226 | Manual Call Points | LSN Manual Call Points
FMC‑420RW Single ActionCall Points LSN improved
Features
▶ Alarm triggering by pressing the black marking orbreaking the glass pane
▶ Protection against injury through foil-labeled glasspane
▶ LED display for triggered alarm or inspectionevaluation
▶ Individual call point identification
▶ Call point query routines with evaluation and multipletransmission
▶ Maintains LSN loop functions in the event of wireinterruption or short-circuit thanks to two integratedisolators
FMC‑420RW Single Action Call Points are used for manualalarm triggering and can be employed in both the LocalSecurityNetwork (LSN) and the LSN improved version.
Functions
Single action call points with glass pane:
1
2
3
Pressing the black marking (1) breaks the glass pane (3),which triggers the alarm and causes the LED display (2) toflash.
Single action call points can be reset with the test key andby replacing the glass pane (3). The LED display (2) goesout.
Resettable single action call points:
1
2
4
Pressing the black marking (1) triggers the alarm. The alarmstatus is displayed by the red window (4) and the flashingLED display (2).
Single action call points can be reset using the test key. TheLED display (2) goes out.
Individual call point identificationNeither single action call points with glass pane norresettable single action call points are reset on the firepanel.
Individual call point identification with display of the callpoint address on the fire panel ensures the quick locationof the triggered call point.
Certifications and Approvals
Region Certification
Europe CPD 0786-CPD-20333 FMC-420RW
Germany VdS G 207087 FMC-420RW
Installation/Configuration Notes
• Manual call points must be mounted visibly alongescape and rescue routes (e.g. exits, passageways,stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm (55 in. ±8in.), measured from the middle of the manual call pointto the floor, must be maintained.
• Manual call points must be sufficiently lit with daylightor another light source (including emergency lighting ifpresent).
• The maximum number of LSN elements that can beconnected depends on their current consumption fromthe LSN data line. The limit values should be taken fromthe product information supplied with the fire panelused.
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | LSN Manual Call Points | 227
• Standards, guidelines and planning recommendationsregarding the installation location etc. should also betaken into consideration.
• The regulations of the local fire services must beobserved.
Parts Included
Quanti-ty
Components
1 FMC-420RW-GSGRD Manual Call Point with Glass Pane, Surface-mounted, Red
1 FMC-420RW-GSRRD Manual Call Point Resettable, Surface-mounted, Red
1 FMC-420RW-GFGRD Manual Call Point with Glass Pane, Flush-mounted, Red
1 FMC-420RW-GFRRD Manual Call Point Resettable, Flush-mount-ed, Red
1 FMC-420RW-GSGYE Manual Call Point with Glass Pane, Surface-mounted, Yellow
1 FMC-420RW-GSRYE Manual Call Point Resettable, Surface-mounted, Yellow
1 FMC-420RW-GSGBU Manual Call Point with Glass Pane, Surface-mounted, Blue
1 FMC-420RW-GSRBU Manual Call Point Resettable, Surface-mounted, Blue
Note The FMC‑KEY‑RW Test Key is not included inthe scope of delivery and must be orderedseparately.
Technical Specifications
Electrical
Operating voltage 15 VDC to 33 VDC
Current consumption 0.4 mA
Mechanical components
Dimensions (H x W x D)
• FMC‑420RW‑GFGRD,FMC‑420RW‑GFRRD
107 mm x 107 mm x 38.5 mm (4.2in. x 4.2 in. x 1.5 in.)
• FMC‑420RW‑GSGRD,FMC‑420RW‑GSGBU,FMC‑420RW‑GSGYE
87 mm x 87 mm x 56 mm (3.4 in. x3.4 in. x 2.2 in.)
• FMC‑420RW‑GSRRD,FMC‑420RW‑GSRBU,FMC‑420RW‑GSRYE
87 mm x 87 mm x 56 mm (3.4 in. x3.4 in. x 2.2 in.)
Housing material Plastic, ASA
Colors
• Red RAL 3001
• Blue RAL 5005
• Yellow RAL 1003
Environmental conditions
Protection category according toEN 60529
IP 52
Permissible operating temperature -25 °C to +70 °C
Ordering Information
FMC‑420RW‑GSGRD Manual Call Point withGlass Pane, RedSurface-mounted
FMC-420RW-GSGRD
FMC‑420RW‑GSRRD Manual Call PointResettable, RedSurface-mounted
FMC-420RW-GSRRD
FMC‑420RW‑GFGRD Manual Call Point withGlass Pane, Flush-mounted, RedFlush-mounted
FMC-420RW-GFGRD
FMC‑420RW‑GFRRD Manual Call PointResettable, Flush-mounted, RedFlush-mounted
FMC-420RW-GFRRD
FMC‑420RW‑GSGYE Manual Call Point withGlass Pane, YellowSurface-mounted
FMC-420RW-GSGYE
FMC‑420RW‑GSRYE Manual Call PointResettable, YellowSurface-mounted
FMC-420RW-GSRYE
FMC‑420RW‑GSGBU Manual Call Point withGlass Pane, BlueSurface-mounted
FMC-420RW-GSGBU
FMC‑420RW‑GSRBU Manual Call PointResettable, BlueSurface-mounted
FMC-420RW-GSRBU
Accessories
FMC‑SPACER‑RWRD Spacer, RedFor the flush-mounted variant of the RW callpoints. Its use increases the storage room forthe cables.1 unit = 5 spacers
FMC-SPACER-RWRD
FMC‑SPGL‑RW Spare GlassesSpare glasses for all RW call points.1 unit = 5 spare glasses
FMC-SPGL-RW
FMC‑SIGN‑RW Out of Order SignUsed instead of the glass pane when a call pointis not ready for use.1 unit = 5 signs
FMC-SIGN-RW
FMC‑KEY‑RW Test KeyThe key can open, check, and reset manual callpoints.1 unit = 1 key
FMC-KEY-RW
FMC‑FLAP‑RW Clear Hinged FlapTo protect against accidental triggering; withseal.1 unit = 5 flaps
FMC-FLAP-RW
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
228 | Manual Call Points | LSN Manual Call Points
