Drinking Water Treatment Using Air Strippers Dave Fischer Dave Fischer QED Environmental Systems Inc. Ann Arbor, MI / San Leandro, CA Copyright © QED Environmental Systems, Inc. 2007- 2011; all rights reserved.

Upload: others

Post on 24-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Drinking Water TreatmentUsing Air Strippers

Dave FischerDave FischerQED Environmental Systems Inc.Ann Arbor, MI / San Leandro, CA

Copyright © QED Environmental Systems, Inc. 2007- 2011; all rights reserved.

Page 2: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Presentation Overview

• US Drinking Water SourcesVOCs in Public Water Supplies• VOCs in Public Water Supplies

• VOC Treatment Methods• Air Stripping and Types of Air StrippersAir Stripping and Types of Air Strippers• QED E-Z Tray®

• The QED Air Stripper Modelerpp• Process Requirements• THM Removal• Ammonia, H2S, Radon and Methane• Case Studies

Page 3: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Drinking Water Sources

• 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are defined as “community water systems” (CWS)community water systems (CWS)

• 92% of the US population receive their water from a CWS

• 40,600 or 80% obtain part or all of their water from groundwater supply wells

Page 4: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

VOCs in Public Water SuppliesChloroform

Methyl tert-butyl ether (MTBE)Perchloroethene (PCE)Perchloroethene (PCE)

BromoformDibromochloromethaneTrichloroethene (TCE)

BromodichloromethaneBromodichloromethane1,1,1-Trichloroethane (TCA)

1,1-Dichloroethane (1,1-DCA)Dichlorodifluoromethane (CFC-12)

cis-1,2-Dichloroethene (cis-1,2-DCE), ( , )1,1,-Dichloroethene (1,1-DCE)

Trichlorofluoromethane (CFC-11)Trans-1,2-Dichloroethene (trans-1,2-DCE)

Toluene

DETECTION FREQUENCY IN PERCENT

Page 5: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

“Traditional” Treatment Methods

• Filtration with granular activated carbon (GAC)• Chemical treatment systemsChemical treatment systems• Biological treatment methods

R d ti f THMReduction of THMs

• Reducing organic carbon prior to disinfection• Alternate disinfectant (e.g., ozone)• Removal of THMs downstream

Page 6: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Air StrippingA process that removes or “strips” volatile organic compounds from contaminated water by contacting clean air with

t i t d tcontaminated water across a high surface area, causing the volatile compounds to move fromcompounds to move from the water into the air.

Process is governed by H ’ LHenry’s Law.

Driving dissolved volatile organic contaminants fromorganic contaminants from water into air.

Page 7: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Air Stripping Air Flow Contaminated water

Counter-current flow means the cleanest air

t t th l t

water

contacts the cleanest water. This ensures efficient mass transfer throughout the entire oug ou e e eflow path.

Clean water

Page 8: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Air Stripping

Air water contact happens in the active tray areas. yHigh air to water surface for transfer is created by the turbulent froth mixture.

Page 9: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Air Stripping

The froth in action.

Page 10: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Air Stripping

T t ff t th hi h

Some physical elements

• Temperature affects the process – higher temperature = better stripping

• Process temperature is roughly equal to water• Process temperature is roughly equal to water temperature; air temperature not a big factor

• Freezing is not a concern for continuous operationFreezing is not a concern for continuous operation

• Discharged air is saturated (high humidity) at the process temperature, so consider condensation and thermal impacts if air treatment is planned

Page 11: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Air Stripping Methods

Simple Storage Tank Aeration• Simple Storage Tank Aeration• Tower Strippers• Stacking Tray Strippers• Sliding Tray Stripper (QED E-Z Tray)g y pp ( y)

Page 12: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Simple Storage Tank Aeration• Water is circulated within a holding

tank and discharged from spray lnozzles

• Nozzles develop significant back pressure (30-40psi)

• Mass transfer occurs as droplets fall through free air

• Multiple passes are needed to provide p p pTHM removal

• 8 passes required to reach 50-60% removal1. (compare to 60-80% TTHM ( preduction with 1 pass through an E-Z Tray stripper)

Spray Nozzles1. “Violation Prompts Treatment Change”, July 2011 Opflow

Page 13: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Tower StripperMethodThin film of water flows over a high surface area gpacking

AdvantagesAdvantages• Lower energy use in the air mover, due to lower overall pressurelower overall pressure drop

DisadvantagesDisadvantages• Flow turn-down difficult• Difficult to clean• Tall structure• Tall structure• Short circuiting

Page 14: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Tower Stripper

If fouling conditions d l th tdevelop, the tower can quickly loose mass transfer area. Small local areas ofSmall local areas of deposition can produce flow short circuiting that furthercircuiting that further limits available contact area.

