drip irrigation - penn state university

Upload: central-ohio-rain-garden-initiative

Post on 29-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 Drip Irrigation - Penn State University

    1/71

    3/19/2010

    DRIP IRRIGATIONSYSTEM

    bybyAlbert Jarrett,Albert Jarrett,

    Professor of BiologicalProfessor of Biological

    EngineeringEngineeringPenn State UniversityPenn State University

  • 8/9/2019 Drip Irrigation - Penn State University

    2/71

    3/19/2010

    The Pennsylvania Protocol

    In Chapter 73 (In Chapter 73 (ConventionalConventional).). InIn--Ground Systems (Limiting Zone >60 in).Ground Systems (Limiting Zone >60 in).

    Beds.Beds.

    Trenches.Trenches.

    Subsurface Sand Filters.Subsurface Sand Filters. Elevated Sand Mounds (Limiting Zone >20 in).Elevated Sand Mounds (Limiting Zone >20 in).

    Individual Residential Spray Irrigation SystemIndividual Residential Spray Irrigation System

    Bedrock Limiting Zone > 16 in.Bedrock Limiting Zone > 16 in.

    Water Table Limiting Zone >10 in.Water Table Limiting Zone >10 in.

  • 8/9/2019 Drip Irrigation - Penn State University

    3/71

    Drip Irrigation Drip Irrigation is an Alternate OnDrip Irrigation is an Alternate On--LotLot

    Disposal System.Disposal System.

    The following slides present the dripThe following slides present the dripirrigation system concept in some detail.irrigation system concept in some detail.

    This presentation ends with an exampleThis presentation ends with an example

    that shows the design process.that shows the design process.

  • 8/9/2019 Drip Irrigation - Penn State University

    4/71

    Soil Conditions:

    Rock Limiting ZoneRock Limiting Zone 26 inches.26 inches.

    Seasonal High Water Table LimitingSeasonal High Water Table Limiting

    ZoneZone 20 inches.20 inches.

    SlopeSlope 25% 25%..

    26 inches 20 inches

  • 8/9/2019 Drip Irrigation - Penn State University

    5/71

    Soil Conditions No Perc Test is required.No Perc Test is required.

    Soil profile must beSoil profile must be

    evaluated by a licensedevaluated by a licensedsoil scientist whosoil scientist who

    evaluates the probes.evaluates the probes.

    Soils must be wellSoils must be well

    drained or moderatelydrained or moderatelywell drained.well drained.

  • 8/9/2019 Drip Irrigation - Penn State University

    6/71

  • 8/9/2019 Drip Irrigation - Penn State University

    7/71

    Drip Irrigation

    Overview w/ Aerobic Tank Major ComponentsMajor Components

    Treatment Tank FiltrationHydraulic

    Pump Tank

    Hydraulic

    Unit

    Zones

  • 8/9/2019 Drip Irrigation - Penn State University

    8/71

    Drip Irrigation

    Overview w/ Sand Filter Major ComponentsMajor Components

    Treatment TankFiltration

    Hydraulic

    Pump Tank

    Hydraulic

    Unit

    Zones

  • 8/9/2019 Drip Irrigation - Penn State University

    9/71

    Treatment Processes

    From Home to Treatment Tank.From Home to Treatment Tank.

    Septic TankSeptic Tank

    Solids settleSolids settle

    Scum floats to surfaceScum floats to surface

    Two Chamber Septic TanksTwo Chamber Septic Tanks

    required.required.

  • 8/9/2019 Drip Irrigation - Penn State University

    10/71

    Treatment Tank

    TwoTwo--Chamber Septic TankChamber Septic Tank

  • 8/9/2019 Drip Irrigation - Penn State University

    11/71

    Treatment Processes

    From the Treatment Tank to the FiltrationFrom the Treatment Tank to the Filtration

    Unit.Unit.

    Secondary Treatment is required ifSecondary Treatment is required if

    Limiting Zone < 48 inches.Limiting Zone < 48 inches.

