“Data Centers De Persgroep”
Antwerp Feb. 14 2013
Luc Verbist
CIO
![Page 3: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/3.jpg)
Activities
MAGAZINES
N°1
N°1
![Page 4: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/4.jpg)
Activities
Print products
5 times around the globe in 1 week
![Page 6: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/6.jpg)
Activities
TELEVISION
N°1
![Page 7: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/7.jpg)
Activities
DIGITAL
Classifiedsites >
E-commerce >
iPad & mobile>
News >
Pay-per-view >
![Page 9: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/9.jpg)
Financial Results
In mio euro 1991 2000 2011
![Page 10: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/10.jpg)
Growth by acquisition
1989
1991
1993
1995
1997
1999
20012003
2005 2007 2009 2011
Netherlands
2012
![Page 11: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/11.jpg)
Growth by acquisition
1989
1991
1993
1995
1997
1999
20012003
2005 2007 2009 2011
Netherlands
All newspapers had problems
• Losing money
• Declinig readership
![Page 12: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/12.jpg)
ICT Strategy
► Atos Origin
► Getronics
► KPN
► ASP4ALL
► Hotitem
►…
Outsourcing
Contract managers and
Business analysts on the payroll
External Datacenters
![Page 13: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/13.jpg)
FTE: 1.800
Locations: 12 in The Netherlands
Newspapers: 3, with 718 journalists
Websites: 18
Printing plants: 2
ICT Strategy
Facts & Figures
► Initially: 3.045
► Restructurings
► Closed printing plant
► Sold NRC (Newspaper)
► Sold Magazines (education)
► Sold Book Publishing Division
![Page 14: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/14.jpg)
Planning
Roll out planning high level
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun
Finance AD 01/01/10 28/02/10
Website AD 01/01/10 30/03/10
Editorial AD 01/01/10 30/06/10
WAN Connectivity 01/01/10 30/06/10
Subscription AD 01/01/10 30/09/10
Office Environment 01/01/10 30/09/10
Salary and HR 01/02/10 31/12/10
Output Management 01/03/10 30/06/10
Website VK 01/04/10 30/09/10
Editorial VK 01/07/10 30/11/10
Finance VK and TR 01/08/10 31/01/11
Single Copy Sales 01/09/10 30/04/10
Mass Mailing 01/09/10 30/06/10
Website Classified 01/09/10 30/02/11
Website TR 01/10/10 31/12/10
Subscription VK and TR 01/10/10 30/04/11
Editorial TR 01/12/10 31/03/11
Printing Plant Den Haag 01/01/11 30/04/11
Printing Plant Amsterdam 01/01/11 30/06/11
2010 2011Project Name Start Finish
![Page 15: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/15.jpg)
Facts & Figures about the Datacenter
Number of servers
OS Physical Virtual Total Virt %
Solaris 86 308 394 78 %
Windows 328 460 788 58 %
Mac 65 13 78 17 %
616 TB in different Tiers
Tier 1 128 TB
Tier 2 144 TB
Tier 3 344 TB
► 3 tiers in 6 storage systems, 3 per DC
► High end storage: Fiber channel and
SAS Technology
► High end storage: SATA Technology
►Mid range storage: SATA Technology
![Page 16: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/16.jpg)
Desktop virtualization
► 120 virtual Windows servers in DC
40 For latency sensitive applications
30 For legacy applications and compatibility
30 For internal ICT management
10 For Windows applications and for Mac users
10 Other
► Very limited use► Effect of line latency
► Being able to work in a non connected mode
► Limited distance of workstation to the production machinery
► Expensive licenses
![Page 17: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/17.jpg)
Service Levels
Business Service Hours Days Max. Downtime
0 6 12 18 24
Newspapers 6/7 15 minMagazines 5/7 60 minWebsites 7/7 15 minPrinting Plant 6/7 15 minTV 7/7 1 minRadio 7/7 1 min
![Page 18: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/18.jpg)
Principe N+1
► Power
UPS
Generator
Public network
► Cooling
► Network
Multiple network cards in servers
Dual uplink
Redundant core network
![Page 19: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/19.jpg)
Principe N+1
![Page 20: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/20.jpg)
Cold corridors
► Full separation of hot
and cold air flows
► High efficiency
![Page 21: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/21.jpg)
2 Datacenters fully redundantIn
to
tal4
cu
be
s
DATACENTER
ROOM 1
DATACENTER
ROOM 2
► Network
equipment
► Server
rack
![Page 22: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/22.jpg)
![Page 23: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/23.jpg)
![Page 24: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/24.jpg)
Real time monitoring
Monitoring of the data centers
Temperature Back
Power usage
Humidity
Temperature Front
![Page 25: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/25.jpg)
Real time monitoring
Monitoring of the chillers
![Page 26: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/26.jpg)
Real time monitoring
Monitoring of the power usage
![Page 27: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/27.jpg)
Real time monitoring
PUE Graphic 2011
0.0 °C
2.0 °C
4.0 °C
6.0 °C
8.0 °C
10.0 °C
12.0 °C
14.0 °C
16.0 °C
18.0 °C
20.0 °C
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
jan feb mar apr may jun jul aug sep oct nov dec
Average monthly PUE Average monthly temperature
![Page 28: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/28.jpg)
Benchmark Hosting
(Opex figures full year basis)
►Websites
˃ Vacature Terramark 180 K€ 120 K€
˃ AD-Trouw-Volkskrant Getronics 3 Mio € 650 K€
˃ Tijd-Echo Cegeka 160 K€ 100 K€
► Cloud Solutions
˃ ASP4ALL (all webservers) 850 K€ 500 K€
˃ Microsoft Assure (MS server park) 2,4 Mio € 1,3 Mio €
(real contract values)
(benchmark checks)
Externalcost
Internalcost
![Page 29: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/29.jpg)
Costs
ICT Cost (Mio €)
0.0
10.0
20.0
30.0
40.0
50.0
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012
► After integrationBefore integration◄
Stop outsourcing contracts
Switch to DP standards
![Page 30: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/30.jpg)
50
60
70
80
90
100
110
120
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012
Costs
Evolution ICT Cost/employee (Index cleared)
► After integrationBefore integration◄
![Page 31: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/31.jpg)
Design lessons
► During design consider impact minimization of potential failures
►Make sure all drivers, hardware version, setup parameters, … are
identical for clustered servers
► Difficult to assess upfront the load on physical servers with a lot of
virtual machines
► Easy to manage but also easy to make (human) mistakes
► Consider data recovery requirements during design of storage tiers
► (B)Leading edge technology (aggressive pricing but non-mature technology)
► Think big (anticipate on growth strategy)
► Think green
![Page 32: “Data Centers De Persgroep”download.minoc.com › 2012 › 47 › 20120214_BMIT_Datacenters... · 2013-02-14 · Facts & Figures about the Datacenter Number of servers OS Physical](https://reader034.vdocuments.site/reader034/viewer/2022042408/5f2490e0f315265d1630bc02/html5/thumbnails/32.jpg)
Considerations internal or external data center
► Be sure you have enough critical mass, if not → outsource
► 24/7 business or just business hours
► Business Applications are very specific (no support from third parties available)
► Strong support of end users of business applications is required
► Fysical distance between servers and production machinery
► Costs
► Opex versus Capex strategy of the company
► Availability of skilled resources
► Building restrictions and regulations
► Employees churn rate