COOLING TOWERS
Definition:
# In power plants the hot water from condenser iscooled in cooling tower, so that it can be reused incondenser for condensation of steam.
# In a cooling tower water is made to trickle downdrop by drop so that it comes in contact with the airmoving in the opposite direction.
# As a result of this some water is evaporated andis taken away with air. In evaporation the heat istaken away from the bulk of water, which is thuscooled.
-
8/3/2019 Cooling Towers 2003
2/27
Factors affecting cooling of water in
a cooling tower are:
1. Temperature of air.
2. Humidity of air.
3. Temperature of hot air.4. Size and height of tower.
5. Velocity of air entering tower.
6. Accessibility of air to all parts of tower.7. Degree of uniformity in descending water.
8. Arrangement of plates in tower.
-
8/3/2019 Cooling Towers 2003
3/27
The cooling towers may be classified as
follows:
1. Natural draught cooling towers2. Mechanical draught cooling towers:
(i) Forced draught cooling towers
(ii) Induced draught cooling towers.
-
8/3/2019 Cooling Towers 2003
4/27
NATURAL DRAUGHT COOLING
TOWER:
# In this type of tower, the hot water from thecondenser is pumped to the troughs and
nozzles situated near the bottom.# Troughs spray the water falls in the form of
droplets into a pond situated at the bottom ofthe tower.
# The air enters the cooling tower from airopenings provided near the base, rises upwardand takes up the heat of falling water.
-
8/3/2019 Cooling Towers 2003
5/27
-
8/3/2019 Cooling Towers 2003
6/27
Advantages:
# Low operating and maintenance cost.
# It gives more or less trouble free operation.
# Considerable less ground area required.
# The towers may be as high as 125 m and 100 m indiameter at the base with the capability of withstandingwinds of very high speed. These structures are more or less
self-supported structures.# The enlarged top of the tower allows water to fall out of
suspension
Disadvantages:# High initial cost.
# Its performance varies with the seasonal changes in DBT(dry bulb temperature) and R.H. (relative humidity) of air.
-
8/3/2019 Cooling Towers 2003
7/27
MECHANICAL DRAUGHT
COOLING TOWERS:
# In these towers the draught of air for cooling
the tower is produced mechanically by
means of propeller fans.
# These towers are usually built in cells or
units, the capacity depending upon thenumber of cells used.
-
8/3/2019 Cooling Towers 2003
8/27
FORCED DRAUGHT COOLING
TOWER:
It is similar to natural draught tower as far asinterior construction is concerned, but the sides of
the tower are closed and form an air and water tight
structure, except for fan openings at the base for theinlet of fresh air, and the outlet at the top for the exit
of air and vapours.
There are hoods at the base projecting from themain portion of the tower where the fans are placed
for forcing the air, into the tower.
-
8/3/2019 Cooling Towers 2003
9/27
-
8/3/2019 Cooling Towers 2003
10/27
ADVANTAGES OF FORCED
DRAUGHT COOLING TOWER:
1. More efficient (than induced
draught).
2. No problem of fan blade erosion (asit handles dry air only).
3. More safe.4. The vibration and noise are
minimum.
-
8/3/2019 Cooling Towers 2003
11/27
DISADVANTAGES OF FORCED
DRAUGHT COOLING TOWER:
1. The fan size is limited to 4 meters.
2. Power requirement high (approximately
double that of induced draught system forthe same capacity).
3. In the cold weather, ice is formed on
nearby equipments and buildings or in thefan housing itself. The frost in the fan
outlet can break the fan blades.
-
8/3/2019 Cooling Towers 2003
12/27
INDUCED DRAUGHT
COOLING TOWER: In these type of cooling towers ,the
fans are placed at the top of thetower and they draw the air in
through louvers extending all
around the tower at its base.
-
8/3/2019 Cooling Towers 2003
13/27
-
8/3/2019 Cooling Towers 2003
14/27
Advantages of induced draught
cooling tower:
1. The coldest water comes in contact withthe driest air and warmest water comes incontact with the most humid air.
2. In this tower, the recirculation is seldom aproblem.
3. Lower first cost (due to the reduced pump
capacity and smaller length of waterpipes).
4. Less space required.
5. This tower is capable of cooling through awide range.
-
8/3/2019 Cooling Towers 2003
15/27
Disadvantages of induced draught
cooling tower:
1. The air velocities through the packingare unevenly distributed and it has verylittle movement near the walls and centre
of the tower.
2. Higher H.P. motor is required to drivethe fan comparatively. This is due to the
fact that the static pressure loss is higheras restricted area at base tends to chokeoff the flow of higher velocity air.
