Functional RangeEC2 PLUS :AMF Relay
C&S Electric Limited(Protection & Control Division)
-
8/13/2019 EC2 PLUS
2/24
EC 2 PLUS :AMF Relay
2
Contents
1 Introduction and Application
2 Features and Characteristics
2.1General features2.2 AMF function features
2.3 Measurement, display and supervision features2.4 Protection features2.5 Communication features
3 Operating Mode
3.1 Automatic mode3.2 Manual mode3.3 Test mode
4 Mains Supervision
4.1 Parameter selection4.1.1 Voltage4.1.2 Frequency4.1.3 Frequency blocking voltage4.2 Circuit breaker supervision
5 Generator Supervision
5.1 Parameter selection5.2 Overload , CT Ratio, Run time, Rest time, Room
temp, Ex battery lower setting
5.3 Run time and Rest time5.4 Exchange battery voltage supervision5.5 DG battery voltage supervision5.6 Thermal management5.7 Emergency stop5.8 Time circuits5.9 Time elements5.9.1 Auto Hooter reset period5.9.2 Generator CB on delay5.9.3 Generator Re-cooling time5.9.4 Generator cranking period5.9.5 Generator cranking wait period5.9.6 Mains restoration time
5.9.7 Generator start delay5.9.8 Delayed supervision time5.9.9 Generator off delay
6 Design
6.1 Connection6.2 Output relays6.3 Inputs6.3.1 Mains voltage connection6.3.2 Generator voltage connection6.3.3 Auxiliary supply
6.3.4 CB feedback No contacts
6.3.5 External fault inputs6.3.6 Internally processed fault display6.4 Display6.4.1 Display for 16 * 2 LCD6.4.2 Display for 20 * 4 LCD
6.5 LEDs6.6 Front panel keypad6.7 GSM communication6.8 Protection6.8.1 Over load6.8.2 Phase reversal6.9 Digital inputs
7 Parameters Procedure & Display
7.1 Mode selection7.2 Measuring parameters display
8 Getting Started
8.1 EC2+ display for MMI-18.2 Faults displayed on LCD8.3 EC2+ display for MMI-28.4 Edit para mode8.5 View para mode8.6 Selection mode8.7 Password modes8.8 Load default mode
9 Functional Specification
10 Performance Specification
11 Hardware Specification
12 Snap Shot of CSE LIVE LINK Frontend Software
13 Front Panel of EC2 PLUS
14 Snap Shot of Data Logging & Data
Management in Standard ExcelFormat
15 Snap Shot of Daily Energy Reportin Excel Format
16 Terminal Details
16.1 Terminal arrangement
16.2 Terminal description
17 Order Form
-
8/13/2019 EC2 PLUS
3/24
EC 2 PLUS :AMF Relay
3
1. Introduction and Application
AMF & Engine Control Relay Type - EC2 PLUS
EC2 PLUS is designed for the control of emergency andstandby power systems. It integrates the functions of enginestart relay, engine and alternator supervision and
annunciator. The relay measures and displays variouselectrical parameters and has a user friendly MMI in theform of a keypad and a LCD display.
EC2 PLUS measures and displays various parameters likevoltages, currents, power factors, active power consumedin all the three phases. It also measures the energyconsumed by the load and records start and stop times ofthe generator. The display of month-wise energyconsumption is available.
EC2 PLUS provides the overload protection and thepermissible overload limit can be selected on the relay.The Actual load current is displayed by selecting the actualCT ratio used for the purpose of measurement.
The relay has excellent communication features includingGPRS and SMS connectivity through Modem and any faultevent thus can be immediately conveyed to the base stationor to the concerned persons.
2. Features & Characteristics
Features of the relays are explained in five differentcategories like General features, AMF features,Measurement Display and Supervision features, Protectionsfeatures and Communication related features.
2.1 General Features
Micro controller technology
Wide range of auxiliary supply: 7 V to 35VDC.
Withstands a dip to 0V of auxiliary supply for 1second.
Alphanumeric LCD displays with keypad for easy ofoperation.
LED indications to know the status of variousparameters
Provision for operating externally mounted 12Auxiliary relays for control and protection purpose.
Isolated inputs and outputs.
Periodic test feature
Flush Mounting
2.2 AMF Funct ion Features
Continuous supervision of mains & D.G breakerstatus - ensures human /equipment safety
Internal interlock for EB & DG breaker for fail safe
operation.
DG starting process supervision Indication of CB status
Wide array of time circuits for start delay, stop delay,mains restoration, re-cooling etc.
2. 3 Measurement, Display & Supervision Features
Measures and displays different electrical parametersof mains and generator for different phases including
Current, Voltage, Frequency, Power Factor, Power andEnergy.
Supervision of three phase mains voltages for UV,OV & unbalance.
Supervision of D.G voltages for UV, OV.
Supervision of mains & D.G frequency.
Supervision of battery voltage.
Parameter setting from front panel keypad.
24 LEDs to indicate status of the relay and the type offault occurred. Fault indications in RED color & statusindications in GREEN color.
Exchange battery voltage supervision.
Fuel level monitoring at two different levels.
2. 4 Protection Features
Over-frequency indication / shutdown.
Internal fault annunciation for fail to start, over speed& low battery.
Overload protection with selectable overload setting.
Protection against undesired conditions of variousDigital inputs.
Protection against LLOP, HCT, Faults in the engine.
2. 5 Communication Features
Connectivity through Modem on GPRS for transfer ofdata and event.
Connectivity through Modem on SMS to maximum 6persons for event related information transfer.
Records and communicates monthly energyconsumed by Generator and Mains to base station(As shown in section 15).
Records and communicates the five Logs ofGenerator start and stop times to base station tomonitor run hours of the DG.