    Aerobic Treatment TankAerobic Treatment Tank

    Free Access Sand Filter (5 gal/d/ftFree Access Sand Filter (5 gal/d/ft22))

    Subsurface Sand Filter (0.8 gal/d/ftSubsurface Sand Filter (0.8 gal/d/ft22))

  • 8/9/2019 Drip Irrigation - Penn State University

    12/71

    Aerobic Treatment Tank

  • 8/9/2019 Drip Irrigation - Penn State University

    13/71

    Free Access Sand Filter

    (side view)

  • 8/9/2019 Drip Irrigation - Penn State University

    14/71

    Free Access Sand Filter

    (top view)

  • 8/9/2019 Drip Irrigation - Penn State University

    15/71

    Subsurface Sand Filter

    (partial side view)

  • 8/9/2019 Drip Irrigation - Penn State University

    16/71

  • 8/9/2019 Drip Irrigation - Penn State University

    17/71

    Treatment Processes From the Filtration Unit to the Hydraulic UnitFrom the Filtration Unit to the Hydraulic Unit

    to the Drip Zones.to the Drip Zones.

    The filtered effluent flows, by gravity, intoThe filtered effluent flows, by gravity, intothe Hydraulic Unit Pump Tank:the Hydraulic Unit Pump Tank:

    Here a series of float switches controlsHere a series of float switches controlsthe flow of partially treated wastewaterthe flow of partially treated wastewaterto the Hydraulic Unit.to the Hydraulic Unit.

    The Hydraulic Unit is 2 (or 3) discThe Hydraulic Unit is 2 (or 3) discfilters that provide final filtrationfilters that provide final filtrationbefore application to the soil.before application to the soil.

  • 8/9/2019 Drip Irrigation - Penn State University

    18/71

    Hydraulic Unit Pump Tank

    Pump TankPump Tank

    Receives Filter Unit effluentReceives Filter Unit effluent

    Doses effluent to Hydraulic Unit and Zones.Doses effluent to Hydraulic Unit and Zones.

    Contains pumpContains pump--control switches.control switches.

  • 8/9/2019 Drip Irrigation - Penn State University

    19/71

    Hydraulic Unit Contains 2 (or 3)Contains 2 (or 3)

    disc filters.disc filters.

    Provides finalProvides finalfiltration beforefiltration before

    going to dripgoing to drip

    zones.zones.

    Must have at leastMust have at least

    2 zones.2 zones.

  • 8/9/2019 Drip Irrigation - Penn State University

    20/71

    Drip Zones

  • 8/9/2019 Drip Irrigation - Penn State University

    21/71

    Drip Zones Each long sectionEach long section

    of a zone is on theof a zone is on thecontour.contour.

    Each zone mayEach zone mayhave more thanhave more than

    one lateral.one lateral. Each lateral mayEach lateral may

    have more thanhave more thanone zone.one zone.

    Each zone mustEach zone musthave a supply andhave a supply and

    return line.return line. Air vents are alsoAir vents are also

    required on eachrequired on eachzone.zone.

  • 8/9/2019 Drip Irrigation - Penn State University

    22/71

    Drip System With Water LimitingWith Water Limiting

    ZoneZone uu 20 inches.20 inches.

    u 20 inchesEmitters spaced 2 feet

    apart; 0.68 gal/d/em

    0 to 12 in deep; 6 to 12 in

    of cover over the tubing.

    Maybe as small as 8 in

  • 8/9/2019 Drip Irrigation - Penn State University

    23/71

    Drip System With Rock LimitingWith Rock Limiting

    ZoneZone uu 26 inches.26 inches.

    u 20 inchesEmitters spaced 2 feet

    apart; 0.68 gal/d/em

    0 to 12 in deep; 6 to 12 in

    of cover over the tubing.

  • 8/9/2019 Drip Irrigation - Penn State University

    24/71

    Drip System; 3rd

    Configuration

    With Rock Limiting ZoneWith Rock Limiting Zone uu 20 inches.20 inches.

    u 20 inchesEmitters spaced 2 feet

    apart; 0.65 gal/d/em

    Driplines laid on soil

    surface and covered

    with native topsoil.

