    EARTHING AND

    PROTECTION

    EARTHING

  • 7/28/2019 Earthing and Protection Rev1

    2/56

    REQUIREMENT OF EARTHING

    Earthing arrangement of proper type is

    required to protect the equipment and

    working personals from high induced

    voltage, due to lightning and high

    electromagnetic induction.

  • 7/28/2019 Earthing and Protection Rev1

    3/56

    INSTALLATIONS TO BE

    EARTHED The lever frame and other metallic frames of the cabin.

    Metallic sheath and armouring of all under ground Main cables atevery1 Kilo meter.

    Block circuits working on earth return through the respective BlockFilters.

    The surge arrestors provided in Block filters as well as thoseprovided for Telecom equipments in switching stations

    All Telecommunication equipments.

    The signals provided on bracketed posts or gantries locatedabove contact wire level, falling with in 2 meters from electrifiedtrack.

    All Telecommunication equipments, and cable sheath to beearthed.

  • 7/28/2019 Earthing and Protection Rev1

    4/56

    REASONS FOR EATHING THE

    TELECOMMUNICATION

    EQUIPMENT

    i) To prevent or to reduce the risk of cross

    talk.ii)To complete earth return signaling circuits.

    iii) To avoid risk of shock.

    iv) To provide direct connection to the earthfor lightening protection.

  • 7/28/2019 Earthing and Protection Rev1

    5/56

    SOIL RESISTVITY

    It is the resistivity offered by soil. It is indicatedby the symbol p (RO). it is a constant and

    depends on the length l and area a of theconductor.

    l

    R = p --- where p = resistivitya

  • 7/28/2019 Earthing and Protection Rev1

    6/56

    RESISTIVITY

    OR

    THE SPECIFIC RESISTANCE The resistivity or the specific resistance is

    defined as the resistance between opposite

    faces of a conductor of unit length and unit cross

    sectional area.

    The value of resistivity is given Ohm- metre.

    The resistance of the electrode depends on the

    resistivity of the soil or Soil resistivity. To get low earth resistance( R ) the Resistvity of

    the soil must be low.

  • 7/28/2019 Earthing and Protection Rev1

    7/56

    SOIL RESISTIVITY

    The soil resistivity depends on

    moisture content,

    chemical composition of soil concentration of salts dissolved in the

    contained moisture.

    These factors vary locally and seasonally.

  • 7/28/2019 Earthing and Protection Rev1

    8/56

    SOIL RESISTIVITY

    The resistivity or the specific resistance is defined as theresistance between opposite faces of a conductor of unitlength and unit cross sectional area. The value ofresistivity is given Ohm- metre. The resistance of the

    electrode depends on the Resistivity of the soil or Soilresistivity.

    To get low earth resistance( R ) the Resistvity of the soilmust be low.

    The soil resistivity depends on moisture content,

    chemical composition of soil and concentration of saltsdissolved in the contained moisture. These factors varylocally and seasonally.

  • 7/28/2019 Earthing and Protection Rev1

    9/56

    VALUES OF EARTH RESISTACE

    TO BE MAINTAINED

    The resistance of the earth shall not

    exceed maximum 10

    In case of Telecommunication it is 5.

    In case of Microwave it is less than1.

  • 7/28/2019 Earthing and Protection Rev1

    10/56

    TOTAL EARTHING RESISTANCE

    IS THE SUM OF

    The resistance of earth lead wires

    contact resistance between the surfaceof the earth electrode and the soil

    the resistance of the body of the soilsurrounding the earth electrode

    Among the three, the resistance of theearth is primarily determined by thenature of the soil.

  • 7/28/2019 Earthing and Protection Rev1

    11/56

    EARTHING ARRANGEMENT

    A single earthing

    system consists of,

    Soil.

    Earth lead wire.

    Earth electrode.

    Connecting wire to

    extend earth toequipment.

  • 7/28/2019 Earthing and Protection Rev1

    12/56

    SOIL

    The soil is to be prepared to obtain optimumresistvity.

