dr. slavomir seman, abb drives, wind ac, finland slavomir ... · need for confidentiality. a...
TRANSCRIPT
© ABB Group June 13, 2011 | Slide 1
Need for confidentiality. A converter manufacturer's view
Dr. Slavomir Seman, ABB Drives, Wind AC, Finland
Wind Integration Symposium, 16-17 June 2011, Frankfurt / Main
© ABB Group June 13, 2011 | Slide 2
ABB’s discrete automation and motionDrives business unit
� Dedicated to the manufacturing and marketing of low voltage AC and DC drives, wind turbine converters and solar inverters.
� Wind turbine converters from 0.6 to 6 MW, for both doubly-fed and full converter turbine concepts (16% market share).
� Wind Turbine Converters are manufactured in Finland (Helsinki), Estonia (Jüri), China (Beijing), USA (New Berlin, WI), India (Bangalore) .
© ABB Group June 13, 2011 | Slide 2
© ABB Group June 13, 2011 | Slide 3© ABB Inc. June 13, 2011 | Slide 3
� 1. Wind turbine models – definitions and purpose of study
� 2. Detailed Models – EMT – example Type 3 (DFIG)
� 3. Generic Models – RMS – example Type 4 (Full converter)
� 4. How to validate? – Model acceptance (Examples)
� 5. Summary and Conclusions
Resolving the conflict between realistic validated models & manufacturer's confidentiality
© ABB Group June 13, 2011 | Slide 4
Simulation models of WT and WPP� Definition EMT model RMS models
RMS models – primarily for power system stability studies
� Standardized
� Ts typicaly ¼ cycle or shorter
� Generic
� Open source and well documented
� Not vendor specific
� Tool independent (not related to particular simulation SW)
EMT models – detail studies
� Detailed
� Ts typicaly at microsecond level
� Vendor specific
� Tool dependent
� Documented in general
� Could include ”black box” part
© ABB Group June 13, 2011 | Slide 5
WT Standardized models – example IEC ongoing standardization
SOURCE IEC T88 -27 WG disseminated presentation
Reference to wind turbine terminals (part 1 - POC)
� Fundamental frequency positive sequence response as a minimum
� Is not� intended for long-term stability analysis
� intended for studies of wind speed variability
� covering power quality aspects
� for short-circuit calculations
� applicable to studies of islanded or extremely weak systems
� including wind power plant level controls and additional
� equipment (models will be defined in part 2 - PCC).
© ABB Group June 13, 2011 | Slide 6
WT Standardized models – IEC standardization Models should be developed with the following specifications in mind -
continued
� Span at least the existing four categories of wind turbine technologies
� To be used primarily for power system stability studies
� - faults (balanced and unbalanced ) in the transmission grid
� - grid frequency disturbances (~ ±6% from 50/60 Hz) (discussed)
� - set-point changes
� Numerical capability to handle phase jumps
� Initialise to a steady state from power flow solutions in the full power
� range [and for voltage deviations ~ ±10%]
� Valid for dynamic voltages ~ 0…130%.