  • 8/9/2019 Drip Irrigation - Penn State University

    25/71

    Simple Example A site, with a 3A site, with a 3--bdrm home, has a well drained soilbdrm home, has a well drained soil

    with a rock limiting zone at 35 inches and a seasonalwith a rock limiting zone at 35 inches and a seasonalhigh watertable at 25 inches.high watertable at 25 inches.

    The site has a 10% slope.The site has a 10% slope.

    Soil Scientist report states:Soil Scientist report states:

    Maximum soil linear load rate = 0.25 gal/ft/d.Maximum soil linear load rate = 0.25 gal/ft/d.

    Horizontal linear load = 3.5 gal/ft/d.Horizontal linear load = 3.5 gal/ft/d.

    Drip tubing spacing to be at least 2.0 feet.Drip tubing spacing to be at least 2.0 feet. Tubing to be buried at least 6 inches deep.Tubing to be buried at least 6 inches deep.

  • 8/9/2019 Drip Irrigation - Penn State University

    26/71

  • 8/9/2019 Drip Irrigation - Penn State University

    27/71

    Soil Conditions:

    Rock Limiting ZoneRock Limiting Zone == 35 inches.35 inches.

    Seasonal High Water Table LimitingSeasonal High Water Table Limiting

    ZoneZone == 25 inches.25 inches.

    SlopeSlope = 10%= 10%..

    = 35 inches

    = 25 inches

  • 8/9/2019 Drip Irrigation - Penn State University

    28/71

    Soil Conditions:

    Rock Limiting ZoneRock Limiting Zone == 35 inches.35 inches.

    = 35 inches

    6 inches

    29 inches

  • 8/9/2019 Drip Irrigation - Penn State University

    29/71

    Soil Conditions:

    Seasonal High Water Table LimitingSeasonal High Water Table Limiting

    ZoneZone == 25 inches.25 inches.

    = 25 inches

    6 inches

    19 inches

  • 8/9/2019 Drip Irrigation - Penn State University

    30/71

    Example Soil Scientists ReportSoil Scientists Report

    Maximum linear loading rate = 0.25Maximum linear loading rate = 0.25

    gal/d/ft.gal/d/ft.

    Horizontal linear load = 3.5 gal/d/ftHorizontal linear load = 3.5 gal/d/ft

  • 8/9/2019 Drip Irrigation - Penn State University

    31/71

    Example The septic tank is sized as per Chapter 73 forThe septic tank is sized as per Chapter 73 for

    a 3 bdrm home.a 3 bdrm home.

    This is a drip system, so a SecondaryThis is a drip system, so a SecondaryTreatment unit is needed. The choices are:Treatment unit is needed. The choices are:

    Aerobic Treatment TankAerobic Treatment Tank

    Free Access sand filter.Free Access sand filter.

    Subsurface sand filter.Subsurface sand filter. See the Secondary Treatment slides forSee the Secondary Treatment slides for

    sizing guidelines for these units.sizing guidelines for these units.

  • 8/9/2019 Drip Irrigation - Penn State University

    32/71

    Example Following the PreFollowing the Pre--treatment unit the effluenttreatment unit the effluent

    will flow into a Dose/Pump tank.will flow into a Dose/Pump tank.

  • 8/9/2019 Drip Irrigation - Penn State University

    33/71

    Example The Pump/Dose Tank must be at leastThe Pump/Dose Tank must be at least

    2 times larger than the maximum daily2 times larger than the maximum daily

    flow.flow.

    The maximum daily flow from a 3The maximum daily flow from a 3--bdrmbdrm

    home is taken to be 400 gpd.home is taken to be 400 gpd.

    Therefore the Pump/Dose Tank must beTherefore the Pump/Dose Tank must beat least 800 gallons in size.at least 800 gallons in size.

