SwitchgearType SIMOSEC up to 24 kV,Air-Insulated, Extendable
Medium-VoltageSwitchgear
Catalog HA 41.212003
Supersedes:
Catalog HA 41.21 . 2002
-
7/26/2019 Simosec En
2/44
2 SiemensHA41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Contents Application
Page
Application, Requirements
Typical uses, features 2 and 3
Technical Data
Electrical data, pressure values,temperature 4 and 5
Switchgear installation 6
Shipping data 7
Product Range
Product range overview, equipmentfeatures 8 and 9
Panels 10 to 15
Design
Panel design 16 and 17
Components
3AH vacuum circuit-breakers 18 to 20
Three-position switches 21
Busbars, HV HRC fuse assembly 22 and 23
Operating mechanisms 24
Indicating and measuring equipment 25
Interlocking systems and locking devices 26
Transformers 27 to 29
Cable connection 30 and 31
Low-voltage equipment 32
Dimensions
Panels 33 to 39
Floor openings, fixing points 40
Standards
Standards, specifications, guidelines 41 to 43
Notes
43
Siemens AG 2003
Example4-panel transfer switchgear withintegrated low-voltage niche
R-HA41-082eps
R-HA41-055eps
Utilities transfer substationfor industrial plants
Typical uses
-
7/26/2019 Simosec En
3/44
SiemensHA 41.21 2003 3
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Application, Requirements
Reliability
Type and routine-testedStandardized and manu-
factured using numericallycontrolled machines
Quality management systemaccording to DIN EN ISO 9001
More than 350,000 switchgearcomponents in operationworldwide for many years
No cross-insulation betweenphases
Personal safety
All switching operations can
be performed with closedpanel front
Metal-enclosed, cubicle-typeor metal-clad switchgear
HV HRC fuses and cable seal-ing ends are only accessiblewhen the outgoing feeders areearthed
Logical mechanical interlocking
Capacitive voltage detectionsystem for verification of safeisolation from supply
Earthing of outgoing feedersby means of make-proof
earthing switches
Security of operation
Components, e.g. operatingmechanisms, three-positionswitches, vacuum circuit-breakers proven for years
Metal-clad panels (metal com-partmentalization betweenbusbar and switching deviceand between switching deviceand cable connection compart-ment)
Cubicle-type panels with
metal compartmentalizationbetween switching device andbusbar compartment
Three-position switch metal-enclosed with gas-insulatedswitching functions
Welded sealed-for-lifeswitchgear vessel
No cross-insulation betweenphases
With welded-in bushings forcable connection, busbar andoperating mechanism
Switch operating mechanismsoutside switchgear vessel
Maintenance-free operatingmechanism parts (IEC 60 694/VDE 0670 Part 1000 *)
SIMOSEC switchgear is afactory-assembled, type-
tested, three-phase, metal-enclosed, metal-clad indoorswitchgear according toIEC 60 298 / VDE 0670,Part 6 for single busbars.
Typical uses
SIMOSEC switchgear isused for power distribution indistribution systems withfeeder currents up to 1250 A.
Modular space-saving designallows use in
Substations, customer trans-
fer substations, distributionsubstations and switchingsubstations of power supplyand public utilities
Public buildings, such ashigh-rise buildings, railwaystations, hospitals
Industrial plants
Typical examples
Wind power stations
High-rise buildings
Airports
Underground railway stations
Sewage treatment plants
Port facilities
Traction power supplysystems
Automobile industry
Petroleum industry
Chemical industry
Unit-type heating powerstations
Textile, paper andfood industry
Emergency power supplyinstallations
Modular design
Individual panels, for freecombination and extension
Option: low-voltage compart-ments can be supplied intwo overall heights
Technical features
Air-insulated indoorswitchgear
Gas-insulated, maintenance-free switching functions forthe three-position switch
Three-pole primary enclosure
Phases arranged one behindthe other
No cross-insulation betweenphases
Busbar system at top
Air-insulated busbar and cableconnection system
Three-position switch, metal-enclosed, with air-insulatedprimary terminals and gas-insulated switching functions
Vacuum circuit-breaker 3AH5,metal-enclosed, up to 630 A,fixed-mounted in gas-insulatedswitchgear vessel
Vacuum circuit-breaker 3AH6,air-insulated, up to 1250 A,easy to withdraw after loose-ning the fixing bolts
Hermetically-sealed bywelding, stainless-steelswitchgear vessel,
For switching devices With welded-in bushings
(for electrical connections andmechanical components)
With insulating gas SF6
Cubicle-type or metal-cladpanel design
Pressure relief To the rear and upwards Separately for each
compartment
Air-insulated cable connectionsystem for conventional cablesealing ends
Three-phase current trans-former, factory-assembled onthe feeder bushings
Integrated low-voltage niche(standard) for installationof, e.g.
Terminals, MCBs, push-buttons
Protection devices
Option: Top-mounted low-voltage compartment
Option: Panel heating forsevere ambient conditions,e.g. condensation
Mechanical switch positionindications integrated in
mimic diagram
Switchgear interlockingsystem with logicalmechanical interlocks
Reavailability
Three-position switch discon-nector with gas-insulated,maintenance-free quenchingprinciple
Metal compartmentalizationbetween busbar compart-ment, switching devices andcable connection compart-
mentSeparate pressure relief for
each compartment
Cable testing without theneed to isolate the busbar
Mounting location of three-phase current transformer forselective disconnection ofcircuit-breaker feeders
Cost-efficiency
Extremely low life-cycle costsand extremely high availabilitythroughout the entire product
service life cycle as a result of:Three-position switch with
gas-insulated quenchingprinciple
3AH vacuum circuit-breaker
Minimum space requirement
Easy switchgear extension
Standard protection relays,e.g. multifunction protectionSIPROTEC 4
Electrical features
Rated voltages up to 24 kV
Rated short-time withstandcurrent up to 25 kA
Rated normal current offeeders
Up to 630 A, e.g. forring-main, metering andcircuit-breaker panels
Up to 1250 A, forcircuit-breaker and bussectionalizer panels
Rated normal current ofbusbar up to 1250 A
* Standards see page 41
Features
-
7/26/2019 Simosec En
4/44
4 SiemensHA41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Electrical data of panels, pressure values, temperature
1) The rated normal currents apply to ambient tempera-tures of 40 C. The 24-hour-mean value is max. 35 C(according to IEC 60 694 / VDE 0670 Part 1000)
2) Pressure values for SF6-insulated vessels
* Type designationof the vacuumcircuit-breaker
Common details on electrical data, filling pressure and temperature
Rated insulation level Rated voltageUr kV 7.2 12 15 17.5 24
Rated short-dur. power-freq. withstand voltageUd kV 20 28 35 38 50
Rated lightning impulse withstand voltageUp kV 60 75 95 95 125
Rated frequencyfr 50/60 Hz
Rated normal currentIr1)of busbar
Standard 630 A
Option 1250 A
Rated short-timewithstand currentIk
for switchgear withtk= 1 s up to kA 20 25 20 25 16 20 25 16 20 25 16 20
for switchgear withtk= 3 s up to kA 20 20 20 20 20
Rated peak withstand currentIp up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated filling pressurepre2) for insulation 1500 hPa (absolute) at 20 C
Minimum operating pressurepme2) for insulation 1300 hPa (absolute) at 20 C
Ambient temperatureT for panels without secondary equipment 25 C to +55 C
for panels with secondary equipment 5 C to +55 C
Ring-main panel type RK and cable connection panel type K
Rated normal currentIr1
) for feeder and transfer, panel type RK 400, 630 Afor feeder, panel type K 400, 630 A
for feeder, panel type K1 400, 630, 1250 A
Rated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Transformer panel type TR
Rated normal currentIr1) for feeder3) 200 A
Rated peak withstand currentIp 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit making currentIma 3) up to kA 25 25 25 25 25 25 25 25 25 25 25 25
Reference dimension e for HV HRC fuse links mm 2924) 292 442 442 442
Circuit-breaker panel type LS
Rated normal currentIr1) f. panel type LS1 and LS1-U 3AH5 * 630 Af. panel type LS11 andLS11-U 3AH6 * 630 Af. panel type LS31,LS32 and LS31-U 3AH6* 1250 A
Rated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit breaking currentIsc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20
Busbar earthing panel type SE
Rated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Busbar voltage metering panels type ME3 and type ME31-F
Rated peak withstand currentIp 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit making currentIma 3) up to kA 25 25 25 25 25 25 25 25 25 25 25 25
Reference dim. e in panel type ME31-F for HV HRC fuse links 292 mm
Billing metering panels type ME1
Rated normal currentIr1) for transfer, panel types ME1 and ME1-H 630 A, 1250 A
for feeder as cable-connection panel type ME1-K 630 A, 1250 Afor busbar connection, panel type ME1-S 630 A, 1250 A
for bus riser panel type HF 630 A, 1250 A
Bus sectionalizer panels type LT
Rated normal currentIr1) for panel types LT10 and HF, with 3AH5 * 630 Afor panel type LT1, with 3AH5 *: On request 630 Afor panel types LT11 and HF, with 3AH6 * 630 Afor panel types LT2 and LT22 630 A
for panel types LT31 and HF, with 3AH6 * 1250 ARated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit breaking currentIsc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20
Electrical service life for 3AH vacuum circuit-breaker:
at rated normal currentIr1) 10,000 operating cycles
at rated short-time breaking currentIsc 50 breaking operations, 35 breaking operations on3AH6 *with 25 kA
for feeder for transfer with
3) For panel types TR and ME31-F depending on the max.cut-off current of the HV HRC fuse link
4) With reference dimension e = 192 mm, an extension tube(100 mm long) is additionally required for fuse mounting 292 mm
Technical Data
-
7/26/2019 Simosec En
5/44
SiemensHA 41.21 2003 5
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
1) Depending on the HV HRCfuse links
2) Depending on the cut-offcurrent of the HV HRC fuse