EC2 PLUS gives first priority to Base stationcommunication via TCP/IP through GPRS. In case ofunavailability of GPRS, EC2 PLUS update its status toMonitoring base station via SMS communication.
Data communication occurs through TCP/IP protocol.IP address of monitoring base station is configurablein EC2 PLUS relay.
CSE LIVELINK front end software interface gives thecomplete data base management for AMF controller
-
8/13/2019 EC2 PLUS
4/24
EC 2 PLUS :AMF Relay
4
at base station. Front end monitoring interface s/w,gathers all the information of EC2 PLUS like runningenergy, voltages, load currents, PF , Run hours , DG/Mains Fault status in Excel format. One base stationcan handle more then 100 EC2 PLUS simultaneouslyvia GSM/GPRS modem connection (as shown insection 13,14)
EC2 PLUS communication record at base station isdistinguished through unique Site Name and Site Nowhich is configurable in relay.
3. Operating Modes
EC2 PLUS operates in one of the three modes as describedbelow. The operating mode can be selected from frontkeypad. The three modes are:
1 . Automatic
2 . Manual3 . Test
The three operating modes are described below:
3.1 Automatic Mode
In Automatic mode starting and stopping of the engine andon/off control of circuit breakers is governed by sixconditions: Availability of healthy mains supply, the roomtemperature (analog i/p) ,room temperature (digital i/p),*BTS2 voltage , *BTS3 voltage and the Exchange battery
voltage. If mains supply is healthy, genset is not started orswitched off if running. If mains supply is unhealthy then alow Exchange battery voltage as compared to lower setvalue or a high room temperature(digital i/p) or low roomtemperature (analog i/p) as compared to set value or low*BTS2 voltage or low *BTS3 voltage start the genset.Gensetwill be stopped when mains recovered.
NOTE: *BTS2 voltage and *BTS3 voltage areavailable only in version 1.1
3.2 Manual Mode
In this mode EC2 PLUS ignores mains voltage. It onlyresponds to STARTand STOP commands from the keypad.Similarly generator and mains CBs are also operated fromthe keypad.
Precaution:Before giving Start command to generator,one must ensure that the generator CB is open. Start keyshould be held down until the engine reaches thresholdspeed. The generator CB may now be switched on fromkeypad provided that the Mains CB is off. Stop key turns offthe engine (remove this line).
When stop key is pressed, the generator CB is switched offand then the generator is stopped.
The mains CB can also be activated from the keypad.Interlocking of mains and generator CBs is built into thefirmware.
3.3 Test Mode
In this mode no-load and load test run of the Gen-set is
possible. In TEST mode, the engine is automatically startedand supervised and it is checked whether the generatorhas reached its rated voltage. Should a mains failure occurduring test mode operation, the mains emergencyoperation is initiated automatically.
Mains CB open/close switches are active. Similarlygenerator CB open/close switches are also active.
4. Mains Supervision
EC2 PLUS continuously monitors three phase mains supplyvoltage and detects unhealthy conditions. If unhealthy
conditions are detected, then it trips mains CB and initiatesstarting of genset depending upon thermal managementcondition. Unhealthy condition shall be defined by user inEdit mode.
Unhealthy conditions are defined as follows:
If voltage of any phase falls below a lower set limit orexceeds a higher set limit.
If difference between voltages of any two phasesexceeds a preset limit (% unbalance)
If frequency falls below a lower set limit or exceeds ahigher set limit.
If Single phase enable is selected then all thephases must become unhealthy for a valid unhealthycondition.
4.1 Parameter Selection
4.1.1 Voltage
User selects lower and upper limits of line voltage inparameter setting mode. EC2 PLUS can be used for singlephase / 3 phase systems. However the user can set theunder and over voltage values.
If mains voltage in any phase either exceeds the upper setlimit or falls below the lower set limit, then it is deemed tobe an unhealthy condition. In Auto mode the relay tripsmains CB if the condition prevails continuously for the userdefined time delay.EC2 PLUS is also provided with mainsvoltage unbalance monitoring.
4.1.2 Frequency
User selects lower and upper limits of acceptable frequency.If the frequency is beyond the limits then it is considered tobe an unhealthy supply condition and the mains CB must
trip if the condition prevails longer than user defined timedelay.
-
8/13/2019 EC2 PLUS
5/24
EC 2 PLUS :AMF Relay
5
4.1.3 Frequency Blocking Voltage
Frequency supervision is disabled below this voltage.
4.2 Circuit Breaker Supervision
The unit is also equipped with Circuit Breaker Supervision.For supervising the healthiness of circuit breaker thefeedback is to be connected at terminal 19 & 21 fromnormally open contacts of Mains & Gen. Circuit Breakerrespectively.
After issuing closing command, if the feedback signal fromNO contact of breaker is not received, the unit will indicatea fault by displaying message on the LCD (16*2) displayfor Mains & Generator respectively.
5. Generator Supervision
While the genset supplies power, it can also show all thoseabnormalities which were anticipated in mains supervision;there are however two added parameters: engine speedand battery voltage.
5.1 Parameter Selection
The voltage/frequency limits for the DG set can be setindependently. The setting procedures are similar to themains parameters settings.
The over-speed is sensed through the frequency of the
generating set. In case of high frequency the relayaccordingly trips the generator CB and proceeds to shut-down the engine.
5.2 Overload, CT Ratio, Run Time, Rest Time,
Room Temperature, Exchange Battery Lower Setting
Min Max Increment in Step
Over Load 10A 30A 0.5A
CT Ratio 1 10 0.5
Run Time 1Hr 10Hr 0.5Hr
Rest Time 1Hr 10Hr 0.5Hr
Room Temp 30deg 100deg 5deg
Exchange Battery 40V 48V 1V Lower Setting
*NOTE: Editable through serial comm. port
5.3 Run Time and Rest Time
Generator will continuously run till the set Run Time elapsesafter that generator will shut down and LCD(20*4) will
display REST_TIME in its status(screen nos 1,last line).Itwill remain in the off state till the set Rest time expires.