  • 8/9/2019 Drip Irrigation - Penn State University

    34/71

    Example In a Drip Irrigation system the effluent isIn a Drip Irrigation system the effluent is

    pumped from the Dose/Pump Tank to thepumped from the Dose/Pump Tank to the

    Hydraulic Unit and on to the drip zones.Hydraulic Unit and on to the drip zones.

  • 8/9/2019 Drip Irrigation - Penn State University

    35/71

    Example The Hydraulic Unit controls the flow toThe Hydraulic Unit controls the flow to

    zones and backflushing. Two units arezones and backflushing. Two units are

    available: 2available: 2--disc and 3disc and 3--disc units.disc units.The twoThe two--disc unit supports:disc unit supports:

    1,200 ft of drip tubing/zone.1,200 ft of drip tubing/zone.

    Tubing forward flush rate = 15 gpm.Tubing forward flush rate = 15 gpm.

    4 zones and one return connection.4 zones and one return connection.

    4,800 ft of drip tubing (4x1200).4,800 ft of drip tubing (4x1200).

  • 8/9/2019 Drip Irrigation - Penn State University

    36/71

  • 8/9/2019 Drip Irrigation - Penn State University

    37/71

    Example Length of drip tubing required:Length of drip tubing required:

    Max daily flow/linear loading rateMax daily flow/linear loading rate

    400 gpd/0.25 gal/d400 gpd/0.25 gal/d--ft = 1600 ft.ft = 1600 ft.

    We will use 2 zones.We will use 2 zones.

    1600 ft/2 = 800 ft/zone1600 ft/2 = 800 ft/zone

  • 8/9/2019 Drip Irrigation - Penn State University

    38/71

    Example Each zone will consist ofEach zone will consist of

    8 runs of 100 ft each.8 runs of 100 ft each.

    4 laterals, each 200 ft long. (24 laterals, each 200 ft long. (2

    runs/lateral).runs/lateral).

    Supply Line

    Return line

    Air Vent & Check Valve

    Run

    Lateral (4)

  • 8/9/2019 Drip Irrigation - Penn State University

    39/71

    Example Check to make sure the runs are longCheck to make sure the runs are long

    enough.enough.

    Based on the Average daily flowBased on the Average daily flow

    400 gpd (.5) = 200 gpd.400 gpd (.5) = 200 gpd.

    Horizontal linear load = 3.5 gal/gHorizontal linear load = 3.5 gal/g--ftft

    Minimum run length = 200/3.5 = 57 ft.Minimum run length = 200/3.5 = 57 ft.

    Our runs are 100 ft long; Okay.Our runs are 100 ft long; Okay.

  • 8/9/2019 Drip Irrigation - Penn State University

    40/71

    Example (Summary) Peak daily flow = 400 gpd.Peak daily flow = 400 gpd. Soil linear load = 0.25 gal/dSoil linear load = 0.25 gal/d--ft.ft.

    Total tubing length required = 1600 ft.Total tubing length required = 1600 ft.

    2 zones used.2 zones used.

    Hydraulic Unit used = 2 disc.Hydraulic Unit used = 2 disc. Tubing length/zone = 1600/2 = 800 ft.Tubing length/zone = 1600/2 = 800 ft.

    No. Laterals/zone = 4No. Laterals/zone = 4

    Lateral length = 800/4 = 200 ft.Lateral length = 800/4 = 200 ft.

    Run length = 100 ft.Run length = 100 ft. Horizontal linear load = 3.5 gal/dHorizontal linear load = 3.5 gal/d--ft.ft.

    Minimum run length = 200/3.5 = 57 ft.Minimum run length = 200/3.5 = 57 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    41/71

    Example Flow required to each zone duringFlow required to each zone during

    Forward Field Flush HydraulicForward Field Flush Hydraulic

    Condition.Condition.

    Need:Need:

    Dose flow rate PLUSDose flow rate PLUS

    Field flush flow rateField flush flow rate

  • 8/9/2019 Drip Irrigation - Penn State University

    42/71

    Example Dose flow rate (for each zone)=Dose flow rate (for each zone)=

    hrgphx

    nemittersdistbetweenelengthofzo

    min/6065.0

    gpmhr

    gphxemittersft

    ft 3.4min/6065.0

    /2800 !