* Higher values of electrical data available on request
**Indications in parenthesis acc. to previous standards
Electrical data*of the switching devices
Technical Data
Make-proof earth-ing function ofthe three-positionswitch-disconnector
Make-proofearthing functionin panels LS11,LS31, LS32
Earthing functionof the three-positiondisconnector
Three-position switch-disconnector
Rated voltage Ur kV 7.2 12 15 17.5 24Rated insulationlevel
Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
Rated lightning impulse withstand voltage Uw kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normalcurrent for
ring-main feeders Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
transformer feeders1) Ir A 200 200 200 200 200
Rated short-timewithstand current
for switchgear withtk(ttk)**= 1 s Ik(Ith)** up to kA 25 25 25 25 20
for switchgear withtk(ttk)**= 3 s Ik(Ith)** kA 20 20 20 20 20
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuitmaking current for
transformer feeders2) Ima kA 25 25 25 25 25
ring-main feeders Ima up to kA 63 63 63 63 50
Switching capacity of general-purpose switches (class E3) according to IEC 60 265-1 / VDE 0670 Part 301 (Standards see page 41)
Test duty 1 Rated mainly active for 100 switching operations I1 A 630 630 630 630 630
load breaking current for 20 switching operations I1 A 31.5 31.5 31.5 31.5 31.5
Test duty 2a Rated closed-loop breaking current I2a A 630 630 630 630 630
Test duty 3 Rated transformer breaking current I3 A 40 40 40 40 40
Test duty 4a Rated cable-charging breaking current I4a(IC orI6)** A 68 68 68 68 68
Test duty 4b Rated line-charging breaking current I4b A 68 68 68 68 68
Test duty 5 Rated short-circuit making current Ima up to kA 63 63 63 63 50
Test duty 6a Rated earth-fault breaking current I6a(Ie)** A 60 60 60 60 60
Test duty 6b Rated cable-charging breaking current and line- I6b A
charging breaking current under earth-fault conditions (HJ3 vICL)**35 35 35 35 35
Cable-charging breaking current under IL +HJ3 vICL Aearth-fault conditions with superimposed load current
630+50 630+50 630+50 630+50 630+50
Switching capacity of switch-disconnector/fuse combination(Standards see page 41)
Rated transfer current I4 A 1150 1150 830 830 830
Earthing switch
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
3AH5 and 3AH6 vacuum circuit-breakersRated voltage Ur kV 7.2 12 15 17.5 24
Rated insulationlevel
Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normal current of feeders for 3AH5 Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
for 3AH6 Ir A 630, 1250 630, 1250 630, 1250 630, 1250 630,1250
Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
Rated short-circuit duration tk (tth)** s 3 3 3 3 3
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Electrical service life at rated normal current 10,000 operating cycles
HA41-29aeps
-
7/26/2019 Simosec En
6/44
6 SiemensHA41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Technical Data
Switchgear installation
Room planning
Switchgear installation
Wall-standing arrangement Single row Double row (for face-to-face
arrangement)
Room dimensions
See opposite dimensiondrawings
Door dimensions
The door dimensionsdepend on the Number of panels in a
transport unit Design with or withoutlow-voltage compartment
Switchgear fastening
For floor openings andfixing points of the switch-gear, see page 40
Foundations: Steel structure Steel-reinforced concrete
Panel dimensions
See pages 34 to 39
Weight
The weight of a panel dependson the extent to which it isequipped (e.g. with motoroperating mechanism, voltagetransformer). For details,please refer to page 7.
1 Relief opening
2 Direction of pressure relief
3 Pressure relief of switchgear
4 Room height
5 Individual panel depth
6 Panel depth including end wall
7 Control aisle
8 Option: Floor cover
9 Cable
10 Foundation
11 Height of cable basement corresponding to
cable bending radius
12 Wall distance
13 Side wall distance
14 Installation flush with rear wall
15 Panel width
16 End wall
17 Depth of pressure relief duct
18 Option: For free-standing arrangementpressure relief duct for each panelfor rated short-time withstand currentIk w 20 kA
19 Option: Front cover
20 Option: Low-voltage compartment
21 Option: High end wall
Room planning
Plan view Plan view
Wall-standing arrangement(side view) Free-standing arrangement(side view)
Cable basement Cable basement
Switchgear room Switchgear room
* Switchgear height 2100 mm if height oflow-voltage compartment 350 mm;switchgear height 2300 mm if height oflow-voltage compartment 550 mm
** Depending on bending radius of cable
-
7/26/2019 Simosec En
7/44
SiemensHA 41.21 2003 7
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Transport unitsfor shipping(plan view)
1) Thenet weightdepends on theextent to which it is equipped(e.g. current transformers, motoroperating mechanisms) and istherefore given as mean value
* Low-voltage compartment,350 mm high, weight approx.60 kg depending on thepanel type and on the extentto which it is equipped
With individual panel
With combinations of differentindividual panels
1 T1 = Depth of individual panel
2 Individual paneldimension B1 x T1
3 Transport unit,dimension B2 x T2
4 B3 = Overall width ofcombination of differentindividual panels
5 B2 = Width of thetransport unit
**Packingweight
Shipping data
2)Sum of thenet weightsofindividual panels
Individual panelor combinations
thereof for standard switchgear(without pressure relief duct)
Paneltype
Panel or panelcombination
Transport unit (including packing)for standard panels (without pressure relief duct)
WidthB1mm
Netweight1)approx. kgwith- / withoutLVC*/LVC*
Width
B2m
Height
m
with- / withoutLVC*/LVC*
DepthT2m
Volume
m3
with- / withoutLVC*/LVC*
Grossweightapprox. kg
with- / withoutLVC*/LVC*
Transport of individual panels
Ring-main panel RKRK1
375500
190 / 250210 / 270
0.70.7
1.9 / 2.3 1.40 1.86 / 2.251.86 / 2.25
250 / 310270 / 330
Ring-mainpanelforpanelcombinations RK-U 375 260 / 320 0.7 1.86 / 2.25 320 / 380
Cable panel K, K-EK1, K1-E
375500
190 / 250190 / 250
0.70.7
1.86 / 2.251.86 / 2.25
250 / 310250 / 310
Transformer panel TRTR1
375500
210 / 270230 / 290
0.70.7
1.86 / 2.251.86 / 2.25
270 / 330290 / 350
Circuit-breaker panel 630 A LS1
LS11
750
750
340 / 400
340 / 400
1.08
1.08
2.87 / 3.48
2.87 / 3.48
410 / 460
410 / 460
Circuit-breaker panel 1250 A
For connection of max. 2 cables For connection of 3 cables
LS31LS32
750875
400 / 460460 / 520
1.081.08
2.87 / 3.482.87 / 3.48
470 / 520530 / 580
Bus sectionalizer panel 1250 A LT31 750 450 / 510 1.08 2.87 / 3.48 520 / 570
Bus sectionalizer panel 630 Awith vacuum circuit-breaker
LT10LT11
750750
320 / 380320 / 380
1.081.08
2.87 / 3.482.87 / 3.48
390 / 440390 / 440
Bus sectionalizer panel with1 three-position switch-disconnector
LT2LT2-W
750750
250 / 310310 / 370
1.081.08
2.87 / 3.482.87 / 3.48
320 / 370380 / 430
Bus sectionalizer panel with2 three-position switch-disconnectors
LT22LT22-W
750750
290 / 350350 / 410
1.081.08
2.87 / 3.482.87 / 3.48
360 / 410420 / 470
Billing metering panel ME1....ME1-H
750750
270 / 330330 / 390
1.081.08
2.87 / 3.482.87 / 3.48
340 / 390400 / 450
Busbarvoltage metering panel
ME3ME31-F
375500
210 / 270270 / 330
0.70.7
1.86 / 2.251.86 / 2.25
270 / 330330 / 390
Bus riser without transformers
panel with transformers
HF 375 170 / 230 0.7 1.86 / 2.25 230 / 290
HF 375 260 / 320 0.7 1.86 / 2.25 320 / 380
Busbarearthing panel
SE1SE2
375500
190 / 250270 / 330
0.70.7
1.86 / 2.251.86 / 2.25
250 / 310330 / 390
For individual panel Panelwidthmm
Additionalweightapprox. kg
Pressure relief ductfor free-standing arrangementof switchgear
375 30
500 40
750 60
875 70
Transport of combinations of different individual panels
Transport unit: Standard: As individual panels arranged
side by side and not screwed together
Option: As multi-panel transport unit,panels screwed together
Overall width B3
w 875 mm
B2
1.08 1.9 / 2.3
T2
1.40 2.87 / 3.48 2)+ 70 **
w 1125 mm 1.20 1.9 / 2.3 1.40 3.19 / 3.86 2
)+ 80 **w 1500 mm 1.70 1.9 / 2.3 1.40 4.52 / 5.47 2)+ 100 **
w 2000 mm 2.33 1.9 / 2.3 1.40 6.20 / 7.50 2)+ 120 **
Packing, transport(examples)
Packing Version For supply Transport
Panels mounted on wooden floorand covered with PE protection sheeting
Open In Europe Rail, truck
In container Overseas Ship + truck
Technical Data
-
7/26/2019 Simosec En
8/44
8 SiemensHA41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Product range overview
1) Metal-clad
2) With additional make-proof earthing switch
3) Type designation of vacuum circuit-breaker
4) With 1 three-position switch-disconnector
5) With 2 three-position switch-disconnectors
6) With voltage transformer for busbar metering
Product Range
Paneltype
Panelwidth
RKRK1
375 mm500 mm
RK-U 375 mm
TRTR1
375 mm500 mm
KK1
375 mm500 mm
K-EK1-E
375 mm500 mm
LS1 750 mm
LS1-U 750 mm
LS11 750 mm
LS11-U 750 mm
LS31LS32
750 mm875 mm
LS31-U 750 mm
LT10 750 mm
LT11 750 mm
LT31 750 mm
LT2LT2-W
750 mm750 mm
LT22LT22-W
750 mm750 mm
ME1ME1-S
750 mm750 mm
ME1-KME1-KS
750 mm750 mm
ME1-H 750 mm
ME3ME31-F
375 mm500 mm
SE1 375 mm
SE2 500 mm
HF 375 mm
Panel designation
Ring-mainpanel1)
asfeeder
astransfer
Transformerpanel1)
asfeeder
Cable panel asfeeder
Cable panel1)2) asfeeder
Circuit-breaker panel 630 A1)with 3AH53)
asfeeder
astransfer
Circuit-breaker panel 630 Awith 3AH63)
asfeeder
astransfer
Circuit-breaker panel 1250 Awith 3AH63)
asfeeder
astransfer
Bussectionalizer panel630 A 1)with 3AH53), for panel type HF
Bus sectionalizer panel 630 Awith 3AH63), for panel type HF
Bus sectionalizer panel 1250 Awith 3AH63), for panel type HF
Bus sectionalizer panel630 A 1) 4)
5)
Billing meteringpanel
Standard
asend panel
Billing metering panelfor additional current transformer
Busbar voltage meteringpanel1)
Busbar earthingpanel1)
6)
Bus riser panel
Standard panels
Ring-main paneltype RK
Circuit-breaker paneltype LS1
Transformer paneltype TR
Circuit-breaker paneltype LS11
Cable paneltype K
Billing metering paneltype ME1
R-HA41-073eps
R-HA41-076eps
R-HA41-074eps
R-HA41-077eps
R-HA41-075e
ps
R-HA41-078e
ps
Column No.
