EOLO SERIES
Power Range kW kVA
MODELS:HGGO - 60
Standby Natural gas 55.7 - 58.5 55.7 - 73.1HGGE - 60Standby Propane 60.4 - 63.5 60.4 - 79.4
STANDARD EQUIPMENT
Open Set Model: HGGO-60 Accessories Available for HGGO/E - 60
■ Himoinsa CMD2.0 digital auto-start control panel (Page 4) Mechanical Accessories Offered
■ Dry-type replaceable element air-cleaner ■ Weather protective canopy (for Open Set)
■ Battery, battery rack, and cables ■ Critical grade exhaust mufflers
■ Lubrication oil replaceable element filters ■ Flexible exhaust connection for open sets
■ Stamford AVR brushless 12-wire reconnectable alternator ■ Oil pressure and engine temperature gauges
■ Vibration Isolators between base and set assembly ■ Extended warranty coverage above the standard one year
■ Main Line Circuit Breaker for overload protection Generator End Accessories Offered
■ Belt driven charging alternator ■ PMG excitation for enhanced motor-starting
■ Guards for shielding all rotating parts ■ Anti-condensation heaters
■ Fuel cut-off solenoid and protection switches Electrical and Control Accessories Offered
■ Radiator with pusher fan ■ Automatic battery chargers 5 and 10 amp
■ Operation and installation manuals ■ NFPA 110 controls and remote annunciator
■ Analog instrumentation in lieu of digital
Sound Attenuated Set Model: HGGE-60 ■ Transfer switch and paralleling control panels
■ Fully sound attenuated enclosure (equipped as open set) ■ Water Jacket Heater
■ Powder Painted with finish that exceeds 1000-hr salt test ■ Remote control from PC via hard and/or wireless link
■ Rock wool insulation behind protective barrier ■ GPS for mobile sets
■ Curved edges and minimum outside fasteners ■ Digital Timer (Auto-start sets only)
■ Single lifting point
GENERATOR RATINGS
NATURAL GAS PROPANE
Stand by Rating, 125ºC Stand by Rating, 125ºC
Alternator Voltage Ph Hz kW/kVA Amps kW/kVA Amps
UCI 224G
120 / 208 3 60 58.2 / 72.8 202 63.1 / 78.9 219
127 / 220 3 60 58.3 / 72.9 191 63.3 / 79.1 208
120 / 240 3 60 58.2 / 72.8 175 63.1 / 78.9 190
139 / 240 3 60 58.5 / 73.1 176 63.5 / 79.4 191
277 / 480 3 60 58.5 / 73.1 88 63.5 / 79.4 96
347 / 600 3 60 58.5 / 73.1 70 63.5 / 79.4 76
120 / 240 1 60 55.7 / 55.7 232 60.4 / 60.4 252
Application DataAlternator Specifi cations Engine Mechanical Specifi cations
Manufacturer Newage Stamford Manufacturer General Motors Powertrain
Type 4-pole, rotating fi eld Engine model VORTEC 5700
Exciter type Brushless, self excited. (PMG option)
Engine type 4-cycle, Naturally aspirated
Leads: quantity, type 12, reconnectable Cylinder arrangement V - 8
Voltage regulator Solid state, volts/Hz and excitation overload protection
EPA Certifi cation for mobile use: Not available
Insulation: Material...................... Temperature rise..........
Class H125° C , standby
Displacement, L (cu. in.)
Bore and stroke, mm (in.)
5.7 (350)
101.6 x 88.4 (4.0 x 3.48)
Bearing: quantity, type Single bearing sealed Compression ratio 9.4 : 1
Coupling Flexible disc Piston speed, m/min. (ft./min.) 318.2 (1,044)
Amortisseur Windings Full Main bearings: quantity, type 5, replaceable insert
Voltage regulation, no-load to full load
± 1.5% (self-excited) Rated rpm 1,800
Unbalanced load capability 100% of rated standby current Max. power at rated rpm, kWm (BHP).
LPG = 76.8 (103.0)NG = 70.9 (95.0)
Load acceptance Per ISO - 8528 BMEP, gross, psi ( Bar )
Overall thermal effi ciency
LPG = 129.5 (8.93)NG = 119.5 (8.24)
LPG = 30.5% NG = 29.1%
Peak motor starting kVA: 480 V 480 V
(30% dip)self-excited series 4 - 270 kVAPMG series. 3 - 355 kVA
Engine Electrical Specifi cationsExhaust Gas Flow, m³ /min (cfm)Exhaust gas temperature °C (°F)
15.8 (558)649 (1,200)
Engine Electrical System (12 Volt) 60 HzFrequency regulation, no-load to full load
Isochronous
Battery charging alternator: Ground (negative/positive). Volts (DC)......................... Ampere rating..................