    The site for earthing should be chosen in thefollowing order:

    1. Wet marshy ground and grounds containingrefuse such as ashes, cinders.

    2. Clay soil or loam mixed with small quantity ofsand.

    3. Clay and loam mixed with varying properties ofsand, gravel and stone.

    4. Damp and wet sand peak.

    LIGHTENING CONDUCTOR

  • 7/28/2019 Earthing and Protection Rev1

    13/56

    LIGHTENING CONDUCTOR

    OR

    EARTH LEAD WIREIt is the metallic wire which connects the earthelectrode to the equipment / protector/ Installation.Size and metal of the conductor is given below,

    Material Size G.I. Wire 8 mm Dia

    G.I Strip 20mm x 3 mm

    Copper wire 29 Sq.mm

    ( 19 strand wireof 1.4 mm dia)

    ACSR wire 6 / 1 / 2.11 mm

  • 7/28/2019 Earthing and Protection Rev1

    14/56

    PRECAUTIONS TO BE TAKEN IN CASE

    OF LEAD IN WIRE

    Protect them from mechanical damage

    Apply anti-corrosive paint/ bitumen

    compound on the portion of wire buried inground

    The lead in wire of different earth must be

    electrically insulated from each other, frommetallic structures etc.

  • 7/28/2019 Earthing and Protection Rev1

    15/56

    EARTH ELECTRODE

    It may be a metal plate, pipe or other conductor or an array ofconductors electrically connected to the general mass of earth.

    Type Size

    Length in Mtrs Dia /Cross section

    a) G.I. Pipe 2.5 to 3.5 above 38 mm (internal)

    b) G.I. Angle 2.5 to 3.5 50 mm x 50 mm x 5mm

    c) Copper Rod 2.5 to 3.5 16 mm

  • 7/28/2019 Earthing and Protection Rev1

    16/56

    PROCEDURE OF INSTALLATION

    The hole can be made by manual

    trenching or by using Earth auger.

    The top of the electrode shall be 30 cm

    above the ground.

    After inserting the electrode, the hole shall

    be filled with earth properly and water

    should be spread to ensure good contact

    between electrode and filling.

  • 7/28/2019 Earthing and Protection Rev1

    17/56

    PROCEDURE OF INSTALLATION

    The hole can be made bymanual trenching or byusing Earth auger.

    The top of the electrode

    shall be 30 cm above theground.

    After inserting theelectrode, the hole shallbe filled with earth

    properly and water shouldbe spread to ensure goodcontact betweenelectrode and filling.

  • 7/28/2019 Earthing and Protection Rev1

    18/56

    PROCEDURE OF INSTALLATION

    In the soils of high rersistivity, can be treated with saltand charcoal in appropriate proportion.

    Earth pit of 600 mm dia and 2.5 mtrs depth shall beformed by excavation and the electrode shall be placed

    at the center. The pit shall be filled alternately with layers of common

    salt and charcoal each layer of about 2.5 cm thick up toa depth of about 200 cm from the ground level.

    The pit shall be filled with several times with water, andthen covered with excavated earth and water shall besprayed to ensure good electrical contact.

  • 7/28/2019 Earthing and Protection Rev1

    19/56

    PROCEDURE OF INSTALLATION

    A brick wall of 400 mm height below the groundlevel shall be constructed in rectangular fashionas shown in the figure and walls shall beplastered and then filled with sand.

    The surroundings of the earth electrode shouldbe kept moist by periodically pouring waterthrough the pipe in order to keep the resistancebelow specified value.

    Coke treated electrodes shall not be situatedwithin 6 meters of other metal structure.

  • 7/28/2019 Earthing and Protection Rev1

    20/56

    PROBLEUMS OF CONVETIONAL

    EARTHING

    The salt poured in pit causes severecorrosion of G.I.pipe and makes theearthing ineffective.

    The earth resistance value depends onSoil resistivity which depends on strataso the effect of earthing is dependent onproperty of soil.