-
7/26/2019 Simosec En
9/44
SiemensHA 41.21 2003 9
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Basic equipment
Additional equipment (option),further additionalequipment on request
Not available
Product Range
Equipment features
1) Three-position switch as three-position switch-disconnector
2) Three-position switch as three-position disconnector in paneltypes LS31, LS31-U, LS32 and LT31
3) Type designation of the vacuum circuit-breaker
4) In special cases, deeper floor cover required
Manua
lope
rating
mec
hanis
mfort
hree-p
ositio
nswi
tch
Interloc
kfor
cable
com
partm
entc
over
Cable
com
partm
entc
over
locke
dinp
lace
C-rai
lasc
able
bracke
t
Low-
volta
genic
heas
term
inalc
ompa
rtmen
t
Relea
seas
shun
trele
ase
Mec
hanic
alrea
dy-fo
r-serv
iceind
icator
forthr
ee-po
sition
switc
h
Signa
llings
witch
(1NO)
forrem
oteele
ctrica
l
ready
-for-s
ervice
indica
tionf
orthr
ee-po
sition
switc
h
Aux.
switc
h(2N
O+
1NC
forC
LOSE
D/EA
RTHE
Dan
d2NO
for
OPE
N)fo
rthr
ee-po
sition
switc
hand
mak
e-proo
feart
hings
witch
Moto
rope
rating
mecha
nism
forthr
ee-po
sition
switc
h1)
2)
Localre
mote
switc
hfor
mot
orop
erat.m
ech.
ofthree
-posit
ionswi
tch1)
2)
Interl
ocki
ncirc
uit-br
eake
rpan
elbetw
een
three
-posit
ionsw
itch
1)2)a
nd3A
H...v
acuu
mcir
cuit-b
reake
r
Locking
devic
efor
switc
hpos
ition
CLOS
EDo
f3AH
6vacuu
m
circu
it-brea
kerw
ithearth
edthr
ee-po
sition
switc
h
De-ea
rthing
lock-o
utfor
mak
e-proo
feart
hings
witch
Inspe
ction
wind
owin
theconn
ectio
n/cab
lecom
partm
entc
over
Low-
volta
gecom
partm
ento
rshu
tter
Closin
gloc
k-out
fort
hree
-posit
ionsw
itch
Moto
rope
rating
mecha
nism
forva
cuum
circu
it-bre
aker
Relea
seas
c.t.-ope
rated
relea
sein
3AH
3)
Locking
devic
efor
three
-posit
ionsw
itch
Short-c
ircuit
orearth
-fault
indica
tor
Sec
ondary
equip
men
t
Floo
rcov
er4)
Pan
elhe
ating
Mou
ntedc
able
clam
ps
6)
6)
RK
RK1
RK-U
TR
TR1
K
K1
K-E
K1-E
LS1
LS1-U
5)
LS11
LS11-U
5)
LS31LS32
LS31-U
LT10
LT11
LT31
LT2
LT2-W
LT22
LT22-W
ME1ME1-S
ME1-KME1-KS
ME1-H
ME3ME31-F
SE1
SE2
HF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Panel type
5) Not to be applied for versions with separate feeder earthing switch inpanel types LS11, LS31 and LS32
6) Inspection window is a standard equipment in panel types LS11, LS31and LS32 for versions with separate earthing switch
7) Option (on request): Closing lock-out possible for panels LT11 or LT31in combination with the adjacent panel type HF
7)
7)
7)
-
7/26/2019 Simosec En
10/44
10 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Ring-main panels
Type RK-U375 mm wide
Ring-main panels
as feeder panels
either:Version withtransformers
HA41-2390beps
Type RK375 mm wide
Type RK1500 mm wide
Type LT10750 mm wide
Type RK1500 mm wide
Ring-main panel
as transfer panel for attachmentto panel types ME1... or ME1-H
* On requestup to 12 kV
or:Version withconnectionfittings
For other panel combinations
Capacitivevoltage detectionsystem
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Cable (notincluded in thescope of supply)
2nd cable (notincluded in thescope of supply)
Surgearrester
Block-typecurrent transformer4MA,cast-resin insulated
Cable-typecurrent transformere.g. 4MC703 . . .
Three-phasecurrent transformer4MC63 . . .
P1 and P2are terminaldesignationsof the currenttransformer
Type RK-U375 mm wide
With3AH5vacuumcircuit-breaker,fixed-mounted
With3AH6vacuumcircuit-breaker,with-drawable
Bus sectionalizer panel type LT10 withring-main transfer panel type RK-U
Type RK-U375 mm wide
Type LT11750 mm wideBus sectionalizer panel type LT11 withring-main transfer panel type RK-U(non-interchangeable arrangement)
3AH5 vacuumcircuit-breaker
Three-positionswitch-disconnector
3AH6 vacuumcircuit-breaker
Standard:transferto theright
Option:transferto theleft
The ring-main transferpanel RK-U can beattached on the left orright of the bus section-alizer panel LT10
Product Range
-
7/26/2019 Simosec En
11/44
SiemensHA 41.21 2003 11
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Transformer panels
as feeder panels
Cable panels
as feeder panels, 630 A
Transformer and cable panels
Type K375 mm wideType TR375 mm wide
Type TR1500 mm wide
Cable panels
as feeder panels withmake-proof earthing switch
Type K-E375 mm wide
Type K1500 mm wide
Type K1-E500 mm wide
* On request
up to 12 kV** Current
transformerlocated partlyunderneaththe panel
either:Version withtransformers
or:Version withconnectionfittings
either:Version withtransformers
or:Version withconnectionfittings
HV HRC fuse
Capacitivevoltage detectionsystem
Make-proofearthing switch
Earthingswitch
Three-positionswitch-disconnector
Fixedearthing point
Cable-typecurrent transformer,e.g. 4MC703 . . .
Block-type
current transformer4MA,cast-resin insulated
Three-phasecurrent transformer4MC63 . . .
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Cable (notincluded in thescope of supply)
2nd cable (notincluded in thescope of supply)
Surgearrester HA
41-2390beps
Type K1500 mm wide
Type K1-E500 mm wide
as feeder panels630 A and 1250 A
Product Range
-
7/26/2019 Simosec En
12/44
12 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Circuit-breaker panels
Circuit-breaker panels 630 A
as feeder panels
as transfer panels for attachmentto panel types ME1... or ME1-H
Type LS1750 mm wide
Type LS1-U750 mm wide
Footnotes for the left and right columns:
* On request
** Standard: Feeder earthingvia the 3AH6 vacuum circuit-breaker
with interlocks (without earthing switch)BMounting position of the current
transformer with terminal P1 at the top only
P1 and P2 are terminal designationsof the current transformer
With 3AH5 vacuum circuit-breaker,fixed-mounted
Voltage transformere.g. 4MR, 1-pole,cast-resin insulated
Cable (notincluded in thescope of supply)
Addit. cables (not
included in thescope of supply)
Surgearrester
Three-phasecurrent transformer4MC63 . . .
Capacitivevoltage detectionsystem
Fixedearthing point HA
41-2390beps
Type LS31750 mm wide
With 3AH6vacuum circuit-breaker,withdrawable
Type LS11750 mm wide
With 3AH5vacuum circuit-breaker, fixed-mounted
With 3AH6vacuum circuit-breaker, withdrawable
Type LS11-U750 mm wide
as transfer panel for attachmentto panel types ME1... or ME1-H
With 3AH6vacuum circuit-breaker, withdrawable
Type LS31-U750 mm wide
Standard:transferto theright
Option:transferto theleft
Transferpossibleonly tothe right
3AH5 vacuumcircuit-breaker
Three-positionswitch-disconnector
Three-positiondisconnector
3AH6 vacuumcircuit-breaker
Cable-typecurrent transformere.g. 4MC703 . . .