Page 15: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Tower Stripper vs. Tray Stripper• Biggest issue is cleaning -towers are hard to access and often require flooding with acid solution; high O&M costs• Very tall structure - wind loading, thermal issues, unsightly in some locationsunsightly in some locations• Operating conditions difficult to observe

C l d i• Complex design process due to structural issues• No web based performance pmodel, models harder to use

Page 16: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

E-Z Tray® vs. Tower O&M Example• Site in Sturgis, MI treating 250 GPM water containing:

1 1 1 t i hl th1,1,1-trichloroethanec-1,2-dichloroethylenehexachlorobutadienemethylene chlorideynaphthalenetetrachloroethylene (PERC,PCE)trichloroethylene (TCE)

• Oversized tower replaced with a 500 GPM E-Z Tray

• Historical tower cleaning with acid cost about $54 000/year• Historical tower cleaning with acid cost about $54,000/year

• Pressure washing the E-Z Tray every 40-50 days estimated at $8,000/year$ , y

Page 17: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Stacking Tray Stripper• Stacking tray strippers are a

series of stacked rectangular gboxes with bottom perforations

• Trays layers are sealed with k t d f t d t thgaskets and fastened together

with clamps around outer edges• Cleaning requires lifting trays g q g y

and breaking pipe connections, often requires two or more people or an overhead crane

Stacking Tray Design

people or an overhead crane• Requires access to all sides for

installation and maintenance g y g

More information at -- http://www.qedenv.com/davislf/

Page 18: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Sliding Tray Stripper (E-Z Tray)MethodAir bubbles - froth and turbulent mixing creates mass transfer surface area

Advantages• Easy access• Less prone to fouling• Less prone to fouling• Less intrusive at site• Wide flow turn-down

Disadvantage• Requires higher pressure• Requires higher pressure blower (HP)

Page 19: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

E-Z Tray® Advantages … Cleaning

E-Z Tray Tower Stacking TrayAir Strippers Air Strippers Air Strippers----------------------------------------------------------------------------------------------------

• Single person cleaning(Tray weight is 24 3 lb )

• Packing access and removal is

• Major disassembly and multi person crew

24-73 lbs) difficult needed

Page 20: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

E-Z Tray® Advantages … Footprint

E-Z Tray Tower Stacking TrayAir Strippers Air Strippers Air Strippers----------------------------------------------------------------------------------------------------• Reduced footprint

for installation and maintenance

• Small footprint but very tall structure often required

• Lots of space needed for disassembly, lifting from all sides, pipe disconnection anddisconnection and tray stage stacking

Page 21: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

E-Z Tray® Advantages … Monitoring

E-Z Tray Tower Stacking TrayAir Strippers Air Strippers Air Strippers----------------------------------------------------------------------------------------------------

• Easy process monitoring and inspection, even

• Condition of packing and air flow distribution are very

• Difficult or impossible to observe air and liquid flow distribution

while in operation difficult to observe during operation

Page 22: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

E-Z Tray® Advantages … Modeling

E-Z Tray Tower Stacking TrayAir Strippers Air Strippers Air Strippers----------------------------------------------------------------------------------------------------

• Easily modeled online by customer to help process

• More complex design process due to structural aspects,

• Online modeler not offered

evaluation assistance normally required

Page 23: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

E-Z Tray® Design

One piece shell with single gasketed door cuts down ongasketed door cuts down on possible air leaks

Clear front door gives easy visual check of air stripper performancep

Front access cleaning means piping stays put no need topiping stays put – no need to break connections

Page 24: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Ancillary Equipmenty q p

• Pressure Switch• Skid

• Liquid Flow Meter

• Air Flow Meter

• Blower

• Infeed Pump

• Bag Filters

• Solenoid Valve

• Discharge Pump

• Gravity Drain • Solenoid Valve

• Tank

• Gravity Drain

• Control Panel

• Level Switches

Page 25: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

QED Air Strippers

E-Z Tray E-Z Tray E-Z Tray E-Z TrayyModel 6.4

yModel 16.4

yModel 24.4

yModel 96.6

Page 26: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Modeling the ProcessWeb based Modelhttp://www.qedenv.com/modeler

Xin = aqueous concentration entering the air stripperXout = aqueous concentration exiting the air stripperYin = gas concentration entering the air stripperNth = number of theoretical trays in the air stripper The performance modeler is based on the designNth = number of theoretical trays in the air stripperS = stripping factorKh = Henry’s Law constantL = liquid flow rateG = gas flow rate

The performance modeler is based on the designprocedure discussed in -- Kibbey, T. C. G., K. F. Hayes andPennell, K.D., ‘‘Application of Sieve-Tray Air Strippers tothe Treatment of Surfactant-Containing Wastewaters’’,AIChE Journal, Vol. 47, No. 6, June 2001. Also -- Perry, R.H., and D. W. Green, Perry’s Chemical Engineer’s Hand-book, 7th ed., McGraw-Hill, New York 1997.