FMC-420RW Single Action Call Points LSN improved version
FMC-420RW-GSGRD FMC-420RW-GSRRD FMC-420RW-GFGRD FMC-420RW-GFRRD
Design with glass pane resettable with glass pane resettable
Range of use indoor indoor indoor indoor
Mounting surface-mounted surface-mounted flush-mounted flush-mounted
Operating voltage 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC
Current consumption 0.4 mA 0.4 mA 0.4 mA 0.4 mA
Protection category IP 52 IP 52 IP 52 IP 52
Permissible operating tem-perature
-25°C . . . +70°C -25°C . . . +70°C -25°C . . . +70°C -25°C . . . +70°C
Color red, RAL 3001 red, RAL 3001 red, RAL 3001 red, RAL 3001
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | LSN Manual Call Points | 229
FMC-420RW Single Action Call Points LSN improved version
FMC-420RW-GSGYE FMC-420RW-GSRYE FMC-420RW-GSGBU FMC-420RW-GSRBU
Design with glass pane resettable with glass pane resettable
Range of use indoor indoor indoor indoor
Mounting surface-mounted surface-mounted surface-mounted surface-mounted
Operating voltage 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC
Current consumption 0.4 mA 0.4 mA 0.4 mA 0.4 mA
Protection category IP 52 IP 52 IP 52 IP 52
Permissible operating tem-perature
-25°C . . . +70°C -25°C . . . +70°C -25°C . . . +70°C -25°C . . . +70°C
Color yellow, RAL 1003 yellow, RAL 1003 blue, RAL 5005 blue, RAL 5005
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
230 | Manual Call Points | LSN Manual Call Points
FMC‑210‑DM Manual CallPoints
Features
▶ Adjustment of the Manual Call Point after alarmtriggering
▶ Automatic or manual detector addressing via rotaryswitch possible
▶ Indicator LED for alarm or for inspection evaluation
▶ Call point query routines with evaluation and multipletransmission
▶ Individual call point identification
▶ Maintains LSN loop functions in the event of wireinterruption or short-circuit thanks to two integratedisolators
The FMC‑210‑DM Manual Call Points are used to trigger thealarm manually, and are deployed in the LocalSecurityNetwork LSN and LSN improved. Form H ManualCall Points are designed for outdoor deployment, form GManual Call Points are designed for indoor deployment.
Functions
1 1
2
23
3
4
5
In the event of an alarm, the glass pane (2) is broken first,then the manual call point (3) is pressed hard. This activatesthe microswitch for alarm triggering and the indicator LED(4) blinks. A mechanism holds the pressed call point down.
The manual call point can be reset with the reset lever (5)or by closing the door of the manual call point (1). Theindicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Individual call point identification with display of the callpoint address on the fire panel ensures the quick locationof the triggered call point.
VariantsThe designs of the manual call points for outdoor and indooruse are identical. The manual call points for indoor use(form G) are available in red, blue, and yellow; the manualcall points for outdoor use (form H) are available in red andblue.
Form H manual call points are equipped with an especiallyresistant PC board layered with parylene.
Improved LSN featuresThe manual call points offer all the features of the improvedLSN technology:
• Flexible network structures, including "T-tapping"without additional elements
• Up to 254 LSN improved elements per loop or stub line• Automatic or manual detector addressing selectable via
rotary switch, in each case with or without auto-detection
• Power supply for connected elements via LSN bus up to300 mA
• Shielded and unshielded cables can be used• Cable length up to 1000 m• Downwards compatibility to existing LSN systems and
control panels.
Certifications and Approvals
Region Certification
Europe CE FMC-210-DM-G-B / -H-B / -SM-G-B
FMC-210-DM-G-R / -H-R / -SM-G-R
FMC-210-DM-G-Y / EST-G-B
CPD 0786-CPD-20293 FMC-210-DM-G/H-R
0786-CPD-20244 FMC-210-DM-G-Y
0786-CPD-20245 FMC-210-EST-G-B
Germany VdS G 206100 FMC-210-EST-G-B
G 206098 FMC-210-DM-G-R /-G-R-A/ -H-R
G 206099 FMC-210-DM-G-Y
Poland CNBOP 0082/2008 FMC-210 DM-G-R, FMC-210DM-H-R
CzechRepublic
TZÚS 080_12987 FMC-210
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | LSN Manual Call Points | 231
Region Certification
Russia GOST POCC DE.C313.B06297
Slovakia EVPÚ SK08-ZSV-0071 FMC-210-DM,FMC-210-EST
Type Number Complies with
FMC‑210‑DM‑G‑R EN 54-11:2001/A1:2005, EN 54-17:2005
FMC‑210‑DM‑H‑R EN 54-11:2001/A1:2005, EN 54-17:2005
FMC‑210‑DM‑G‑Y EN 12094-3:2003, EN 54-17:2005
FMC‑210‑EST‑G‑B EN 12094-3:2003, EN 54-17:2005
Installation/Configuration Notes
• Manual call points must be mounted visibly alongescape and rescue routes (e.g. exits, passageways,stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm, measuredfrom the middle of the manual call point to the floor,must be maintained.
• Manual call points must be adequately illuminated bysunlight or another light source (including emergencylighting if present).
• The maximum number of LSN elements that may beconnected depends on their current consumption fromthe LSN data line. The limit values should be taken fromthe product information supplied with the fire panelused.
• Additional norms, guidelines, and planningrecommendations with respect to installation location,etc. must be taken into account (see fire detectormanual).
• The regulations of the local fire services must beobserved.
Installation• The cable duct can be surface-mounted or flush-
mounted.
