www.districtenergy.comDistrict Energy St. Paul
Heat Exchanger Extraordinaire Expo
Jonathan Martens [email protected]
![Page 2: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/2.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heat Exchangers• Specifications
• Temperature/Pressure Ratings
• Design Selection
• Testing
• Configuration Options• Single Pass
• Double Pass
• Expandable Capacities
• Double Wall
![Page 3: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/3.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heat Exchangers• Diagnostics
• Common Installation Errors
• Pressure
• Temperature
• Cleaning• Decision to Replace or Clean
• Chemicals
• Process
![Page 4: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/4.jpg)
www.districtenergy.comDistrict Energy St. Paul
Temperature and Pressure Rating
• Heating
• 250 Degree F.
• 250 PSI
• Cooling
• 180 Degree F.
• 150 PSI
![Page 5: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/5.jpg)
www.districtenergy.comDistrict Energy St. Paul
What Does that Mean?
![Page 6: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/6.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heating Design
![Page 7: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/7.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heating TemperaturesApproach Temperature:
Minimum of 10 Degree F.
![Page 8: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/8.jpg)
www.districtenergy.comDistrict Energy St. Paul
Cooling TemperaturesApproach Temperature:
Minimum of 2 Degree F.
![Page 9: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/9.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heating Flow RatesHeat Exchanger Flows
![Page 10: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/10.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heating Pressure Drops
Equal volumes on each side of the heat exchanger means
that one side has a much higher fluid velocity. This is true for
plate/frame and brazed plate heat exchangers but not shell
and tube
![Page 11: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/11.jpg)
www.districtenergy.comDistrict Energy St. Paul
Cooling Pressure Drops
![Page 12: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/12.jpg)
www.districtenergy.comDistrict Energy St. Paul
Fouling Factor/Oversurfacing
Fouling factor is an engineering safety factory.
![Page 13: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/13.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heat Exchanger Turndown
• Reynolds Number Below 2000 Is Laminar
![Page 14: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/14.jpg)
www.districtenergy.comDistrict Energy St. Paul
Heat Exchangers Testing• Nameplate Pressure Rating (NPR)
• Hydro Test Pipe to 1.5 X NPR
• ASME Certifies Heat Exchangers as 1.3 X
NPR
• European Standard is 1.2 X NPR
• Heating Hydro Tests to 375 PSI
• Cooling Hydro Tests at 225 PSI
![Page 15: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/15.jpg)
www.districtenergy.comDistrict Energy St. Paul
Single-Pass
Heat
Exchanger
Linan Beta Mechanical & Electrical Co., Ltd
![Page 16: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/16.jpg)
www.districtenergy.comDistrict Energy St. Paul
Two-Pass
Heat
Exchanger
Danfoss ASEAN
![Page 17: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/17.jpg)
www.districtenergy.comDistrict Energy St. Paul
Expandable
Capacities
SWEP International AB
![Page 18: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/18.jpg)
www.districtenergy.comDistrict Energy St. Paul
Expandable
Capacities
http://1.bp.blogspot.com/_l-cNNS3j7UU/S7FhqbBQwII/AAAAAAAAAR4/AsODQ-al8k8/s1600/pack.png
![Page 19: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/19.jpg)
www.districtenergy.comDistrict Energy St. Paul
Double Wall (Domestic Hot
Water)
http://tse2.mm.bing.net/th?id=OIP.M9b673b3070f9375fc0f985629f5c35b1o0&pid=15.1
![Page 20: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/20.jpg)
www.districtenergy.comDistrict Energy St. Paul
How often to clean if no signs of trouble?
Your Preventative Maintenance Friend
• Building Hx • House side - 1x/5yrs
• District side – 1x/5yrs
• DHW Hx• House side – 1x/yr
• District side – 1x/5yrs
• Process Cooling Hx• Process side – 1x/yr
• District side – 1x/yr
![Page 21: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/21.jpg)
www.districtenergy.comDistrict Energy St. Paul
Pressure
Diagnostics
High Pressure
Drop on either
side of the
heat
exchanger.
![Page 22: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/22.jpg)
www.districtenergy.comDistrict Energy St. Paul
Pressure Mechanical Rating
![Page 23: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/23.jpg)
www.districtenergy.comDistrict Energy St. Paul
Low Temperature Differential
250
190 150
180
![Page 24: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/24.jpg)
www.districtenergy.comDistrict Energy St. Paul
Low Temperature Differential
250
190 150
165
![Page 25: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/25.jpg)
www.districtenergy.comDistrict Energy St. Paul
Temperature Mechanical Schedule
![Page 26: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/26.jpg)
www.districtenergy.comDistrict Energy St. Paul
How often to clean if no signs of trouble?
Your Preventative Maintenance Friend
• Building Hx • House side - 1x/5yrs
• District side – 1x/5yrs
• DHW Hx• House side – 1x/yr
• District side – 1x/5yrs
• Process Cooling Hx• Process side – 1x/yr
• District side – 1x/yr
![Page 27: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/27.jpg)
www.districtenergy.comDistrict Energy St. Paul
Installation SNAFUs:
• Horizontal Installation
• Piped from Bottom of
Header
• Thermal shock
• Oversized (+2x
needed capacity)
• Parallel flow
• No P/T gauges
• No CIP ports
http://www.corrview.com/images/phocagallery/109-Improper_Dielectric_Fittings/thumbs/phoca_thumb_l_109_001.jpg
![Page 28: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/28.jpg)
www.districtenergy.comDistrict Energy St. Paul
Time to Replace
Signs of
physical
damage or
leaks
![Page 29: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/29.jpg)
www.districtenergy.comDistrict Energy St. Paul
Time to Clean Vs. Replacement
• Doesn’t meet the criteria of one of the
common installation errors
• No signs of Physical Damage or Leaking
• Heat Exchanger Replacement is > 3 X Cost
to Clean
![Page 30: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/30.jpg)
www.districtenergy.comDistrict Energy St. Paul
Cleaning: The Process
• Test loop water sample to identify
the foulant
• Mix chemicals to appropriate
concentrations – excessive pH in
either direction can adversely
accelerate corrosion rates
• Connect pump in reverse of
typical flow
• Note:• Do not exceed 100F
• Target flow rate: 2 – 9 ft/sec
• Flush hx with city water until
conductivity of rinse water
matches city water
![Page 31: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/31.jpg)
www.districtenergy.comDistrict Energy St. Paul
Cleaning: Determining the Foulant
• Iron Oxides
• Hardness (Calcium,
Magnesium, etc.)
• Biologicals
![Page 32: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/32.jpg)
www.districtenergy.comDistrict Energy St. Paul
Chemical Flush
Time Lapse -
5 Minutes
![Page 33: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/33.jpg)
www.districtenergy.comDistrict Energy St. Paul
Chemical Flush
Time Lapse -
15 Minutes
![Page 34: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/34.jpg)
www.districtenergy.comDistrict Energy St. Paul
Chemical Flush
Time Lapse -
30 Minutes
![Page 35: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/35.jpg)
www.districtenergy.comDistrict Energy St. Paul
Chemical Flush
Time Lapse -
40 Minutes
![Page 36: District Energy St. Paul presentation template](https://reader034.vdocuments.site/reader034/viewer/2022051504/586a2d3b1a28ab2a738b802b/html5/thumbnails/36.jpg)
Questions?
Thank you!