5.4 Exchange Battery Voltage Supervision
EC2 PLUS relay continuously monitors exchange batteryvoltage. If the Exchange battery voltage falls below a lowerset value, it only gives the visual indication by glowing theLED marked Exchange Battery Lowon the front plateof the relay. When the exchange battery voltage returns to
its operating limit, then the LED marked ExchangeBattery Low returns to normal state.
5.5 DG Battery Voltage Supervision
EC2 PLUS relay continuously monitors DG battery voltageand if the voltage falls below a set value, LCD (20*4) willdisplay DG_BAT_LOW in its fault status. Indication of highbattery voltage is also available with fixed settings i.e. iflow battery voltage is set below 12 V high battery voltagewill be automatically set as 14 V & if low battery voltage isset above 12 V, setting of high battery will be 28V.
5.6 Thermal Management
EC2 PLUSrelay will not start Generator even when mainsfail. If exchange battery voltage exceeds higher set valueand room temperature (analog i/p) is more than set valueand room temp (digital i/p) is low and *BTS2 voltage and*BTS3 voltages are high when all these above conditionssatisfies EC2_PLUS will not issue start command and LCD(20*4) will display DG_ON_HOLD in its status (screen nos1, last line). When any of this condition gets violated andmains voltage is not present generator will get the startcommand.
NOTE: *BTS2 voltage and *BTS3 voltage are available
only in version 1.1
5.7 Emergency Stop
The Gen-set can be stopped in the event of an emergencyby shorting terminal marked Emergency to the negativeterminal of battery. In this case the re-cooling phase isbypassed.
5.8 Time Circuits
EC2 PLUS provides a user friendly MMI (Man-MachineInterface) for setting different time circuits for engine startdelay, stop delay, mains restoration, re-cooling etc.All theseparameters can be viewed in MMI-2.
The Table 1 gives the entire time settings.
5.9 Time Elements
5.9.1 Auto Hooter Reset Period
It is related to hooter operation and it can be set by theuser. It starts as soon as hooter starts. If hooter is not silencedwithin auto-silence period, then at the expiry of this periodhooter is automatically stopped.
-
8/13/2019 EC2 PLUS
6/24
EC 2 PLUS :AMF Relay
6
5.9.2 Generator CB on Delay:
Generator circuit breaker is not closed immediately aftergenerator exceeds ignition speed. A time delay isintroduced. This time delay can be set by the user. Duringthis time EC2 PLUS checks if generator voltage is healthy.
This timer starts after generator voltage reaches safe limit.
5.9.3 Generator Re-cooling Time:
Engine is not switched off immediately after GCB is opened.The Gen-set needs time to cool off. If it is stopped coolingaction also stops and the heat stored in its mass starts raisingits temperature. The temperature can attain dangerouslevels depending on the duty to which Gen-set was subjectedto before GCB was opened. Generator is allowed to runat no load for sometime, this is known as re-cooling time.Re-cooling time can be set by the user.
5.9.4 Generator Cranking Period
Engine is cranked for the duration of Generator CrankingPeriod and then waits for engine to start. If engine starts(generator Voltage > Ignition voltage OR Ignition Oncontact closes), during Generator Cranking Period thenalso cranking is stopped. This period can be set by theuser.
5.9.5 Generator Cranking Wait Period
It is the time interval between two start attempts. During
this period cranking is not repeated.
5.9.6 Mains Restoration Time:
It is the time from mains recovery to closing of mains CB.This timer is started when mains recover. Mains must remainhealthy during this period otherwise the timer is reset.
5.9.7 Generator Start Delay:
Time between mains failure and initiation of start procedure.
5.9.8 Delayed Supervision Time:
Oil pressure takes time to build up and hence low pressurealarm is initially on. Thus the alarm is not meaningful. Wemust give time for oil pressure to build up and then monitorthe alarm. The process is called Delayed Supervisionand this time is user settable.The timer starts after generator voltage exceeds ignitionvoltage.
This is also a form of delayed supervision.When GCB is closed, entire load is taken by the generator.If there are loads which draw heavy starting current, thengenerator voltage will dip as soon as GCB is closed. Thedip will persist for some time. During this time generatorvoltage should not be monitored otherwise EC2 PLUS willdecide to trip generator. The time allowed for this delayedsupervision is Generator tripping delay. It is usersettable.
5.9.9 Generator Off Delay:
This timer is started as soon as generator unhealthycondition is detected and generator is turned off when the
set time elapses. This time is set to Generator Off delay.
