2013
13P01E
R410A
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
2
-15C +43C
-20C +20C
50403020100-10-20-30
Heating
Cooling
: Heating operation down to -20C
: Nominal heating capacity maintained at -15C
-20C-15C
FDC100VSX(4HP, 3phase 380V)
FDC125VSX(5HP, 3phase 380V)
FDC140VSX(6HP, 3phase 380V)
Micro InverterHyper Inverter
12.5
16.0
16.5
16.0
18.0
20.0
Max.heating capacity (kW)
Heightdifference(Outdoor higherthan Indoor)
30mPipinglength
100m
Thanks to optimization of refrigeration control with use of electric expansion valve anddevelopment of new twin rotary compressors, max heating capacity has been increased.Hyper Inverter series can reach the set temperature very quickly, keeping nominalheating capacity when outdoor temperature is -15C.It is effective to be used even in cold area.
Temperature of supply air can reach 40C in 4minutes after start up under low temperatureoperation conditions (at both indoor and outdoortemperature of 2C) and can reach 50C in 8minutes after that.
FDC100VSX(4HP, 3phase 380V)
FDC125VSX(5HP, 3phase 380V)
FDC140VSX(6HP, 3phase 380V)
11.2kW
14.0kW
16.0kW
nominal heating capacity(kW at outdoor temperature of 7C)model name
11.2kW
14.0kW
16.0kW
heating capacityat outdoor temperature of -15C
Heating capacity (in case of 5HP, 3phase 380V)
nominalheatingcapacity14.0kW
Keeping nominal heatingcapacity at -15C
(kW)
18.0
14.514.0
8.8
0-15C 2C 7C
Hyper Inverter
Micro Inverter
Heating capacity
50C
40C
30C
20C
10C
0C4minutes 8minutes
Hyper Inverter
Micro Inverter
Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities. (including 1phase 220V)
Leading powerful heating capacity in the industry
Our new advanced technology has realized high efficiency,
strong heating and long piping.
This contributes to the environmental protection through energy
saving and permits installation of the units (3~6HP) considering
a heating operation under temperature conditions down to -
20C and design flexibility has been improved by extension of
piping length to 100m.Hyper Inverter
1.5 2 2.5 3 4 5 6 8 10
- -
HPLine up
Long piping(in case of 4~6HP)Strong heating(in case of 3~6HP)
SRC40ZJX-S (1.5HP)SRC50ZJX-S (2.0HP)SRC60ZJX-S (2.5HP) FDC71VNX (3.0HP)
FDC100VNX/VSX (4.0HP)FDC125VNX/VSX (5.0HP)FDC140VNX/VSX (6.0HP)
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
3
Employment of the scrollinverter compressors(8/10HP)
A control over wide range of capacity and a high efficiency has
been realized by inverter-driven scroll compressors.In addition, the starting current significantly is improved.The size has also been reduced by 3.2% in height and 31.8% involume.
Wide range of operation
Though the nominal efficiency is lower than that ofFDC71VNX (Hyper inverter), higher SEER & SCOP areachieved by optimizing control.
Compact Design of outdoor unitsHigh SEER & SCOP Refer to page 41
Our new advanced technology has expanded the heating and coolingoperation range.This permits installation of the units under a low outdoor temperatureconditions down to -20C In heating operation and -15C in coolingoperation.
* Vector control meansa. technique to realizean optimum control byconverting the currentwave to a smoothsinusoidal waveform
Employment of DC twin rotary compressor has enabled to utilize a high-speed range of up to 120 rps at the maximum to secure the requiredcapacity.Optimum compressor control has been realized by employing the vectorcontrol* and the starting current has been improved significantlycompared with former models. Moreover, vibration has been reduced.
Formercompressor
New modelDC rotary compressor
Heightat440mm
Outside diameter of shell
185mm
Heigh
tat342mm
Reduction in height by 22.3%Reduction in volume by 44.1%
133mm
Micro Inverter
Standard Inverter
Size reduction and high efficiencyperformance on the DC twinrotary compressors(Micro Inverter 4-6HP)
(FDC 100/125/140)
50403020100-10-20-30
Heating
Cooling +43C
+20C
-15C
-20C
Micro Inverter
1.5 2 2.5 3
- - - -
4 5 6 8 10
HPLine up
3
Standard Inverter
1.5 2 3.5
- -
4 5 6 8 10
HP
- - - --
Line up
FDC100VN/VS (4.0HP)FDC125VN/VS (5.0HP)FDC140VN/VS (6.0HP)
FDC200VS(8.0HP)
FDC250VS(10.0HP)
Fits into elevators
Easyinstallation
FDC71VNP (3.0HP) FDC90VNP (3.5HP)
FDC71VNX FDC71VNP
Volume
33% lessWeight
25% lessSCOP
6
7
5
4
3
4.09 4.27
SEER
5.726.14
FDC71VNX FDC71VNP FDC71VNX FDC71VNP
2.5
-
(in case of indoor unit: FDT71VF1)
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
4
Previous New
Due to optimization of outlet design of air flow with ournew advanced technology, sufficient air flow is securedand long reach of air flow is realized.(FDT)
For person who is farfrom the indoor unit
For both persons who arefeeling hot or cold
Can cool both the kitchenand the guests
Expansion of outlet air flow area realizes
reduction of pressure loss caused by air flow
in the indoor unit. Load of fan motor is
decreased and efficiency is increased.
Reduction of air flow pressure loss
Previous New
Shape of heat exchanger365mm
298mm
FDT125~140
18%reduction!!
Increase of heat transfer efficiency
Applying high efficient piping in heat exchanger and
optimization of heat exchanger (2parts 1part)
increases heat transfer efficiency.
Individual flap control system
According to room temperature conditions, four
directions of air flow can be controlled individually by
following Flap control system.
As individual flap control is available even after
installation, installation area became wider than before.
The thinnest design
Thanks to new design of heat exchanger changed from 2 parts to 1 part, the height of
indoor unit is reduced drastically.
High efficiency
Selectedupper position
Max swingrange
Selectedlower position
Flap control system
The flap can swing within the range of upper and
lower flap position selected with wired remote control.(this system is applied for FDEN, SRK type also)
*Wireless remote control and RCH-E3 is not applicable to the Individual flapcontrol system and the Flap control system.
Ceiling Cassette -4way- Indoor units
FDT.FDTC
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
5
External Static Pressure(E.S.P) control
Reduction of sound pressure level
FDU
Duct Connected -High Static Pressure-
NEW
Keep the same
air flow volume
Longer DuctDuct
Ceiling
New
FDUDuct
External Static Pressure (E.S.P.) canbe set by E.S.P. button.
*Range of 80~150 Pa is set at ex-factory default. Range of 10~200 Pa is available by setting SW8-4 switch on at site.
E.S.P. button
RC-E5
Setting No.
E.S.P.
No.8
80Pa
No.9
90Pa
No.10
100Pa
No.11
110Pa
No.12
120Pa
No.13
130Pa
No.14
140Pa
No.15
150Pa
case1 case2
Current
10~130PaNew
10~200Pa
FDU71/100 37 25 12dB less!!
New
New
Lo mode(FDU71VF1, in the Lo mode) Current
Current
FDU125/140 38 30 8dB less!!
0 5 10 15 20 25 30 35 40 dB(A)
12dB less!!
You can set External Static Pressure (E.S.P.) by method
of manual setting on remote control. Indoor unit will
control fan-speed to keep rated air
flow volume at each fan speed setting.
