eau claire area study northern mapp subregional planning group january 11, 2007 daniel kline
TRANSCRIPT
3
Outline
Description of Area Various Load Serving Problems Study Methodology & Initial Alternatives Final Alternatives Final Recommendation Questions
4
Description of Area
Located in West-Central Wisconsin Eau Claire & Chippewa Counties About an hour east of Twin Cities on I-94
Area fed by 345 and 161 kV sources and 69 kV transmission
Load belonging to NSPW and DPC
Lines belonging toNSPW and DPC
5
Description of Area
Area NSPW Sources: Eau Claire Substation Seven Mile Substation Wheaton Substation Chippewa River Generation
Area DPC Sources (2011): Elk Mound Substation
6
Description of Area
Area NSPW Loads (2011): Jeffers Road (27 MW) Truax (41 MW) Otter Creek (35 MW) London (42 MW) Hallie (31 MW)
Area DPC Loads (2011): Seymour (4 MW) Elco (4 MW) Equity (3 MW) Washington (3 MW) Brunswick (2 MW)
7
Description of Area
To WPL ArpinTo NSPW King
Presto
NSPW US Rubber
NSPW Hallie
NSPW Chippewa Falls NSPW Wissota
To NSPW Jim Falls
NSPW Otter Creek
NSPWSevenMile
NSPW Tremval
NSPW EllisNSPW Shawtown
NSPW Truax
NSPW Dells
NSPW Madison Street
To NSPW Red Cedar
NSPWEau Claire
DPC Elk Mound
To NSPW Red Cedar
NSPW Hydro Lane
To NSPW T-Corners
NSPW Jeffers Road
NSPW Wheaton
To NSPW Cotton School
DPC Seymour
DPC Ludington
To Xcel Jim Falls
DPC Barron
To DPC Alma
DPC Union
DPC Brunswick DPC Washington DPC Equity
To NSPW Red Wing
& DPC Alma
NSPW London
DPC Elco
NSPW Sterling
8
Description of Problems Eau Claire transmission system is
designed to rely upon Eau Claire 69 kV bus Eau Claire 161/69 kV transformers are
heavily loaded and cannot endure loss of parallel bank
Eau Claire substation is crowded and not enough space exists to increase the size of the existing 161/69 kV banks
Increasing size of banks would require moving to non-standard bank sizes
9
Description of Problems
During peak load conditions, 69 kV system to north overloads
DPC system served out of Seven Mile overloads for various contingencies
High load growth throughout area Interconnection requests at Hallie Substation
requrie auto-transfer scheme to be turned off Area transmission system highly susceptible to
fluctuations in Chippewa River generation
10
Study Methodology
2006 MAPP Series Cases 2011 Near-Term 2016 Out-Year
Worked with DPC through Joint Planning Process
11
Study Methodology
Assumptions and Adjustments made Assumed Chisago Line Project not in service in
2011 (In-service in 2016) Included New Richmond Area Load Serving
Study projects Assumed Monroe County – Council Creek 161
kV line in service in 2011 Moved Riverview load to Hallie
12
Study Methodology
Bus Name ContVolt BaseVolt Contin.Description
Shawtown 69 kV 0.8736 1.0151 Eau Claire - Dells - Sterling 69 kV Line
Folsom 69 kV 0.8699 1.0218 Eau Claire - Dells - Sterling 69 kV Line
Madison St. 69 kV 0.8700 1.0209 Eau Claire - Dells - Sterling 69 kV Line
Sterling 69 kV 0.8697 1.0234 Eau Claire - Dells - Sterling 69 kV Line
Shawtown 69 kV 0.8920 1.0151 Eau Claire - Sterling - Madison St. 69 kV Line
Madison St. 69 kV 0.8894 1.0209 Eau Claire - Sterling - Madison St. 69 kV Line
London 69 kV 0.8994 1.0040 Eau Claire - Sterling - Madison St. 69 kV Line
Washington 69 kV 0.9064 1.0029 Eau Claire - Sterling - Madison St. 69 kV Line
Equity 69 kV 0.9354 1.0056 Eau Claire - Sterling - Madison St. 69 kV Line
Eagle Point 115 kV 1.0501 1.0425 Hydro Lane - Wissota 115 kV Line
Hydro Lane 115 kV 1.0516 1.0437 Hydro Lane - Wissota 115 kV Line
Chippewa Falls 115 kV 1.0501 1.0425 Hydro Lane - Wissota 115 kV Line
13
Study Methodology
Base Case Results Base Case Results
Affected Facility ContMVA Loading% Contingency