• Installation in fire hose cabinets is possible in threeways:
135 mm
140 mm
2,5 mm
2 mm
139 m
m
1
2
3
149,5 mm
12,5 mm
Pos. Description
1 Installation depth version 1: ca. 40 mm
2 Installation depth version 2: 14 mm
3 Installation depth version 3: min. 30 mm
Parts Included
Type Number Component
FMC‑210‑DM‑G‑RForm G, Red
Manual Call Point for indoor use, indirect triggering(type B), housing color red
FMC‑210‑DM‑H‑RForm H, Red
Manual Call Point for outdoor use, indirect triggering(type B) , housing color red
FMC‑210‑DM‑G‑BForm G, Blue
Manual Call Point for indoor use, indirect triggering(type B), housing color blue
FMC‑210‑DM‑H‑BForm H, Blue
Manual Call Point for outdoor use, indirect triggering(type B), housing color blue
FMC‑210‑DM‑G‑YForm G, Yellow
Manual Call Point for indoor use, indirect triggering(type B), housing color yellow
FMC‑210‑EST‑G‑BForm G, Blue
Electronic Stop Device for indoor use, indirect trig-gering (type B), housing color blue
Note The key must be ordered separately.
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
232 | Manual Call Points | LSN Manual Call Points
Technical Specifications
Electrical
Operating voltage 24 V DC (15 V DC . . . 33 V DC)
Current consumption 0.4 mA
Mechanics
Dimensions (W x H x D) 135 x 135 x 40 mm /5.31 x 5.31 x 1.5 in.
Housing material Plastic, ASA
Colors Red, RAL 3001Blue, RAL 5005Yellow, RAL 1003
Weight Approx. 235 g
Environmental Considerations
Protection class as per EN 60529
• Form H (outdoor use) IP 54
• Form G (indoor use) IP 52
Norm
• FMC‑210‑DM‑G‑R,FMC‑210‑DM‑H‑R
EN 54-11
• FMC‑210‑DM‑G‑Y,FMC‑210‑EST‑G‑B
EN 12094-3
Permissible operating temperature
• Form H (outdoor use) -25 °C . . . +70 °C /-13 °F … 158 °F
• Form G (indoor use) -10 °C . . . +55 °C /14 °F … 131 °F
Ordering Information
FMC‑210‑DM‑G‑R Form G, RedManual call point for indoor use, indirect trig-gering (type B)
FMC-210-DM-G-R
FMC‑210‑DM‑H‑R Form H, RedManual call point for outdoor use, indirect trig-gering (type B)
FMC-210-DM-H-R
FMC‑210‑DM‑G‑B Form G, BlueManual call point for indoor use, indirect trig-gering (type B)
FMC-210-DM-G-B
FMC‑210‑DM‑H‑B Form H, BlueManual call point for outdoor use, indirect trig-gering (type B)
FMC-210-DM-H-B
FMC‑210‑DM‑G‑Y Form G, YellowManual call point for indoor use, indirect trig-gering (type B)
FMC-210-DM-G-Y
FMC‑210‑EST‑G‑B Form G, BlueElectronic stop device for indoor use, indirecttriggering (type B)
FMC-210-EST-G-B
Ordering Information
Accessories
FMX‑FSO‑LSN Punched, Self-adhesive FoilSets (Blank)For the labeling field of manual call points ofthe Series FMC‑210.1 unit = 10 sheets
FMX-FSO-LSN
FMC‑FST‑DE Printed Labeling Foils for theUpper Label FieldFor yellow and blue manual call points of SeriesFMC‑120 and FMC‑210, 1 unit = 5 sheets
FMC-FST-DE
FMC‑SPGL‑DEIL Spare GlassesFor manual call points of Series DM, DKM, SKM,FMC‑120 and FMC‑210.1 unit = 5 spare glasses
FMC-SPGL-DEIL
Sign with label "Nicht in Betrieb"Metal sign for fire detectors form G or H
FMM-SIGN
Key for Fire Detectors Types G and Hmade of red plastic (ASA)
FMM-KEY-Form G/H
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | LSN Manual Call Points | 233
FMC-210-DM Single Action Call Points
FMC-210-DM-G-R FMC-210-DM-H-R FMC-210-DM-G-B
Range of use indoor outdoor indoor
Mounting surface-mounted/flush-mounted
surface-mounted/flush-mounted
surface-mounted/flush-mounted
Operating voltage 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC
Current consumption 0.4 mA 0.4 mA 0.4 mA
Protection category IP 52 IP 54 IP 52
Permissible operating tempera-ture
-10°C . . . +55°C -25°C . . . +70°C -10°C . . . +55°C
Color red, RAL 3001 red, RAL 3001 blue, RAL 5005
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
234 | Manual Call Points | LSN Manual Call Points
FMC-210-DM Single Action Call Points
FMC-210-DM-H-B FMC-210-DM-G-Y FMC-210-EST-G-B
Range of use outdoor indoor indoor
Mounting surface-mounted/flush-mounted
surface-mounted/flush-mounted
surface-mounted/flush-mounted
Operating voltage 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC 15 V DC . . . 33 V DC
Current consumption 0.4 mA 0.4 mA 0.4 mA
Protection category IP 54 IP 52 IP 52
Permissible operating tempera-ture
-25°C . . . +70°C -10°C . . . +55°C -10°C . . . +55°C
Color blue, RAL 5005 yellow, RAL 1003 blue, RAL 5005
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | LSN Manual Call Points | 235
FMC‑210‑SM Single ActionCall Points
Features
▶ Alarm triggering by breaking of the glass pane
▶ Automatic or manual detector addressing via rotaryswitch possible
▶ Indicator LED for alarm or for inspection evaluation
▶ Call point query routines with evaluation and multipletransmission
▶ Individual call point identification
▶ Maintains LSN loop functions in the event of wireinterruption or short-circuit thanks to two integratedisolators
The FMC‑210‑SM Single Action Call Points are used totrigger the alarm manually, and can be used in the LocalSecurityNetwork LSN and LSN improved. The FMC‑210‑SMSingle Action Call Points are designed for indoordeployment.