    The earth resistance value is very high,fluctuating & increases heavily with time.

  • 7/28/2019 Earthing and Protection Rev1

    21/56

    CONVENTIONAL EARTHING

  • 7/28/2019 Earthing and Protection Rev1

    22/56

    EFFECTIVE EARTHING

    This is also called as Maintenance freeearthing because no maintenance is required.

    Effective earthing electrode eliminates

    problems of conventional earthing: By providing Highly corrosive resistance

    Earthing Electrode.

    By eliminating the corrosion causing elements th

    salt. By providing uniform non corrosive, low soil

    resistivity material around the electrode.

  • 7/28/2019 Earthing and Protection Rev1

    23/56

    WORKING PRINCIPLE

    Hollow pipe of solid bar

    highly conductive, non

    corrosive technology

    In the annular space

    highly conductor rich with

    anti corrosive crystalline

    material is filled.

    Outside pipe is also

    galvanized up to 100microns.

  • 7/28/2019 Earthing and Protection Rev1

    24/56

    WORKING PRINCIPLE

    Specially developed anti corrosive PackingMaterial having less resistivity, 6.5 pH & highmoisture retaining capacity is used surroundingthe electrode.

    This complete arrangement provides goodresistance to any possibilities of corrosion of theelectrode unlike conventional system.

    The packing material helps in maintaining

    uniformly at different strata & offers lessresistance to current dissipation, with goodmoisture retaining property. The whole systemstogether results in most effective earthing.

  • 7/28/2019 Earthing and Protection Rev1

    25/56

    APPLICATIONS

    1. House hold earthing,

    2. Transmission & distribution systems,

    3. Substation & Power Generators Transformer

    earths,4. Telecommunication Towers & Microwave

    Antennas,

    5. Lightning protection earths in difficult

    conditions for home as well as indusries,6. Manufacturing Facilities & Refineries,

    7. Computers & Data processing Centers.

  • 7/28/2019 Earthing and Protection Rev1

    26/56

    PROPER INSTALLATION

    METHODIn normal Soil:

    Make the bore of 8 to 10 in diameter manually up to theelectrode length (2 Mtr or 3 Mtr).

    Put a little quantity of Packing Material (a layer of min. 3

    to 4 inch) inside the pit and drop the electrode exactly inthe center of the pit

    Now mix the soil that has been dug out with B.F.C likesand 7 cement.

    Now pour the above mixture in small quantity in the pitfollowed by water and remove the trapped air inside thepit by poking a rod in to the mixture repeatedly.

  • 7/28/2019 Earthing and Protection Rev1

    27/56

    PROPER INSTALLATION

    METHOD Repeat the above exercise

    till the pit is completely filledup. Pour sufficient water sothat mixture is in paste / mudform.

    Allow the pit to absorb thewater and becomescompact.

    Test the earth pit andconnect to the electricalcircuit.

    Avoid excess watering.

    Do not hammer the earthelectrode.

  • 7/28/2019 Earthing and Protection Rev1

    28/56

    LIMITS OF EARTH RESISTANCE

    Type of earth Max. value

    Telegraph and Block instrument return 10 Circuit earths

    Earth for surge arrestors/ lightning

    Dischargers for S&T equipment 10 Signalling equipment earths 10 Signalling cable screen earths in

    A.C. electrified areas 10 Telephone exchange earth 5 Aluminium sheathed Telecom cable

    screen earths in A.C. electrified area 1

    Equipment earth in V.F. Repeater stations

    and cable Huts 5 M.W. Station tower earth 1

  • 7/28/2019 Earthing and Protection Rev1

    29/56

    SINGLE EARTH SYSTEM

    The Telecom installations shall use single earth

    system in which the different earth connections

    from equipments, towers, D.C. power supply,

    metallic structures etc. shall be interconnected toeach other through low resistance earthing

    conductors.

    This method is recommended to keep all the

    points to be earthed at approximately samepotential level.