Eau Claire 161/69 kV Transformer 113.4 101.2 Eau Claire - Arpin 345 kV Line
Independence to Elk Creek 69 kV Line 26.3 105.1 Eau Claire - Arpin 345 kV Line
Seven Mile to Elco 69 kV Line 91.1 193.8 Eau Claire - Dells - Sterling 69 kV Line
London to London Tap 69 kV Line 79.9 111.0 Eau Claire - Dells - Sterling 69 kV Line
London Tap to Equity 69 kV Line 83.7 178.1 Eau Claire - Dells - Sterling 69 kV Line
Elco to Equity 69 kV Line 86.5 184.0 Eau Claire - Dells - Sterling 69 kV Line
Seven Mile to Elco 69 kV Line 82.2 175.0 Eau Claire - Sterling - Madison St. 69 kV Line
London Tap to Equity 69 kV Line 74.9 159.5 Eau Claire - Sterling - Madison St. 69 kV Line
Elco to Equity 69 kV Line 77.7 165.3 Eau Claire - Sterling - Madison St. 69 kV Line
Independence to Elk Creek 69 kV Line 25.9 103.5 Hydro Lane - T-Corners 115 kV Line
Independence to Elk Creek 69 kV Line 25.7 103.0 Hydro Lane - J im Falls 115 kV Line
Eau Claire 161/69 kV Transformer 116.6 104.1 Eau Claire - Jeffers Road 161 kV Line
Independence to Elk Creek 69 kV Line 25.6 102.2 Eau Claire - Jeffers Road 161 kV Line
Eau Claire 161/69 kV Transformer 117.1 104.6 Eau Claire - Seven Mile 161 kV Line
Eau Claire 161/69 kV Transformer 113.6 101.5 Wheaton - Jeffers Road 161 kV Line
Eau Claire 161/69 kV Transformer 144.8 129.3 Eau Claire 161/69 kV Transformer
Eau Claire 161/69 kV Transformers 121.0 108.0Chippewa River Generation & Hydro Lane - Red Cedar 161 kV Line
Remaining Eau Claire - Chippewa Falls 69 kV Line 90 to 106 105 to 123
Low Chippewa River Generation & Eau Claire - Chippewa Falls 69 kV Line
14
Initial Ideas
Reconductor double-circuit 69 kV corridor between Eau Claire and Chippewa Falls
Convert 69 kV double-circuit corridor to 161 kV
Add circuit breakers at Otter Creek Shift load from 69 kV system to 161 kV
system
15
Final Alternatives
Alternative 1 Convert entire 69 kV corridor from Eau Claire to
Chippewa Falls to 161 kV Convert all 69 kV load along corridor to 161 kV operation
Alternative 2 Extend 161 kV from Presto Tap to Hallie Substation Place US Rubber on loop from Eau Claire Substation Place Chippewa Falls on loop from Wissota Substation
16
Final Alternatives
Alternative 3 Convert double-circuit 69 kV corridor to single-
circuit 161 kV Convert Hallie to 161 kV operation Place US Rubber on loop from Eau Claire
Substation
17
Final Recommendation
Alternative 3 Recommended Reterminate Wheaton to Presto Tap 161 kV line at Eau
Claire Substation Tear down existing 69 kV double-circuit line between Eau
Claire and the point where line intersects with Hydro Lane – Red Cedar 161 kV line
Construct 161/69 kV substation (50th Avenue Substation) where double-circuit 69 kV line intersects Hydro Lane – Red Cedar 161 kV line
Construct single circuit 161 kV line from Eau Claire to 50th Avenue Substation
Convert Hallie Substation to 161 kV operation
18
Final Recommendation
To WPL ArpinTo NSPW King
Presto
NSPW US Rubber
NSPW Hallie
NSPW Chippewa Falls NSPW Wissota
To NSPW Jim Falls
NSPWOtter Creek
NSPWSevenMile
NSPW Tremval
NSPW EllisNSPW Shawtown
NSPW Truax
NSPW Dells
NSPW Madison Street
To NSPW Red Cedar
NSPWEau Claire
DPC Elk Mound
To NSPW Red Cedar
NSPW Hydro Lane
To NSPW T-Corners
NSPW JeffersRoad
NSPW Wheaton
To NSPW Cotton School
DPC Seymour DPC Ludington
To Xcel Jim Falls
DPC Barron
To DPC Alma
DPC Union
DPC Brunswick DPC Washington DPC Equity
To NSPW Red Wing
& DPC Alma
NSPW London
DPC Elco
NSPW Sterling
NSPW 50th Avenue(Proposed)
19
Final Recommendation
Very robust service provided to area north of Eau Claire
Off-loading of Eau Claire 161/69 kV transformers buys approx. 12 years of life expectancy
Strong corridor to support Chippewa River generation
Increased Load-serving north of Jim Falls