You can set required E.S.P. by wired
remote control that calculated with the
set air flow rate and pressure loss ofthe duct connected.
FDU71 297 280 17mm less!!
NewCurrent
FDU100/125/140 350 280 70mm less!!
Thin design
Reduction of weight
FDU71 40 34 6kg less!!
NewCurrent
FDU100/125/140 63 34 29kg less!!
FDUM has the same E.S.P. control.
FDUMDUCT CONNECTED -Middle Static Pressure-
FDUM
Refer to page 14.
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
6
SINGLE [OUTDOOR UNIT : INDOOR UNIT = 1 : 1]
CEILINGSUSPENDED
Type
4way
FDT
4way compact(600 x 600mm)
FDTC
Low/MiddleStaticpressure
FDUM
High Static
pressure
FDU
FDEN
CEILINGCASSETTE
DUCT
CONN
ECTED
Indoor
unit
Outdoor
unit
Indoor
unit
Outdoor unit
Indoor
unit
Indoor
unit
Indoor
unit
Set 1phase
1phase1phase
3phase
1phase
3phase
1phase
1phase
1phase
3phase
1phase
3phase
1phase
3phase
1phase
3phase
1.5
FDT40VF
FDT40ZJXVF FDT50ZJXVF FDT60ZJXVF FDT71VNXVF1
FDT50VF FDT60VF FDT71VF1
Set
FDTC40VF
FDTC40ZJXVF FDTC50ZJXVF
FDTC50VF
Set
FDU71VF1
Set FDUM50ZJXVF FDUM60ZJXVF FDUM71VNXVF1
3phase
FDUM50VF FDUM60VF FDUM71VF1
Set
FDEN40VF
FDEN40ZJXVF FDEN50ZJXVF FDEN60ZJXVF FDEN71VNXVF1
SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX
SRC40ZJX-S SRC50ZJX- S
FDTC60ZJXVF
FDTC60VF
SRC60ZJX-S
FDC71VNX
SRC50ZJX-S SRC60ZJX-S FDC71VNX
3phase
SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX
FDEN50VF FDEN60VF FDEN71VF1
HP
kW
Btu/h
kcal/h
2.0 2.5 3.0
4.013,7003,440
5.0
17,100
4,300
6.0
19,100
4,816
7.1
23,900
6,020
Capacity
FDU71VNXVF1
FDT100VNXVF1
FDT100VSXVF1
FDT100VF1
FDUM100VNXVF1
FDUM100VSXVF1
FDUM100VF1
FDEN100VNXVF1
FDC100VNX
FDC100VSX
FDU100VNXVF1
FDU100VSXVF1
FDU100VF1
FDC100VNX
FDC100VSX
FDC100VNX
FDC100VSX
FDC100VNX
FDEN100VSXVF1
FDC100VSX
FDEN100VF1
4.0
10.0
34,100
8,600
Outdoor
unit
Outdoor
unit
Outdoor
unit
FLOOR
STANDING
OUTDOOR UNIT
FDF
Indoor
unit
1phase
3phase
1phase
3phaseSet
FDF71VNXVD1
FDC71VNX
FDF71VD1
FDF100VNXVD1
FDC100VNX
FDF100VSXVD1
FDC100VSX
FDF100VD1
Outdoor
unit
NEW
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
7
FDT100VF1 FDT125VF FDT140VF
FDU100VSVF1 FDU125VSVF FDU140VSVF FDU200VSVF FDU250VSVF
FDU125VF FDU140VF FDU100VF1 FDU125VF FDU140VF FDU200VF FDU250VF
FDUM100VNVF1FDUM125VNVF FDUM140VNVF
FDUM100VSVF1 FDUM125VSVF FDUM140VSVF
FDUM100VF1 FDUM125VF FDUM140VF
FDEN100VNVF1 FDEN125VNVF FDEN140VNVF
FDEN100VSVF1
FDU125VSXVF
FDUM125VNXVF
FDUM125VSXVF
FDEN125VNXVF
FDEN125VSXVF
FDU140VSXVF
FDUM140VNXVF
FDUM140VSXVF
FDEN140VNXVF
FDEN140VSXVF FDEN125VSVF FDEN140VSVF
FDC100VS FDC125VS FDC140VS
FDC100VN FDC125VN FDC140VN
FDC125VNX FDC140VNX FDC100VN FDC125VN FDC140VN
FDC100VS
FDC125VSX
FDC125VSX
FDC140VSX
FDC140VSX
FDEN125VF FDEN140VF
FDC125VNX FDC140VNX
FDC125VSX FDC140VSX
FDUM125VF FDUM140VF
FDC125VNX FDC140VNX
FDC125VSX FDC140VSX
FDC125VS FDC140VS FDC200VS FDC250VS
FDU71VF1 FDU100VF1
FDC100VN FDC125VN FDC140VN
FDUM71VNPVF1 FDUM90VNPVF1
FDUM71VF1 FDUM100VF1
FDC71VNP FDC90VNP
FDC100VS FDC125VS FDC140VS
FDC100VS FDC125VS FDC140VS
FDC100VN FDC125VN FDC140VN
FDEN100VF1 FDEN125VF FDEN140VF
FDEN71VNPVF1 FDEN90VNPVF1
FDC71VNP FDC90VNP
FDEN71VF1 FDEN100VF1
4.0 5.0 6.0 8.0 10.05.0
FDT125VF FDT140VF
FDC125VNX FDC140VNX
6.0
12.5
42,700
10,750
14.0
47,800
12,040
10.0
34,100
8,600
12.5
42,700
10,750
14.0
47,800
12,040
20.0
68,300
17,200
25.0
85,400
21,500
3.0 3.5
7.1
23,900
6,020
9.0
30,300
7,630
Range(Rated Cooling Capacity)
FDT100VNVF1 FDT125VNVF FDT140VNVF
FDT100VSVF1
FDT125VNXVF
FDT125VSXVF
FDT140VNXVF
FDT140VSXVF FDT125VSVF FDT140VSVF
FDT71VF1 FDT100VF1
FDC71VNP FDC90VNP
FDT71VNPVF1 FDT90VNPVF1
FDU100VNVF1 FDU125VNVF FDU140VNVF
FDC71VNP FDC90VNP
FDU71VNPVF1 FDU90VNPVF1FDU125VNXVF FDU140VNXVF
Micro Inverter Standard Inverter
FDF100VNVD1 FDF125VNVD FDF140VNVD
FDF100VSVD1
FDF125VNXVD
FDF125VSXVD
FDF140VNXVD
FDF140VSXVD FDF125VSVD FDF140VSVD
FDF125VD FDF140VD
FDC125VNX FDC140VNX
FDC125VSX FDC140VSX FDC100VS FDC125VS FDC140VS
FDC100VN FDC125VN FDC140VN
FDF100VD1 FDF125VD FDF140VD
FDF71VNPVD1 FDF90VNPVD1
FDC71VNP FDC90VNP
FDF71VD1 FDF100VD1
NEW
NEWNEW
NEW NEW
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
8
FDTCEILING CASSETTE -4way-
Dimensions(Unit:mm)
R410A
Easy checking of drain pan
condition is available by
removing corner lid only.
Due to new design
changing fan motor is
available without removinga panel. Temporally setting
of drain pan is also
available.
Point
2 Easy checking of drain panDrain can be discharged
upwards by 700mm from the
ceiling surface. It allows a
piping layout with a high
degree of freedom
Depending on the installationlocation and 260mm flexible
hose as a standard
equipment supports easy
workability.