Functions
1 1
2
23
3
4
5
With single action call points, the alarm is triggered whenthe glass plate (2) is broken and the button (3) springs up.
This activates the microswitch for alarm triggering and theindicator LED (4) blinks.
The call point (3) can be reset after inserting a new glasspane (2) and closing the door of the single action call point(1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Individual call point identification with display of the callpoint address on the fire panel ensures the quick locationof the triggered call point.
Certifications and Approvals
FMC‑210‑SM‑G‑R applies to
• EN 54‑11:2001/A1:2005• EN 54‑17:2005
Region Certification
Europe CPD 0786-CPD-20316 FMC-210-SM-G-R
Germany VdS G 207008 FMC-210-SM-G-R
Installation/Configuration Notes
• Manual call points must be mounted visibly alongescape and rescue routes (e. g. exits, passageways,stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm, measuredfrom the middle of the manual call point to the floor,must be maintained.
• Manual call points must be adequately illuminated bysunlight or another light source (including emergencylighting if present).
• The maximum number of LSN elements that may beconnected depends on their current consumption fromthe LSN data line. The limit values should be taken fromthe product information supplied with the fire panelused.
• Further standards, guidelines and planningrecommendations regarding the installation locationetc., should also be taken into consideration (see FireDetection manual).
• The regulations of the local fire services must beobserved.
Installation notes in accordance with VdS/VDE• The distance between manual call points should not be
more than 100 m according to DIN 14675 or 80 maccording to VdS.
• In high risk areas, manual call points should be installedat a distance of max. 40 m (VDE 0833 Part 2,Point 7.2.6).
Installation• The cable duct can be surface-mounted or flush-
mounted.
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
236 | Manual Call Points | LSN Manual Call Points
• Installation in fire hose cabinets is possible in threeways:
135 mm
140 mm
2,5 mm
2 mm
139 m
m
1
2
3
149,5 mm
12,5 mm
Pos. Description
1 Installation depth version 1: ca. 40 mm
2 Installation depth version 2: 14 mm
3 Installation depth version 3: min. 30 mm
Parts Included
TypeNumber. Component
FMC‑210‑SM‑G‑BForm G, Blue
Single Action Call Point for indoor use, direct trig-gering (type A)
FMC‑210‑SM‑G‑RForm G, Red
Single Action Call Point for indoor use, direct trig-gering (type A
Note The key must be ordered separately.
Technical Specifications
Electrical
Operating voltage 15 V DC . . . 33 V DC
Current consumption 0.4 mA
Mechanics
Dimensions (H x W x D) 135 x 135 x 40 mm
Housing material Plastic, ASA
Colors
• FMC-210-SM-G-R Red, RAL 3001
• FMC-210-SM-G-B Blue, RAL 5005
Weight Approx. 235 g
Environmental Considerations
Protection class as per EN 60529 IP 52
Permissible operating temperature -10 °C. . . +55 °
Ordering Information
FMC‑210‑SM‑G‑R Form G, RedSingle Action Call Point for indoor use, directtriggering (type A)
FMC-210-SM-G-R
FMC‑210‑SM‑G‑B Form G, BlueSingle Action Call Point for indoor use, directtriggering (type A)
FMC-210-SM-G-B
Accessories
FMX‑FSO‑LSN Punched, Self-adhesive FoilSets (Blank)For the labeling field of manual call points ofthe Series FMC‑210.1 unit = 10 sheets
FMX-FSO-LSN
FMC‑FST‑DE Printed Labeling Foils for theUpper Label FieldFor yellow and blue manual call points of SeriesFMC‑120 and FMC‑210, 1 unit = 5 sheets
FMC-FST-DE
FMC‑SPGL‑DEIL Spare GlassesFor manual call points of Series DM, DKM, SKM,FMC‑120 and FMC‑210.1 unit = 5 spare glasses
FMC-SPGL-DEIL
Key for Fire Detectors Types G and Hmade of red plastic (ASA)
FMM-KEY-Form G/H
Sign with label "Nicht in Betrieb"Metal sign for fire detectors form G or H
FMM-SIGN
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Conventional Manual Call Points | 237
FMC‑300RW Single ActionCall Points
Features
▶ Alarm triggering by pressing the black marking orbreaking the glass pane
▶ Protection against injury through foil-labeled glasspane
▶ LED display for triggered alarm or inspectionevaluation
FMC‑300RW Single Action Call Points are used for manualalarm triggering and are employed in conventionaltechnology.
Functions
Single action call points with glass pane:
1
2
3
Pressing the black marking (1) breaks the glass pane (3),which triggers the alarm and causes the LED display (2) toflash.
Single action call points can be reset with the test key andby replacing the glass pane (3). The LED display (2) goesout.
Resettable single action call points:
1
2
4
Pressing the black marking (1) triggers the alarm. The alarmstatus is displayed by the red window (4) and the flashingLED display (2).
Single action call points can be reset using the test key. TheLED display (2) goes out.
Certifications and Approvals
Applies to EN 54‑11:2001/A1:2005
Region Certification
Europe CPD 0786-CPD-20332 FMC-300RW
Germany VdS G 207086 FMC-300 RW
Installation/Configuration Notes
• Manual call points must be mounted visibly alongescape and rescue routes (e.g. exits, passageways,stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm (55 in. ±8in.), measured from the middle of the manual call pointto the floor, must be maintained.
• Manual call points must be sufficiently lit with daylightor another light source (including emergency lighting ifpresent).
• The maximum number of LSN elements that can beconnected depends on their current consumption fromthe LSN data line. The limit values should be taken fromthe product information supplied with the fire panelused.
• Standards, guidelines and planning recommendationsregarding the installation location etc. should also betaken into consideration.
• The regulations of the local fire services must beobserved.
