the
bus from the generator and IDi is the current flowing into the load
58
![Page 59: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/59.jpg)
Ybus Example, cont’d
1 1
2 2
3 3
4 4
We can get similar relationships for buses 3 and 4
The results can then be expressed in matrix form
0
0
0 0
bus
A B A B
A A C D C D
B C B C
D D
I Y Y Y Y V
I Y Y Y Y Y Y V
I Y Y Y Y V
I Y Y V
I Y V
For a system with n buses, Ybus is an n by n
symmetric matrix (i.e., one where Aij = Aji)
59
![Page 60: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/60.jpg)
Ybus General Form
• The diagonal terms, Yii, are the self admittance terms, equal to the sum of the admittances of all devices incident to bus i.
• The off-diagonal terms, Yij, are equal to the negative of the sum of the admittances joining the two buses.
• With large systems Ybus is a sparse matrix (that is, most entries are zero)
• Shunt terms, such as with the line model, only affect the diagonal terms.
60
![Page 61: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/61.jpg)
Modeling Shunts in the Ybus
from other lines
2 2
Since ( )2
21 1
Note
kcij i j k i
kcii ii k
k k k kk
k k k k k k k
YI V V Y V
YY Y Y
R jX R jXY
Z R jX R jX R X
61
![Page 62: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/62.jpg)
Two Bus System Example
1 21 1
1 1
2 2
( ) 112 16
2 0.03 0.04
12 15.9 12 16
12 16 12 15.9
cYV VI V j
Z j
I Vj j
I Vj j
62
![Page 63: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/63.jpg)
Power Flow Analysis
• When analyzing power systems we know neither the complex bus voltages nor the complex current injections
• Rather, we know the complex power being consumed by the load, and the power being injected by the generators plus their voltage magnitudes
• Therefore we can not directly use the Ybus
equations, but rather must use the power balance equations
63
![Page 64: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/64.jpg)
Power Balance Equations, cont’d
** * *
i1 1
S
This is an equation with complex numbers.
Sometimes we would like an equivalent set of real
power equations. These can be derived by defining
n n
i i i ik k i ik kk k
ik ik ik
i
V I V Y V V Y V
Y G jB
V
jRecall e cos sin
iji i i
ik i k
V e V
j
64
![Page 65: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/65.jpg)
Real Power Balance Equations
* *i
1 1
1
i1
i1
S ( )
(cos sin )( )
Resolving into the real and imaginary parts
P ( cos sin )
Q ( sin cos
ikn n
ji i i ik k i k ik ik
k k
n
i k ik ik ik ikk
n
i k ik ik ik ik Gi Dik
n
i k ik ik ik ik
P jQ V Y V V V e G jB
V V j G jB
V V G B P P
V V G B
)k Gi DiQ Q
65
![Page 66: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/66.jpg)
Gauss Iteration
There are a number of different iterative methods
we can use. We'll consider two: Gauss and Newton.
With the Gauss method we need to rewrite our
equation in an implicit form: x = h(x)
To iterate we fir (0)
( +1) ( )
st make an initial guess of x, x ,
and then iteratively solve x ( ) until we
find a "fixed point", x, such that x (x).ˆ ˆ ˆ
v vh x
h
66
![Page 67: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/67.jpg)
Gauss Iteration Example
( 1) ( )
(0)
( ) ( )
Example: Solve - 1 0
1
Let = 0 and arbitrarily guess x 1 and solve
0 1 5 2.61185
1 2 6 2.61612
2 2.41421 7 2.61744
3 2.55538 8 2.61785
4 2.59805 9 2.61798
v v
v v
x x
x x
v
v x v x
67
![Page 68: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/68.jpg)
Gauss Power Flow
** * *
i1 1
* * * *
1 1
*
*1 1,
*
*1,
We first need to put the equation in the correct form
S
S
S
S1
i i
i
i
n n
i i i ik k i ik kk k
n n
i i i ik k ik kk k
n ni
ik k ii i ik kk k k i
ni
i ik kii k k i
V I V Y V V Y V
V I V Y V V Y V
Y V Y V Y VV
V Y VY V
68
![Page 69: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/69.jpg)
Gauss Two Bus Power Flow Example
•A 100 MW, 50 Mvar load is connected to a generator •through a line with z = 0.02 + j0.06 p.u. and line charging of 5 Mvar on each end (100 MVA base). Also, there is a 25 Mvar capacitor at bus 2. If the generator voltage is 1.0 p.u., what is V2?
SLoad = 1.0 + j0.5 p.u.
69
![Page 70: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/70.jpg)
Gauss Two Bus Example, cont’d
2
2 bus
bus
22
The unknown is the complex load voltage, V .
To determine V we need to know the .
15 15
0.02 0.06
5 14.95 5 15Hence
5 15 5 14.70
( Note - 15 0.05 0.25)
jj
j j
j j
B j j j
Y
Y
70
![Page 71: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/71.jpg)
Gauss Two Bus Example, cont’d
*2
2 *22 1,2
2 *2
(0)2
( ) ( )2 2
1 S
1 -1 0.5( 5 15)(1.0 0)
5 14.70
Guess 1.0 0 (this is known as a flat start)
0 1.000 0.000 3 0.9622 0.0556
1 0.9671 0.0568 4 0.9622 0.0556
2 0
n
ik kk k i
v v
V Y VY V
jV j
j V
V
v V v V
j j
j j
.9624 0.0553j71
![Page 72: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/72.jpg)
Gauss Two Bus Example, cont’d
2
* *1 1 11 1 12 2
1
0.9622 0.0556 0.9638 3.3
Once the voltages are known all other values can
be determined, such as the generator powers and the
line flows
S ( ) 1.023 0.239
In actual units P 102.3 MW
V j
V Y V Y V j
1
22
, Q 23.9 Mvar
The capacitor is supplying V 25 23.2 Mvar
72
![Page 73: ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu](https://reader035.vdocuments.site/reader035/viewer/2022081506/5697bf911a28abf838c8e671/html5/thumbnails/73.jpg)
Slack Bus
• In previous example we specified S2 and V1 and then solved for S1 and V2.
• We can not arbitrarily specify S at all buses because total generation must equal total load + total losses
• We also need an angle reference bus.• To solve these problems we define one bus as the
"slack" bus. This bus has a fixed voltage magnitude and angle, and a varying real/reactive power injection.
73