Point
3 700mm Drain Pump
Flexible hose
less than
700mm
Models FDT100VF1,125VF,140VFModels FDT40VF,50VF,60VF,71VF1
[ INDOOR UNIT ]
Point
1 Arrangement of installationbalance of indoor unit
Checking from access ports with
detachable covers at each corner,arrangement of installation balance of
indoor unit can be available without
removing a panel. Workability is improved
and time of installation is reduced.
RCN-T-36W-E
Wireless
RC-E5
Wired
RCH-E3RC-EX1AFDT 40/50/60/71/
100/125/140
Remote control (Option)
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
9
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
Powerful-Hi can be selected. Sound level: 40/50ZJXVF 39dB, 60ZJXVF 46dB, 71VNXVF1 46dB, 100VN(S)XVF1 51dB, 125/140VN(S)XVF 51dBAir flow: 40/50ZJXVF 20m3/min, 60ZJXVF 28m3/min, 71VNXVF1 28m3/min, 100VN(S)XVF1 37m3/min, 125/140VN(S)XVF 37m3/min
Set model name FDT40ZJXVF FDT50ZJXVF FDT60ZJXVF FDT71VNXVF1 FDT100VNXVF1
Indoor unit FDT40VF FDT50VF FDT60VF FDT71VF1 FDT100VF1
Outdoor unit SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX FDC100VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 0.93 / 1.06 1.29 / 1.29 1.52 / 1.70 2.04 / 1.94 2.50 / 2.58
EER/COP Cooling/Heating 4.30 / 4.25 3.88 / 4.19 3.68 / 3.94 3.48 / 4.12 4.00 / 4.34
Inrush current 220/230/240 VA
5 5 5 5 5
Max. running current 12 15 15 17 24
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
55 / 55 55 / 55 60 / 60 64 / 64 65 / 65
Outdoor Cooling/Heating 63 / 63 63 / 63 64 / 64 66 / 66 70 / 70
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 33 / 31 / 30 33 / 31 / 30 33 / 31 / 30 35 / 33 / 31 40 / 37 / 35
Heating (Hi/Me/Lo) 33 / 31 / 30 33 / 31 / 30 33 / 31 / 30 35 / 33 / 31 40 / 37 / 35
Outdoor Cooling/Heating 50 / 50 54 / 50 54 / 54 51 / 48 48 / 50
Air owIndoor
Cooling (Hi/Me/Lo)
m3/min
18 / 16 / 14 18 / 16 / 14 18 / 16 / 14 21 / 19 / 17 27 / 24 / 20
Heating (Hi/Me/Lo) 18 / 16 / 14 18 / 16 / 14 18 / 16 / 14 21 / 19 / 17 27 / 24 / 20
Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39 60 / 50 100 / 100
Exteriordimensions
IndoorHeightxWidthxDepth mm
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950 Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
Outdoor 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
Net weight
Indoor
kg
27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) 32.5(Unit:27 Panel:5.5)
Outdoor 45 60 105
Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.30 Max. 50 Max. 100
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -15~20 -20~20
Panel T-PSA-3BW-E
Air lter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
Set model name FDT125VNXVF FDT140VNXVF FDT100VSXVF1 FDT125VSXVF FDT140VSXVF
Indoor unit FDT125VF FDT140VF FDT100VF1 FDT125VF FDT140VFOutdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 3.28 / 3.43 4.19 / 4.20 2.50 / 2.58 3.28 / 3.43 4.19 / 4.20
EER/COP Cooling/Heating 3.81 / 4.08 3.34 / 3.81 4.00 / 4.34 3.81 / 4.08 3.34 / 3.81
Inrush current 220/230/240 VA
5 5 5 5 5
Max. running current 26 26 15 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
68 / 68 68 / 68 65 / 65 68 / 68 68 / 68
Outdoor Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38
Heating (Hi/Me/Lo) 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38
Outdoor Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52
Air owIndoor
Cooling (Hi/Me/Lo)
m3
/min
30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23
Heating (Hi/Me/Lo) 30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exteriordimensions
IndoorHeightxWidthxDepth mm
Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
Outdoor 1,300 x 970 x 370
Net weightIndoor
kg32.5(Unit:27 Panel:5.5)
Outdoor 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Panel T-PSA-3BW-E
Air lter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
10
FDTC
R410A
CEILING CASSETTE -4way Compact (600 X 600mm)-
Point
3 CLEARERAir Flow
Point
4 Installation Workability
RCN-TC-24W-ER
New shape & angled louver redirects the air
current away from the ceiling, to reduce
ceiling stains
For wireless control simply insert the
infrared receiver kit on a corner of thepanel
wirelessremote control
Point
5 Compact and Convenient
Fits into standard600 x 600 ceiling
Point
1 Taking OA (Outside Air) into inside Point
2 Quiet operation(Sound Pressure level in the Lo mode)
Current(Cooling/Heating)
New(Cooling)
New(Heating)
36
35
34
33
32
31
30
29
28
27
26
25
(dB)
35dB
30dB
32dB
5dBDown
3dBDown
[ INDOOR UNIT ]
600mm Drain PumpDrain can be discharged upward by 600 mm from the ceiling
surface close to the indoor unit.
It allows a piping layout with a high degree of freedom
depending on the installation location.
600 x 600 ceilingIndoor unit size (W:570 x D:570) brings easy installation for
600 x 600 ceiling and Panel size (700 x 700) is suitable for
600 x 600 ceiling. Height is the industry's lowest height level
248mm and weight is 15kg only.
Flexible hose
248mm
600mm
FDTC 40/50/60
RCN-TC-24W-ERRC-E5RC-EX1A
WirelessWired
RCH-E3
Remote control (Option)
OA Spacer TC-OAS-E (option)
Joint Duct TC-OAD-E (option)
Utilizing OA spacer which comes as optional equipment, outside aircan be taken inside.
OA OAPanel
300mm
Ceilingsurface
Indoor Unit FDTC
OA Spacer
Joint Duct
Using 1 joint duct:OA up to 1.3m3/min.
Using 2 joint ducts:OA from 1.3 to 2.6m3/min.
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
11
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Dimensions(Unit:mm)
Powerful-Hi can be selected. Sound level: 40/50/60ZJXVF 47dB Air flow: 40/50/60ZJXVF 13.5m3/min
Set model name FDTC40ZJXVF FDTC50ZJXVF FDTC60ZJXVF
Indoor unit FDTC40VF FDTC50VF FDTC60VF
Outdoor unit SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 )
Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 6.7 )
Power consumption Cooling/Heating kW 1.04 / 1.10 1.56 / 1.45 1.99 / 2.07
EER/COP Cooling/Heating 3.85 / 4.09 3.21 / 3.72 2.81 / 3.24
Inrush current 220/230/240 VA
5 5 5
Max. running current 12 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
60 / 60 60 / 60 60 / 60
Outdoor Cooling/Heating 63 / 63 63 / 63 64 / 64
Soundpressurelevel*
1
IndoorCooling (Hi/Me/Lo) 42 / 36 / 30 42 / 36 / 30 46 / 39 / 30
Heating (Hi/Me/Lo) 42 / 36 / 32 42 / 36 / 32 46 / 39 / 32
Outdoor Cooling/Heating 50 / 50 54 / 50 54 / 54
Air flowIndoor Cooling (Hi/Me/Lo)
m3/min11.5 / 9 / 7 11.5 / 9 / 7 13.5 / 10 / 7
Heating (Hi/Me/Lo) 11.5 / 9 / 8 11.5 / 9 / 8 13.5 / 10 / 8
Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39
Exteriordimensions
IndoorHeightxWidthxDepth mm
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
Outdoor 640 x 800(+71) x 290
Net weightIndoor
kg18.5(Unit:15 Panel:3.5)
Outdoor 45
Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2")
Refrigerant line (one way) length m Max.30
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -15~20
Panel TC-PSA-25W-E
Air filter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
12
Quiet, Lightweight and Compact
With the FDU71, the noise level is
only 25dB (low), weight is only 34kgand height is only 280mm.