Negative12V70A
Governor: Type: Make: Standard:
LC - 50WoodwardISO 8528
Starter motor rated voltage (DC) 12V Frequency regulation, steady state ± 0.35%
Starter motor rated kW:Battery CCA rating:Battery & qty, AH rating:
TBA KwTBA A TBA AH
Frequency Fixed
Battery Voltage (DC) 12V Air cleaner type Dry
Remote Radiator System Fuel Consumption 60 HzExhaust manifold type
Not Available
NG ft3/hr (m3/hr) Standby RatingConnection sizes: 100% 744 (21.1)Water inlet ID hose, mm (in) 75% 631 (17.9)Water outlet ID hose, mm (in) 50% 483 (13.7)Charge air cooling (CAC) 25% 333 (9.4)Water inlet ID hose, mm (in) LPG ft3/hr (m3/hr) Standby RatingWater outlet ID hose, mm (in) 100% 295 (8.4)Static head allowable aboveengine, ft.H²O (kPa) 75% 230 (6.5)
Maximum CAC restriction H²O in. 50% 178 (5.0)
Contact the HIMOINSA distributor for special cooling options 25% 129 (3.7)
Application DataCooling Lubrication
Radiator Systems 60 Hz Lubricating System 60 Hz
Ambient temperature, °C (°F) 49 (120) Type Full pressure
Engine jacket water capacity L (gal) 7.7 (2.0) Oil pan capacity, L, (qt.)Recommended lube oil
4.7 (5.0)SAE 10W30 Type SJ
Radiator system capacity, including engine, L (gal.) 22.8 (6.0) Oil pan capacity with fi lter, L (qt.) 5.2 (5.5)
Engine jacket water fl ow, L/min (g/min) 115.5 (30.5) Oil fi lter: quantity, type 1, cartridge
Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) 64.2 (3,650)
Oil coolerMaximum oil temperature, ºC (ºF)
Not available132 (270)
Water pump type Centrifugal Ventilation and Air-Flow RequirementsFan, kWm (HP) 6.5 (8.7) Air Requirements 60 Hz
Radiator-cooled cooling air, m³/min. (scfm) 205.3 (7,250)
Air density kg/m³ (ibm/ft³) 1.20 (0.075)
Max. restriction of cooling air, intake and discharge side of radiator, Pa (in. H²O)
62.2 (0.25)Heat rejected to exhaust, kW (btu/min) 63.7 (3,625)
dBA LEVELS SOUND ATTENUATED ENCLOSEDA LEVELS SOUND ATTENUATED ENCLOSEDA Within (under) 70dBA@ 21 feet
Heat radiated to surrounding air Engine: kW (Btu/min) 32.5 (1,850)
Combustion air, m³/min. (cfm) 5.2 (182)
Dimensions and Weights
Open Set Model: HGGO-60 Sound Attenuated Set Model: HGGE-60Overall size, L x W x H, mm (ins.) 1,949 x 724 x 1348 Overall size, L x W x H, mm (ins.) 2,980 x 1,200 x 1,556
(76.7 x 28.5 x 53) (117.3 x 47.2 x 61.3)
Weight, radiator-mounted model, wet, kg (lb.): 801 (1,765) Weight, radiator-mounted model, wet, kg (lb.): 1,598 (3,523)
H
W L
H
W L
NOTE: The drawings above are only representative of the overall dimensions. For full detailed installation drawings please consult your local distributor or contact Himoinsa @ www.himoinsausa.com
RATINGS: Power factor three-phase is 0.8 and single-phase unity. Standby Ratings: Standby ratings assume installation normally served by reliable utility power. The standby rating is available for varying loads for the length of the power outage. No overload is available with the standby rating. Ratings are in accordance with ISO-3046/1 and DIN 6271. Prime Power Ratings: Prime power ratings assume no or unreliable utility power. For varying loads the generator set has unlimited operating hours. A 10% overload capacity is available for any 1 hour in a 12 hour continous running period. Ratings are in acoordance with ISO-3046/1 and DIN 6271. Consult Himoinsa for limited running time and base load ratings. Himoinsa reserves the right to change the design or specifi cations without notice and without any obligation or liability whatsoever. DERATION GUIDELINES: Altitude: Derate 1.3% per 100 m (328 ft) elevation above 1000 m (3280 ft). Temperature: Derate 1.0% per 10ºC (18ºF) temperature above 40ºC (104ºF).
L L L L L
H
L L
HIMOINSA CMD2.0 Auto Digital Control Panel
1. Switch-on button 10. 1. Stopping cycle indicator
2. Display 1. (visual display ofphase voltage ) 2. Pre-heating indicator
3. Push-button V. (to select voltage) 3. Engine on indicator
4. Display 2. (visual display of ampage) display of ampage) display of 4. LT closed indicator
5. Push-button A. (to select amps) 11. Push-button mode (start/manual)
6. Display 3. (Visual display of frequency, battery 12. Push-button mode (stop/reset)
level, fuel level or alarm code) 13. Push-button mode (automatic operation)
7. Push-button D3. (Selects the frequency, 14. Alarm codes showed in display 3.
battery level, fuel level or alarm code) E00 Correct operation E09 Over voltage
8. Display 4. (Visual display of working hours, E01 High water temp. E10 Under voltage
speed, water and oil temperature) E02 Low oil pressure E11 Asymmetry phases
9. Push-button D4. (to select hour run, speed, E03 Auxiliary input failure E12 Over current
water-level and temperature and oil pressure) E04 Bat. Alternator failure E13 Over frequency
E05 Start failure E14 Under frequency
E06 Engine failure E15 High bat. volts
E07 Low fuel level E16 Low bat. volts
E08 Fuel reserve E17 Emergency stop
3
6
2 154
7
11
9
8
14
13
12
10
Distributor:
Himoinsa USA, Inc. ▪ 16210 West 110th street, Lenexa, KS 66219 ▪ Tel: 913-495-5557 ▪ Fax: 913-495-5575 ▪ www.himoinsausa.com