� Typical simulation time frame of interest (10…30 seconds)
� Typical integration time step not smaller than ¼ cycle
© ABB Group June 13, 2011 | Slide 7
WT Standardized models – IEC standardization
Models should be developed with the following specifications in mind -continued
� Constant wind speed
� External conditions such as wind speed must be taken into account in those instances where it may significantly influence power swings
� Over-/underfrequency, overcurrent and over-/undervoltage protection included
� Turbine-generator inertia and first shaft torsional mode
� Numerically sound in both high and low (~2.5) short-circuit systems
� Independent of any provider of simulation tools
� Modular in nature
� Generic models for protection and control systems should be easily parameterized to represent any manufacturer-specific systems
� Possibility of replacing the generic control and protection system blocks with manufacturer-specific blocks
� Reactive power capability of the wind turbine
© ABB Group June 13, 2011 | Slide 8
Doubly fed asynchronous generator – EMT model
10...24 kV, f = 50 Hzor 60 Hz
line coupling transformer
generatorsideconverter
grid sideconverter
gearbox
brake
pitch drive
rotor bearing
main circuit breaker for protection
converter control
wind turbine control
medium voltageswitchgear
frequency converter
main contactor for normal on-off operation
Activecrowbarprotection
asynchronous generator with slip rings1500 rpm ±30%
© ABB Group June 13, 2011 | Slide 9
Black box model - DFAG
X2
X1
Sk, Xnet
132 kV/20kV 20kV/690V
DFIG WTGrid
Wind park network
ZWP
ITrpra
ITrprb
ITrprc
Upra
Uprb
Uprc
Grid + WF network
Upra
Uprb
Uprc
ITpra
ITprb
ITprc
DFIG Wind Turbine (drive train not included)
© ABB Group June 13, 2011 | Slide 10
Generic model of WT 3 type model – DFAG•Generator and converter represented as controlled current source. Fits well for Full converter concept
•Can be also applied for steady state and quasi-steady state of Type 3 DFAG
•However, it is not suitable for transient analyses of DFAG under severe balanced and especially unbalanced fault!
•DFAG is directly coupled with power grid and therefore dynamic behavior of electromechanical system is to be represented by more detailed model or optionally reduced (generic) model shall be extended by additional protection logic that would represent operation of crowbar and transient behavior during unbalance
Generator/Converter model
Generator usually reduced to first order model
© ABB Group June 13, 2011 | Slide 11© ABB Inc. June 13, 2011 | Slide 11
Model validation by site test – example DFAG
Type test of a single wind turbine – typically performed by so-called “container test”.
Wind power plant compliance assessment – performed by simulation.
Tester
Photo: E2Q
© ABB Group June 13, 2011 | Slide 12
DFAG – Detailed model 3-phase fault 0% Un, 180 ms
4900 5000 5100 5200 5300 5400 5500 56000
50
100
150
200
250
300
350
400
450
500
Time [ms]
Urm
s[V
]MEASURED INSTANTANEOUS VALUES AT LV SIDE OF TR
uurmsgrid
[V]
uvrmsgrid [V]
uwrmsgrid [V]
© ABB Group June 13, 2011 | Slide 13
DFAG – Detailed model 3-phase fault 0% Un, 180 ms
4900 5000 5100 5200 5300 5400 5500 5600-6000
-4000
-2000
0
2000
4000
6000
8000
t [ms]
i s [A
]
comparison of measured and simulated LV TR currents
simulatedmeasured
© ABB Group June 13, 2011 | Slide 14
� Full power test at 2 MW DFAG Turbine equipped by ABB converter – measurement performed at 20kV terminals by certificated test laboratory during grid code validation in Nov. 2006 vs. simulated results by DFAG RMS model.
Validation – DFAG generic model simulation vs. measurement
RMS Models � Full power test at 2 MW DFIG at 20kV terminals
� 20% Un 3 phase Voltage Dip, Full power dip lasts for 500 ms
� Voltage support starts within 1,5 - 2 cycles (30-40 ms)
© ABB Group June 13, 2011 | Slide 15
� Full power test at 2 MW DFAG Turbine equipped by ABB converter – measurement performed at 20kV terminals by certificated test laboratory during grid code validation in Nov. 2006 vs. simulated results by DFAG RMS model.
RMS models � Full power test at 2 MW DFIG at 20kV terminals
� 20%Un 3 phase Voltage Dip, Full power, dip lasts for 500 ms
� Q supply starts within 2 cycles (40 ms) and required value is supplied within 150 ms
Validation – DFAG generic model vs. measurement
© ABB Group June 13, 2011 | Slide 16
� 2 MW DFAG WT drive fed from ABB laboratory network under symmetrical voltage dip with 35% Un remaining voltage performed in 03/2008
Present status of advanced ABB DFAG technology performance
38 ms !
� 100% of reactive current is provided within 40 ms –comparable with Full –Scale concept
� Crowbar operates 0.5 -1 cycle (10-20 ms)!!!