In addition 600mm Drain Pump is
mounted in FDU71/100/125/140.
The indoor unit is completely
hidden in the ceiling, so this is
suitable for spaces with classy
interior decoration.
Dimensions (Unit:mm)
R410A
FDU 71/100/125/140
FDU
DUCT CONNECTED -High Static pressure-
Model FDU71VF1 Models FDU100VF1,125VF,140VF
Models FDU200,250VF (Micro inverter only, refer to P23)
RC-E5RC-EX1A
Wired
RCH-E3 RCN-KIT3-E
Wireless
600mm
[ INDOOR UNIT ]
Remote control (Option)
Enhanced installation workability
NEW
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
13
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.External static pressure is 35Pa(71), 60Pa (100/125/140).
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 200Pa.
*3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
Powerful-Hi can be selected. Sound level: 71VNXVF1 38dB, 100VN(S)XVF1 44dB, 125VN(S)XVF 45dB, 140VN(S)XVF 47dBAir flow: 71VNXVF1 24m3/min, 100VN(S)XVF1 36m3/min, 125VN(S)XVF 39m3/min, 140VN(S)XVF 48m3/min
Set model name FDU100VSXVF1 FDU125VSXVF FDU140VSXVF
Indoor unit FDU100VF1 FDU125VF FDU140VF
Outdoor unit FDC100VSX FDC125VSX FDC140VSXPower source 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0)
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42
EER/COP Cooling/Heating 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62
Inrush current 220/230/240 VA
5 5 5
Max. running current 16 18 19
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
65 / 65 67 / 67 70 / 70
Outdoor Cooling/Heating 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor Cooling/Heating 48 / 50 48 / 50 49 / 52
Air owIndoor
Cooling (Hi/Me/Lo)
m3/min
28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo) 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100External static pressure*2 Pa Standard:60 Max:200
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 1,370 x 740
Outdoor 1,300 x 970 x 370
Net weightIndoor
kg54
Outdoor 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3
Heating -20~20
Air lter Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Set model name FDU71VNXVF1 FDU100VNXVF1 FDU125VNXVF FDU140VNXVF
Indoor unit FDU71VF1 FDU100VF1 FDU125VF FDU140VF
Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 )
Power consumption Cooling/Heating kW 2.05 / 2.01 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42
EER/COP Cooling/Heating 3.46 / 3.98 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62
Inrush current 220/230/240 VA
5 5 5 5
Max. running current 17 25 29 30
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
65 / 65 65 / 65 67 / 67 70 / 70
Outdoor Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo) 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52
Air owIndoor
Cooling (Hi/Me/Lo)
m3/min
19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo) 19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100
External static pressure*2 Pa Standard:35 Max:200 Standard:60 Max:200
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 950 x 635 280 x 1,370 x 740
Outdoor 750 x 880(+88) x 340 1,300 x 970 x 370
Net weightIndoor
kg34 54
Outdoor 60 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50 Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3
Heating -20~20
Air lter Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
14
R410A
FDUM
DUCT CONNECTED -Middle Static pressure-
FDUM 50/60/71/
100/125/140
Dimensions (Unit:mm)Model FDUM50VF
Models FDUM100VF1,125VF,140VF
Models FDUM60VF,71VF1
Automatic external static pressure (E.S.P.) control
[ INDOOR UNIT ]
RC-E5RC-EX1A
Wired
RCH-E3
Filter kit (option)
UM-FL1EF : for 50UM-FL2EF : for 60, 71UM-FL3EF : for 100, 125, 140external static pressure loss:5pa
RCN-KIT3-E
WirelessRemote control (Option)
Round duct adapterIn case of requirements of
round duct adapter, please
access the followings for
details.Company
e-mailtel
: AIRZONE: [email protected]: +34-902-400-445
Duct design was simplified.
Using DC motor, the most optimum air flow volume can be achieved by
this automatic control.
Indoor unit will recognize external static pressure by itself automatically
and keep rated air flow volume.
Keep the sameair flow volume
Longer DuctDuct
Ceiling
New
FDUMDuct
Setting No.
E.S.P.
No.1
10Pa
No.2
20Pa
No.3
30Pa
No.4
40Pa
No.5
50Pa
No.6
60Pa
No.7
70Pa
No.8
80Pa
No.9
90Pa
No.10
100PaExternal Static Pressure (E.S.P.)can be set by E.S.P. button.
E.S.P. button
RC-E5
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
15
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
External static pressure is 35Pa (50/60/71), 60Pa (100/125/140).*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 100Pa.
*3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
Powerful-Hi can be selected. Sound level: 50ZJXVF 37dB, 60ZJXVF 36dB, 71VNXVF1 38dB, 100VN(S)XVF1 44dB, 125VN(S)XVF 45dB, 140VN(S)XVF 47dBAir flow: 50ZJXVF 13m3/min, 60ZJXVF 20m3/min, 71VNXVF1 24m3/min, 100VN(S)XVF1 36m3/min, 125VN(S)XVF 39m3/min, 140VN(S)XVF 48m3/min
Set model name FDUM50ZJXVF FDUM60ZJXVF FDUM71VNXVF1 FDUM100VNXVF1
Indoor unit FDUM50VF FDUM60VF FDUM71VF1 FDUM100VF1
Outdoor unit SRC50ZJX-S SRC60ZJX-S FDC71VNX FDC100VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 5.0 ( 1.1~ 5.6 ) 5.6 ( 1.1~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 1.38 / 1.45 1.54 / 1.75 2.03 / 1.99 2.68 / 3.02
EER/COP Cooling/Heating 3.62 / 3.72 3.64 / 3.83 3.50 / 4.02 3.73 / 3.71
Inrush current 220/230/240 VA
5 5 5 5
Max. running current 15 15 17 24
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
60 / 60 60 / 60 65 / 65 65 / 65
Outdoor Cooling/Heating 63 / 63 64 / 64 66 / 66 70 / 70
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 38 / 36 / 30
Heating (Hi/Me/Lo) 32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 38 / 36 / 30
Outdoor Cooling/Heating 54 / 50 54 / 54 51 / 48 48 / 50
Air owIndoor
Cooling (Hi/Me/Lo)
m3/min
10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 28 / 25 / 19
Heating (Hi/Me/Lo) 10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 28 / 25 / 19
Outdoor Cooling/Heating 40 / 33 41.5 / 39 60 / 50 100 / 100
External static pressure*2 Pa Standard:35 Max:100 Standard:60 Max:100
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 750 x 635 280 x 950 x 635 280 x 1,370 x 740
Outdoor 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
Net weightIndoor
kg29 34 54
Outdoor 45 60 105
Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.30 Max.50 Max.100
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3
Heating -15~20 -20~20
Air lter Filter kit : UM-FL1EF/UM-FL2EF/UM-FL3EF (option)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Set model name FDUM125VNXVF FDUM140VNXVF FDUM100VSXVF1 FDUM125VSXVF FDUM140VSXVF
Indoor unit FDUM125VF FDUM140VF FDUM100VF1 FDUM125VF FDUM140VF
Outdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSXPower source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0)