Block-typecurrent transformer4MA,cast-resin insulated
Make-proofearthing switch
Transferpossibleonly tothe right
Circuit-breaker panels 1250 A
as feeder panels
forconnectionof max.2 cables
With 3AH6vacuum circuit-breaker, withdrawable
forconnectionof max.3 cables(4 cables *)
With 3AH6vacuum circuit-breaker,withdrawable
Type LS32875 mm wide
Product Range
-
7/26/2019 Simosec En
13/44
SiemensHA 41.21 2003 13
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Bus sectionalizer panels 630 A
in combination with bus riser panel
Type HF375 mm Type LT10750 mm wide
Type HF375 mm wide
Type LT10750 mm wide
Type HF375 mm wide
Type LT11750 mm wide
Type LT2750 mm wide
Bus sectionalizer panels 630 A
with 1 three-position switch-disconnector
Type LT2-W750 mm wide
with 2 three-position switch-disconnectors
Type LT22750 mm wide
Type LT22-W750 mm wide
Paneltype
HF
attached
on
the
right
Bus sectionalizer panels
3AH5 vacuumcircuit-breaker
Three-positionswitch-disconnector
3AH6 vacuumcircuit-breaker
Three-positiondisconnector
Voltage transformer
e.g. 4MR, 1-pole,cast-resin insulated
Block-typecurrent transformer4MA,cast-resin insulated
Three-phasecurrent transformer4MC63 . . .
Capacitivevoltage detectionsystem
Fixedearthing point HA
41-2390beps
With3AH5vacuumcircuit-breaker,
fixed-mounted
corresponds to type RK-Uwith type HF
Type HF375 mm wide
Type LT31750 mm wide
corresponds to type RK-Uwith type RK-U
corresponds to type RK-Uwith type RK-U
corresponds to type RK-Uwith type HF
With3AH5vacuumcircuit-breaker,
fixed-mounted
With3AH6vacuumcircuit-breaker
with-drawable
Bus sectionalizer panel 1250 Ain combination with bus riser panel
Paneltype
HF
attached
on
the
left
Paneltype
HF
can
only
be
attached
on
the
right
Pan
eltype
HF
can
only
be
attached
on
the
right
P1 and P2are terminaldesignationsof the currenttransformer
With3AH6vacuumcircuit-breaker
with-drawable
Product Range
-
7/26/2019 Simosec En
14/44
14 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Billing metering panels
Billing metering panels
630 A and 1250 AStandard
Type ME1750 mm wide Standard **:Transfer to the right Type ME1-S750 mm wide
Billing metering panels
630 A and 1250 Afor busbar connection
Type ME1750 mm wide
Type ME1-S750 mm wide
Type ME1750 mm wide
Type ME1-S750 mm wide
Type ME1750 mm wide
Type ME1-S750 mm wide
Type ME1-H750 mm wide
Type ME1-H750 mm wide
Billing metering panels
630 A and 1250 Afor additional current transformer
HA41-2390beps
Capacitivevoltage detectionsystem
On request:Voltage transformer,e.g. 4MR,cast-resin insulatedwith HV HRC fuse
Block-typecurrent transformer4MA,cast-resin insulated
Fixedearthing point
Fixed earthingpoint forbusbar earthing
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Standard **:Transfer to the right
Type ME1-H750 mm wide
Type ME1-H750 mm wide
Standard **:Transfer to the right
* On request
** Option:Transferto the left
Voltage transformer,e.g. 4MR,1- or 2-pole,cast-resin insulated
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Scheme 1 Scheme 1 Scheme 1
Scheme 2 Scheme 2 Scheme 2
Scheme 3 Scheme 3 Scheme 3
Scheme 4 Scheme 4 Scheme 4
Transformerterminalsinterchanged
P1 and P2are terminaldesignationsof the currenttransformer
Product Range
-
7/26/2019 Simosec En
15/44
SiemensHA 41.21 2003 15
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Make-proofearthing switch
Three-positionswitch-disconnector
HA41-2390beps
Capacitivevoltage detectionsystem
Fixedearthing point
Voltage transformer,e.g. 4MR,1- or 2-pole,cast-resin insulated
Billing metering panels, busbar voltage metering panels,busbar earthing panels and bus riser panels
HV HRC fuse
* On requestup to 12 kV
** Connectionfor 3 cablespossible
B Option:Transferto the left
BB For
attachmentto left orrightring-mainpanelstype RK-U
Billing metering panels
630 A and 1250 A**for cable connection
Type ME1-K750 mm wide StandardB
):Transfer to the right Type ME1-KS750 mm wide
Billing metering panels
630 A and 1250 A**for busbar connection
Type ME1-K750 mm wide
Type ME1-KS750 mm wide
Type ME1-K750 mm wide
Type ME1-KS750 mm wide
Type ME1-K750 mm wide
Type ME1-KS750 mm wide
Type ME31-F500 mm wide
Type ME3375 mm wide
Busbar voltage
metering panels
Standard B):Transfer to the right
StandardB):Transfer to the right
Standard B):Transfer to the right
Type SE1375 mm wide
Type SE2500 mm wide
Bus riser panels
630 A and 1250 A
Type HFBB
)375 mm wide
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Type HF BB)375 mm wide
Type HF BB)375 mm wide
Busbarearthing panels
Type HF BB)375 mm wide
Earthing switch
Make-proofearthing switch
Transformerterminalsinterchanged
Transformerterminalsinterchanged
Scheme 1 Scheme 1 Scheme 1
Scheme 2 Scheme 2 Scheme 2
Scheme 3 Scheme 3 Scheme 3
Scheme 4 Scheme 4 Scheme 4
P1 and P2are terminaldesignationsof the currenttransformer
as right or leftend panel
as right or leftend panel
as right or leftend panel
as right or leftend panel
Voltage transformer,e.g. 4MR,1-polecast-resin insulated
Block-typecurrent transformer4MA,cast-resin insulated
Product Range
-
7/26/2019 Simosec En
16/44
16 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Panel design(examples)
Ring-main panel as feeder Transformer panel as feeder
Billing metering panel Legend for pages 14 and 15
1 Option: Low-voltage compartment
2 Niche for optional low-voltage equipment,cover can be unscrewed
3 Option: CAPDIS voltage detection system
4 Option: Short-circuit/earth-fault indicator
5 Option: Ready-for-service indicatorfor switching device
6 Switch position indication for load-breakfunction CLOSED OPEN
7 Switch position indication for earthingfunction OPEN EARTHED
8 Feeder designation label9 Mimic diagram
10 Option: Sockets for capacitive voltage detection system(depending on arrangement)
11 Option: Momentary-contact rotary control switchCLOSED OPEN for motor operating mechanismwith local-remote switchfor three-position switch-disconnector
12 Option: Locking device for three-positionswitch-disconnector
13 Pressure relief device for switching device
14 Manual operation for the mechanism ofthe earthing function
15 Manual operation for the mechanism ofthe load-break function
16 Rating and type plate
17Gas-insulated vessel for switching device
18 Interlocking of the cable compartment cover
19Bushing-type insulator for busbar
20 Bushing-type insulator for feeder
Type RK Type TR
Type ME1
Section Section
Section
Design
-
7/26/2019 Simosec En
17/44
-
7/26/2019 Simosec En
18/44
18 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Common features
Circuit-breakers withvacuum interrupters
Stored-energy spring-operated mechanism for10,000 operating cycles
Maintenance-free for in-door installation accordingto IEC 60694 / VDE 0670Part1000, subsequentlyIEC 62 271-1*
Individual secondaryequipment
Switching duties andoperating mechanisms
The switching duties of thevacuum circuit-breaker aredependent, among otherfactors, on its type of oper-ating mechanism. Threeoperating mechanismversions are available:
Motor operating stored-energy mechanism
For auto-reclosure (K), For synchronization and
rapid load transfer (U)
Manual operating stored-energy mechanism
For auto-reclosure (K)Manual spring-operated
mechanism(= spring CLOSED,stored-energy OPEN)
Not for auto-reclosure (K) For normal closing and For storage of one
opening
Trip-free mechanism
The vacuum circuit-breakers are fitted with atrip-free mechanismaccording to IEC 60 056
and VDE 0670.
3AH5 and 3AH6 vacuum circuit-breakers
3AH5 vacuum circuit-breaker
Metal-enclosed
Up to 630 A
Pole parts with vacuuminterrupters fixed-mountedin hermetically welded,gas-filled switchgear vessel
System-conforming usewith three-position switchin gas-insulated switchgearvessel
Operating mechanismarranged outside theswitchgear vessel and
behind the control boardAir-insulated primary
terminals
Installation in metal-cladpanels
Feeder panels type LS1,panel width 750 mm
Transfer panels type LS1-U,panel width 750 mm
Bus sectionalizer panelstype LT10 (for adjacent busriser panel type HF),panel width 750 mm
3AH6 vacuum circuit-breaker
Withdrawable1) lateral-mechanism circuit-breaker,air-insulated
Up to 1250 A
Circuit-breaker polesarranged one behind theother
Operating mechanism inseparate box behind lowerpanel cover
Logical mechanical inter-
locking between 3AH6vacuum circuit-breaker andthree-position switch
Installation in: Feeder panel type LS11,
panel width 750 mm Transfer panel type LS11-U,
panel width 750 mm Bus sectionalizer panels
type LT11 and LT31 (foradjacent bus riser paneltype HF), panel width750 mm
Feeder panel type LS31(for connection of
max. 2 cables),panel width 750 mm Feeder panel type LS32
(for connection of 3 cables;4 cables on request),panel width 875 mm
3AH5vacuum circuit-breaker(operating mechanism box open)
Abbreviations for switchingduties and applications:
U = Synchronization andrapid load transfer(make timew 90 ms)
K =Auto-reclosure
R-HA41-066eps
1
2
3
4
5
* Standards see page 41
1) Withdrawable after looseningthe respective contactconnections and fixing bolts
7 Operating mechanism box with controlelements
8 Circuit-breaker poles with vacuuminterrupters
9 Truck
1 Operating mechanism box
2 Bushing-type insulator for busbar
3 Switchgear vessel, gas-filled, with3AH5 vacuum circuit-breaker andthree-position switch-disconnector
R-HA41-068eps 9
8
7
3AH6vacuum circuit-breaker
6
Components
4 Spring-operated mechanism ofthree-position switch-disconnector
5 Bushing-type insulator for feeder
6 Location for three-phase currenttransformer (option)
10 Locking device for the3AH6 vacuum circuit-breakerin switch position CLOSEDwith earthed three-position switchin switch position EARTHED
11 Logical mechanical interlocking(standard when earthing the
feeder with closed vacuumcircuit-breaker) in panel types:
630 A: LS11, LS11-U and LT11 1250 A: LS31, LS31-U, LS32
and LT31For further details, please referalso to Catalog HG 11.113AH Vacuum Circuit-Breakers
11
10
-
7/26/2019 Simosec En
19/44
SiemensHA 41.21 2003 19
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
3AH5 and 3AH6 vacuum circuit-breakers
Operating mechanismelements of the3AH6 vacuum circuit-breaker
Operating mechanism elements
1 Gear
2 Coupling on gear for operationwith hand crank
For closing with manualspring-operated mechanism
For charging the closing springwith stored-energy mechanism
3 Closing spring
4 Motor (M1 *)
5 Closingspring charged indicator
6 Circuit-breaker OPEN
7 Circuit-breaker CLOSED8 Operating rod
Operating mechanismfunctions
Motor operating mechanism1)(M1 *)
In the case of the motor operat-ing mechanism, the closingspring is charged by means ofa motor and latched in thecharged position (the springcharged indication is visible).Closing is effected either bymeans of an ON pushbutton ora closing solenoid. The closingspring is recharged automati-cally (for auto-reclosure).
