drawing must be viewed in adobe reader to ......vapor retarder/air barrier coverboard deck fasten at...
TRANSCRIPT
PROJECT:
TITLE:
DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY
NO.: DATE:REVISION:
DATE: 7.9.2015
SCALE: NTS
DRAWING NUMBER:
US.RSBS.05.01
2 PLY SBS MEMBRANE, INSULATEDCURB WITH NON-REMOVABLE
COUNTERFLASHINGUSAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS.
PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING.
US CORPORATE ADDRESS310 QUADRAL DRIVE
WADSWORTH, OHIO 44281www.soprema.usTel:330.334.0066
W I L L I A M G R A N T G A L L O W A Y
DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING
NOTES:1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL
INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THEDETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES.
2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO THE NRCA CERTA RECOMMENDATIONS, LOCALCODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS.
3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS4. FLASHING PLIES MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE. FLASHING PLIES EXTENDING VERTICALLY MORE THAN 24" FROM ROOF SURFACE MUST BE ADHERED AND
MECHANICALLY FASTENED ALONG THE TOP LEADING EDGE. REFER TO PUBLISHED DOCUMENTATION.5. FOR 90° TRANSITIONS, FLASHING PLIES MUST MEET THE FOLLOWING REQUIREMENTS: HEAT WELD POLYESTER REINFORCED FLASHING BASE PLIES. HEAT WELD POLYESTER REINFORCED
GRANULE FLASHING CAP SHEET, OR HEAT WELD FOIL/FILM CLAD FLASHING CAP SHEET.
CURB NON-REMOVABLE CURB COUNTERFLASHING
FASTEN AT 8" O.C. ALONG TOP LEADING EDGE
SHEET METAL COUNTERFLASHING
FLASHING CAP SHEET
CAP SHEET
POLYESTER REINFORCED FLASHING BASE PLY
BASE PLY
FLASHING CAP SHEET
CAP SHEET
POLYESTER REINFORCED FLASHING BASE PLY
BASE PLY
BASE SHEET/ANCHOR SHEET
VAPOR RETARDER/AIR BARRIER
COVERBOARD
DECKDECKDECKDECKDECKDECKDECKDECK
FASTEN AT 8" O.C.IN BOTH DIRECTIONS
FASTEN AT 8" O.C.IN BOTH DIRECTIONS
EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY
EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CANT
EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATE
INSTALL FASTENER PLATE A MINIMUMOF 1" FROM CANT AND SPACED A
MAXIMUM OF 12" APART ALONG WALL
EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY
CANT
EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CURB
EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY
INSTALL FASTENER PLATE A MINIMUMOF 1" BEYOND BASE OF CURB AND
SPACED A MAXIMUM OF 12" ALONG WALL
EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CURB
EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY
FASTEN AT 8" O.C. ALONG TOP LEADING EDGE
REMOVE/EMBEDSURFACING AS REQUIREDREMOVE/EMBED
SURFACING AS REQUIRED
BASE SHEET/ANCHOR SHEET
INSULATION
INSULATION
INSULATION
THERMAL BARRIER
INSULATION
THERMAL BARRIERTHERMAL BARRIER
VAPOR RETARDER/AIR BARRIER/BACKER PLYBASE SHEET/ANCHOR SHEET/BACKER PLYBASE SHEET/ANCHOR SHEET/BACKER PLY
EXTEND A MINIMUM OF 3" BEYOND BASE OF WALL