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0) 16.0 ( 4.0 ~ 18.0) 11.2 ( 4.0 ~ 16.0) 14.0 ( 4.0 ~ 18.0) 16.0 ( 4.0 ~ 20.0)
Power consumption Cooling/Heating kW 3.49 / 3.77 4.28 / 4.42 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42
EER/COP Cooling/Heating 3.58 / 3.71 3.27 / 3.62 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62
Inrush current 220/230/240 VA
5 5 5 5 5
Max. running current 26 26 15 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
67 / 67 70 / 70 65 / 65 67 / 67 70 / 70
Outdoor Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo) 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52
Air owIndoor
Cooling (Hi/Me/Lo)
m3/min
32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo) 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100External static pressure*2 Pa Standard:60 Max:100
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 1,370 x 740
Outdoor 1,300 x 970 x 370
Net weightIndoor
kg54
Outdoor 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3
Heating -20~20
Air lter Filter kit : UM-FL3EF (option)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
17
SPECIFICATIONS
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZJXVF 46dB, 60ZJXVF 48dB, 71VNXVF1 50dB, 100VN(S)XVF1 46dB, 125/140VN(S)XVF 50dBAir flow: 40/50ZJXVF 11m3/min, 60ZJXVF 20m3/min, 71VNXVF1 20m3/min, 100VN(S)XVF1 28m3/min, 125/140VN(S)XVF 32m3/min
Set model name FDEN40ZJXVF FDEN50ZJXVF FDEN60ZJXVF FDEN71VNXVF1 FDEN100VNXVF1
Indoor unit FDEN40VF FDEN50VF FDEN60VF FDEN71VF1 FDEN100VF1
Outdoor unit SRC40ZJX-S SRC50ZJX-S SRC60ZJX-S FDC71VNX FDC100VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 1.02 / 1.10 1.53 / 1.46 1.78 / 1.87 2.11 / 2.11 2.80 / 2.88
EER/COP Cooling/Heating 3.92 / 4.09 3.27 / 3.70 3.15 / 3.58 3.36 / 3.79 3.57 / 3.89
Inrush current 220/230/240 VA
5 5 5 5 5
Max. running current 12 15 15 17 24
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
60 / 60 60 / 60 60 / 60 62 / 62 64 / 64
Outdoor Cooling/Heating 63 / 63 63 / 63 64 / 64 66 / 66 70 / 70
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 44 / 41 / 39
Heating (Hi/Me/Lo) 39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 44 / 41 / 39
Outdoor Cooling/Heating 50 / 50 54 / 50 54 / 54 51 / 48 48 / 50
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 26 / 23 / 21
Heating (Hi/Me/Lo) 10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 26 / 23 / 21
Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39 60 / 50 100 / 100
Exteriordimensions
IndoorHeightxWidthxDepth mm
210 x 1,070 x 690 210 x 1,320 x 690 250 x 1,620 x 690
Outdoor 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
Net weight
Indoor
kg
28 37 37 49
Outdoor 45 60 105
Ref.piping size Liquid/Gas mm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.30 Max.50 Max.100
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -15~20 -20~20
Air filter, Q'ty Pocket Plastic net x2(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R
Set model name FDEN125VNXVF FDEN140VNXVF FDEN100VSXVF1 FDEN125VSXVF FDEN140VSXVF
Indoor unit FDEN125VF FDEN140VF FDEN100VF1 FDEN125VF FDEN140VFOutdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 3.86 / 3.77 4.98 / 4.69 2.80 / 2.88 3.86 / 3.77 4.98 / 4.69
EER/COP Cooling/Heating 3.24 / 3.71 2.81 / 3.41 3.57 / 3.89 3.24 / 3.71 2.81 / 3.41
Inrush current 220/230/240 VA
5 5 5 5 5
Max. running current 26 26 15 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
67 / 67 67 / 67 64 / 64 67 / 67 67 / 67
Outdoor Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43
Heating (Hi/Me/Lo) 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43
Outdoor Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52
Air flowIndoor
Cooling (Hi/Me/Lo)
m3
/min
29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23
Heating (Hi/Me/Lo) 29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exteriordimensions
IndoorHeightxWidthxDepth mm
250 x 1,620 x 690
Outdoor 1,300 x 970 x 370
Net weightIndoor
kg49
Outdoor 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Air filter, Q'ty Pocket Plastic net x2(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
18
Dimensions(Unit:mm)
R410A
Piping and drain hose connection can be selected out of 4-directions
and the selection makes installation workability more effective.
Due to slim design (Depth: 320mm), easy transportation and
installation are realized.
Easy MaintenanceThe surface of heat exchanger can be appeared only removing the
front panel. Easy cleaning of heat exchanger is possible.
Point
1 Wide and powerful air flowFDF
FLOOR STANDING
[ INDOOR UNIT ]
RCN-KIT3-E
Wirelessremote control (Option)
Wide and powerful air flow increase your comfort, realizing high
efficiency in combination with our highly advanced outdoor units.
Point
2Easy Transportation and Installation workability
FDF 71/100/125/140
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
19
SPECIFICATIONS
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level:71VNXVD1 42dB, 100VN(S)XVD1 54dB, 125/140VN(S)XVD 54dBAir flow: 71VNXVD1 20m3/min, 100VNXVD1 29m3/min, 125/140VN(S)XVD 29m3/min
Set model name FDF71VNXVD1 FDF100VNXVD1 FDF125VNXVD FDF140VNXVD
Indoor unit FDF71VD1 FDF100VD1 FDF125VD FDF140VD
Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 )
Power consumption Cooling/Heating kW 2.21 / 2.21 2.83 / 3.04 3.89 / 3.88 4.65 / 4.69
EER/COP Cooling/Heating 3.21 / 3.62 3.53 / 3.68 3.21 / 3.61 3.01 / 3.41
Inrush current 220/230/240 VA
5 5 5 5
Max. running current 17 24 26 24
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
61 / 61 65 / 65 73 / 73 73 / 73
Outdoor Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Heating (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Outdoor Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
18 / 16 / 14 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Heating (Hi/Me/Lo) 18 / 16 / 14 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Outdoor Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100
Exteriordimensions
IndoorHeightxWidthxDepth mm
1,850 x 600 x 320
Outdoor 750 x 880(+88) x 340 1,300 x 970 x 370
Net weight
Indoor
kg
49 52
Outdoor 60 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50 Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E(option)
Set model name FDF100VSXVD1 FDF125VSXVD FDF140VSXVD
Indoor unit FDF100VD1 FDF125VD FDF140VDOutdoor unit FDC100VSX FDC125VSX FDC140VSX
Power source 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 2.83 / 3.04 3.89 / 3.88 4.65 / 4.69
EER/COP Cooling/Heating 3.53 / 3.68 3.21 / 3.61 3.01 / 3.41
Inrush current 220/230/240 VA
5 5 5
Max. running current 15 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
65 / 65 73 / 73 73 / 73