  • 8/9/2019 Drip Irrigation - Penn State University

    43/71

    Example Field flush flow rate/zone = 1.6Field flush flow rate/zone = 1.6

    gpm/lateral (to maintain a velocity of 2gpm/lateral (to maintain a velocity of 2

    fps in drip tubes)fps in drip tubes)=1.6gpm/lat x 4 laterals = 6.4=1.6gpm/lat x 4 laterals = 6.4

    gpm/zonegpm/zone

    Total flow required during Forward FieldTotal flow required during Forward FieldFlush is 4.3 + 6.4 = 10.7 gpm.Flush is 4.3 + 6.4 = 10.7 gpm.

  • 8/9/2019 Drip Irrigation - Penn State University

    44/71

    Example (Pump Selection) The remaining task is to size the pump.The remaining task is to size the pump.

    This means that we must determine:This means that we must determine:

    Systems total headSystems total head

    Systems maximum flow rate.Systems maximum flow rate.

  • 8/9/2019 Drip Irrigation - Penn State University

    45/71

    Example (Bernoulli Analysis) The Total Head for the pump in the DoseThe Total Head for the pump in the Dose

    Tank is the sum of three components:Tank is the sum of three components:

    Head Loss in all the pipes.Head Loss in all the pipes. Pressure needed to run the system, eitherPressure needed to run the system, either

    the emitters or the Hydraulic Unit.the emitters or the Hydraulic Unit.

    Elevation difference between the waterElevation difference between the waterlevel in the dose tank to the drip zones.level in the dose tank to the drip zones.

    The Total Head is the SUM of these threeThe Total Head is the SUM of these threevalues.values.

  • 8/9/2019 Drip Irrigation - Penn State University

    46/71

    Example (Friction; HL) The Head Loss (or Friction) is the mostThe Head Loss (or Friction) is the most

    difficult to determine. This must be donedifficult to determine. This must be done

    in parts:in parts:HHLL in the pipe from the dose tank toin the pipe from the dose tank to

    the Hydraulic Unit.the Hydraulic Unit.

    HHLL in the Zone supply pipes.in the Zone supply pipes.

    HHLL in the drip lines.in the drip lines.

    HHLL in the Zone return pipes.in the Zone return pipes.

  • 8/9/2019 Drip Irrigation - Penn State University

    47/71

    Example (HL from tank to HU) First size this pipe to carry theFirst size this pipe to carry the

    maximum flow.maximum flow.

    During dosing the pipe will carry 10.7During dosing the pipe will carry 10.7

    gpm.gpm.

    During back flushing this pipe will carryDuring back flushing this pipe will carry

    15 gpm.15 gpm. Size for theSize for the 15 gpm15 gpm..

  • 8/9/2019 Drip Irrigation - Penn State University

    48/71

    Example (Size the pipe to HU) With a design flow rate of 15 gpm andWith a design flow rate of 15 gpm and

    using PVCusing PVC--scheduleschedule--40 pipe, we will40 pipe, we will

    need a 1.5need a 1.5--inch pipe to keep theinch pipe to keep thevelocity above 2.0 fps. (V = 2.35 fps).velocity above 2.0 fps. (V = 2.35 fps).

    This 1.5This 1.5--in PVC pipe has a frictionin PVC pipe has a friction

    factor, Ffactor, Fcc = 0.63 psi/100 ft or 1.46 ft/100= 0.63 psi/100 ft or 1.46 ft/100ft.ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    49/71

  • 8/9/2019 Drip Irrigation - Penn State University

    50/71

    Example (HL from tank to HU) The HThe HLL is calculated from:is calculated from:

    HHLL = F= FccLL

    HHLL = 1.46 ft/100 ft(70ft) = 1.02 ft.= 1.46 ft/100 ft(70ft) = 1.02 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    51/71

    Example (HL in Supply Pipe) First size the Supply pipe to carry theFirst size the Supply pipe to carry the

    maximum flow.maximum flow.