Manual operating stored-energy mechanism
The closing spring is chargedby means of the supplied handcrank until latching of theclosing latch is indicated(= spring charged indication).
Subsequently the vacuumcircuit-breaker can be closedeither manually or electrically.The closing spring can be re-charged manually. The possibil-ity to close is thus stored oncemore (for auto-reclosure).
Manual spring-operatedmechanism(= spring CLOSED,stored-energy OPEN)
The closing spring of the vacuumcircuit-breaker is charged bymeans of the supplied handcrank until the vacuum circuit-breaker closes. Subsequentlyeither manual or electrical open-ing is possible.
Vacuum circuit-breakers withspring-operated mechanism arenot suitable for auto-reclosure.
1) Motor rating at24 V to 220 V DC: 350 W110 V and 220 V AC: 400 VA
2) With closing solenoid
* Equipment code
Abbreviations:
O = OPEN operation
CO = CLOSE operation with subse-quent OPEN operation at theshortest internal close-open timeof the vacuum circuit-breaker
t = Dead time 0.3 s
t = Dead time 3 min
Operating mechanism
elements of the3AH5 vacuum circuit-breaker
6
4
3
1
R-HA4
1-080eps
2
8
7
R-HA41-069eps
2
1
3
47
8
6
Differences between the vacuum circuit-breakers depending on the operating mechanism version
Operatingmechanism version
Motor operatingstored-energy mechanism
Manual operatingstored-energy mechanism
Manual spring-operatedmechanism
Typical uses Utility substationsand industrial plants
Classic transfer substationsand substations withoutauxiliary voltage supply
Simple utility substations(circuit-breaker astransformer switch)
Mechanismfunction
Stored-energy CLOSED,stored-energy OPEN
Stored-energy CLOSED,stored-energy OPEN
Spring CLOSED,stored-energy OPEN
Mechanismoperation
With motor1), manual(emergency) operationat the panel includinganti-pumping
With handcrank
With handcrank
Closing thevacuumcircuit-breaker
Electrically2) ormechanically at the panelwith pushbutton
Mechanically at the panelwith pushbutton, option:electrically2)
Mechanically at the panelwith hand crank(charging process)
Closing solenoid,e.g. for remoteelectrical closing
Always provided, withelectrical signalclosing spring charged
Option Without
Rated switchingsequence
O-t-CO orO-t-CO-t-CO
O-t-CO O or CO
Auto-reclosure (K)
Suitable (multipleauto-reclosure possible)
Suitable (only with closingsolenoid)
For further details, please refer also toCatalog HG 11.11 3AH VacuumCircuit-Breakers
5
5
Components
-
7/26/2019 Simosec En
20/44
20 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Secondary equipment of the 3AH5 and 3AH6 vacuum circuit-breakers
The scope of the secondaryequipment of the 3AH vacu-
um circuit-breaker dependson the type of applicationand offers a wide range ofvariations, thus allowingeven the highest require-ments to be satisfied.
Closening solenoid
Type 3AY15 10 (Y9 *)
For electrical closing
Shunt releases
Types: Standard: 3AY15 10 (Y1 *)
Option: 3AX11 01 (Y2 *),with energy store
Tripping by protection re-lay or electrical operation
Current transformer-operated release
Type 3AX11 04 (Y6 *) fortripping pulseW 0.1 Ws inconjunction with suitableprotection systems, e.g.7SJ4 protection relay,SEG relay (other designson request)
Used where no externalauxiliary voltage is avail-able, tripping by protec-tion relay
Undervoltage release
Type 3AX11 03 (Y7 *)
Comprising: Energy store and
unlatching mechanism Electromagnetic system,
to which voltage is perma-nently applied in theCLOSED position of thevacuum circuit-breaker;tripping is initiated whenthis voltage drops
Connection to voltagetransformer possible
Position switch
Type 3SE4 (S4 *)
For signalling closingspring charged
Only in conjunctionwithstored-energymechanisms
Secondary equipment of the 3AH6vacuum circuit-breaker(typical example)
Anti-pumping(standard)(mechanical and electrical)
Function: If CLOSE andOPENcommands are ap-plied simultaneouslyandcontinuously to thevacuumcircuit-breaker, this revertsto itsOPENposition afterclosing.The circuit-breakerremains in this positionuntilthe OPENcommand is eli-minated and a new CLOSEcommandis given.Thuscontinuous closingandope-ning (=pumping) is avoided.
Breaker tripping signal
(standard)For electrical signalling
(as pulse > 10 ms), e.g. toremote control systems,in the case of automatictripping (e.g. protection)
Via NO contact (S6 *)and cut-out switch (S7 *)
Varistor module
As overvoltage protectionfor protection devices inconjunction with inductivedevices in the vacuumcircuit-breaker (limiting toapprox. 500 V)
Recommended for auxil-iary voltagesW 60 V DC
Auxiliary switch
Type 3SV9 (S1 *)
Standard: 6NO+6NC,of which 2NO+2NC+2 changeover contactsare free1)
Option:12NO+12NC,ofwhich 7NO+4NC+2 change-overcontactsare free 1)
Mechanical interlocking
Dependent on the typeof operating mechanism:
Spring-operatedmechanism or
Stored-energy mechanism
Option:Switchgear interlockingwith the three-positionswitch-disconnector
For further details concer-ning interlocking functions,refer to page 26.
For further details, please refer also toCatalog HG 11.11 3AH Vacuum Circuit-Breakers
1) For utilizationby thecustomer
Abbreviations:NO = normally-open contactNC = normally-closed contact
* Equipmentcode
Basic equipment
1 Auxiliary switch 6NO+6NC (S1*),option: 12NO+12NC
2 1st release (Y1 *)
Additional equipment
3 Position switch (S4 *)
4 Closing solenoid (Y9*)
5 Operating cycle counter
6 2nd release
(e.g. Y2 *, Y6* and Y7 *)
7 Mechanical interlockingwith interrogationof the three-positionswitch-disconnector
1
1
2
5
6
2
7
4
3
5
R-HA41-080eps
4
3
R-HA41-046eps
Components
Secondary equipment of the 3AH5vacuum circuit-breaker(typical example)
-
7/26/2019 Simosec En
21/44
SiemensHA 41.21 2003 21
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Three-position switches as three-position switch-disconnectors or disconnectors
Common features
Metal-enclosedLocated in a
gas-insulatedswitchgear vessel
Switch positions:CLOSED-OPEN-EARTHED
No cross insulationbetween phases
Three-position switchwith air-insulatedprimary connectionsfor busbar and feeder
Operation via a
gas-tight welded-inbushing in the front ofthe switchgear vessel
Mode of operation
The switch shaft with themoving contact piecesrotates inside the cham-ber containing the fixedcontact pieces.
Compression vanes,which rotate in conjunc-tion with the switchshaft, divide the arcingchamber into two sub-
chambers each of whichchanges in conjunctionwith the rotation.
During the switchingmovement, the compres-sion vanes generate apressure difference be-tween the subchambers.The SF6gas flowsthrough a nozzle, causesa directional blow-out ofthe breaking arc andquenches it rapidly.
Interlocking is not neces-sary as the CLOSED
and EARTHED func-tions cannot be imple-mented simultaneously.