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
238 | Manual Call Points | Conventional Manual Call Points
Parts Included
Quanti-ty
Components
1 FMC-300RW-GSGBU Manual Call Point with Glass Pane, Blue
1 FMC-300RW-GSRBU Manual Call Point Resettable, Blue
1 FMC-300RW-GSGRD Manual Call Point with Glass Pane, Red
1 FMC-300RW-GSRRD Manual Call Point Resettable, Red
1 FMC-300RW-GSGYE Manual Call Point with Glass Pane, Yellow
1 FMC-300RW-GSRYE Manual Call Point Resettable, Yellow
Note The FMC‑KEY‑RW Test Key is not included inthe scope of delivery and must be orderedseparately.
Technical Specifications
Electrical
Operating voltage 20 VDC(8.5 VDC to 30 VDC)
Current consumption specified by the respective securitysystem
Alarm resistor 820 Ω +/- 10%(8.5 VDC to 30 VDC)
Mechanical components
Dimensions (H x W x D) 87 mm x 87 mm x 56 mm (3.4 in. x3.4 in. x 2.2 in.)
Housing material Plastic, ASA
Colors
• Red RAL 3001
• Blue RAL 5005
• Yellow RAL 1003
Environmental conditions
Protection category according to EN60529
IP 52
Permissible operating temperature -25 °C to +70 °C
Ordering Information
FMC‑300RW‑GSGBU Manual Call Point withGlass Pane, Blue
FMC-300RW-GSGBU
FMC‑300RW‑GSRBU Manual Call PointResettable, Blue
FMC-300RW-GSRBU
FMC‑300RW‑GSGRD Manual Call Point withGlass Pane, Red
FMC-300RW-GSGRD
FMC‑300RW‑GSRRD Manual Call PointResettable, Red
FMC-300RW-GSRRD
FMC‑300RW‑GSGYE Manual Call Point withGlass Pane, Yellow
FMC-300RW-GSGYE
FMC‑300RW‑GSRYE Manual Call PointResettable, Yellow
FMC-300RW-GSRYE
Ordering Information
Accessories
FMC‑SPACER‑RWRD Spacer, RedFor the flush-mounted variant of the RW callpoints. Its use increases the storage room forthe cables.1 unit = 5 spacers
FMC-SPACER-RWRD
FMC‑SPGL‑RW Spare GlassesSpare glasses for all RW call points.1 unit = 5 spare glasses
FMC-SPGL-RW
FMC‑SIGN‑RW Out of Order SignUsed instead of the glass pane when a call pointis not ready for use.1 unit = 5 signs
FMC-SIGN-RW
FMC‑KEY‑RW Test KeyThe key can open, check, and reset manual callpoints.1 unit = 1 key
FMC-KEY-RW
FMC‑FLAP‑RW Clear Hinged FlapTo protect against accidental triggering; withseal.1 unit = 5 flaps
FMC-FLAP-RW
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Conventional Manual Call Points | 239
FMC-300RW Single Action Call Points
FMC-300RW-GSGBU FMC-300RW-GSRBU FMC-300RW-GSGRD
Design with glass pane resettable with glass pane
Range of use indoor indoor indoor
Mounting surface-mounted surface-mounted surface-mounted
Operating voltage 8.5 V DC . . . 30 V DC 8.5 V DC . . . 30 V DC 8.5 V DC . . . 30 V DC
Current consumption specified by the respective se-curity system
specified by the respective se-curity system
specified by the respective se-curity system
Protection category IP 52 IP 52 IP 52
Permissible operating tempera-ture
-25°C . . . +70°C -25°C . . . +70°C -25°C . . . +70°C
Color blue, RAL 5005 blue, RAL 5005 red, RAL 3001
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
240 | Manual Call Points | Conventional Manual Call Points
FMC-300RW Single Action Call Points
FMC-300RW-GSRRD FMC-300RW-GSGYE FMC-300RW-GSRYE
Design resettable with glass pane resettable
Range of use indoor indoor indoor
Mounting surface-mounted surface-mounted surface-mounted
Operating voltage 8.5 V DC . . . 30 V DC 8.5 V DC . . . 30 V DC 8.5 V DC . . . 30 V DC
Current consumption specified by the respective se-curity system
specified by the respective se-curity system
specified by the respective se-curity system
Protection category IP 52 IP 52 IP 52
Permissible operating tempera-ture
-25°C . . . +70°C -25°C . . . +70°C -25°C . . . +70°C
Color red, RAL 3001 yellow, RAL 1003 yellow, RAL 1003
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Conventional Manual Call Points | 241
FMC‑120‑DKM Manual CallPoints
Features
▶ Adjustment of the manual call point after alarmtriggering
▶ Indicator LED for alarm or for inspection evaluation
▶ Second contact with connections for panel control
▶ Variants for indoor and outdoor use
The FMC-120-DKM Manual Call Points handle manual alarmtriggering and are used with conventional technology.
Functions
1 1
2
23
3
4
5
In the event of an alarm, the glass pane (2) is broken first,then the manual call point (3) is pressed hard.
This activates the micro switch for alarm triggering and theindicator LED (4) blinks.
A locking mechanism holds the pressed manual call point.
The manual call point can be reset with the reset lever (5).The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
VariantsThe design of the manual call points for indoor (form G) andoutdoor use (form H) are identical. Three color variants,red, blue, and yellow are available.
Detectors for outdoor use (form H) have a cover equippedwith a seal.
Certifications and Approvals
Region Certification
Europe CE FMC-120-EST-G-B / -DKM-G-Y
FMC-120-DKM-G-R / -H-R
FMC-120-DKM-G-B
CPD 0786-CPD-20294 FMC-120-DKM-G/H-R
0786-CPD-20231 FMC-120-DKM-G-Y
0786-CPD-20232 FMC-120-EST-G-B/-H-HE
Germany VdS G 298061 FMC-120-DKM-G-R / -H-R
G 206079 FMC-120-DKM-G-Y
G 206080 FMC-120-EST-G-B
PTB 01 ATEX 2163 X OTC/OC 310/410, OT/O/T 300/400, DKM/SKM 120, DM/SM210, MPA
01 ATEX 2163 X FMC-120-DKM
Russia GOST POCC DE.C313.B06297
Type Number Complies with
FMC‑120‑DKM‑G‑R EN54-11:2001/A1:2005
FMC‑120‑DKM‑H‑R EN54-11:2001/A1:2005
FMC‑120‑DKM‑G‑Y EN12094-3:2003
FMC‑120‑EST‑G‑B EN12094-3:2003
Installation/Configuration Notes
• Manual call points have to be mounted visibly alongescape and rescue routes (e.g. exits, passageways,stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm, measuredfrom the middle of the manual call point to the floor,must be maintained.