Outdoor Cooling/Heating 70 / 70 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Heating (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Outdoor Cooling/Heating 48 / 50 48 / 50 49 / 52
Air flowIndoor
Cooling (Hi/Me/Lo)
m3
/min
26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Heating (Hi/Me/Lo) 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19Outdoor Cooling/Heating 100 / 100 100 / 100 100 / 100
Exteriordimensions
IndoorHeightxWidthxDepth mm
1,850 x 600 x 320
Outdoor 1,300 x 970 x 370
Net weightIndoor
kg52
Outdoor 105
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E(option)
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
20
FDT
FDT 100/125/140
CEILING CASSETTE -4way-
R410A
[ INDOOR UNIT ]
RC-E5RC-EX1A
Wired
RCH-E3 RCN-T-36W-E
Wireless
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VN(S)VF1 51dB, 125/140VN(S)VF 51dBAir flow: 100VN(S)VF1 37m3/min, 125/140VN(S)VF 37m3/min
Dimensions : refer to page 8
Micro Inverter
Remote control(Option)
Set model name FDT100VNVF1 FDT125VNVF FDT140VNVF FDT100VSVF1 FDT125VSVF FDT140VSVF
Indoor unit FDT100VF1 FDT125VF FDT140VF FDT100VF1 FDT125VF FDT140VF
Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capaci ty (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 2.76 / 2.74 4.05 / 3.77 4.98 / 4.57 2.76 / 2.74 4.05 / 3.77 4.98 / 4.57
EER/COP Cooling/Heating 3.62 / 4.09 3.09 / 3.71 2.81 / 3.50 3.62 / 4.09 3.09 / 3.71 2.81 / 3.50
Inrush current 220/230/240 VA
5 5 5 5 5 5
Max. running current 24 24 24 15 15 15
Sound powerlevel*
1
Indoor Cooling/Heating
dB(A)
65 / 65 68 / 68 68 / 68 65 / 65 68 / 68 68 / 68
Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38
Heating (Hi/Me/Lo) 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38 40 / 37 / 35 42 / 40 / 37 43 / 41 / 38
Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
27 / 24 / 20 30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23
Heating (Hi/Me/Lo) 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23 27 / 24 / 20 30 / 27 / 23 30 / 27 / 23
Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
Exteriordimensions
IndoorHeightxWidthxDepth mm
Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
Outdoor 845 x 970 x 370
Net weightIndoor
kg32.5(Unit:27 Panel:5.5)
Outdoor 81 83
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Panel T-PSA-3BW-E
Air filter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
21
FDU 100/125/140
FDU
DUCT CONNECTED -High Static pressure-
FDU 200/250
U-FCRA[For FDU 200/250]
Fan control kit(100~200Pa) (option)
RC-E5RC-EX1A
Wired
RCH-E3
SPECIFICATIONSDimensions : refer to page 12
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7 CDB, 6CWB.External static pressure is 60Pa (100/125/140), 100Pa (200/250).
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 200Pa.
*3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
R410A
SPECIFICATIONS
RCN-KIT3-E
Wireless
Remote control (Option)
Control box
Fan motorHigh static pressuresilent fan
Slide type fan system
Thin type duct connectionopening
Adaptability to higher static pressures
High static pressure of 200 Pa
NEW
Powerful-Hi can be selected. Sound level: 100VN(S)VF1 44dB, 125VN(S)VF 45dB, 140VN(S)VF 47dBAir flow: 100VN(S)VF1 36m3/min, 125VN(S)VF 39m3/min, 140VN(S)VF 48m3/min
Set model name F DU100VNVF1 F DU125VNVF
Indoor unit FDU100VF1 FDU125VFOutdoor unit FDC100VN FDC125VN
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cool ing capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 )
Power consumption Cooling/Heating kW 2.80 / 3.02 3.90 / 3.88
EER/COP Cooling/Heating 3.57 / 3.71 3.21 / 3.61
Inrush current 220/230/240 VA
5 5
Max. running current 25 27
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
65 / 65 67 / 67
Outdoor Cooling/Heating 70 / 70 72 / 72
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29
Heating (Hi/ Me/Lo) 38 / 36 / 30 40 / 34 / 29
Outdoor Cooling/Heating 49 / 49 50 / 51
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
28 / 25 / 19 32 / 26 / 20
Heating (Hi/ Me/Lo) 28 / 25 / 19 32 / 26 / 20
Outdoor Cooling/Heating 75 / 73 75 / 73
External static pressure*2 Pa Standard:60 Max:200
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 1,370 x 740
Outdoor 845 x 970 x 370
Net weightIndoor
kg54
Outdoor 81
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3
Heating -20~20
Air filter Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Set model name FDU140VNVF FDU100VSVF1 FDU125VSVF FDU140VSVF FDU200VSVF FDU250VSVF
Indoor unit FDU140VF FDU100VF1 FDU125VF FDU140VF FDU200VF FDU250VF
Outdoor unit FDC140VN FDC100VS FDC125VS FDC140VS FDC200VS FDC250VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0) 14.0 ( 5.0 ~ 14.5) 20.0 (7.0 ~ 22.4 ) 25.0 ( 10.0 ~ 28.0)
Nominal heating capacity (Min~Max) kW 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 22.4 ( 7.6 ~ 25.0 ) 28.0 ( 9.5 ~ 31.5 )
Power consumption Cooling/Heating kW 4.95 / 4.69 2.80 / 3.02 3.90 / 3.80 4.95 / 4.6950Hz:6.59 / 6.08 50Hz:9.91 / 8.50
60Hz:6.58 / 5.84 60Hz:10.21 / 8.22
EER/COP Cooling/Heating 2.83 / 3.41 3.57 / 3.71 3.21 / 3.61 2.83 / 3.4150Hz:3.03 / 3.68 50Hz:2.52 / 3.29
60Hz:3.04 / 3.84 60Hz:2.45 / 3.41
Inrush current 220/230/240 VA
5 5 5 5 5 5
Max. running current 28 16 18 19 24 27
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
70 / 70 65 / 65 67 / 67 70 / 70 75 / 75 76 / 76
Outdoor Cooling/Heating 73 / 73 70 / 70 72 / 72 73 / 73 74 / 74 74 / 74
Soundpressure
level*1
IndoorCooling (Hi/Me/Lo) 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 51 / 51 52 / 52
Heating (Hi/ Me/Lo) 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 51 / 51 52 / 52
Outdoor Cooling/Heating 51 / 51 49 / 49 50 / 51 51 / 51 57 / 57 57 / 58
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 51(Hi) / 60(Hi) 68(Hi) / 80(Hi)
Heating (Hi/ Me/Lo) 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 51(Hi) / 60(Hi) 68(Hi) / 80(Hi)
Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 150 / 145
External static pressure*2 Pa Standard:60 Max:200 Standard:100 Max:200
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 1,370 x 740 360 x 1,570 x 830
Outdoor 845 x 970 x 370 1,300 x 970 x 370 1,505 x 970 x 370
Net weightIndoor
kg54 92
Outdoor 81 83 122 140
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8") 9.52(3/8") / 25.4(1") 12.7(1/2") / 25.4(1")
Refrigerant line (one way) length m 50 Max.70
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15 Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3 -15~43*3
Heating -20~20 -15~20
Air filter Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
22
R410A
RCN-KIT3-E
Wireless
FDUM 100/125/140
RC-E5RC-EX1A
Wired
RCH-E3
Filter kit (option)
UM-FL3EF : for 100, 125, 140
external static pressure loss:5pa
Remote control (Option)
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
External static pressure of indoor units is 60Pa.*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 100Pa.