1 Bushing-type insulator for busbar
2 Switchgear vessel for gas insulation
3 Three-position switch-disconnector
4 Bushing-type insulator for feeder
5 Spring-operated mechanism with detachable lever
6 Mounting location for three-phase current transformer (option)
Detachable lever mechanism
with three-position switch-disconnector
Three-positionswitch-disconnector630 A
R-HA41-057eps
1
2
3
4
7 Operating lever, plugged inserted
Three-positionswitch-disconnector 630 A
Up to 630 A
With gas-insulated,maintenance-free quench-ing principle
Operating mechanism
Spring-operated mechanismwith detachable lever
Manual operation with theaid of a detachable lever
Options: Mechanical ready-for-
service indication
Auxiliary switch Motor operating mecha-nism for switch-disconnector
Locking device
Spring-operated/stored-energy mechanism fortransformer panel types TR,TR1 and ME31-F
Interlocks
Opening of lower panelcover or cable compartmentcover only in EARTHEDposition
Option: Logical mechanical
interlocking of three-positionswitch-disconnector withvacuum circuit-breaker
Three-positiondisconnector 1250 A
Up to 1250 A, for paneltypes LS31, LS31-U, LS32and LT31
Metal-enclosed
Operating mechanism
Spring-operated mechanismwith detachable lever
Manual operation with theaid of a detachable lever
Options: Mechanical ready-for-
service indication Auxiliary switch Motor operating mecha-
nism for disconnector Locking device
Interlocks
Opening of lower panelcover or cable compartmentcover only in EARTHEDposition
Logical mechanicalinterlocking with vacuumcircuit-breaker
Switch positions:
EARTHED
OPEN
CLOSED
5
6
Switching functions of thethree-position switch-disconnector630 A
Switching and disconnecting underload
Switching function as general purposeswitch-disconnector (class E3 and M1)according to
IEC 60 265-1
VDE 0670 Part 301 IEC 62 271-102 VDE 0670 Part 2/ EN 60 129
Make-proof earthing function
Switching functions of thethree-position disconnector1250 A
Disconnecting
Switching functions according to IEC 62 271-102 VDE 0670 Part 2/ EN 60 129
Earthing function
For panel types LS31, LS31-U,LS32 and LT31
Note: Standards see page 41
asthree-positionswitch-disconnector630 A
asthree-positiondisconnector1250 A
Components
-
7/26/2019 Simosec En
22/44
22 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Busbars, HV HRC fuse assembly
Busbar compartment extending over 3 panels(example)Side view
R-HA41-061eps
Busbars
Safe-to-touch due tometallic enclosure
Metal-clad busbarcompartment
Three-pole design,bolted from panel topanel
Easy switchgearextension
Made of copper: Fl E-Cu forw 630 A Rd E-Cu for > 630 A to
1250 A
For > 12 kV:
With insulated busbar
HV HRC fuse assembly
For transformer paneltypes TR and TR1
For busbar voltage meter-ing panel type ME31-F
HV HRC fuse linksacc. to DIN 43 625 (maindimensions) with strikerpin; version mediumacc. to IEC 60 282/VDE 0670 Part 4 *
As short-circuit protec-tion before transformers
With selectivity (depend-ing on correct selection)to upstream and down-
stream connectedequipment Single-pole insulation
Requirements acc. toIEC 60 420 * fulfilled bycombination of HV HRCfuse and three-positionswitch-disconnector
Fuse replacement possi-ble only when feeder isearthed
Option: Shunt release onoperating mechanism ofthree-position switch-disconnector
Option: Tripped indica-tion of three-positionswitch-disconnector intransformer feeder (trans-former switch) for remoteelectrical indication withone normally-open con-tact (1NO)
HV HRC fuse tripped
Following the tripping of anHV HRC fuse link, the me-chanism for charging thespring must be set to theOPEN position
Subsequently, earthing canbe implemented by meansof the three-positionswitch-disconnector ande.g. the fuse can bereplaced.
Replacement of HV HRCfuse links
Isolating and earthing ofthe transformer feeder
Subsequent manualreplacement of theHV HRC fuse link
2
3
1
1 Busbar
2 Insulating cap (e.g.forUr> 17.5 kV) onbusbar
3 Bushing-typeinsulator for busbar
Busbars
HV HRC fuse assembly
6
4
5
8
R-HA41-052eps 4 Insulating sleeve
5 HV HRC fuse(not included in thescope of supply)
6 Earthing switch (ratedshort-circuit makingcurrentIma= 4 kA)for cable connection
7 Cover for boltedcable lug connection(e.g. for rated voltageUr= 24 kV)
8 Cable sealing end(not included in thescope of supply)
HV HRC fuses in transformer panel type TRSide view
7
R-HA41-071eps
Control board of a transformer feeder
CLOSED indi-cation, manual ormotor operation
Indication HVHRC fuse trippedor shuntrelease tripped
OPEN indication
* Standards see page 41
Components
-
7/26/2019 Simosec En
23/44
SiemensHA 41.21 2003 23
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Allocation of HV HRC fuses and transformers
The table opposite shows therecommended 3GD HV HRC
fuse links (electrical data validfor ambient temperatures of upto 40oC) for the fuse protec-tion of transformers
Recommendation
The three-position switch-disconnector in the trans-former feeder (transformerswitch) was combined withSiemens HV HRC fuse linksof type 3GD and tested inaccordance with IEC 60 420 *
Standards
HV HRC fuse links withstriker pin, medium versionaccording to
IEC 60 282 *
VDE 0670 Parts 4 and 402
DIN 43 625 main dimensions
Ratedsystem
voltage
kV
Transformer
RatingSN
kVA
Relativeimpedancevoltageuk
%
RatedcurrentI1
A
Rated normal current of the HV HRCfuse link at ambient temperature of 40 OC
Lowest Highestvalue value
A A
6 to 7.2 5075
100
444
4.87.29.6
161620
161625
125160200
444
12.015.419.2
253240
253240
250315400
444
24.030.338.4
505063
5063
100
500630
44
48.061.0
6380
100100
10 to 12 5075
100
44
4
2.94.3
5.8
1010
16
1010
16
125160200
444
7.29.3
11.5
162025
162025
250315400
444
14.518.323.1
253240
324050
500630800
445 to 6
29.036.446.2
506363
638080
10001250
5 to 65 to 6
58.072.3
80100
100100
13.8 5075
100
444
2.13.24.2
61010
61010
125160200
444
5.36.78.4
161616
161620
250315400
444
10.513.216.8
202532
253232
500630800
445 to 6
21.026.433.5
405050
505050
10001250
5 to 65 to 6
41.952.4
6380
6380
15 to 17.5 5075
100
444
1.92.93.9
61010
61010
125160200
444
4.86.27.7
101616
101620
250
315400
4
44
9.7
12.215.5
20
2532
25
2532
500630800
445 to 6
19.324.330.9
324050
405050
10001250
5 to 65 to 6
38.548.2
6363
6380
20 to 24 5075
100
444
1.52.22.9
66
10
66
10
125160200
444
3.64.75.8
101016
101016
250315400
444
7.39.2
11.6
162020
162025
500
630800
4
45 to 6
14.5
18.223.1
25
3232
32
4032
100012501600
5 to 65 to 65 to 6
29.036.046.5
405063
405080
2000 5 to 6 57.8 80 80* Standards see page 41
Components
-
7/26/2019 Simosec En
24/44
24 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Manual operatingmechanism
Standard:As detachable levermechanism
Option: Design accordingto VDEW recommenda-tion Association ofGerman Power Stations VDEW e.V.
Spring-operated mecha-nism
For ring-main paneltypes RK and RK1
For all three-positionswitches (except in panel
types TR and TR1)Spring-operated-/stored-
energy mechanismFor transformer paneltypes TR and TR1 as wellas for busbar voltage me-tering panel type ME31-F
The three-position switch isoperated via a rocker withmetal bellows which isgas-tight and welded at theswitchgear vessel.
Motor operatingmechanism(option)
The manual operating me-chanisms can be equippedwith motor operating mecha-nisms both for the three-position switch-disconnectorand for the three-positiondisconnector.
Operating voltages for motoroperating mechanisms: 24, 48, 60, 110, 220 V DC 50/60 Hz 110 and 230 V AC
Electrical operation:
Standard: Remote opera-tion (applied to terminal)
Option: Local operationby momentary-contactrotary control switch
Shunt release(option)
Spring-operated/stored-en-ergy mechanisms can beequipped with a shunt re-lease. Remote electrical trip-ping of the three-positionswitch-disconnector is possi-ble via the magnetic coilof the shunt release, e.g.transformer overtemperaturetripping.
To avoid thermal overloadingof the shunt release in theevent of a continuous signalthat may be applied, theshunt release is switched offvia an auxiliary switch whichis mechanically coupled withthe three-position switch-disconnector.
Auxiliary switch(option)
Each operating mechanismof the three-position switch-disconnector can be option-ally equipped with an auxil-iary switch for the switchposition indication: 1NO + 1NC for
CLOSED/EARTH 2NO for OPEN
Separate earthing switch: 2NO and 1NC for
EARTH 2NO for OPEN
Operating mechanisms for three-position switches
Operating mechanisms(examples)
Detachable lever mechanismas spring-operated mechanismfor ring-main feeders
R-HA41-079eps
1 Terminal strip locatedin the low-voltageniche (optionally inthe low-voltagecompartment)
2 M.c.b. (option)in the low-voltageniche
3 Local-remote switch(option)
4 Actuation for themotor operatingmechanism of thethree-position
switch-disconnector5 Auxiliary contactors
of the motor operatingmechanism for lockingthe motor
6 Auxiliary switch
7 Switch positionindicator for thethree-positionswitch-disconnector
8 Locking device(standard for motoroperating mechanism)
9 Operating mechanismfor the three-positionswitch-disconnectorcoupled with the motor
operating mechanism10 Shunt release (option)
11 Motor operatingmechanism
R-HA41-070eps
Abbreviations:
NO = normally-open contactNC = normally-closed contact
Rated insulationvoltage250 V AC/DC
Insulation groupC to VDE 0110
Continuous current10 A
Making capacity50 A
Technical data of the auxiliary switch
Breaking capacity
AC operation at40 Hz to 60 Hz
Operating Normalvoltage current
V A
DC operation
Operating Normal currentvoltage resistive inductive:
T=20 msV A A
up to 230 10 24 10 10
48 10 9
60 9 7
110 5 4
220 2.5 2
Rated switching capacity
Operating mechanism parts intransformer feeder
6
8
7
9
10
11
5
4
3
2
1
Components
-
7/26/2019 Simosec En
25/44
SiemensHA 41.21 2003 25
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Short-circuit/earth-faultindicator (option)
The ring-main feeders canbe equipped with a 3-phaseshort-circuit or earth-faultindicator:
Optical signal when a pre-selected pickup value isexceeded
With ring-type sensors
Display panel, withdraw-able housing, dependingon the type
Short-circuit pickup values:e.g. 400, 600, 800 or
1000 AOption: Remote electricalindication via contact (1NO +1NC contact, passing con-tact), applied to terminal
Ready-for-service indicator(option for three-positionswitch)
Self-monitoring; easy toread
Independent of tempera-ture and pressure varia-tions
Independent of site altitude
Only responds to changesin gas density
Option: Alarm switch1NO contact
Mode of operation
For the ready-for-service indi-cator, a gas-tight measuringbox is installed on the insideof the switchgear vessel.
