Code No. LPI-24-8-5 Sarah Electric article no. 2008010307-1 Rated voltage 24kv Bending load (kN) 8KN Creepage distance 660mm Power frequency voltage (dry) 110kv Power frequency voltage (wet) 90kv Lightning impulse withstand voltage 150kv Arcing distance 238mm Number of sheds 5 Type of Insulator Substation insulator Rod size 38mm Weight ≈3KG IEC61109/62217
YUEQING SARAH ELECERIC TECHNOLOGY CO.,LTD.
Substation Insulator 24KV
Code No. FZSW-52/12.5
Sarah Electric article no. 2015170-2
Rated voltage 52kv
Bending load (kN) 12.5KN
Creepage distance 1100mm
Power frequency voltage (wet) 185kv
Lightning impulse withstand voltage 250kv
Dimensions Section Length 540±10mm
Min Arc distance >470mm
Number of sheds 11PCS
Type of Insulator LINE POST
Rod size 53mm
Weight ≈10.6KG
IEC61109
LINE POST INSULATOR 52KV
YUEQING SARAH ELECTRIC
TECHNOLOGY CO.,LTD.
REV-0-2013-08-21-1
Code No. FZSW-72.5/15
Sarah Electric article no. 2015119-4
Rated voltage 72.5kv
Bending load (kN) 15KN
Creepage distance 2080mm
Power frequency voltage (dry) 200kv
Power frequency voltage (wet) 200kv
Lightning impulse withstand voltage 380kv
Dimensions Section Length 900±15mm
Min Arc distance 795±15mm
Number of sheds 15PCS
Type of Insulator POST
Rod size 70mm
Weight ≈10KG
IEC62231
POST INSULATOR 72.5KV
YUEQING SARAH ELECTRIC
TECHNOLOGY CO.,LTD.
REV-3-2015-11-26-3
REV-6-2013-04-16-01
SUBSTATION INSULATOR 170KV
Code No. FZSW-170/12.5 Sarah Electric article no. 200938-5 Rated voltage 170kv Bending load (kN) 12.5KN Creepage distance 4660mm Power frequency voltage (dry) 275kv Power frequency voltage (wet) 275kv Lightning impulse withstand voltage 675kv Dimensions Section Length 1450±15mm Min Arc distance 1310±15mm Number of sheds 30PCS Type of Insulator Substation Rod size 70mm Weight ≈26KG IEC62231/62217
YUEQING SARAH ELECTRIC TECHNOLOGY CO.,LTD.