    SEPARATION BETWEEN MAINS

  • 7/28/2019 Earthing and Protection Rev1

    30/56

    SEPARATION BETWEEN MAINS

    EARTH AND TELECOM EARTH

    The protective earth of Telecom system

    shall not be connected to the earth of

    mains power supply system.

    A minimum distance of 10 Meters is

    desirable..

  • 7/28/2019 Earthing and Protection Rev1

    31/56

    EARTH RESISTANCE

    MEASURMENT Special instruments such as Megger earth testers

    are recommended for making tests to avoid theeffect of back e.m.f. and stray currents.

    While making the earth resistance measurements

    two electrodes called as Auxiliary electrodes onenamed as current electrode(C) and the otherPotential electrode(P) are required to be installed inaddition to the original electrode ie. Earthelectrode(E). The two auxiliary electrodes to be

    installed as given below, Earth resistance shall be measured once in a year by

    suitable measuring instruments.

  • 7/28/2019 Earthing and Protection Rev1

    32/56

    EARTH RESISTANCE

    MEASURMENT

    The current electrode C must be

    sufficiently for away from the Earth

    electrode (E) under test about 30 to 40

    Meters from E. The Potential electrode must be placed in

    between E and C 15 to 20 Meters

    distance taking exactly half of the distance

    between E and C. All the three must be insame straight line.

    METHOD OF EARTH

  • 7/28/2019 Earthing and Protection Rev1

    33/56

    METHOD OF EARTH

    RESISTANCE MEASURMENT

  • 7/28/2019 Earthing and Protection Rev1

    34/56

    PROCEDURE OF TESTING

    Follow the given procedure to get correct value of earth resistance.

    1) Mark the two points named as P and C in a straight line with E,positioning at a distance of 20 Meters from E and 40 Meters fromE respectively as shown in the above figure. Drive the electrodesinto the ground up to 1 Meter. They are M.S. rods of 12.5mmdiameter.

    2) Link C1 and P1 terminals of earth tester.

    3) Connect E to C1 and P1 terminals, P to P2 terminal and C to C2terminal.

    4) Now rotate the handle of the megger and adjust the resistanceknobs to bring the needle to null point.

    5) The range switch to be kept on the required position, beforeadjusting the resistance knobs.

    6) Multiply the reading of the resistance knobs with the rangeselected to get the value of earth resistance in Ohms.

  • 7/28/2019 Earthing and Protection Rev1

    35/56

    MEASURMENT WITH DIGITAL

    EARTH TESTER

  • 7/28/2019 Earthing and Protection Rev1

    36/56

    PROCEDURE OF TESTING

    Follow the given procedure to get correct value of earth resistance. 1) Mark the two points named as P and C in a straight line with E,

    positioning at a distance of 20 Meters from P and 40 Meters fromC respectively as shown in the above figure. Drive the electrodesinto the ground up to 1 Meter. They are M.S. rods of 12.5mmdiameter.

    2) Link E1 and P1 terminals of earth tester. 3) Connect electrode E to E1 and P1 terminals, P to P2 terminal

    and C to E2 terminal.

    4) The range switch to be kept on the required position, beforeoperating the push switch.

    5) Now operate the push switch until the display digits are stable.

    6) Now record the reading on the LCD display. This is the value ofearth resistance in Ohms.

    7) At the end of measurement keep the rang switch in OFF position.

  • 7/28/2019 Earthing and Protection Rev1

    37/56

    MAINTENANCE OF EARTHS

    1) Check earth and its connections periodically at interval of not morethan one month, to ensure that all connections are in tact andsoldered joints are in proper condition.

    2) Measure the earth resistance once in a year. Enter the value, date oflast test and location of earth should be entered in a register.

    3) Earth resistance, date of last testing should also be printed suitablyon the wall of near by structure or post on a conveniently placedsign board.

    4) Water to be added every day to the earth electrode in summer andonce in two days in other seasons.

    5) If earth resistance is more than the nominal value either renew theold earth or provide a new earth.

