L1
L2
L3
N
R
S
T
N
1 2R RR S SS T TT 3 N
RATED VOLTAGES
Test block unit 600V
Terminal Block 800VJumper plugs 600V CAT IV
RATED CONNECTION CAPACITY
Test block unit fi tted w ith ERB8-C6 cover 1,5...6 mm²
Maximum clampling capacity of terminal block 16 mm²
2x6 mm²
CURRENT RATINGSPerpendicular plug connections (T=-5°C..30°C) 32 A
Perpendicular plug connections (T=-5°C..60°C) 14 A
Longitudinal line of Terminal block 76 A
549265 END 10E-6I-4T-EPI Endesa549206 UF 10E-6I-4T-EPI Unión Fenosa
549205 ID 10E-6I-4T-EPI Iberdrola
549207 VSG 10E-6I-4T-EPI Viesgo
549208 HC 10E-6I-4T-EPI Hidrocantábrico
549244 REE 10E-6I-4T-EPI Red Eléctrica de EspañaShipment details:
Weight: 516 g Packaging : 1 Un. Shipping box: 20 Un.
Code Reference Specifications
Measuring category IV is for measurements made at the origin of
low voltage instalation.
Environment testing conditions: relative humidity 80%, sea level
elevation 2000 m, pollution degree 2.Current limits as per environment temperature:
- temperature -5 ºC ..+30 ºC current 32A,
- temperature -5 ºC ..+40 ºC current 24A,- temperature -5 ºC ..+60 ºC current 14A,
Class II DOUBLE INSULATION fully protected plugs
Uimp Impulse rated Voltage 8KV.
•
•
•
•
•
HAND HELD PLUGGING CONNECTIONS
INDIRECT MEASURING
KWH METER TEST BLOCK
with removable (jumper plugs) perpendicular disconnections
Terminal block RB8 (without partition) 1Terminal block RB8-R (with right partition) 3Terminal block RB8-RL (with dual partition) 6Jumper plug ECD600-2P 3EN 60715 TH35-7.5 rail (128mm) 1Multifunction end plate, stopper, panel fixing and seal device 2Marking strip 1Sealable and screwless transparent cover IP40 - IK08 1Self drilling fixing screws 2
Components
SPECIFICATIONS
ORDERING DATA
DVE
800V 16mm² 76AEN 60947-7-1
For protected Testing Plugs as per EN 61010-031
10E 6I-4T-EPI
7/26/2019 Morsettiera misura
http://slidepdf.com/reader/full/morsettiera-misura 2/4
L1
L2
L3
N
R
S
T
N
7 81 2 3 4 5 6 9 NL1 L2 L3
Terminal block RB8-SS P2 (with perpendicular disconnector) 3Terminal block RB8-P1 (with longitudinal and perpendicular disconnector) 3Terminal block RB8 (with longitudinal disconnector) 7EN 60715 TH35-7.5 rail (160mm) 1Multifunction end plate, stopper, panel fixing and seal device 2RMD Marking strip 1Sealable and screwless transparent cover IP40 - IK08 1Self drilling fixing screws 2
Components
RATED VOLTAGESTest block unit 600V
Terminal Block 800V
Jumper plugs 600V CAT IV
RATED CONNECTION CAPACITYTest block unit fi tted with ERB8-C6 cover 1,5...6 mm²
Maximum clampling capacity of terminal block 16 mm²
2x6 mm²
CURRENT RATINGS
Perpendicular plug connections (T=-5°C..30°C) 32 A
Perpendicular plug connections (T=-5°C..60°C) 14 ALongitudinal line of Terminal block 76 A
549291 UNB 13E 9I-4T EPI -
Shipping details:Weight: 632 g Packaging : 1 Un. Shipping box: 20 Un.
Code Reference Specifications
Measuring category IV is for measurements made at the origin of
low voltage instalation.Environment testing conditions: relative humidity 80%, sea level
elevation 2000 m, pollution degree 2.
Current limits as per environment temperature:
- temperature -5 ºC ..+30 ºC current 32A,- temperature -5 ºC ..+40 ºC current 24A,
- temperature -5 ºC ..+60 ºC current 14A,
Class II DOUBLE INSULATION fully protected plugs
Uimp Impulse rated Voltage 8KV.
•
•
•
•
•
HAND HELD PLUGGING CONNECTIONS
INDIRECT MEASURING
KWH METER TEST BLOCK
with buit in perpendicular disconnections
800V 16mm² 76A
EN 60947-7-1DVE
ORDERING DATA
SPECIFICATIONS
For protected Testing Plugs as per EN 61010-031
13E 9I-4T-EPI
7/26/2019 Morsettiera misura
http://slidepdf.com/reader/full/morsettiera-misura 3/4
IP 20 Protection
granted
Access to the plug sockets, to the longitudinal sliding link, to theRB8 terminal block fastening screws, all meet the fingerprooftest thereby affording an IP20 protection as per EN 60947-1
standard.