-
8/13/2019 EC2 PLUS
7/24
EC 2 PLUS :AMF Relay
7
Description Displayed As Range Steps Default Setting
Mains Rated Voltage MAINS RATED VOLT 0-999 1V 230V
Mains Under Voltage MAINS RATED VOLT 0-999 1V 180V
Mains Over Voltage MAINS OVER VOLT 0-999 1V 250V
Mains Rated Frequency MAINS RATED FREQ 40-99.9 0.1 Hz 50Hz
Mains Under Frequency MAINS UNDER FREQ 40-99.9 0.1 Hz 47.5Hz
Mains Over Frequency MAINS OVER FREQ 40-99.9 0.1 Hz 52.5Hz
Generator Rated Voltage GEN RATED VOLT 0-999 1V 230V
Generator Under Voltage GEN UNDER VOLT 0-999 1V 180V
Generator Over Voltage GEN OVER VOLT 0-999 1V 250V
Generator Rated Frequency GEN RATED FREQ 40-99.9 0.1 Hz 50.0Hz
Generator Under Frequency GEN UNDER FREQ 40-99.9 0.1 Hz 47.5Hz
Generator Over Frequency GEN OVER FREQ 40-99.9 0.1 Hz 52.5Hz
Mains Frequency Blocking Voltage M_FREQ_BLK_VOLT 0-999 1V 100V
Generator frequency Blocking Voltage G_FREQ_BLK_VOLT 0-999 1V 100V
Over Speed OVER SPEED 40-99.9 0.1 Hz 55.0 Hz
Ignition Voltage IGNITION VOLT 0-999 1V 60V
Generator CB on Delay GEN CB ON DELAY 0-999 1 Sec. 3 Sec
Generator Re-cooling time GEN RECOOL TIME 0-999 1 Sec. 180 Sec
Generator Cranking Wait Period GEN CK WAIT TIME 0-999 1 Sec. 10 Sec
Mains Restoration Time MAIN RESTOR TIME 0-999 1 Sec. 30 Sec
Generator Start Delay GEN START DELAY 0-999 1 Sec. 3 Sec
Generator Off Delay GEN OFF DELAY 0-999 1 Sec. 3 Sec
Delayed Supervision Time DELAY SUPER TIME 0-999 1 Sec. 10 Sec(LLOP protection only)
Single Phase Enable 1 PHASE ENABLE 0-1 - 0
Generator Tripping Delay GEN TRIP DELAY 0-999 1 Sec. 0 Sec
Auto Hooter Reset Period HOOTER RST TIME 0-999 1 Sec. 5 Sec
Mains Unbalance Voltage M UNBALANCE VOLT 1-999 1% 25%
Number of Generator Cranking NO. OF GEN CRANK 1-9 1 3
Generator Cranking Period GEN CRANK PERIOD 0-999 1 Sec. 1 Sec
Stopper Time STOPPER TIME 1-999 1Sec 10Sec
Battery low Indication BAT LOW INDICATN 6-999 1V 10.5V
Periodic Test Delay PERIOD TEST TIME 0-999 1 Hour 0 Hour
Table 1: Different parameter settings in edit mode
-
8/13/2019 EC2 PLUS
8/24
EC 2 PLUS :AMF Relay
8
6. Design
6.1 Connection:
The connection diagram for the AMF relay EC2PLUS isshown in the Fig. 2
6.2 Output Relays
The EC2 PLUS has twelve output lines which controls thetwelve different relays. Which are mounted externally onthe relay card .The function and the termination of theseoutput relays are described in the Table 2 below:
Relay No. Description Terminal No.
1 Hooter 35
2 DG Stop 36
3 Fuel 37
4 DG Start 385 MBK 39
6 GBK 40
7 Fail to Start 52
8 Mains Fail 53
9 Alt DG Stop 54
10 LLOP 55
11 Low Fuel 56
12 Fire Alarm 57
Table 2: Output relay description
6.3 Inputs
6.3.1 Mains Voltage Connection
Mains supply voltage connection to the relay EC2 PLUS isshown in the Fig2. The mains line voltage supply is connectedto the terminal numbers 1, 3, 5 with neutral at 6 to theEC2 PLUS relay.
6.3.2 Generator Voltage Connection
Generator supply voltage connection to the relay EC2 PLUSis shown in the Fig2. The generator line voltage supply isconnected to the terminal numbers 7, 9, 11 with neutral at12 to the EC2 PLUS relay.
6.3.3 Auxiliary Supply
The relay EC2 PLUS has SMPS auxiliary supply, which hasthe DC supply voltage range 7 - 35 V dc. This voltagesupply is connected positive (+ VE) to the terminal No.-14and negative (-VE) to the terminal No. 13.
6.3.4 CB Feedback No Contacts
The relay EC2 PLUS has two numbers CB feedback contactsone for mains CB and other for generator CB which areconnected to the terminal 19, 21 respectively.
6.3.5 External Inputs:
There are three external input fault signals provided inrelay EC2 PLUS. Details of these faults are listed as below.
Description Type DefaultSetting
Fault No.1 0,1,2,3,4 0
Fault No.2 0,1,2,3,4 0
Fault No.3 0,1,2,3,4 0
Fault setting
0 Disable.1 Display only.
2 Display with Hooter/ Alarm.
3 Display, Hooter/Alarm with normal shut down ofgenerating set.
4 Display, Hooter/Alarm with emergency shut
down of generating set
Fault priority level
Annunciation
External fault Inputs Displayed As
Low lube oil pressure LOW LUBE OIL PRE
Over Speed OVER SPEED
High cooling water HIGH COOL TEMPtemperature
6.3.6 Internally Processed Fault Display
Different internally processed fault displays in the relay
are
1 Mains CB open fail
2 Mains CB close fail
3 Generator voltage unhealthy
4 Generator fails to start
5 Generator fails to stop
6 Generator CB open fail
7 Generator CB close fail
8 Fail to build
9 Generator over speed10 Generator Emergency Stop
-
8/13/2019 EC2 PLUS
9/24
EC 2 PLUS :AMF Relay
9
6.4 Display
6.4.1 Display for 16 * 2 LCD
The AMF relay EC2 PLUS is equipped with four digits sevensegment numeric LCD display to provide the mode selectionstatus. The mains/ generator editable parameters checking
when required as shown in table 1. It also displays theabnormalities of the mains/generator parameters, CBs etc.
6.4.2 Display for 20 * 4 LCD
The AMF relay EC2 PLUS is equipped with four digits sevensegment numeric LCD which displays measuringparameters for Mains/Gen, RTC, fault status, site name &number, log duration for start/stop of DG, Energy registerfor 12 months for both Mains & DG and editableparameters.
6.5 LEDs
There are twenty-four LED indication provided in the frontpanel of the relay EC2 PLUS. Fault indications in RED color& status indications in GREEN color.The function of thesetwenty-four LEDs is described in the Table 6.