A coupling magnet, whichis fitted to the bottom endof the measuring box, trans-mits its position to an outsidearmature through the stain-less steel switchgear vessel.This armature moves theready-for-service indicator ofthe switchgear.
While changes in the gasdensity during the loss ofgas, which are decisive forthe insulating capacity, aredisplayed, temperature-dependent changes in thegas pressure are not. Thegas in the measuring box hasthe same temperature asthat in the switchgear.
The temperature effect iscompensated via the samepressure change in both gasvolumes.
Verification of safeisolation from supply
Voltage detection systems
For voltage detectionaccording to IEC 61 243-5 /VDE 0682 Part 415 with:
Standard: HR system
Option: LRM system
Option: LRM system asCAPDIS-S1 or CAPDIS-S2
Features of theHR/LRM system
Voltage indicator
HR system (standard) or LRM system (option)
Verification of safe isolationfrom supply phase byphase through insertion ineach socket pair
For continuous operation
Safe-to-touch
Measuring system andvoltage indicator can betested
Voltage indicator flashesif high voltage is present
Fixed-mounted capacitive
voltage divider in bushings
Features of CAPDIS-S1, -S2
Maintenance-free
Without auxiliary power
Self-checking
Option: With remoteindication of the voltagestate (auxiliary powerrequired for CAPDIS-S2)
Mounting of voltagedetection systems
Standard:In all ring-main andcircuit-breaker feeders
Option:In transformer feeders
Verification of correct ter-minal-phase connections
Verification of correctterminal-phase connec-tions possible by means ofa phase comparison testunit (can be ordered sepa-rately)
Safe-to-touch handling of
the phase comparison testunit by inserting it into thecapacitive taps (socketpairs) of the switchgear
Indicating and measuring equipment
Indicating and measuring equipment(examples)
Voltage indicator, HR system(standard)
R-HA40-088
eps
R-HA40-032eps
Short-circuit indicator ALPHA M(example)
6 Measuring box
7 Magnetic coupling
8 Red indication:not ready for service
9 Green indication:ready for service
Principle of operation of gas monitoringwith ready-for-service indicator
Stainless-steel vesselfilled with SF6gas,gauge pressure500 hPa at 20 C
Ready-for-serviceindicator
Reset:manual
For phase indicationsL1, L2 and L3
Mounting locations inthe control board for
1 Short-circuit / earth-fault indicator (option)
2 Ready-for-serviceindicator (option)
3 Voltage indicator, HRsystem, plugged-in(standard)
R-HA41-072beps
Control board of a ring-main panel
(example)
3
1
2
Components
-
7/26/2019 Simosec En
26/44
26 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Interlocking systems and locking devices
Interlocking of connectioncompartment
Ring-main andcircuit-breaker panel
Access to the cable con-nection compartment(e.g. for cable testing) isonly possible providedthat the feeder is isolatedand earthed (three-posi-tion switch-disconnectorin EARTHED position)
Option: Closing lock-outThis prevents the three-position switch-disconnec-tor from being switchedfrom OPEN toCLOSED position,when the cable compart-ment cover is removed
Transformer panel
Access to the cable con-nection compartment andto the HV HRC fuse com-partment (e.g. for replace-ment of HV HRC fuselinks) is only possible pro-vided that the feeder isisolated and earthed(three-position switch-
disconnector inEARTHED position)
Option: De-earthinglock-outThis prevents thethree-position switch-disconnector from beingswitched from positionEARTHED to OPEN.
Switchgear interlocking
Dependent on the va-cuum circuit-breaker oper-ating mechanism with
Spring-operated or
Stored-energy mechanism
Option: Switchgear-sidemechanical interlockingwith three-positionswitch-disconnector
Vacuum circuit-breakercannot be closed whenthree-position switch-disconnector is in theOPEN position:
Spring-operated mecha-nism: Hand crank openingis blocked
Stored-energy mechanismwith closing solenoid3AY15 10: Pushbutton(S12) operated by mecha-nical interlock preventscontinuous command toclosing solenoid
Interlocking in circuit-breaker panel types LS1,
LS1-U and LT10 (with 3AH5fixed-mounted vacuumcircuit-breaker)
Option: Logical mechanicalinterlocking with three-po-sition switch-disconnector
Earthing of feeder viathree-position switch-disconnector inEARTHED position
Interlocking in circuit-breaker panels (with 3AH6removable vacuum circuit-breaker)
Option: For 630 A paneltypes LS11, LS11-U andLT11: Logical mechanicalinterlocking with three-po-sition switch-disconnector
Standard: For 1250 Apanel types LS31, LS31-U,LS32 and LT31: Logicalmechanical interlockingwith three-positiondisconnector
Logical mechan. interlock-ing of cable compartmentcover: Opening of cable
compartment cover onlypossible provided that thefeeder is earthed
Feeder earthing
Standard: Earthing byswitching of vacuumcircuit-breaker 3AH61) inposition CLOSED andof three-position switch2)in position EARTHED
Option: For circuit-breakerpanel types LS11, LS31and LS32: Earthing bymeans of an additional
make-proof earthingswitch at the feeder withinspection window in thecable compartment cover
Locking devices
The three-position switch-disconnector can be lockedon the operating mechanismside in any position (option).
1) With additional locking device optionally with signallingswitch for securing theCLOSED position of the
vacuum circuit-breaker forfeeder EARTHED
2) Three-position switch as Switch-disconnector in panel
types LS11, LS11-U and LT11 Disconnector in panel types
LS31, LS31-U, LS32 and LT31
Interlocking systems
Locking device(option)
R-HA41-064ceps
R-HA41-081eps
Interlocking for cable compartment cover
Removed cable compartment coverwith earthed bus sectionalizer panel
Locking device of the detachable lever mechanisme.g. for padlock
Components
-
7/26/2019 Simosec En
27/44
SiemensHA 41.21 2003 27
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
4MC63 three-phase current transformers for panel types LS ... and LT ...
Application
For circuit-breaker panelstype LS ...
For bus sectionalizer panelstype LT ...
Option: For ring-main panelstype RK ...
Features
According to IEC 60 044-1/VDE 0414 Part 1
Designed as a three-polering-core currenttransformer
Free of dielectrically
stressed cast-resin parts(due to design)
Insulation class E
Inductive type
Climate-independent
Secondary connection bymeans of a terminal stripinside the panel
Installation
Arranged outside the switch-gear vessel on the bushings
Factory-assembled
Other designs(option)
Three-phase current transfor-mers for protection equipmentbased on c.t. operation:
7SJ4 protection relay asdefinite-time overcurrentprotection
Definite-time overcurrentprotection relay,make SEG, type WIP 1
Technical data 4MC63 53 three-phase current transformer
forIN
-
7/26/2019 Simosec En
28/44
28 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
4MC70 33, 4MC70 31 cable-type current transformers and 4MC70 32 bus-type current transformers
4MC70 33 cable-type current transformerson the cable at the panel connection
Application
For circuit-breaker panelstype LS ...
For ring-main panelstype RK ...
For transformer panelstype TR ...
Features
According to IEC 60 044-1/VDE 0414 Part 1
Designed as a single-polering-core current transformer
Only for shielded cables
Climate-independent
Free of dielectricallystressed cast-resin parts(due to design)
Insulation class E
Inductive type
Secondary connection bymeans of a terminal stripinside the panel
Installation
4MC70 33 cable-type currenttransformer and 4MC70 32bus-typecurrent transformer
for panel typeLS ...4MC70 31 cable-type current
transformer: e.g. for paneltypes RK ..., K ... and TR ...