Page 27: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Henry’s Constant (H)Larger H = more easily stripped (atm/mol frac)Larger H = more easily stripped (atm/mol-frac)

• vinyl chloride - 1245• TCE – 648

• MTBE - 32• acetone - 2 4TCE 648

• benzene - 309acetone - 2.4

Page 28: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

2 – Other Information

Process Variables

• Temperatures (air and water)• Altitude (air density)• Flow rates (air and water)• Flow rates (air and water)

- Process impacts- Hydraulic impacts

Page 29: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

3 – Pick a Stripper

• First pass – pick the stripper model that matches project flowproject flow

Metric units available on Model Site

Page 30: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

4 – Contaminant Concentrations

• Concentration in ppb (ug/L) – 1000ppb = 1ppm• Each contaminant “operates” independently

Page 31: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

(URL listed to allow easy remodeling)

Page 32: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Successful Process Requirements• Dissolved volatile organics

in a water matrix• No free-phase organics• Clean air (concentration gradient

driven)driven)• High surface area of contact

between air and water• High air to water ratio• Sufficient contact time• No surfactants or other H lowering

Impact of dirty air – less “driving force” for mass transfer

Clean air Contaminated air

• No surfactants or other H lowering factors (dissolved polar organics)

• Stripper is level

Page 33: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Stripper Performance ImpactsStripper Performance Impacts

• Air flow restrictions• Air flow restrictions• Liquid flow issues• Major water/air temperature changes• Major water/air temperature changes• Free phase product or other sorptive

compounds that decrease strippingcompounds that decrease stripping• Surfactants or other polar organic chemicals

that can lower H for target organicsthat can lower H for target organics

Page 34: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Free Phase Product • Coats walls• Residual source in sumpp• Partitioning issues• Interferes with

performance in an unpredictable way

Page 35: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Surfactants / Polar Organics

• Lower effective H for all contaminants due to solubilization of organic compounds by surfactant micelles.C f i• Can cause foaming

– Sometimes subtle (and not required when polar organics are present)

– Demister fouling and blower back-pressure increase– Control = Anti-foam additives (does not recover stripping

effectiveness )– Control = Knock-out tank prior to demister

Page 36: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Surfactants Example

Normal froth Surfactant impacted froth

Page 37: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Types of Tray Air Stripper FoulingTypes of Tray Air Stripper Fouling

• Metal oxides1.Metal oxides• Hardness (scale)• Suspended solidsSuspended solids• Bio solids, slimes• Oils & Greases• Oils & Greases• Free phase non-

aqueous phaseaqueous phase liquids (NAPL)

1. CO2 stripping can cause a slight pH increase, leading to insoluble metal oxide formation

Page 38: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Tray Fouling – Knowing When to Clean

Normal stripper sump pressure = 4-6 inch H2O / tray stage

Page 39: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Tray Fouling - Preventative Measures• Clean trays

– Backup tray set

y g

p y• Sequestering agents

(decrease cleaning frequency)q y)

– inorganic polyphosphates

• Bio-foulingBio fouling– Ozone, etc.

• pH adjustmentI / t– In/out

• Pre-stripper oxidation and filtration for severe cases

Page 40: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Stripper CleaningStripper Cleaning• Cleaning frequency and effort is highly site-g q y g y

specific• Example -

– 1000ppm TDS, 260ppm total hardness, 0.03ppm iron - stripper requires cleaning every 3 weeks

Ti l E Z T i• Time to clean an E-Z Tray stripper– Two 1000gpm, E-Z Tray 96.6 units (8 doors, 48

trays) takes 8-10 minutes/tray to fully removetrays) takes 8-10 minutes/tray to fully remove, pressure wash and reinstall all the trays in this system

Page 41: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

THM Removal

• Trihalomethanes (THMs) can form in drinking water h di i f t t ( hl i ) b k dwhen disinfectant (chlorine) breaks down precursor

organic compounds, normally organic solids• Air stripping is an effective way to reduce THMsAir stripping is an effective way to reduce THMs• THMs can re-form after stripping if organic precursors

are still available

Page 42: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

THM Removal

Henry’s Law predicts that the THM compounds will strip in the following order:the following order:

Chloroform - easiest to stripBromodichloromethane

Parameter H (atm/mol-frac)benzene 309.2chloroform 225.2Bromodichloromethane

DibromochloromethaneBromoform - hardest to strip

bromodichloromethane 63.1dibromochloromethane 44.4MTBE 32bromoform 29.5

Haloacetic Acids (HAAs) are not removed by air stripping

Page 43: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

THM Removal – Some Pilot Data

58.092

Percent THM reduction vs. Water Temperature

QED working with a partner company to

52.0

54.0

56.0

58.0

89909192

mp.