ADVANTAGE OF MECHANICAL
-
8/3/2019 Cooling Towers 2003
16/27
ADVANTAGE OF MECHANICAL
DRAUGHT TOWER OVER
NATURAL DRAUGHT TOWERS:1. These towers require a small land area
and can be built at most locations.
2. The fans give a good control over the air
flow and thus the water temperature.
3. Less costly to install than natural draughttowers.
-
8/3/2019 Cooling Towers 2003
17/27
DISADVANTAGE OF MECHANICAL
DRAUGHT TOWER OVER NATURAL
DRAUGHT TOWERS:
1. Fan power requirements andmaintenance costs make them more
expensive to operate.
2. Local fogging and icing may occur inwinter season.
-
8/3/2019 Cooling Towers 2003
18/27
DRY COOLING TOWERS:
The necessity of using dry cooling towers
has been felt due to the following reasons:
# Natural water resources can be used fordissipating heat in power plants but there
are some limitations to do so, as discussed
earlier. Moreover there is a potentialthermal pollution problem in this system.
-
8/3/2019 Cooling Towers 2003
19/27
# In evaporative cooling system (cooling
towers) due to continuous evaporation of
water, the concentration of impurities goes onincreasing and so the disposal of tower blow
down may become a serious problem at some
sites. Besides this make up water for tower use
is limited in some areas.
# Thus the use of dry cooling towers in power
plants is the only alternative. The dry system
rejects the heat directly to the atmosphere
which is the largest heat sink available.
CLASSIFICATION OF DRY COOLING TOWERS
-
8/3/2019 Cooling Towers 2003
20/27
CLASSIFICATION OF DRY COOLING TOWERS:
Direct system
Indirect system
DIRECT SYSTEM
# In direct system the exhaust steam from the turbine ispassed on to the cooling coils where it is condensed
directly by means of air.# Cooling coils constitute air cooled condenser. This
system has the disadvantage that large ducts are neededto convey the exhaust steam to the exchanger coils, to
minimize the pressure drop.# This places a practical limit on the size of the unit. This
system is limited to maximum generator unit sizes of200 MW to 300 MW.
-
8/3/2019 Cooling Towers 2003
21/27
INDIRECT SYSTEM
-
8/3/2019 Cooling Towers 2003
22/27
INDIRECT SYSTEM:
# In this case, the exhaust steam is condensed in a
spray condenser by means of circulating water.# The major part of the water from the condenser
flows back to the cooling coils and an amount
equal to the exhaust steam from the turbine isdirected back to the boiler feed water circuit.
# Some energy recovery is possible by using
hydraulic turbine (T) to drive the circulatingwater pumps. This system is applicable to all
large unit sizes.
-
8/3/2019 Cooling Towers 2003
23/27
-
8/3/2019 Cooling Towers 2003
24/27
ADVANTAGES OF DRY
COOLING TOWERS:
1.It solves the problem of thermal pollution of waterand as the circulating water does not come intodirect contact with the cooling air, there is noevaporative loss of water as in wet type tower.
2. This system eliminates water supply as a significantplant site selection factor. Power plants can be sitedcloser to the load centre.
3. There is minimum air pollution.
4. From environmental view point, the dry towersoffer several desirable features e.g. no fog, noblowdown treatment, no windage loss of water, noevaporative loss of water and no thermal dischargeto water source.
-
8/3/2019 Cooling Towers 2003
25/27
DISADVANTAGES OF DRY
COOLING TOWERS:
1. Their performance is limited by dry bulb
temperature and so turbine exhaust temperatures are
much higher resulting in a substantial loss of turbine
efficiency, most critical in warm climates.
2. Due to low heat transfer co-efficient, dry cooling
towers require enormous volumes of air large
surface areas and are less effective at high natural airtemperatures.
-
8/3/2019 Cooling Towers 2003
26/27
MAINTENANCE OF COOLING
TOWERS:
The regular maintenance of cooling towers is
very essential to achieve the desired cooling
and to reduce the depreciation costs. Themaintenance of cooling towers includes the
following:
1. The fans, motors housings etc. should be
inspected from time to time.
2. Motor bearings should be greased and gear
boxes oiled. Any unusual noise or vibrations in
them should be corrected immediately.
3 A l i
-
8/3/2019 Cooling Towers 2003
27/27
3. At least once in a year motors gear
boxes should be checked for structural
weakness.4. The circulating water should be tested
for hardness and should be kept free from
impurities to avoid scale formations and
to avoid corrosive action of water.
5. The water spraying nozzles should beinspected regularly for clogging.