Transcript
Page 1: HV Cable Jointing Nexans Euromold Elastimold HV Screened ......158LR INTERFACE A ELBOW CONNECTOR Application Separable elbow connector designed to connect polymeric insulated cable

5

Specifications andstandardsThe separable connector 158LRmeets the requirements ofCENELEC HD 629.1.

Up to 24 kV - 250 A

DesignSeparable connectorcomprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer

moulded between the insertand the jacket.

4. Type A - 250 A interfaceas described by CENELECEN 50180 and 50181.

5. Conductor connector.6. Earthing lead

(-/G version only).

158LRINTERFACE A

ELBOW CONNECTOR

ApplicationSeparable elbow connectordesigned to connect polymericinsulated cable to equipment(transformers, switch gear,motors...).Also connects cable to cable,using the appropriate matingpart.

6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV

12/20 (24) kV12.7/22 (24) kV

Technical characteristics• The thick conductive EPDM

jacket provides a total safe totouch screen which ensuressafety for personnel.

• Each separable connector istested for AC withstand andpartial discharge prior toleaving the factory.

1

3

221 mm

160 mm

2

4

5

6

Separableconnector

type

VoltageUm(kV)

CurrentIr

(A)

Conductor sizes (mm2)(for information only)

min. max.158LR/G

158LRK158LR/G

K158LR

12122424

250250250250

16701625

70952595

michael ryan
New Logo
Page 2: HV Cable Jointing Nexans Euromold Elastimold HV Screened ......158LR INTERFACE A ELBOW CONNECTOR Application Separable elbow connector designed to connect polymeric insulated cable

6

Kit contentsThe complete (K)158LR or(K)158LR/G elbow connectorkit comprises the followingcomponents:

The kit also comprises lubricant, wipers,installation instructions and crimp chart.

Ordering instructionsSelect the part numberwhich gives the best centringto the cable core insulationdiameter and substitute Xusing table X, according to theconductor size and type.Add a 'K' for use up to 24 kV.

Orderingpart number

Dia. over core insulation (mm)

min. max.

158LR/G-11-X158LR/G-13-X

158LR-FG-X+11TL158LR-GA-X+11TL158LR-GAB-X+11TL158LR-GH-X+11TL

12.614.618.419.721.023.2

16.118.721.222.523.826.4

Example:The copper wire screened cableis 24 kV, 50 mm2 strandedaluminium with a diameter overcore insulation of 20.4 mm.Order a K158LR-FG-50(K)M-12-2+11TL elbow connector kit.

Conductorsizes

(mm²)

Aluminium Copper

DIN hexagonal Deep indent DIN hexagonal

162535507095

-25(K)M-12-235(K)M-12-250(K)M-12-270(K)M-12-295(K)M-12-2

-25KM-12-135KM-12-1

50(K)M-12-170(K)M-12-195(K)M-12-1

16(K)M-11-225(K)M-11-235(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2

Table X

+ + +

Conductorcontact

164LRC-X

Pin contact+ hex key

154LRF

Bailrestraint

150BA-B1Connector housing

(K)158BLR-W

+ (K)158LR-W-X+11TLconnector kit for

larger sizes

=

Cable adaptor11TL

Connector housing(K)158BLR/G-W

Cable reducer211CA

= (K)158LR/G-W-Xconnector kit for

smaller sizes

+

Table W

For adaptedbail restraints:

see 'Bail restraints andtypical applications'.

For outdoorapplications.

Order: +MWS.

Components can beordered individually.

For use withcopper tape

screened cables.Order: Kit MT.

For use with Alupe orC 33-226 cables.

Please contact ourrepresentative.

For use withother cable types.

Please contact ourrepresentative.