(F)

cent

pconduct THM removal studies at several small

46.0

48.0

50.0

85868788

Wat

er T

em

Percdrinking water

treatment facilities. Results show

11 11 1140.0

42.0

44.0

82838485

consistent THM removal of 85% or more.

11-2 11-3 11-4 11-5 11-9 11-11

11-17

11-23 12-1

% THM Reduction 90 91 90 90 88 86 88 85 84Water temp. 55.4 55.2 54.5 52.8 52.0 52.6 49.6 50.5 42.8

Page 44: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Chloroform Removal

45

THM Removal

30

35

40

20

25

30

CHCl3 in CHCl3 out In – 24 hour Out – 24 hour

Chl

orof

orm

(ppb

)

5

10

15C

0 5 10 15 20 25 30 350

Time (days)

Page 45: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Dibromochloromethane Removal

25

THM Removal

20

25

10

15 DBCM in DBCM out In – 24 hour Out – 24 hour

DB

CM

(ppb

)

5

0 5 10 15 20 25 30 350

Time (days)

Page 46: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Impact on Chlorine Residual

1 4

Chlorine Residual Change

(before / after stripping)

1

1.2

1.4

0.4

0.6

0.8 Influent Effluent

Cl2

(ppm

)

10/13/1010/14/10

10/15/1010/16/10

10/17/1010/18/10

10/19/1010/20/10

10/21/1010/22/10

10/23/1010/24/10

10/25/100

0.2

Sample Date

(Further residual reduction possible if precursors continue to bet d t THM )converted to THMs)

Page 47: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

THM Removal – Process Design

Successful THM removal process design will needsprocess design will needs account for remaining THM precursors, while providing sufficient residual disinfection.

Cl ll l d i tClear well loop design, remote reservoir loop or stripping prior to immediate use may provideto immediate use may provide the best solution.

Page 48: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Pilot Testing

• Prepackaged, just add electricityjust add electricity

• Rental• Used for scale-upUsed for scale up

design• Allows H correction

from results when NAPLs, surfactants, t k t betc. are known to be

presentRental skids available from QED and some equipment contractorsRental skids available from QED and some equipment contractors –contact us for more information.

Page 49: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Additional Site Information for Designg

• Site history of DNAPL and/or LNAPLP t th t h d t t i (DRO t )• Parameters that are hard to strip (DRO, etc.)

• Is O&G above detection limit (is O&G MDL low enough)• Is there air contamination near the blower inlet• Is there air contamination near the blower inlet• Does stable foam form if target water is shaken in a jar• Is there an offset between TOC and the sum of the

target organics• Is there a site history of surfactant use• Are high shear pumps used to capture the water (stable

emulsions of NAPL)

Page 50: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Other Stripper ApplicationsOther Stripper Applications

Ammonia hard to strip• Ammonia – hard to strip • Hydrogen Sulfide – easy to strip

R d l t l t t i• Radon removal – extremely easy to strip• Methane removal – extremely easy to strip

Page 51: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Case Study 1 - NY

• Gasoline spill in high value gresidential area

• Space for process eq ipment limitedequipment limited

• Need for low profile - sound pand appearance

• Strippers housed i t l hi iin metal shipping containers

Page 52: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Case Study 2 - Australia

• Large industrial Li id I

Air Out

chlorinated cleanup • Strippers one component

in a multi-unit / multi-

Liquid In

phase process string• EZ-Tray design allowed

space saving stripper placement

• Strippers used in series for higher removal Liquid Out

Air In

q

Max. plant flow = 4MGD (3000gpm; 15MLD)

Normal operating range = 1.3-1.7MGD (1000-1400gpm)

Page 53: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Case Study 3 – Cheyenne, WY• Abandoned Atlas Missile

sites contaminated city wells with chlorinatedwells with chlorinated solvent

• US Army Corps is QED’s customer

• Strippers will treat city water during high demand, summer months (4000gpm capacity)capacity)

• Excellent equipment reliability required to ensure continuous water treatment

• System started June 2011

Page 54: Drinking Water Treatment Using Air Strippers · Drinking Water Sources • 52,000 of the 156,000 public drinking water systems in thedrinking water systems in the United States are

Summary

• Air strippers are effective at removing dissolved

y

volatile organic compounds from water • The primary process factor is air to water ratio• The process can be modeled using on-line

computer tools -phttp://www.qedenv.com/modeler

• Air stripping equipment needs to be maintained pp g q pto ensure continued design removals