    During dosing the pipe will carry 10.7During dosing the pipe will carry 10.7gpm.gpm.

    Not used during back flushing.Not used during back flushing.

    Size for theSize for the 10.7 gpm10.7 gpm..

  • 8/9/2019 Drip Irrigation - Penn State University

    52/71

  • 8/9/2019 Drip Irrigation - Penn State University

    53/71

    Example (HL in Supply Pipe) Before we can determine the HBefore we can determine the HLL in thisin this

    pipe, we must determine the length ofpipe, we must determine the length of

    the supply pipe [this is assumed to be athe supply pipe [this is assumed to be astraight pipe].straight pipe].

    The length of pipe was given at 100The length of pipe was given at 100

    ft.ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    54/71

    Example (HL in Supply Pipe) The HThe HLL is calculated from:is calculated from:

    HHLL = F= FccLL

    HHLL = 1.62 ft/100 ft(100ft) = 1.62 ft.= 1.62 ft/100 ft(100ft) = 1.62 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    55/71

    Example (HL inD

    rip Zone) We desire to deliver 10.7 gpm to eachWe desire to deliver 10.7 gpm to each

    zone. Of this water:zone. Of this water:

    4.3 gpm will go out the emitters.4.3 gpm will go out the emitters.

    6.4 gpm will flush through the drip6.4 gpm will flush through the drip

    lines and be returned to the buildinglines and be returned to the building

    sewer.sewer.

  • 8/9/2019 Drip Irrigation - Penn State University

    56/71

    Example (HL inD

    rip Zone) The drip supplier specifies that for 200The drip supplier specifies that for 200--ftft

    laterals, the losses in the drip lines willlaterals, the losses in the drip lines will

    be 18 ft (Table 3A).be 18 ft (Table 3A).

  • 8/9/2019 Drip Irrigation - Penn State University

    57/71

  • 8/9/2019 Drip Irrigation - Penn State University

    58/71

    Example (Size the Return Pipe) With a design flow rate of 6.4 gpm andWith a design flow rate of 6.4 gpm and

    using PVCusing PVC--scheduleschedule--40 pipe, we will40 pipe, we will

    need a 1.0need a 1.0--inch pipe to keep theinch pipe to keep thevelocity above 2.0 fps. (V = 2.30 fps).velocity above 2.0 fps. (V = 2.30 fps).

    This 1.00This 1.00--in PVC pipe has a frictionin PVC pipe has a friction

    factor, Ffactor, Fcc = 0.95 psi/100 ft or 2.19 ft/100= 0.95 psi/100 ft or 2.19 ft/100ft.ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    59/71

    Example (HL in Return Pipe) Before we can determine the HBefore we can determine the HLL in thisin this

    pipe, we must determine the length ofpipe, we must determine the length of

    the supply pipe [this is assumed to be athe supply pipe [this is assumed to be astraight pipe].straight pipe].

    The length of pipe was given at 140The length of pipe was given at 140

    ft.ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    60/71

    Example (HL in Return Pipe) The HThe HLL is calculated from:is calculated from:

    HHLL = F= FccLL

    HHLL = 2.19 ft/100 ft(140ft) = 3.07 ft.= 2.19 ft/100 ft(140ft) = 3.07 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    61/71

    Example (HL Summary) The Head Loss (or Friction) for theseThe Head Loss (or Friction) for these

    four sections of our system is:four sections of our system is:

    HHLL Dose Tank to the HU = 1.02 ft.Dose Tank to the HU = 1.02 ft.

    HHLL Supply Pipe = 1.62 ft.Supply Pipe = 1.62 ft.

    HHLL Drip Lines = 18 ft.Drip Lines = 18 ft.