• Manual call points must be illuminated sufficiently withdaylight or another light source (including emergencylighting, if present).
• Max. one test detector may be used for primary linestogether with automatic detectors. The test detector isconnected at the end of the primary line.
• Further standards, guidelines and planningrecommendations regarding the installation locationetc., should also be taken into consideration (see FireDetection manual).
• Regulations of local fire departments must be observed.
Installation• Cables can be inserted surface-mounted or flush-
mounted.
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
242 | Manual Call Points | Conventional Manual Call Points
ø 3,4
• Installation in fire hose cabinets is possible in threeways:
135°
140°
2,5
2
139
1
2
3
10
147
Pos. Description
1 Installation depth version 1: 36 mm
2 Installation depth version 2: 14 mm
3 Installation depth version 3: approx. 30 mm
Technical Specifications
Electrical
Operating voltage 24 V DC (16.2 V DC . . . 30 V DC)
Current consumption Specified by the respective securitysystem
Mechanics
Dimensions (W x H x D) 135 x 135 x 37 mm /5.31 x 5.31 x 1.4 in.
Housing material Plastic (ASA)
Colors Red, RAL 3001Blue, RAL 5005Yellow, RAL 1003
Weight Approx. 224 g
Environmental conditions
Protection class as per EN 60529
Form G (indoor area) IP 52
Form H (outdoor area) IP 54
Norm
FMC-120-DKM-G-R,FMC‑120‑DKM‑H‑R
EN 54-11
FMC-120-DKM-G-Y,FMC‑120‑EST‑G‑B
EN 12094-3
Permissible operating temperature
Form G (indoor area) -10 °C . . . +55 °C /14 °F … 131 °F
Form H (outdoor area) -25 °C . . . +70 °C /-13 °F … 158 °F
Ordering Information
FMC‑120‑DKM‑G‑R Form G, RedConventional Manual Call Point for indoor use,indirect triggering (type B)
FMC-120-DKM-G-R
FMC‑120‑DKM‑H‑R Form H, RedConventional Manual Call Point for outdooruse, indirect triggering (type B)
FMC-120-DKM-H-R
FMC‑120‑DKM‑G‑B Form G, BlueConventional Manual Call Point for indoor use,indirect triggering (type B)
FMC-120-DKM-G-B
FMC‑120‑DKM‑H‑B Form H, BlueConventional Manual Call Point for outdooruse, indirect triggering (type B)
FMC-120-DKM-H-B
FMC‑120‑DKM‑G‑Y Form G, YellowConventional Manual Call Point for indoor use,indirect triggering (type B)
FMC-120-DKM-G-Y
FMC‑120‑EST‑G‑B Form G, BlueConventional Electronic Stop Device for indooruse, indirect triggering (type B)
FMC-120-EST-G-B
Accessories
FMX‑FSO‑GLT Punched, Self-adhesive FoilSets (Blank)For the labeling field of conventional manualcall points of the Series FMC‑120,1 unit = 10 sheets
FMX-FSO-GLT
FMC‑FST‑DE Printed Labeling Foils for theUpper Label FieldFor yellow and blue manual call points of SeriesFMC‑120 and FMC‑210, 1 unit = 5 sheets
FMC-FST-DE
FMC‑SPGL‑DEIL Spare GlassesFor manual call points of Series DM, DKM, SKM,FMC‑120 and FMC‑210.1 unit = 5 spare glasses
FMC-SPGL-DEIL
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Conventional Manual Call Points | 243
Ordering Information
Sign with label "Nicht in Betrieb"Metal sign for fire detectors form G or H
FMM-SIGN
Key for Fire Detectors Types G and Hmade of red plastic (ASA)
FMM-KEY-Form G/H
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
244 | Manual Call Points | Conventional Manual Call Points
FMC-120-DKM Single Action Call Points
FMC-120-DKM-G-R FMC-120-DKM-H-R FMC-120-DKM-G-B
Range of use indoor outdoor indoor
Mounting surface-mounted/flush-mounted
surface-mounted/flush-mounted
surface-mounted/flush-mounted
Operating voltage 16.2 V DC . . . 30 V DC 16.2 V DC . . . 30 V DC 16.2 V DC . . . 30 V DC
Current consumption specified by the respective se-curity system
specified by the respective se-curity system
specified by the respective se-curity system
Protection category IP 52 IP 54 IP 52
Permissible operating tempera-ture
-10°C . . . +55°C -25°C . . . +70°C -10°C . . . +55°C
Color red, RAL 3001 red, RAL 3001 blue, RAL 5005
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Conventional Manual Call Points | 245
FMC-120-DKM Single Action Call Points
FMC-120-DKM-H-B FMC-120-DKM-G-Y FMC-120-EST-G-B
Range of use outdoor indoor indoor
Mounting surface-mounted/flush-mounted
surface-mounted/flush-mounted
surface-mounted/flush-mounted
Operating voltage 16.2 V DC . . . 30 V DC 16.2 V DC . . . 30 V DC 16.2 V DC . . . 30 V DC
Current consumption specified by the respective se-curity system
specified by the respective se-curity system
specified by the respective se-curity system
Protection category IP 54 IP 52 IP 52
Permissible operating tempera-ture
-25°C . . . +70°C -10°C . . . +55°C -10°C . . . +55°C
Color blue, RAL 5005 yellow, RAL 1003 blue, RAL 5005
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
246 | Manual Call Points | Accessories - Manual Call Points LSN and Conventional
Punched, Self-adhesiveFoil Sets (Blank), for Oper-ating Panel and LabelingField
10 punched foil sets, appropriate for DM/DKM/SM/SKM, forindividual printing with a customary laser printer
The required print file is available on the WinPara diskette.