© ABB Group June 13, 2011 | Slide 17
Conclusions - DFAG WT model validation
� DFAG detailed EMT model can represent dynamic behavior of WT accuratelly. However, EMT model is not suitable for most of the power system stability studies and runs with very short time steps (microseconds).
� Usually EMT model is not open - source – proprietary
� Simplification (obtaining realistic RMS model) is challenging mainly due to:
�Diversity of technologies used for FRT (representation of crowbar, chopper etc.)
�DFAG is directly connected to the grid therefore oversimplification of generator and converter model may lead to unrealistic simulation model performance especially during severe grid fault simulations.
�RMS (usually positive sequence) model has limited ability to represent behavior of concept under severe unbalanced fault– possibly tripping WT or entire WF.
� DFAG Generic RMS model that represents typical performance of the wide range technologies available in the market and connected to power system is still under under development and discussion.
© ABB Group June 13, 2011 | Slide 18
Full power converter concept with IG
© ABB Group June 13, 2011 | Slide 19�© ABB Inc.
�June 13, 2011 | Slide 19
Full converter detailed and generic simulation model
test.v_wind
v_wind
v_wind
Pref_max
dip_flag
ext_dip_flag
Tel
Uabc_lg_grid
flux_ref
Pref_dyn
Cselect
Uac-Q_ref
n_gen
Wind Turbine rev1_1(Aero+mech+wtc)
Scope20
RT
RT
test.Pref_max
Pref_max
Tel
Pref_dyn
n_gen
Tel_out
Initialization/Tel
flux_ref
Pref_dyn
Cselect
Uac-Q_ref
n_gen
Uabc_lg_grid
dip_flag
ext_dip_flag
Tel
Grid+Trafo+Conv+Gen
Generator/Converter model
Electrical Control Model
Q
P
Generic model “open source” (RMS) of WT 4 type model – Full power converterDetailed model “black box” (EMT) of WT
4 type model – Full power converter
© ABB Group June 13, 2011 | Slide 20�© ABB Inc.
�June 13, 2011 | Slide 20
Simulation Models – Validation of full converter WT drive by factory test
© ABB Group June 13, 2011 | Slide 21
Generic WT 4 type model against full power test – Results2,5 MW, Full converter WTD under 3-ph dip, Generic model Ts = 5 ms
0 0.2 0.4 0 .6 0 .8 1 1 .2 1 .4 1 .6 1 .8 20
0 .1
0 .2
0 .3
0 .4
0 .5
0 .6
0 .7
0 .8
0 .9
1
Tim e
Vol
tage
G rid V o ltage
G eneric M ode lM eas ured va lues
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 20
0.2
0.4
0.6
0.8
1
1.2
1.4
Tim e
Cur
rent
Converter Total Current
G eneric M odelM eas ured values
0 0.2 0.4 0 .6 0 .8 1 1 .2 1.4 1 .6 1 .8 20
0.2
0.4
0 .6
0 .8
1
1.2
1.4
Tim e
Cur
rent
C onverte r A c t ive C u rren t
G eneric M ode lM eas ured va lues
0 0 .2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2-0.2
0
0.2
0.4
0.6
0.8
1
1.2
Tim e
Cur
rent
Converter Reac t ive Current
G eneric M odelM eas ured va lues
© ABB Group June 13, 2011 | Slide 22© ABB Group June 13, 2011 | Slide 22
Validation of WT 4 type model – German valid. Procedure TR4
2.5 MW, Full-converter WTD under 3-ph dip, Generic model Ts = 5 ms
0.5 1 1.5 2-0.5
0
0.5
1
1.5
2
VALIDATION ACCORDING TO GERMAN VALIDATION STANDARD FGW TR4 Terminal voltage
A B1 B2 C1 C2
measurementsimulation
© ABB Group June 13, 2011 | Slide 23© ABB Group June 13, 2011 | Slide 23
Reactive current – validation (TR4)
2.5 MW Full-converter WTD under 3-ph dip, Generic model Ts = 5 ms
0.5 1 1.5 2-0.5
0
0.5
1
1.5
2
VALIDATION ACCORDING TO GERMAN VALIDATION STANDARD FGW TR4 Reactive Current
A B1 B2 C1 C2
Time[p.u.]