S.NO
1
2
3
4
5
6
7
8
LEGEND
Chrg AltFail
Load OnDG
Low WaterLevel
or*BTS3_Low
Fire Alarm
RoomTemp Low
Echg BattLow
CanopyTempHigh
Over Load
LED OFF
Charging ok
Load notconnected
Water levelabove theexternalset value*BTS3 voltageis OkFire notoccurred
Temp abovethe externalset value
Exchangebatteryvoltagehealthy
Temperaturewithinexternal setlimit
Load withinexternal setlimit
LED ON
Charging notOK
Loadconnected
Water levelbelow theexternal setvalue*BTS3 voltageis lowFireoccurred
Temp belowthe externalset value
Exchangebattery voltagelow
Temperaturemore than theexternal setlimit
Load is morethan externalset limit
S.NO
9
1 0
1 1
1 2
1 3
1 4
1 5
1 6
1 7
1 8
1 9
2 0
2 1
2 2
2 3
2 4
LEGEND
Mains CB
AlternatorFault
FrequencyLow
FrequencyHigh
LLOP
HCT
FuelLevel1
FuelLevel2
Phase
Reversal
Start Fail
Stop Fail
EmergencyStop
Mains Fail
Over Speed
GenVoltageHigh
GenVoltageLow
LED OFF
Mains CB notconnected
AlternatorOK
Frequencyabove the setlimit
Frequencybelow the setlimit
Pressure valueabove externalthe limit
Cylinder tempOK
Fuel levelabove thevalue of 50%
Fuel levelabove thevalue of 25%
Phase
sequence R-Y-B (correct)
..
..
EmergencyStop notoccurred
Mains Healthy
Speed belowthe set limit
Voltage belowthe set value
Voltage abovethe set value
LED ON
Mains CBconnected
Alternator notOK
Frequencybelow the setlimit
Frequencyabove the setlimit
Pressure valuebelow theexternal set limit
Cylinder temphigh
Fuel levelbelow thevalue of 50%
Fuel levelbelow thevalue of 25%
Phase
sequence is R-B-Y (not OK)
Generator failto start
Generator failto stop
EmergencyStop occurred
Mains not OK
Speed abovethe set limit
Voltage abovethe set value
Voltage below
the set value
Table 6: Function/Indication of LEDs
NOTE : *BTS3 is available only in version 1.1
-
8/13/2019 EC2 PLUS
10/24
EC 2 PLUS :AMF Relay
10
6.6 Front Panel Keypad
The front panel keypad consists of thirteen keys which arearranged into three groups.
These are:
6.6.1 Command keys in MMI 2
The Six Command keys marked as Gen Start, Gen Stop,Gen CB Open, Gen CB Close, Mains CB Open,and Mains CB Close.
6.6.2 Scroll/Editable keys in MMI 2
There are five Edit Keys in MMI-2 marked as Enter, ,, +, and , .Edit keys serve following functions
Key [Select Forward]
This key selects the mode of operation. These are:
Default mode, Edit parameter mode, view para mode,Selection mode Password mode and Load mode. The relayenters the specified mode only after the Enter key ispressed.
Key [Select Backward]
This is a multifunctional key. It performs following functions.
1 When there is no fault, it is used for back scrolling.
2 In the presence of a fault it is used as Silencekey to silence hooter.
3 In the presence of a fault, the fault can be resetby holding down this key for 4 seconds. The displaywill come back on the default screen as theacknowledgement of reset.
+
This key increments the value of the parameter beingdisplayed in Edit Para mode. This key is also used to enterand change the password.
-
This key decrements the value of parameters beingdisplayed in EDIT mode. This key is also used to enter andchange the password.
Enter
This key activates selected mode in mode selection process.
GEN START
This key is active in Manual mode. It starts the generator.
GEN STOP
This key is active in Manual mode only. It stops the generator.
GEN CB OPEN
This key is active in Manual mode. It opens generator CB.
GEN CB CLOSE
This key is active in Manual mode. It closes generator CB.Mains CB OPEN
This key is active in Manual mode. It opens mains CB.
Mains CB CLOSE
This key is active in Manual mode. It closes mains CB.
6.6.3 Scroll/Editable keys in MMI 1
Right Key
This key is used for viewing the next page, Long Press RightKey to Enter in Next Menu.
This key is also used to reset the Hooter, overload and
alternator fault.
Left Key
Left Key is used for viewing the previous page.
6.7 GSM/GPRS Communication
EC2 PLUS is equipped with TCP/IP communication whichallows interfacing of the relay with GSM/GPRS modem. Anull modem cable is required for communication withmodem.
6.8 Protection
1. Over Load2. Phase Reversal
6.8.1 Over Load
EC2 PLUS provides overload protection for the DG, if thecurrent value in any phase or in all phases exceeds the setlimit of overload current & if this condition prevailscontinuously for 1 min, it will shut down the DG, LEDannunciation is also provided. This fault will be reset bypressing Right key in MMI 1.
6.8.2 Phase Reversal
Phase reversal is provided for both Mains & DG.If thesequence is R,Y,B then phase sequence is ok otherwise itwill glow phase reversal LED after 3sec of the load transfer
on Mains or DG.This LED will return to its normal statewhen relay will get the right phase sequence
-
8/13/2019 EC2 PLUS
11/24
EC 2 PLUS :AMF Relay
11
6.9 Digital Inputs
NOTE: *BTS2 voltage and *BTS3 voltage are available
only in version 1.1
7. Parameters Setting/Display Procedure
7.1 Mode Selection
To scroll through various modes press key. We canselect parameters by pressing Enter key.
7.2 Display Measured Parameters
To scroll through parameters, press + key. Refer GettingStarted for details.