Ordering Information
Punched, Self-adhesive Foil Sets (Blank),for Operating Panel and Labeling Field10 units, for DM/DKM/SM/SKM, for individualprinting
DKM120-LABEL
FMX‑FSO‑LSN Punched,Self-adhesive Foil Sets(Blank)
For the labeling field of manual call points of the SeriesFMC‑210.
1 unit = 10 sheets
Appropriate for printing at standard laser printers. Therequired print file is available on the WinPara disk.
Ordering Information
FMX‑FSO‑LSN Punched, Self-adhesive FoilSets (Blank)For the labeling field of manual call points ofthe Series FMC‑210.1 unit = 10 sheets
FMX-FSO-LSN
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Accessories - Manual Call Points LSN and Conventional | 247
FMX‑FSO‑GLT Punched,Self-adhesive Foil Sets(Blank)
For the labeling field of conventional manual call points ofthe Series FMC‑120.
1 unit = 10 sheets
Appropriate for printing at standard laser printers. Therequired print file is available on the WinPara disk.
Ordering Information
FMX‑FSO‑GLT Punched, Self-adhesive FoilSets (Blank)For the labeling field of conventional manualcall points of the Series FMC‑120,1 unit = 10 sheets
FMX-FSO-GLT
FMC‑FST‑DE PrintedLabeling Foils for theUpper Label Field
For yellow and blue manual call points of Series FMC‑120and FMC‑210.
1 unit = 5 sheets
All labeling foils meet the requirements of the EN 12094‑3(use in gas extinguishing system).
Ordering Information
FMC‑FST‑DE Printed Labeling Foils for theUpper Label FieldFor yellow and blue manual call points of SeriesFMC‑120 and FMC‑210, 1 unit = 5 sheets
FMC-FST-DE
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
248 | Manual Call Points | Accessories - Manual Call Points LSN and Conventional
FMC‑SPGL‑DEIL SpareGlasses
For manual call points of Series DM, DKM, SKM, FMC‑120and FMC‑210.
1 unit = 5 spare glasses
Ordering Information
FMC‑SPGL‑DEIL Spare GlassesFor manual call points of Series DM, DKM, SKM,FMC‑120 and FMC‑210.1 unit = 5 spare glasses
FMC-SPGL-DEIL
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Conventional Manual Call Points for Ex Areas | 249
Conventional Manual CallPoints for Ex Areas
The Conventional Manual Call Points for Ex Areas are usedto manually activate the alarm in zones 1 and 2 at risk ofexplosion.
The K type call points are encapsulated, intrinsically safecall points and do not require any safety barriers.
The DM 1103 B‑Ex Manual Call Points for ex zones must beconnected via a Safety Barrier SB 3 incl. Input/OutputModule DCA1192 (see system overview).
System Overview
FLM-420/4-CON
EOL22(Ex)
DM 1103 B-Ex DM 1103 B-Ex
DO1101A-Ex
DCA1192 SB3
DCA1192 SB3
DFA1101A-Ex
DO1101A-Ex
1 2
For DM 1103 B‑Ex:
Pos. Description
1 Non-ex area
2 Ex area zone 1 or 2
Functions
In the event of an alarm, the glass pane (2) is broken first,then the pushbutton (3) is pressed hard. Thus the switchtriggers the alarm.
A locking mechanism holds the pressed manual call point.
The pushbutton can be reset with the reset lever.
This does not reset the alarm on the fire panel.
Certifications and Approvals
Region Certification
Europe CE DM 1103
BASEEFA Ex 98E2304 DM 1103 B-Ex
Germany VdS G 297060 DKM 2014/2-ex/-GLU
G 295036 DM 1103 B-Ex
PTB 97 ATEX 3197 DKM 2014/2 / DKM2014/2-GLU
Hungary TMT TMT-50-05/2004 DM 200, DM 210, DKM120, DM 1103B-Ex
Russia GOST POCC DE.C313.B06297
Installation/Configuration Notes
• Manual call points must be illuminated sufficiently withdaylight or another light source (including emergencylighting, if present).
• An installation height of 1400 mm ±200 mm, measuredfrom the middle of the manual call point to the floor,must be maintained.
• Manual call points must be installed along escape andrescue routes (e.g. exits, passageways, stairwells).
• Further standards, guidelines and planningrecommendations regarding the installation locationetc., should also be taken into consideration (see FireDetection manual).
• Regulations of local fire departments must be observed.
Installation/configuration notes in accordance with VdS/VDE• The distance between manual call points should not
exceed 100 m according to DIN 14675 or 80 maccording to VdS.
• In high risk areas, manual call points should be installedat a distance of max. 40 m (VDE 0833 Part 2,Point 7.2.6).
• According to VdS, up to 10 manual call points can beconnected to a primary line.
DKM 2014/2‑ex Manual Call Point Type K• For connection to the LSN, an NBK 100 LSN Fire
Interface is required.• Can be connected directly to the following conventional
control panels:- BZ 1012- BZ 1060- UEZ 1000 GLT.
• With an NBK 100 LSN Fire Interface, can be connectedto the following control panels:- BZ 500 LSN- UEZ 1000 LSN
www.boschsecurity.com Bosch Security Systems B.V.
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
250 | Manual Call Points | Conventional Manual Call Points for Ex Areas
- UEZ 2000 LSN- UGM 2020 LSN
DKM 2014/2‑ex‑UGM Manual Call Point Type K, forConnection to UGM Conventional• Can be connected directly to the UGM‑GLT Universal
Danger Detection System
DM 1103 B-Ex manual call point for ex area• For connection to the LSN, an NBK 100 LSN interface is
required.• For use in explosive areas of zones 1 and 2, a safety
barrier and an input/output module are required, whichmust be mounted in front of the ex area.