*3 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by naturalwind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VN(S)VF1 44dB, 125VN(S)VF 45dB, 140VN(S)VF 47dBAir flow: 100VN(S)VF1 36m3/min, 125VN(S)VF 39m3/min,140VN(S)VF 48m3/min
FDUM
DUCT CONNECTED -Low/Middle Static pressure-
[ INDOOR UNIT ]Micro Inverter
Dimensions : refer to page 14
Set model name FD UM 10 0V NV F1 FDU M12 5V NV F FD UM 14 0VN VF FD UM1 00 VS VF1 FD UM 12 5VS VF FD UM1 40 VS VF
Indoor unit FDUM100VF1 FDUM125VF FDUM140VF FDUM100VF1 FDUM125VF FDUM140VF
Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capaci ty (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 2.80 / 3.02 3.90 / 3.88 4.95 / 4.69 2.80 / 3.02 3.90 / 3.88 4.95 / 4.69
EER/COP Cooling/Heating 3.57 / 3.71 3.21 / 3.61 2.83 / 3.41 3.57 / 3.71 3.21 / 3.61 2.83 / 3.41
Inrush current 220/230/240 VA
5 5 5 5 5 5
Max. running current 24 24 24 15 15 15
Sound powerlevel*
1
Indoor Cooling/Heating
dB(A)
65 / 65 67 / 67 70 / 70 65 / 65 67 / 67 70 / 70
Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo) 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51
Air flow
IndoorCooling (Hi/Me/Lo)
m
3
/min
28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo) 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
External static pressure*2 Pa Standard:60 Max:100
Exteriordimensions
IndoorHeightxWidthxDepth mm
280 x 1,370 x 740
Outdoor 845 x 970 x 370
Net weightIndoor
kg54
Outdoor 81 83
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*3
Heating -20~20
Air filter Filter kit : UM-FL3EF (option)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
23
Remote control(Option)
R410A
FDEN 100/125/140
RCN-E1R
Wireless
RC-E5RC-EX1A
Wired
RCH-E3
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VN(S)VF1 46dB, 125/140VN(S)VF 50dBAir flow: 100VN(S)VF1 28m3/min, 125/140VN(S)VF 32m3/min
FDEN
CEILING SUSPENDED
Dimensions : refer to page 16
Set model name FD EN 10 0V NVF1 FD EN 125V NVF FD EN 14 0V NV F FD EN 10 0VS VF1 FD EN 12 5V SVF FDE N14 0VS VFIndoor unit FDEN100VF1 FDEN125VF FDEN140VF FDEN100VF1 FDEN125VF FDEN140VF
Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cool ing capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 2.85 / 2.97 4.45 / 4.08 5.80 / 4.92 2.85 / 2.97 4.45 / 4.08 5.80 / 4.92
EER/COP Cooling/Heating 3.51 / 3.77 2.81 / 3.43 2.41 / 3.25 3.51 / 3.77 2.81 / 3.43 2.41 / 3.25
Inrush current 220/230/240 VA
5 5 5 5 5 5
Max. running current 24 24 26 15 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
64 / 64 67 / 67 67 / 67 64 / 64 67 / 67 67 / 67
Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43
Heating (Hi/Me/Lo) 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43
Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
26 / 23 / 21 29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23
Heating (Hi/Me/Lo) 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23
Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
Exteriordimensions
IndoorHeightxWidthxDepth mm
250 x 1,620 x 690
Outdoor 845 x 970 x 370
Net weightIndoor
kg49
Outdoor 81 83
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Air filter, Q'ty Pocket Plastic net x2(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
24
R410A
RCN-KIT3-E
Wireless remote control (Option)
Dimensions : refer to page 18
FDF
FLOOR STANDING
[ INDOOR UNIT ]Micro Inverter
FDF 100/125/140
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level:100VN(S)VD1 54dB, 125/140VN(S)VD 54dBAir flow: 100VN(S)VD1 29m3/min, 125/140VN(S)VD 29m3/min
Set model name FDF100VNVD1 FDF125VNVD FDF140VNVD FDF100VSVD1 FDF125VSVD FDF140VSVD
Indoor unit FDF100VD1 FDF125VD FDF140VD FDF100VD1 FDF125VD FDF140VD
Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capaci ty (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 3.12 / 3.10 4.40 / 4.36 5.15 / 5.31 3.12 / 3.10 4.40 / 4.36 5.15 / 5.31
EER/COP Cooling/Heating 3.21 / 3.61 2.84 / 3.21 2.72 / 3.01 3.21 / 3.61 2.84 / 3.21 2.72 / 3.01
Inrush current 220/230/240 VA
5 5 5 5 5 5
Max. running current 24 24 24 15 15 15
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
65 / 65 73 / 73 73 / 73 65 / 65 73 / 73 73 / 73
Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73
Soundpressurelevel*1
IndoorCooling (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Heating (Hi/Me/Lo) 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Heating (Hi/Me/Lo) 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
Exteriordimensions
IndoorHeightxWidthxDepth mm
1,850 x 600 x 320
Outdoor 845 x 970 x 370
Net weightIndoor
kg52
Outdoor 81 83
Ref.piping size Liquid/Gas mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operatingtemperature range
CoolingC
-15~43*2
Heating -20~20
Air filter, Q'ty Plastic net x 1(Washable)
Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
25
FDC200VS(8.0HP)
FDC71VNX(3.0HP)
FDC250VS(10.0HP)
FDC71VNP(3.0HP)
FDC90VNP(3.5HP)
OUTDOOR UNIT (1.5-10.0HP)
Installation workabilityEnhanced installation workability thanks to the extended pipe length longest levelin the industry and pre-charged refrigerant.
Refrigerant precharged piping length extends up to 30m. This eliminates the need to add refrigerant on site, which sets it free from trouble of
excessive or insufficient charging of refrigerant, and allows carrying out the installation smoothly. That of Hyper inverter 1.5~2.5HP & Standard
inverter is up to 15m.
Point
1Piping length 100m (Hyper Inverter 4~6HP)
Point
2 Refrigerant precharged piping length extending to 30m
Hyper InverterHyper Inverter
Micro InverterMicro Inverter Standard InverterStandard Inverter
FDC125VNXFDC125VSX
(5.0HP)
FDC140VNXFDC140VSX
(6.0HP)
FDC100VNXFDC100VSX
(4.0HP)
SRC40ZJX-SSRC50ZJX-S*SRC60ZJX-S*(1.5HP~2.5HP)
*SRC50/60ZJX-S is common for both of outdoor units ofSRK50/60ZJX-S (Residential Air-conditioners) and 1.5,2, 2.5HP of Inverter Packaged Air-Conditioners.Common components make for easy inventory controland the installation procedure will be the same.
Due to application of blue coated fins (KS101) for the heatexchanger of new outdoor unit, corrosion resistance has beenimproved compared to current models.
Blue Fin(3~10HP)
This kit is recommended to be used in an area where thelowest temperature drops below 0C.