  • 7/28/2019 Earthing and Protection Rev1

    38/56

    PROTECTION ARRANGEMENTS ACROSS A.C

    MAINS SUPPLY TO TELECOM INSTALLATIONS

    Low voltage lightningdischargers of normalrating 650V shall beprovided across the 230V mains power supply as

    shown in the figure. In the case of high

    tension supply (11 KV orabove) are terminatednear telecom installation

    and suitable polemounted high voltagearrester shall beprovided.

  • 7/28/2019 Earthing and Protection Rev1

    39/56

    DIFFERENT TYPES OF

    PROTECTIVE ARRANGEMENTSProtection arrangement shall be made for undergroundcable conductors, by providing gas discharge (GD) tubes& MOVR, at the following places.

    1) Protection at subscriber premises.

    2) Metallic sheath or armour of the cable shall beearthed and the sheath should connected to the body ofthe metal box.

    3) At transmission/ switching end the metallic sheathshall be earthed and protective devices shall be providedfor each pair.

    4) At transmission point between overhead lines andunderground cables are protected with GD tubes&MOVR if the distance exceeds 500 meters from thecable termination box.

  • 7/28/2019 Earthing and Protection Rev1

    40/56

    SURGE PROTECTION

    Now a days all most all equipments used

    in S&T department includes the electronic

    devices which operates on low voltages.

    To protect these devices from transient

    over voltages produced due to lightning,

    switching of inductive loads, ignition and

    interruption of electronic arcs etc., suitablesurge protection arrangement to be done.

  • 7/28/2019 Earthing and Protection Rev1

    41/56

    SURGE PROTECTION

    The low voltage equipments eg. UPS, Battery

    charger, Inverter, control systems, etc are

    provided with surge components like MOVRs,

    avalanche diodes, Gas discharge tubes etc.inside the equipments.

    The internally used Surge protection

    Components prove to be inadequate towards

    the surge protection solution. Hence it isrequired to take appropriate solution at different

    levels.

  • 7/28/2019 Earthing and Protection Rev1

    42/56

    LIGHTNING PROTECTION

    LEVELS

    Class A protection:- Protection against thelightning on the structure housing theequipment.

    This is provided with an external lightningconductor on top of the building connectedthrough a down conductor to ground (EARTH).This is known as class A protection.

    By this arrangement 50% of lightning energyconnected to ground. Depending on the area,size of the structure to be protected, the type ofprotection varies.

  • 7/28/2019 Earthing and Protection Rev1

    43/56

    CLASS B PROTECTION

    The first stage of protection provided before theequipment at mains distribution panel is called classB type.

    These are Spark gap type operates on arc choppingprinciple and designed to handle lightning current

    pulses of 10/350us. The sealed type should be used near places having

    explosive gasses like gasoline.

    Maximum operating voltage 1.1 times nominal supplyvoltage.

    The voltage protection/clamping should be as lessthan 1.5KV.Its response time should be less than 200nano seconds.

  • 7/28/2019 Earthing and Protection Rev1

    44/56

    CLASS C PROTECTION

    An Metal Oxide Varistors (MOV) is provided betweenPhase and Neutral and has a surge rating of 50KA8/20 us. This should be a single compact device ofproper rating and in no case a number of varistorsshould be provided in parallel. This device should have

    following additional features: i) Indication to show health of the device which should

    turn red when failed

    ii) Thermal disconnection to the arrester when it startshaving heavy leakage current due to ageing after

    handling repeated surges. iii) Potential free contact for remote monitoring.

    Provision of one set of Class B and C devices ismust. Its normal arrangement is shown in the figure.

  • 7/28/2019 Earthing and Protection Rev1

    45/56

    CLASS D PROTECTION

    It consists of a combination of MOVs and GDtube. This should have all the features asmentioned above for Class C device.

    All external data/signaling (ac/dc) linesconnected to electronic equipment should beprotected by this arrangement.

    One exception where Class D device shouldnot be provided is the cable conductorscarrying signal lighting fed as leakage in MOVsDue to ageing will have adverse effect onworking of Lamp Proving Relays (ECRs).