• Cables can be inserted surface-mounted or flush-mounted
Parts Included
Type Qty. Components
DKM 2014/2‑ex 1 Manual Call Point Type K, for ex areas, forsurface mounting
DKM 2014/2‑ex‑UGM 1 Manual Call Point Type K, for Connection toUGM Conventional, for ex areas, for surfacemounting
DM 1103 B-Ex 112
DM 1103 B-Ex manual call point, color redKey for DM1103B-Ex manual call pointPG11 cable screws
Technical Specifications
DKM 2014/2‑ex Manual Call Point Type KDKM 2014/2‑ex‑UGM Manual Call Point Type K, for Connection to UGMConventional
Operating voltage 24 V DC
Switch contact Type 366 (encapsulated), II 2 G EExd II C
Maximum contact load 5 A / 250 V AC0,25 A / 250 V DC
Cable entry • 1x M16 x 1.5 tightening diam-eter 4‑8 mm, EEx e II
• Blind plug: 1x M16 x1.5 EEx e II
Housing material Polyester, glass fiber reinforced
Colors Red, RAL 3001
Dimensions (W x H x D) 136 x 138 x 88 mm
Weight Approx. 1800 g
Protection class as per EN 60529 IP 66
Permissible operating temperature -25 °C to +40 °C
Ex classification Eex emd IIC T6
Test certificate / PTB No. 97-37001
ATEX approval no. PTB 97 ATEX 3197
DM 1103 B‑Ex Manual Call Point
Operating voltage 16V DC to 28V DC
Cable duct PG11 screws (2x)
Connection terminals 0.2 mm to 1.5 mm
Housing material Plastic, PC
Color Red, RAL 3000
Dimensions (W x H x D) 134.4 x 134.4 x 43.5 mm
Weight Approx. 200 g
Protection class as per EN 60529 IP 54
Permissible operating temperature -25 °C to +60 °C
Permissible storage temperature -30 °C to +75 °C
Permissible relative humidity ≤100% at T≤34 °C
Ex classification EEx ib IIC T4
Ordering Information
DKM 2014/2‑ex Manual Call Point Type Kfor Ex area
DKM 2014/2-ex
Key for Fire Detector Type K FMX-7743.0.0500
DKM 2014/2‑ex‑UGM Manual Call PointType K, for Connection to UGMConventionalfor ex area, exclusively for use in conjunctionwith the Universal Danger Detection SystemUGM‑GLT
DKM 2014/2-ex-UGM
Key for Fire Detector Type K FMX-7743.0.0500
DM 1103 B‑Ex Manual Call Pointfor zone 1 and 2 areas at risk of explosion
DM1103B-Ex
SB3 Safety Barrier incl. DCA1192 Input/Output Module
SB3
Accessories
FMC‑SPGL‑DEIL Spare GlassesFor manual call points of Series DM, DKM, SKM,FMC‑120 and FMC‑210.1 unit = 5 spare glasses
FMC-SPGL-DEIL
Bosch Security Systems B.V. www.boschsecurity.com
7
Fire_T2365506827_20090818T1526_EMEA_en-US_print_RC8.08f_cza5ot_DatabookPDF
Manual Call Points | Accessories - Manual Call Points for Ex Areas | 251
SB3 Safety Barrier incl.DCA1192 Input/OutputModule
Functions
The SB3 Safety Barrier limits the electrical energy betweennon-inherently safe and inherently safe circuits and thusprevents the ignition of gas mixtures by electrical sparks.
The Safety Barrier must always be installed outside theexplosive area.
The DCA1192 Input/Output Module is the galvanicalisolation between the fire panel and SB3 Safety Barrier.
Certifications and Approvals
Region Certification
Europe CE DC 1192
SB 3
CPD 0786-CPD-20512 DC 1192
Germany VdS G 298021 DC 1192
PTB 01 ATEX 2088 SB 3
Parts Included
Qty. Components
1 SB3 Safety Barrier
1 Installation set for SB3
1 DCA1192 Input/Output Module
1 Terminal carrier for DCA1192
1 EOL22(Ex) line termination, included with the DCA1192
2 Housing with cover
Technical Specifications
SB3 Safety Barrier, with Housing
Max. voltage 28 V DC
Max. permissible current 100 mA
Max. output 0.7 W
Wire gauge 0.2 mm2. . . 2.5 mm2
Cable bushings PG16 (6x)
Dimensions (W x H x D) 135 x 135 x 65 mm
Housing material Plastic, PC
Housing color White, RAL 9010
Weight Approx. 450 g
Protection class as per EN 60529 IP 56
Permissible operating temperature -25 °C . . . +70 °C
Permissible storage temperature -30 °C . . . +75 °C
Ignition protection according toEN 50014/20
Inherent safety EEx ia IIC / IIB
DCA1192 Input/Output Module, with Housing
External supply
• Operating voltage 18 V DC . . . 32 V DC
• Current consumption Max. 5 mA
• Line resistance 50 Ω . . . 250 Ω
• Line termination EOL22(Ex)
Line termination
• Operating voltage 18 V DC . . . 22 V DC
• Standby current ≤45 mA
• Operating current ≤150 mA
• Line resistance 50 Ω . . . 250 Ω
• Line termination EOL22(Ex)
Wire gauge 0.2 mm2. . . 2.5 mm2
Cable bushings PG16 (6x)
Housing material Plastic, PC
Housing color White, RAL 9010
Dimensions (W x H x D) 135 x 135 x 65 mm
Weight Approx. 425 g
Protection class as per EN 60529 IP 56
Permissible operating temperature -25 °C . . . +70 °C
Permissible storage temperature -30 °C . . . +75 °C
Permissible relative humidity ≤100% at T≤34 °C