Base heater kit(option)
CW-H-E1applied forFDC71VNXFDC100~250VN,VSFDC100~140VNX,VSX
Heightdifference(Outdoor higher
than Indoor)
Pipinglength
Micro Inverter Standard Inverter
HP
1.5~2.5
3
4~6
30m
50m
100m
20m
30m
30m
Piping length Height difference
50m
70m
30m
30m
Piping length Height differenceHP
4~6
8.10
30m 20m
Piping length Height difference
3.3.5
HP
FDC100VNFDC125VNFDC140VN
FDC100VSFDC125VSFDC140VS
(4.0HP~6.0HP)
Refer to our Technical Manual in detail
Installation workability (FDC200VS,250VS)Using piping attachment that has flared connection and
brazed connection ends, there is no need conduct
brazing work inside the outdoor unit.Brazedconnection22.2mm
232mm
Flared
connection19.05mm
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
26
Standard Inverter [ INDOOR UNIT ]
4way
FDTLow/Middle Static pressure
FDUMHigh Static pressure
FDU
FDEN FDF Wired
RC-E5 RCH-E3RC-EX1A
Remote control(Option)
Wireless
RCN-KIT3-E
(For FDU, FDUM, FDF)RCN-E1R
(For FDEN)RCN-TC-36W-E
(For FDT)
Filter kit(option)
UM-FL2EF : for 71
UM-FL3EF : for 100
CEILING CASSETTE DUCT CONNECTED
CEILING SUSPENDED FLOOR STANDING
SPECIFICATIONS
(For FDT, FDU, FDUM, FDE)
(For FDUM)external static pressure loss:5pa
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Poewrful-Hi for FDT can be selected. Sound level : FDT71VNPVF1 46dB(A), FDT90VNPVF1 51dB(A) Air flow : FDT71VNPVF1 28m3/min, FDT90VNPVF1 37m3/minPoewrful-Hi for FDU can be selected. Sound level : FDU71VNPVF1 38dB(A), FDU90VNPVF1 44dB(A) Air flow : FDU71VNPVF1 24m3/min, FDU90VNPVF1 36m3/min
NEW
Standard Inverter
Set model name FDT71VNPVF1 FDT90VNPVF1 FDU71VNPVF1 FDU90VNPVF1
Indoor unit FDT71VF1 FDT100VF1 FDU71VF1 FDU100VF1
Outdoor unit FDC71VNP FDC90VNP FDC71VNP FDC90VNP
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 ) 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 )
Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 ) 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 )
Power consumption Cooling/Heating kW 2.50 / 1.90 2.67 / 2.19 2.63 / 1.96 2.65 / 2.25
EER/COP Cooling/Heating 2.84 / 3.74 3.37 / 4.11 2.70 / 3.62 3.40 / 4.00
Inrush current 220/230/240 VA
5 5 5 5
Max. running current 14.5 18.0 14.5 18.0
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
64 / 64 65 / 65 65 / 65 65 / 65
Outdoor Cooling/Heating 67 / 67 69 / 69 67 / 67 69 / 69
Sound
pressurelevel*1
IndoorCooling (Hi/Me/Lo) 35 / 33 / 31 40 / 37 / 35 33 / 29 / 25 38 / 36 / 30
Heating (Hi/Me/Lo) 35 / 33 / 31 40 / 37 / 35 33 / 29 / 25 38 / 36 / 30Outdoor Cooling/Heating 54 / 54 57 / 55 54 / 54 57 / 55
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
21 / 19 / 17 27 / 24 / 20 19 / 15 / 10 28 / 25 / 19
Heating (Hi/Me/Lo) 21 / 19 / 17 27 / 24 / 20 19 / 15 / 10 28 / 25 / 19
Outdoor Cooling/Heating 36 / 36 63 / 49.5 36 / 36 63 / 49.5
Exteriordimensions
IndoorHeightxWidthxDepth mm
unit: 246 x 840 x 840panel: 35 x 950 x 950
unit: 298 x 840 x 840panel: 35 x 950 x 950
280 x 950 x 635 280 x 1,370 x 740
Outdoor 640 x 800 x 290 750 x 880 x 340 640 x 800 x 290 750 x 880 x 340
Net weightIndoor
kg29.5 ( unit: 24 panel: 5.5 ) 32.5 ( unit: 27 panel: 5.5 ) 34 54
Outdoor 45 57 45 57
Ref.piping size Liquid/Gas mm 6.35 / 12.7 9.52 / 15.88 6.35 / 12.7 6.35 / 15.88
Refrigerant line (one way) length m 30
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20
Outdoor operatingtemperature range
CoolingC
-15~46*2
Heating -15~20
Air filter, Q'ty Pocket Plastic net x1(Washable) Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
-
5/24/2018 A - Catalog 2013 Inverter Packaged FD Series - HB91-13P01-E-A-218 Feb (Pls Do Not De...
http:///reader/full/a-catalog-2013-inverter-packaged-fd-series-hb91-13p01-e-a-218-fe
27
SPECIFICATIONS
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7 CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: FDF71VNPVD1 42dB, FDF90VNPVD1 54dB Air flow: FDF71VNPVD1 20m3/min, FDF90VNPVD1 29m3/min
The data are measured under the following conditions(ISO-T1).Cooling:Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating:Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.
*1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.*2 : If a cooling operation is conducted when the outdoor air temperature is 5C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Poewrful-Hi for FDUM can be selected. Sound level : FDUM71VNPVF1 38dB(A), FDUM90VNPVF1 44dB(A) Air flow : FDUM71VNPVF1 24m3/min, FDUM90VNPVF1 36m3/minPoewrful-Hi for FDEN can be selected. Sound level : FDEN71VNPVF1 50dB(A), FDEN90VNPVF1 46dB(A) Air flow : FDEN71VNPVF1 20m3/min, FDEN90VNPVF1 28m3/min
Standard Inverter
Set model name FDF71VNPVD1 FDF90VNPVD1
Indoor unit FDF71VD1 FDF100VD1
Outdoor unit FDC71VNP FDC90VNP
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 )
Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 )
Power consumption Cooling/Heating kW 2.63 / 2.08 2.79 / 2.25
EER/COP Cooling/Heating 2.70 / 3.41 3.23 / 4.00
Inrush current 220/230/240 VA
5 5
Max. running current 14.5 18.0
Sound powerlevel*1
Indoor Cooling/Heating
dB(A)
61 / 61 65 / 65
Outdoor Cooling/Heating 67 / 67 69 / 69
Soundpressurelevel*1
Indoor Cooling (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44Heating (Hi/Me/Lo) 39 / 35 / 33 50 / 48 / 44
Outdoor Cooling/Heating 54 / 54 57 / 55
Air flowIndoor
Cooling (Hi/Me/Lo)
m3/min
18 / 16 / 14 26 / 23 / 19
Heating (Hi/Me/Lo) 18 / 16 / 14 26 / 23 / 19
Outdoor Cooling/Heating 36 / 36 63 / 49.5
Exteriordimensions
IndoorHeightxWidthxDepth mm
1,850 x 600 x 320
Outdoor 640 x 800 x 290 750 x 880 x 340
Net weightIndoor
kg49 52
Outdoor 45 57
Ref.piping size Liquid/Gas mm 6.35 / 12.7 6.35 / 15.88
Refrigerant line (one way) length m 23
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20
Outdoor operatingtemperature range
CoolingC
-15~46*2
Heating -15~20
Air filter, Q'ty Plastic net x1(Washable)
Remote control (option) wired:RC-E5 installed wireless:RCN-KIT3-E
Standard Inverter
Set model name FDUM71VNPVF1 FDUM90VNPVF1 FDEN71VNPVF1 FDEN90VNPVF1
Indoor unit FDUM71VF1 FDUM100VF1 FDEN71VF1 FDEN100VF1
Outdoor unit FDC71VNP FDC90VNP FDC71VNP FDC90VNP
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 ) 7.1 ( 1.4 ~ 7.1 ) 9.0 ( 1.9 ~ 9.0 )
Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 ) 7.1 ( 1.0 ~ 7.1 ) 9.0 ( 1.5 ~ 9.0 )
Power consumption Cooling/Heating kW 2.63 / 1.96 2.65 / 2.25 2.50 / 1.96 2.75 / 2.25
EER/COP Cooling/Heating 2.70 / 3.62 3.40 / 4.00 2.84 / 3.62 3.27 / 4.00
Inrush current 220/230/240 VA
5 5 5 5
Max. running current 14.5 18.0 14.5 18.0
Sound powerlevel*
1
Indoor Cooling/Heating
dB(A)
65 / 65