8 Getting Started
8.1 EC2 PLUS display for MMI-1
The EC2 PLUS relay is equipped with a back-lit LCD displayhaving four lines of twenty alpha-numeric characters todisplay Mains and current, Voltage, power factor, frequency,and etc. The left, right key on the left side is used to see thefollowing screens displaying various parameters. Thegenerator start time, stop time and duration of run arelogged and the last 5 values can be seen on the screen.The number in the left top corner indicates the numberlogged. The data related to energy consumed by generatorand by mains in a given month are recorded. On eachscreen energy values of 3 months are displayed.(The screenfor Jan, Feb, March is shown in screen no. 17).Theinformation related to Generator start time, Stop time andDuration of run are also displayed .Refer screen number19 (On the top right corner E1 is displayed which meansrecord 1). The last 5 records can be displayed and recordnumber will accordingly get changed.
SCREEN NO. 1
# SITE NAME SITE NO #BSNL 12345678
12.08.08 11.03.08> DG_BAT_LOW
8.2 EC2 PLUS display for MMI-2
8.2.1 If any external or internal fault comes, then EC2PLUS comes into fault displaying mode.
8.2.2 In fault screen, one fault is displayed in the first lineand an instruction to reset the fault (by pressing for four seconds) is displayed in second line.
8.2.3 If more than one faults are present they can beviewed by pressing E when fault has beendisplayed followed by +/- keys
OVER SPEEDRST:PRESS MORE
8.3 EC2 PLUSenters in the menu selection by pressing (Forward Select) & (Backward Select)
8.3.1 Scrolling through different modes can be done with (For. Select) & (Back Select) keys.
8.3.2 By pressing E (Enter) we can go in to the selectedmode.
8.3.3 Default mode is meant for returning to the defaultscreen view.
8.3.4 Edit parameter mode is for editing parameter. It isprotected by service password.
8.3.5 View parameter mode is only to view parameters.Parameters cant be changed.
8.3.6 Selection mode is for selecting the operationalmode.
SCREEN NO. 12
# TEMP LEVEL #
RMTEMPLEVEL >50C
SCREEN NO. 18
NEXT MENU >
SCREEN NO. 17
MONTHLY ENERGYMAINS KWH DG KWH
JAN 12345.6 12345.6FEB 12345.6 12345.6MAR 12345.6 12345.6
SCREEN NO. 9
GENERATOREX_BAT_VOLTAGE 48.5
BAT_VOLTAGE 48.5SPEED 1500 RPM
SCREEN NO. 10
MAINSPOWER 5671.2 KWFREQUENCY 49.7 HZ
SCREEN NO. 11
GENERATORPOWER 5671.2 KWFREQUENCY 49.7HZ
-
8/13/2019 EC2 PLUS
13/24
EC 2 PLUS :AMF Relay
13
8.3.7 Password mode is to change the service password.It requires the service password while changing.
8.3.8 Load default mode is for loading the defaultparameters and default service password .It isprotected by the master password.
8.3.9 EC2 PLUS will return to the default screen displaymode if left unattended for more than 16 secondsat any stage.
8.4 Edit Para Mode:
8.4.1 Enter the edit para menu by entering correctservice password and then pressing E. Scrollingthrough different editable parameters can be donewith & keys. By using the + & - keyparameters values can be increased or decreased.
8.4.2 External faults level can be edited by pressing +& - key when fault parameters appear. Type(Level) of the fault can be Inc/Dec when cursorpoints the Type.
8.4.3 Further presses of will roll over theparameter list from the start.
8.4.4 By pressing E, EC2 PLUS will ask whether to savethe edited parameters which can be selected ornot by + & - keys. Pressing E on Yes willsave the parameter set and will automatically exit
to the default mode.
8.4.5 The current mode has been written at the end ofsecond line.
DEFAULT MODE
B. SELECT F. SELECT
EDIT PARA MODE
B. SELECT F. SELECT
VIEW PARA MODE
B. SELECT F. SELECT
MANUAL DIAG MODE
B. SELECT F. SELECT
SELECTION MODE
B. SELECT F. SELECT
PASSWORD MODE
B. SELECT F. SELECT
LOAD DEFAULT MODE
8.5 View Para Mode:
8.5.1 Enter the view para menu by pressing E.Scrolling through different non-editable param-
eters can be done with & keys.
8.5.2 Further presses of will roll over the param-eter list from the start.
8.5.3 By pressing E, EC2 PLUS will revert to thedefault mode.
8.5.4 The current mode has been written at the end ofsecond line
8.6 Selection Mode:
8.6.1 Enter the operational mode selection menu bypressing E. Scrolling through different modescan be done with & keys.
8.6.2 Further presses of will roll over the param-eter list from the start.
8.6.3 Current operational mode can be identified asmode with already written Selected.
8.6.4 By pressing E, EC2 PLUS current selection willbe selected and will return to the default displays.
MAINS RATED VOLT
240V VIEW
B. SELECT F. SELECT
MAINS UNDER VOLT
180V VIEW
B. SELECT F. SELECT
FAULT 1 TYPE 4
LOW FUEL LEVEL
MAINS RATED VOLT
240V EDIT
B. SELECT F. SELECT
MAINS UNDER VOLT
180V EDIT
B. SELECT F. SELECT
FAULT 1 TYPE 4
LOW FUEL LEVEL
ENTER SAVE?? Y
EDIT
SAVED......
-
8/13/2019 EC2 PLUS
14/24
EC 2 PLUS :AMF Relay
14
8.6.5Current mode has been written at end of secondline
8.7 Password Modes:
8.7.1 Enter the change password menu by pressingenter to the Chng Super Pass.
8.7.2 Enter the old supervisor password which if foundinvalid will popup the Invalid Password error andwill return to the default mode.