  • 7/28/2019 Earthing and Protection Rev1

    46/56

    PROTECTION ARRANGEMENTS

    SURGE PROTECTION DEVICES

  • 7/28/2019 Earthing and Protection Rev1

    47/56

    SURGE PROTECTION DEVICES

    (SPDS)

    Electronic equipment can be protected from the

    potentially destructive effects of high-voltage

    transients.

    Protective devices, known by avariety of names(including lightning barriers, surge arrestors ,

    lightning protection units, etc.) are available.

    The correct name (accepted internationally) is

    surge protection devices or SPDs.

  • 7/28/2019 Earthing and Protection Rev1

    48/56

    LIGHTNING

    Figure shows the

    wind, temperature and

    ice/water distribution

    in a thundercloud.The violent up

    draughts and

    downdraughts in the

    cloud centre generatestatic charges.

    MAGNITUDE OF LIGHTNING

  • 7/28/2019 Earthing and Protection Rev1

    49/56

    MAGNITUDE OF LIGHTNING

    VOLTAGE

    The voltage is estimated to be of the order

    of 107 to 108 volts, i.e. 10 million to 100

    million volts. The intense field which is

    generated between the charge centerscauses ionisation of air molecules to take

    place and a conducting channel is opened

    which permits charge neutralisation tooccur i.e., lighting stroke.

  • 7/28/2019 Earthing and Protection Rev1

    50/56

    SURGE CURRENT PULSE

    In order to be able totest protectionnetworks and providecomparison

    data, variousstandard waveformshave been proposedover the years.

    These are all definedin terms of magnitudeand waveshape.

  • 7/28/2019 Earthing and Protection Rev1

    51/56

    SURGE CUTTENT PULSE

    It can refer to current (normally associated withshort-circuit conditions) or voltage (associatedwith open-circuit faults). Waveforms are usuallydouble exponential rise and decay shapes,

    specified by two time periods; rise-time to peakvalue and decay-time to 50% peak value.

    IEC 60060-2 describes a particular method ofdetermining slopes, etc. and is more relevant formanufacturers of test apparatus.

    Instrumentation protection circuits are almostalways specified in relation to 8/20s currentpulses of typically 3kA magnitude.

  • 7/28/2019 Earthing and Protection Rev1

    52/56

    FUNCTION OFSPD

    Surge protection devices should ideally operate

    instantaneously to divert a surge current to

    ground with no residual common-mode

    voltage presented at the equipment terminals. Once the surge current has subsided, the SPD

    should automatically restore normal operation

    and reset to a state ready to receive the next

    surge.

  • 7/28/2019 Earthing and Protection Rev1

    53/56

    SPD DEVICES

    They are,

    1. Gas discharge tubes (GDTs),

    2. Voltage-clamping diodes,

    3. Metal-oxide varistors (MOVs) Feature are,

    1. Rapid operation,

    2. Accurate voltage control and

    3. Automatic resetting once the overvoltagehas ceased.

    2 ELEMENT GAS DISCHARGE

  • 7/28/2019 Earthing and Protection Rev1

    54/56

    2 ELEMENT GAS DISCHARGE

    TUBES CONNECTION Gas discharge tubes (GDTs)

    seek to overcome some of thedisadvantages of air or carbonspark gaps by hermeticsealing, thereby eliminatingenvironmental effects. Gasfilling enables spark dischargeconditions to be quiterigorously controlled since the

    breakdown voltage of such adevice is related to gas

    pressure and electrodeseparation for a particular setof materials.

  • 7/28/2019 Earthing and Protection Rev1

    55/56

    GAS DISCHARGE TUBES

    Typically, low voltage protection devices

    have electrode spacing of 1mm or so in an

    argon/hydrogen mixture sealed within a

    ceramic envelope at about 0.1 bar.

    3 ELEMENT GD TUBE

  • 7/28/2019 Earthing and Protection Rev1

    56/56

    3 ELEMENT GD TUBE

    CONNECTION