Harmonic Calculator is a tool to
estimate the state of power quality
in your electrical system
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Total harmonic current can be
estimated based on the loads of the
system or power quality
measurement results can be used
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Required amount of active
harmonic filtering and reactive
power compensation capacity is
calculated automatically to meet
selected grid code requirements
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
The results are shown on the web
page and a more specific report is
sent to given e-mail address
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Merus™ Harmonic Calculator
Harmonic Calculator can be found on Merus Power web page:
https://www.meruspower.fi/harmoniccalcCurrently three language options are available: English, Spanish and Russian. Change language by using selections on the top of the page
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
https://www.meruspower.fi/harmoniccalc
-
Personal information
Start by filling in your personal data
PDF report will be sent to email address given
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Electrical system
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Electrical system
System voltage and frequency are needed for product selection
Provide line-to-line voltage at the point where Active Harmonic Filter would be installed
Please contact [email protected] for solutions at higher voltage levels
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
mailto:[email protected]
-
Electrical system, supplied from a grid
Upstream short circuit fault level and transformer parameters are needed for voltage harmonics calculations
Short circuit fault level (SSC) can be calculated from fault current (ISC) and upstream voltage (U) using formula
SSC = √3 * U * ISC
If the exact value of the short circuit level is not known, the following values may be used
Stiff medium voltage grid: 400 – 1800 MVA
Weak medium voltage grid: 40 – 150 MVA
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
3W/4W connection
Systems where neutral wire exists can be selected as 4W systems
If system does not have the neutral wire, 3W connection should be selected
4W connection is needed only when neutral wire currents (harmonics 3rd, 9th, 15th …) need to be compensated
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Current reference
TDD (Total Demand Distortion) relates harmonic content to its reference value (nominal or full load, for example).
If current reference is left blank, base value is calculated automatically
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Compensation level
Calculated compensation is based on selected grid code standard
If for example IEEE-519 standard is selected, compensation capacity is calculated to meet the limits of this standard
Limits for individual harmonic component can be seen from the PDF report
By selecting “Custom”, freely chosen voltage THD and current TDD limits can be chosen
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Loads
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Reactive power compensation
Merus Active Harmonic Filters can dynamically compensate load reactive power while compensating harmonics
Select the limit for Displacement Power Factor (DPF, cosphi) or for remaining reactive power. Priority of compensation determines if excess capacity will be used for harmonics or reactive power
Please contact [email protected] for hybrid solutions, where Active Harmonic Filter controls capacitor bank steps to achieve cost-efficient dynamic reactive power compensation
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
mailto:[email protected]
-
Load harmonics, power quality measurement
When power quality measurement has been made and load current harmonics are known, calculation will be based on these values
1st harmonic is the fundamental current
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Load harmonics, example loads
When load current harmonics are not known, calculation can be based on example loads
Load current harmonics will be calculated based on typical harmonic spectrum of each load type
“Linear load” means loads that do not cause harmonics. For example direct-on-line motors are linear loads.
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Results
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
Result page
Results are shown after pressing “Submit”- button. More detailed report will be sent to given email address
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-
PDF report
PDF report includes
• Description of the selected standard
• Information on harmonics and effect of bad power quality
• Power quality analysis before and after compensation
• Proposed solution
The information is this document and any copyright attached to it, is the sole property of Merus Power Dynamics Oy. Any unauthorized reproduction or other utilization in part, or as whole, without a written permission from Merus Power is strictly prohibited.
-