    HHLL Return Pipe = 3.07 ftReturn Pipe = 3.07 ft

    Total HTotal HLL = 23.7 ft.= 23.7 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    62/71

  • 8/9/2019 Drip Irrigation - Penn State University

    63/71

    Example (Pressure Requirements) Without having worked with this system, IWithout having worked with this system, I

    would assume the following:would assume the following:

    The pressure needed to run the HU shouldThe pressure needed to run the HU shouldbe 10 to 20 psi (23 to 46 ft).be 10 to 20 psi (23 to 46 ft).

    The pressure needed to make the emittersThe pressure needed to make the emittersfunction properly is generally about 10 psifunction properly is generally about 10 psi(23 ft).(23 ft).

    The total pressure requirement = 46 + 23 =The total pressure requirement = 46 + 23 =69 ft.69 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    64/71

    Example (ElevationD

    ifference) Elevation differences include:Elevation differences include:

    Rise from enabler float in dose tank toRise from enabler float in dose tank to

    Hydraulic Unit (+ 7 ft).Hydraulic Unit (+ 7 ft).

    Rise from the Hydraulic Unit to theRise from the Hydraulic Unit to the

    drip Zones (+20 ft).drip Zones (+20 ft).

    Total elevation rise = 7 + 20 = 27 ft.Total elevation rise = 7 + 20 = 27 ft.

  • 8/9/2019 Drip Irrigation - Penn State University

    65/71

    Bernoulli Summary (D

    osing) The total energy needed to run thisThe total energy needed to run this

    system is:system is:

    HHLL = 23.7 ft.= 23.7 ft.

    Pressure = 69 ft.Pressure = 69 ft.

    Elevation rise = 27 ft.Elevation rise = 27 ft.

    Total during dosing = 120 ft.Total during dosing = 120 ft.

    Flow rate = 10.7 gpm.Flow rate = 10.7 gpm.

  • 8/9/2019 Drip Irrigation - Penn State University

    66/71

    Bernoulli Summary (Back Flushing)

    The total energy needed to run thisThe total energy needed to run this

    system is:system is:

    HHLL = 115 + 1.02 = 116 ft.= 115 + 1.02 = 116 ft.

    Pressure = 0 ft.Pressure = 0 ft.

    Elevation rise = 7 ft.Elevation rise = 7 ft.

    Total during dosing = 123 ft.Total during dosing = 123 ft.

    Flow rate = 15 gpm.Flow rate = 15 gpm.

  • 8/9/2019 Drip Irrigation - Penn State University

    67/71

    Example (Pump Requirement) ForDosingForDosing

    HHTT = 120 ft= 120 ft

    Q = 10.7 gpmQ = 10.7 gpm

    For Back FlushingFor Back Flushing

    HHTT = 123 ft.= 123 ft.

    Q = 15 gpm.Q = 15 gpm.

    Pump DesignPump Design

    HHTT = 123 ft.= 123 ft. Q = 15 gpmQ = 15 gpm..

  • 8/9/2019 Drip Irrigation - Penn State University

    68/71

    Example (Time/D

    ose)Average daily flow = 200 gpdAverage daily flow = 200 gpd

    Each zone accounts for 50% of flow.Each zone accounts for 50% of flow.

    Zone 1 = 100 gpdZone 1 = 100 gpdZone 2 = 100 gpdZone 2 = 100 gpd

    At 4 doses /zone/day; each dose mustAt 4 doses /zone/day; each dose must

    apply 25 gal.apply 25 gal. Time/dose = 25 gal/dose/4.3 gpmTime/dose = 25 gal/dose/4.3 gpm

    = 5.8 min= 5.8 min

  • 8/9/2019 Drip Irrigation - Penn State University

    69/71

  • 8/9/2019 Drip Irrigation - Penn State University

    70/71

    Example (Time/D

    ose) Under condition of Maximum daily flowUnder condition of Maximum daily flow

    (400 gpd)(400 gpd)

    We apply 200 gal/zone/dayWe apply 200 gal/zone/day

    At 4.3 gpm (25 gal/dose).At 4.3 gpm (25 gal/dose).

    200/25 = 8 doses/day.200/25 = 8 doses/day.

  • 8/9/2019 Drip Irrigation - Penn State University

    71/71

    Thank You