Arranged on the cable atthe panel connection
Transformers mounted on asupporting plate at ourfactory; final assembly onthe cables on site
* Depending on the core data** Available installation height
inside panel types RK or RK1:Approx. 285 mm, depending onmake, type and cross-section ofsealing end
Other values available on request
R-HA41-049aeps
R-HA41-025eps 4MC70 31 cable-type
current transformer
R-HA41-024eps
H
H
4MC70 33 cable-typecurrent transformer,4 different overall heights
R-HA41-027eps
4MC70 32bus-typecurrent transformer
Technical data 4MC70 33 cable-typecurrent transformer
4MC70 31 cable-typecurrent transformer
4MC70 32 bus-typecurrent transformer
Primary data
Max. equipment operatingvoltage Um
0.72 kV 0.72 kV 0.72 kV
Rated currentIN A 30 A to 600 A 50 A to 600 A 200 A to 600 A
Rated short-durationpower-frequencywithstand voltage(winding test)
3 kV 3 kV 3 kV
Rated thermal short-timewithstand currentIth
25 kA 25 kA 25 kA
Rated continuous thermalcurrentID
max. 1.2 xIN max. 1.2 xIN max. 1.2 xIN
Transient overloadcurrent
1.5 xID/ 1 h or2 xID/ 0.5 h
1.5 xID/ 1 h or2 xID/ 0.5 h
1.5 xID/ 1 h or2 xID/ 0.5 h
Rated peak withstandcurrentIdyn
unlimited unlimited unlimited
Secondary data
Rated current 1 A (option: 5 A) 1 A (option: 5 A) 1 A (option: 5 A)
Meas-uringcore
Class 0.2 0.5 1 1 0.2 0.5 1
Overcurrent factor FS10 (option: FS5) FS5 (option: FS10) FS10 (option: FS5)
Rating 2.5 VA to 10 VA 2.5 VA to 10 VA 2.5 VA to 10 VA
Pro-tectioncore
Class 10 P 5 P 10 P 5 P (on request)
Overcurrent factor 10 10 10 10
Rating 2.5 VA to 10 VA 2.5 VA to 15 VA
Option: Secondary tap 1 : 2(e.g. 150 A 300 A)
1 : 2 1 : 2(e.g. 150 A 300 A)
Dimensions
Overall height H ** mm 50* 100* 170*285* 89 80 * 150 *
Outside diameter 145 mm 85 mm x 114 mm 125 mm
Inside diameter 55 mm 40 mm 55 mm
For cable diameter 50 mm 36 mm 50 mm
Components
-
7/26/2019 Simosec En
29/44
SiemensHA 41.21 2003 29
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
4MA7 block-type current transformers and 4MR voltage transformers
4MR single-pole voltage transformer
Primary data
Max. equipment operatingvoltageUm(= 1.2 x UN)12 kV
Rated voltageUNat max.rated short-durationpower-frequencywithstand voltageUd
3.3/ 3kV at 10 kV3.6/ 3 kV at 10 kV
4.8/ 3 kV at 20 kV5.0/ 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3kV at 20 kV7.2/ 3 kV at 20 kV
10.0/ 3 kV at 28 kV11.0/ 3kV at 28 kV
Rated lightning impulsewithstand voltageUp
75 kV
Rated voltage factor(8 h)
1.9 xUN
Max. equipment operating
voltageUm(= 1.2 xUN)
24 kV
Rated voltageUNat max.rated short-durationpower-frequencywithstand voltageUd
13.8/ 3kV at 38 kV15.0/ 3 kV at 38 kV
17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV
Rated lightning impulsewithstand voltage
125 kV
Rated voltage factor(8 h)
1.9 xUN
Secondary data
Rated voltage 100/ 3V110/ 3 V120/ 3 V
Rated voltage for auxiliary
winding (option)
100/3 V
110/3 V120/3 V
Rating 20 VA 50 VA 100 VA
Class 0.2 0.5 1
Other values available on request
Application
For billing metering panelstype ME1 ...
For bus riser paneltype HF
For mounting at thefeeder
Features
4MA7 current transformer
According to IEC 60 044-1/VDE 0414 Part 1
Dimensions according toDIN 42600 Part 8
Designed as a single-poleindoor block-type currenttransformer
Cast-resin insulated
Insulation class E
Secondary connection bymeans of screw-typeterminals
4MR voltage transformer
According to IEC 60 044-2/VDE 0414 Part 2
Dimensions according toDIN 42600 Part 9 (small
model)
Designed as an indoorvoltage transformer:
Type 4MR, single-pole Option: Type 4MR, two-pole
Cast-resin insulated
Insulation class E
Secondary connection bymeans of screw-typeterminals
Other values available on request
R-HA41-060aeps
4MA7 block-type currenttransformer,single-pole
4MR14 voltagetransformer,single-pole
4MR voltage transformer and4MA7 block-type current transformer installed inbilling metering panel type ME1
R-HA41-029aeps
R-HA41-030aeps
Technical data
4MA7 single-pole block-type current transformer
Primary data
Max. equipment operatingvoltageUm12 kV 24 kV
Rated short-durationpower-frequencywithstand voltage
38 kV 50 kV
Rated lightning impulsewithstand voltage
95 kV 125 kV
Rated currentIN 25 A to 1250 A
Rated thermal short-timewithstand currentIth
up to 25 kA
Rated continuous thermalcurrentID
up to 1.2 xIN
Rated peak withstandcurrentIdyn
max. 2.5 x Ith
Secondary data
Rated current 1 A or 5 A
Meas- Classuring Overcurrent factorcore
Rating
0.2 0.5 1
FS5 or FS10
10 VA to 15 VA
Pro- Classtection Overcurrent factorcore
Rating
5 P or 10 P
10
5 VA or 15 VA
Components
-
7/26/2019 Simosec En
30/44
30 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Cable connection
General features
Connecting lugs for sealing endsarranged one behind the other
Uniform cable connection heightfor the respective panel types
Withcablebracket,e.g. type C40according toDIN EN50024
Access to the cable connectioncompartment only if feeder hasbeen isolated and earthed
Special features
In ring-main panels In circuit-breaker panels In cable panels
For thermoplastic-insulated cables
For paper-insulated mass-impregnated cables withadapter systems
For connection cross-sections up to 300 mm2
Cable routing downwards
In transformer panels:
For thermoplastic-insulated cables
For connection cross-sections up to 120 mm2:
Cable lug max. 32 mm wide
For rated normal currentsof 200 A
For options see figures
Cable cross-sections
Note
Cable sealing ends and cable clampsare not included in the scope of supply
Cable connection(examples)
Cable connection compartment with cablesealing ends (options: A, B, C1) and D1), see below)
Ring-main panel type RKCable connection compartment as delivered
L3 L2 L1 L1L2L3
Transformer panel type TRCable connection compartment as delivered
Cable connection compartment with cablesealing ends (option: A2), see below)
L3L2L1
R-HA41-050eps
R-HA41-051eps
R-HA41-053eps
R-HA41-052eps
R-H
A41-055eps
R-HA41-067eps
L3L2L1
Cable connection compartment with cablesealing ends (options: A, B, C and D, see below)
Circuit-breaker panel type LS11Cable connection compartment as delivered
Options A Mounted cable clamps 2)
B Short-circuit / earth-fault indicator
C Double cable connection
D Suitable for connection of surge arresters3)
5
1
4
3
7
8
14
10 13
12
2
6
L1L2
L3
9
11
1) Only with ring-main panel type RK1
2) Cable clamps with transformerpanels type TR ... partly mounted
underneath the panel in the cablebasement
3) Make Siemens, type 3EK7,other makes on request
Panel type Connectable cablesxconnection cross-sections
No. x mm2
for rated voltage
12 kV 17.5kV 24 kV
K Standard
on request
1x300 1x300 1x300
2x300
K1 2x400 2x400 2x400
RK, K-E 2x300 1x300 1x300
RK1, K1-E 2x300 2x300 2x300
LS1 2x300 2x300 2x300
LS11,LS31 2x400 2x400 2x300
LS32 Standard
Option
on request
3x400 3x400 3x300
4x300 4x300
4x300
ME1-K, ME1-KS 3x400 3x400 3x300
Components
-
7/26/2019 Simosec En
31/44
SiemensHA 41.21 2003 31
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
1) Transformer panel types TR ...: Lower edge of sealing end below panel Cable lugs of sealing ends up to 32 mm width Owing to the various sealing end lengths, some of
the mounted cable clamps are underneath the panel
2) Circuit-breaker panel types LS11, LS31 and LS32: Lower edge of sealing end below panel
Selection data for various cable sealing ends
1 As-delivered condition, preparedfor cable sealing endw 12 kV
2 As-delivered condition, preparedfor cable sealing end > 12 kV, w 24 kV,additionally with insulating sleeve
3 Phase L1:Make: Corning Cables (RXS)Type IAEM 20,240 mm2 (20 kV)
4 Phase L2:Make: Tyco Electronics RaychemType EPKT 24 C / 1X,185 mm2 (24 kV),as shrink-on sealing end,for severe ambient conditions
5 Phase L3:Make: PirelliType ELTI mb-1C-2h-C-T3,240 mm2 (24 kV)
6 As-delivered condition, preparedfor cable sealing end
7 Phase L1:Make: Corning Cables (RXS)Type IAEM 20,95 mm2 (20 kV)
8 Phase L2:Make: Tyco Electronics RaychemType TFTI/5131,
95 mm
2
(24 kV),as push-on sealing end
9 Phase L3:Make: EuromoldType AIN, 95 mm2 (24 kV)
10 As-delivered condition, preparedfor cable sealing endw 12 kV
11 As-delivered condition, preparedfor cable sealing end > 12 kV, w 24 kV,additionally with insulating cap
12Phase L1:Make: Corning Cables (RXS)Type IAES 20,240 mm2 (20 kV)
13Phase L2:Make: PirelliType ELTI 1C-24-D-T3,240 mm2 (24 kV),as indoor sealing end,for severe ambient conditions
14Phase L3:Make: EuromoldType AIN 20,240 mm2 (24 kV)
Connection height **of cables above
floor or abovelower edge of panel:
Cable sealing ends
(examples)
Single-core thermoplastic-insulated cables for 12 kV to
-
7/26/2019 Simosec En
32/44
32 SiemensHA 41.21 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable
Low-voltage equipment
Low-voltage niche(standard)
Screwed-on cover as Cover (available mounting
depth behind ofapprox. 184 mm)
Frame cover, approx.46 mm deeper version(available mountingdepth behind ofapprox. 230 mm)
For accommodation ofterminals and standardprotection devices, e.g.in circuit-breaker panelscombined with framecover for panels
Type LS1: Protectionrelays (with max. 75 mmwide mounting frame),e.g. type 7SJ45, 7SJ46and 7SJ60,option: Protection relaymake SEG
Type LS11: Protectionrelays (with max. 150 mmwide mounting frame),e.g. type 7SJ4..., 7SJ60and 7SJ61 (on requesttype 7SJ62), option: Pro-tection relay make SEG
For bus wires and/or con-
trol cables; niche open atthe side to the adjacentpanel
Safe-to-touch, separatedfrom high-voltage part ofthe panel
Degree of protectionIP 3X (standard)
Low-voltagecompartment(option)
Heights 350