8.7.3 Change the new supervisor password andconfirm it.
8.7.4 The current mode has been written at the end of
second line
Test Mode
Selected SeleSELE
Auto Mode
SELE
ENTER ENTERManual Mode
CONFIRM PASSWORD
....... PASS
ENTERCHNG SUPER PASSPASS
ENTER
ENTER OLD PASS...... PASS
ENTER
ENTER NEW S. PASS...... PASS
PASSWORD CHANGED
ENTER
LOAD DEFAULT PARA
LOADED LOADENTER
LOAD DEFAULT PARALOAD
B. SELECT
LOAD DEF. S. PASS LOAD
F. SELECT
8.8 Load Default Mode
8.8.1 Enter the load default menu by entering correctmaster password and then pressing E. Scrollingthrough different parameters can be done with & keys.
8.8.2 Further presses of will roll over the parameterlist from the start.
8.8.3 By pressing E, EC2 PLUS will load defaultparameter or service password or will reset theengine run hours.
8.8.4 The current mode has been written at the end ofsecond line
-
8/13/2019 EC2 PLUS
15/24
EC 2 PLUS :AMF Relay
15
S.No Parameter Specification
1 Selection modeIn MMI-2 Auto mode
2 Manual mode
3 Test mode
4 Functions Mains 3 phase
voltage,Current,Freq,Power,P.F,cumulative andmonthly Energy
5 DG 3 phase Voltage,Current,Freq,Power,P.F,cumulative and monthly Energy,Speed,RunHours,DG Battery voltage,Exchange Battery voltage
6 Overload Current,CT Ratio,Exchange battery lowersetting, Exchange battery higher setting
7 Voltage rated, upper and lower limits for mains andGenerator
8 Frequency rated, upper and lower limits for mainsand generator
9 Unbalance limit for mains voltage
10 Enable mains operation on single phase
11 Voltage limit below which frequency ofmains/generator is not read
12 Battery voltage Low value
13 Ignition voltage
14 Over speed limit
15 Number of cranking attempts
16 Generator start delay
17 Generator cranking period
18 Stopper delay 19 Cranking wait period
20 Re-cooling Time
21 Generator CB on delay
22 Generator Tripping delay
23 Delayed supervision
24 Generator off delay
25 Mains restoration time
26 Periodic test delay
27 Hooter Reset Time
28 Set all above parameters. This mode is protectedby Supervisor Password.
29 Supervisor password can be modified.
30 Load Default Mode This mode loads default parameters and supervisorpassword It is protected by Master password.
31 Supervision Three line voltages & current of mains-voltage band-unbalance limit
32 Three line voltage & current of generator-voltage band
33 Frequency of mains-frequency band
34 Frequency of generator-frequency band
35 Battery voltage-voltage band
View actual values in
MMI-1EditParametersin MMI-1
Edit Parameters inMMI-1
View Set Parameters(View Para Mode)In MMI-2
Edit Parameters (Edit ParaMode)in MMI-2
Change Password(Password Mode)in MMI-2
9. Functional Specifications
-
8/13/2019 EC2 PLUS
16/24
EC 2 PLUS :AMF Relay
16
10. Performance Specifications
S.No Parameter Specification
1 Aux supply 7.0 35.0 V DC
2 Aux supplyInterruption Time One second sustains battery dip down to zero voltsfor one second without requiring external capacitorbank.
3 Aux supply burden
-
8/13/2019 EC2 PLUS
17/24
EC 2 PLUS :AMF Relay
17
26 Key pad 13 Keys 1 Scroll/ Editable Keys Forward, Increment, Decrement,11 keys on right side & 2 on Backward, Enterleft side
5 Keys
27 2 Control Keys Gen Start, Gen Stop, Open
Mains CB, Close Mains CB, Open DG 6 Keys CB, Close DG CB
28 Scroll / editable keys Left, Right2 Keys
29 External faults - 4 Opto-isolated I/Ps
30 Controls 3 Opto-isolated I/Ps Emergency Stop
31 Feed Back 3 Opto-isolated I/Ps MCB check back
32 GCB check back
33 Ignition On
34 Relay HOOTER
35 Relay DG STOP36 Relay FUEL
37 Relay DG START
38 Relay- MBK
41 Relay- GBK
42 Relay FAIL TO START
43 Relay MAINS FAIL
44 Relay ALT DG STOP
45 Relay LLOP
46 Relay LOW FUEL
47 Relay FIRE ALARM48 Communication Serial full duplex
RS232Modem enabled (Bi-directional)Windows based Proprietary Software
49 Serial connector 9-pin subminiature DB9-connector
50 Storage temp. 0C - +70C
51 Operating Temp 0C - +70C
52 Connecting terminals max 2.5 mm2
Recommended 2.5 mm2conductor
53 Enclosure 1. Flush mounting
2. Panel cut-out :( W x H) 2850.5 x 1600.5 mm (max.)
3. Installation Depth: 80 mm (max.)
4. Weight: 0.8 Kg approx.
Relay 12 nos.O/PContact rating (Allrelays) 250 V AC, 4Aresistive
NOTE: *BTS3 is available only in version 1.1
-
8/13/2019 EC2 PLUS
18/24
EC 2 PLUS :AMF Relay
18
12. Snap Shot of CSE LIVE LINK Frontend Software:
13. Front Panel of EC2 PLUS
-
8/13/2019 EC2 PLUS
19/24
-
8/13/2019 EC2 PLUS
20/24
EC 2 PLUS :AMF Relay
20
16. Terminal Details
16.1 Terminal arrangement
Terminal DescriptionNo.