Vol
tage
[p.u
.]
measurementsimulation
0.5 1 1.5 2
0
1
2
VALIDATION ACCORDING TO GERMAN VALIDATION STANDARD FGW TR4 Reactive Current
Mea
sure
d R
eact
ive
Cur
rent
A B1 B2 C1 C2
positive sequenceaverage
0.5 1 1.5 2
0
1
2
Sim
ulat
ed R
eact
ive
Cur
rent
Time [s]
A B1 B2 C1 C2
positive sequenceaverage
0.5 1 1.5 2-0.5
0
0.5
VALIDATION ACCORDING TO GERMAN VALIDATION STANDARD FGW TR4 Reactive Current
Diff
eren
ce o
f ave
rage
s (p
u)
A B1 B2 C1 C2
0.5 1 1.5 2
-1
0
1
Diff
eren
ce o
f pos
itive
seq
uenc
es (p
u)
A B1 B2 C1 C2
Time [s]
Averages difference
Area Actual Limit
© ABB Group June 13, 2011 | Slide 24
Validation WT4 generic model - FRT test according TR4 RMS values comparison
Transient mode too short – definitions
Good Fit
© ABB Group June 13, 2011 | Slide 25
Validation WT4 generic model - FRT test according to TR4 error evaluation
Almost not passed !
© ABB Group June 13, 2011 | Slide 26
Validation WT4 generic model - FRT test according Spanish PVVC - Comparison and error evaluation
© ABB Group June 13, 2011 | Slide 27
Generic model implementation Simulink vs. DigSilent PF
� Model is tool independent !
2 2.5 3 3.5 40
0.5
1
1.5
Time
Vol
tage
Terminal Voltage
Terminal Voltage, SimulinkTerminal Voltage, DigSilent
2 2.5 3 3.5 40
0.5
1
1.5
Time
Vol
tage
Reactive Power
Reactive Power, SimulinkReactive Power, DigSilent
2 2.5 3 3.5 40
0.5
1
1.5
Time
Cur
rent
Active Current
Active Current, SimulinkActive Current, DigSilent
2 2.5 3 3.5 40
0.5
1
1.5
Time
Cur
rent
Reactive Current
Reactive Current, SimulinkReactive Current, DigSilent
© ABB Group June 13, 2011 | Slide 28
Conclusions - generic full-Power WT model validation
� ABB generic model based on modified WECC Type 4 model was validated - Generic model presented assumes: DC bus voltage controlled to be mantained within the limits during transients (e.g. Break chopper).
� Usually WT4 model is reduced into model of WT Network converter and simplified generator. However, different full power WT concept may bring necessity to model whole drive train.
� Model is tool independent and not vendor specific.
� Generator and converter represented as controlled current source -valid for full converter concept.
� Successfully validated against measurements following German and Spanish guideline.
© ABB Group June 13, 2011 | Slide 29
Summary and conclusions� We need proper classification of WT models
� EMT – Models are vendor specific and usually tool dependent – detailed Black Box
� RMS – Generic, structure shall not be vendor specific and simulation tool independent Model definitions still ongoing – for power system stability studies, have limitations (e.g. short-circuit calculation – WT3, power quality)
� RMS - WT Standardized Models – IEC standardization ongoing (T88 -27 WG)
- based on work performed by the
- WECC Wind Generator Modeling Group
- IEEE Dynamic Performance of Wind Power Generation Working Group
� Issues under Discussion:
� Type 4 model might be tunable for types 3-4??
� - “common” LVFRT profile is emerging - (grid code definitions influence).
� - except for sustained crowbar action (type 3)?
� Validation - How to validate? Engeneer’s judgement or detailed validation (e.g. TR4) ?
� Proper validation = validation of model against measurement from full scale set-up (site or factory test).
© ABB Group June 13, 2011 | Slide 30