•
Fully protected
plugs used
The sockets of each element are so designed as to take protectedplugs fitted with fixed sleeve, as stipulated by the EN 61010-031standard. They afford the required insulation for the workingvoltage (higher than 33 V a.c.).The 10,5 mm. pitch of the RB8 terminal block also allows for
simultaneous insertion of standard Ø 4 mm. plugs.
•
•
Open circu it
indication
Longitudinal disconnection provides an easy visual red stripeindication when the sliding link is in the open position.Fitted with a rugged screw operated by means of insulated 5
mm. width screwdriver.
•
•
Recess for the
jumper plugs
The removable jumper plugs are housed on both side endbrackets and remain always protected by the sealableenveloping cover.Each end bracket can house either one 4-pole or two 2-pole
plugs.
•
•
Fastening and
sealing
Fixing of both test block unit to panel and end brackets to Dinrail is carried out by the same fastening screw. The sealedenveloping cover offers safe protection and prevents removal ofthe screw.The enveloping cover is fastened and sealed on both endbrackets by means of an ergonomic clip latch system. Sealingwire to be used, 1,5 mm. max.
•
•
Connections up to
16 mm²
Whenever transformers lie at some distance and the use of alarger cable section is therefore required, Unibloc test blockunits make the task of using 16 mm2 stranded wire cable mucheasier by means of a modeller for cable end terminals built inat both end brackets, which enables to set on the spot suchterminals with no extra tools.
•
Dual marking
system
Unibloc test block units use two marking possibilities :On the front, showing to the controller the circuit beingoperated.On both top and bottom sides, showing connection points to the
panel builder.
•
•
Unibloc test block units can be delivered in several differentconfigurations.Insulated colour coded plug sockets can be fitted for an easieridentification of circuits.Jumper comb bars are available when cross-connection +earthing necessary. A special RBT8 earthing terminal block asper EN 60947-7-2 standard is also available.
•
•
•
Blank spacer
This accessory to be used for filling in unused spacing wheneverless than 10 or 13 elements are required in both Unibloc 10E or13E test block units.
•
Cover options
Enveloping covers for Unibloc test block units are made of fireresistant transparent polycarbonate, offering an IP 40 degreeof protection and an IK08 impact strength as per EN 50102standard.Optional non-transparent covers can also be supplied.
Additionally, both types of covers can have one or both predrilledtop/bottom sides providing an easier connection of incomingcables atop the base plate.
•
•
Other accessories
7/26/2019 Morsettiera misura
http://slidepdf.com/reader/full/morsettiera-misura 4/4
L1
N
L1
N
A
L1
N
~ ~
L1
N
L1
N
A
V
L1
N
L1
N
A
L1
N
~
~
L1
N
L1
N
A
V
1 Normal working condition
2 Current and voltage testings
3 Full equipment disconnection
4 Auxiliary equipment connections
5 External power supply
Disconnection pro cedures
Longitudinal (on current line) sliding-link disconnector is operated by a5x1 screwdriver on a M4 screw at 1.5 Nm torque.
Sliding-link opens when slided to transformer’s side.
Perpendicular disconnectors are connected by inserting the safety jumper plugs on the unique side matching socket.
Disconnected Jumper plugs can be housed in the stopper’s receptacle.
All sockets can take insulated safety 4 mm Ø test plugs with a 10 mmtotal width.
•
•
•
•
•
1 Normal working condition
2 Current and voltage testings
3 Full equipment disconnection
4 Auxiliary equipment connections
5 External power supply
Disconnection pro cedures
Longitudinal (on current line) sliding-link disconnector is operated by a5x1 screwdriver on a M4 screw at 1.5 Nm torque.
Sliding-link opens when slided to transformer’s side.
Perpendicular disconnectors are connected by inserting the unloseablesafety jumper plugs on the unique side matching socket.
Jumper plugs are disconnected when in vertical position.
All sockets can take insulated safety 4 mm Ø test plugs with a 10 mm
total width.
•
•
•
•
•
OPERATION FUNCTIONS for removable jumper plugs (10E)
OPERATION FUNCTIONS for buit in jumper plugs (13E)
1 2 3 4 5
1 2 3 4 5
OVERALL SIZES
Type 10E 6I-4T-EPI Type 13E 9I-4T-EPI