1 Mains Voltage R
2 --
3 Mains Voltage Y
4
5 Mains Voltage B
6 Mains Neutral N
7 Generator Voltage R
8
9 Generator Voltage Y
10
11 Generator Voltage B
12 Generator Neutral N
13 Auxiliary Voltage[Negative]
14 Auxiliary Voltage [Positive]
15
16 Ignition On
17 SPARE
18 High Cylinder Temp (HCT)
19 MCB_CB
20 Over Speed
21 GCB_CB
22 LLOP
23 Emergency Stop
24
25 Load Current IR
26 Load Current IY
27 Load Current IB
28 Load Current IN
29 Room temp level (analog input)
30 Under Speed / *BTS2 voltage
31 Canopy Temp Hi
32 Charge Alternator
33 LOP
34 Low Water Level / *BTS3 voltage
35 Relay-HOOTER
36 Relay-DG STOP
37 Relay-FUEL
38 Relay-DG START
39 Relay-MBK
40 Relay-GBK
41
42
43 Relay- SPARE 0
44 Relay- SPARE 1
45 Relay- SPARE 2
46 Relay- SPARE 3
47 Relay- SPARE 4
48 Exchange Battery[Negative]
49 Exchange Battery[Positive]
50
51 Relay-SPARE 5
52 Relay-FAIL TO START
53 Relay-MAINS FAIL
54 Relay-ALT DG STOP
55 Relay-LLOP
56 Relay-LOW FUEL
57 Relay- FIRE ALARM
58 Fire Alarm
59 Room Temp Low (DI)
60 Door Open
61 Fuel Sensor 50%
62 Fuel Sensor 25%
NOTE : *BTS2 voltage and *BTS3 voltage are available
only in version 1.1
-
8/13/2019 EC2 PLUS
21/24
EC 2 PLUS :AMF Relay
21
16.2 Terminal Description
1
2
3
4
MainsVoltageR
MainsVoltageY
MainsVoltageN
MainsVoltageB 5
6
13AuxiliaryVoltage[-]
AuxiliaryVoltage[+]
29
30
UnderSpeed/*BTS2
CanopyTempHi
RoomTempLevel
LowWaterLevel/*BTS3
31
Fuel Sensor 50%
Fuel Sensor 25%
Fire Alarm
Room Temp Low
Door Open
Relay-Fail to Start
Relay-Mains Fail
Relay-Alt-DG-STOP
Relay-LLOP
Relay-Low Fuel
Relay-Fire Alarm
Relay-HOOTER
Relay-DG STOP
Relay-Fuel
Relay-DG START
Relay-MBK
Relay-GBK
Relay-SPARE 4
Exchange Battery[-]
Exchange Battery[+]
MAINS
VOLTAGE
DIGITALINPUT
S
ANOLOG
INPUT
RELAYPOTENTIALOUTPUTS
DIGITALINPUT
DIGITALINPUTS
RELAYPOTENTIALOUTPUTS
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
7
8
GeneratorVoltageY
GeneratorVoltageB
GeneratorVoltageR
GeneratorVoltageN12
11
9
10
DG
VOLTAGE
32
33
3
4
ChargeAlt
25
26
LoadCurrentIY
LoadCurrentIB
LoadCurrentIRCURRENT LoadCurrentIN
27
28
17
18
SPARE
HCTDIGITALINPUTS
16
IgnitionOn
14
15
Relay-SPARE 3
Relay-SPARE 2
Relay-SPARE 1
Relay-SPARE 0
Relay SPARE 5
61
62
Group
LOP
GCB_CB
LLOP
EmergencyStop
22
23
24
21
19
MCB_CB
OverSpeed 20
RS 232
-
8/13/2019 EC2 PLUS
22/24
EC 2 PLUS :AMF Relay
22
!
WAR
NING
PLEASEPROVIDEAP
PROPRIATEFUSES
ONCIRCUITWIRED
TOTERMINALS
35,36,37,38,39,40,52,53,54,55,55,56,57
Mains
G
Generator
Contractor
ConsumerLoad
1
2
3
4
5
6
7
8
+VE12V
-VE
11
12
N
N
Auxillary Voltage
Auxillary Voltage
13
14
15
16
17
18
19
20
21
22
242
9
30
31
LLOP
HCT
Spare
Ignition On
Emergency Stop
MCB_CB
GCB_CB
Fire Alarm
Room Temp Low
Door Open
Fuel Sensor 50%
Fuel Sensor 25%
35
3637
38
3940
52
53
54
55
56
57
RelayCard
60
61
Exchange Battery -
Exchange Battery +
+V48V
HOOTER
DGStopFuel
DGStart
MBK
GBK
FailtoStart
MainsFail
AltDGStop
LLOP
LowFuel
UR
UY
UB
UR
UY
UB
28
27
26
25
IR
IB
IYIR
IY
IB
OverSpeed
23
33
34
58
59
Under Speed/*BTS2
Charge Alternator
Low Water Level/*BTS3
32
FireAlarm
Room Temp Level
Contractor
91
0
Canopy Temp Hi
LOP
62
48
49
CTCommon
Com
mon
Fig2ConnectionDiagram
NOTE:*BTS2voltageand*BTS3voltageare
availableonlyinversion
1.1
-
8/13/2019 EC2 PLUS
23/24
-
8/13/2019 EC2 PLUS
24/24
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413E-mail: [email protected] Web : www.cselectric.co.in
Marketing Offices :AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI :+91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD :+91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
BASIC RANGE
Micro-controller based compact economical design
DIN rail mounted
Status indication via LED
Step-less settings through front potentiometer
FUNCTIONAL RANGE
Genset Supervision & Control
Auto Synchroniser
Load Balancing & Control
Related Protection
HIGH-TECH RANGE
Microprocessor based numerical protection
Event & fault recording
RS 485 communication
Bright alpha-numeric display
INTEGERATED RANGE Numeric protection, solution for sub-station in association