Understanding fire-resistantglazing systems
Presented by Russell DayTechnical officerThe Glass and Glazing Federation
![Page 2: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/2.jpg)
What is important when specifying and installingFire-resistant Glazing Systems?
• The framing system
• Timber
• Steel
• Aluminium
• The glass
• The glazing components/compounds
• Fire test or assessment evidence
• Quality of installation
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 3: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/3.jpg)
Potential issues with Framing Systems
• In particular, with timber framingsystems, the framing may bemanufactured and installed by differentcontractors to the glazing contractor. Theglazier must confirm:
• The framing has been manufactured inaccordance with the fire test or assessmentspecification
• It is installed into the building fabric correctly
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 4: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/4.jpg)
The Framing System
• Timber framing – critical factors
• Species and density of timber used
• Section sizes and profile
• Rebate upstand size
• Glazing bead profile, in particular:
• Square edge top face or
• Chamfered or beveled top face
• Bead fixing details
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 5: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/5.jpg)
The Framing System
• Steel and aluminium frame systems
• Generally supplied and fitted by a singlecompany or contractor
• Critical to ensure it is installed into thebuilding fabric correctly
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 6: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/6.jpg)
The Fire-Resistant Glass
• Performance of Fire-Resistant Glass
• When tested for Fire-Resistance, glass will becatagorised for use in the UK as:
• Exx (e.g. E30) – Integrity only glass, thenumber indicating the period it willprovide protection
• EIxx (e.g. EI60) – Integrity and insulationglass, the number indicting the period itwill provide protection
• EWxx (e.g. EW60) – Not recognized in UK
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 7: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/7.jpg)
The Fire-resistant Glass
• Marking of Fire-resistant Glass
• Glass to be used in fire-resistant systemsshould be permanently marked with thefollowing in a visible location:
• Manufacturers name, trading name or producttradename
• Product standard e.g. BS EN 12150, BS EN 14449etc.
• Safety classification if appropriate
• Fire-resistance e.g. E30, EI60 etc.
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 8: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/8.jpg)
Pilkington Pyrodur Plus (7mm)
EN 12150 = ToughenedEN 14449 = Laminated
2014
Understanding Fire-ResistantGlazing Systems
![Page 9: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/9.jpg)
Pyroguard
Understanding Fire-ResistantGlazing Systems
![Page 10: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/10.jpg)
VetroflamVetroflam Laminated
Pyroswiss
Pyroswiss Laminated
Contraflam DoorLite
Contraflam
ContraflamStructure
(Butt Jointed)
Swissflam DGU Stamp
Understanding Fire-ResistantGlazing Systems
![Page 11: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/11.jpg)
Understanding Fire-ResistantGlazing Systems
![Page 12: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/12.jpg)
Understanding Fire-ResistantGlazing Systems
![Page 13: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/13.jpg)
Glazing components and compounds
• The glazing components and compoundsmust be as stated in the test orassessment evidence:
• Substitution without supporting evidence isnot allowed
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 14: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/14.jpg)
Quality of Installation
• Provided the framing material, glass andglazing components/compounds are asspecified in the test or assessmentevidence, the performance of the Fire-resistant Glazed System is reliant on:
• The correct installation of the frame into thebuilding fabric and
• The fire-resistant glass being installed in theframe correctly using the materials specified
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 15: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/15.jpg)
Quality of Installation
• The installation is as critical as thecomponent parts of a barrier to fire
• The GGF has developed installer trainingbased on 2 GGF documents:
A Best Practice Guide in theSpecification and Use of Fire-Resistant
Glazed Systems
• Referenced in Approved Document B
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 16: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/16.jpg)
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 17: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/17.jpg)
Quality of Installation
• The installation is as critical as the componentparts of a barrier to fire
• The GGF has developed installer training basedon 2 GGF documents:
A Best Practice Guide in the Specification and Use of Fire-Resistant Glazed Systems
and
The Specification, Supply and Installationof Fire-Resistant Barriers containing Glassfor Resistance against the passage of Fire
and Products of Combustionwww.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 18: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/18.jpg)
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 19: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/19.jpg)
Quality of Installation
• The GGF installer training workshop:
• Knowledge based workshop
• Knowledge assessment at end of course
• Initial courses in Northern Ireland
• Will be rolled out in England, Scotland andWales during 2014
• Delegates received a certificate to showattainment
• Intend to move to a registered list and issue anapproved installer card
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 20: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/20.jpg)
What is the result if the wrong system, glassor components are used?
What happens if the quality of installation isnot ‘up-to-standard’?
Getting it Wrong - Getting it Right
www.ggf.org.uk
Understanding Fire-ResistantGlazing Systems
![Page 21: Understanding fire-resistant glazing systems - ASFP seminar 2014/2. RD Glazing.pdf · • Product standard e.g. BS EN 12150, BS EN 14449 ... EN 14449 = Laminated 2014 Understanding](https://reader030.vdocuments.site/reader030/viewer/2022020413/5b3a8feb7f8b9a0e628bc55a/html5/thumbnails/21.jpg)