Programmable displays with a wide se-
lection o inputs and outputs or display o temperature,
volume and weight, etc. Feature linearisation, scaling,
and dierence measurement unctions or programming
via PReset sotware.
Interaces or analogue and digital
signals as well as HART signals between sensors / I/P
converters / requency signals and control systems in Ex
zone 0, 1 & 2 and or some modules in zone 20, 21 & 22.
Galvanic isolators or analogue and digital
signals as well as HART signals. A wide product range
with both loop-powered and universal isolators eaturing
linearisation, inversion, and scaling o output signals.
PC or ront programmable modules with
universal options or input, output and supply. This range
oers a number o advanced eatures such as process
calibration, linearisation and auto-diagnosis.
A wide selection o transmitters or DIN
orm B mounting and DIN rail modules with analogue
and digital bus communication ranging rom application-
specifc to universal transmitters.
Displays
Temperature
Isolation
Ex interfaces
Universal
DK
UK
FR
DE
Side 1
Page 23
Page 45
Seite 67
S I G N A L S T H E B E S T
5 7 1 4
P r o g r a m m a b l eL E D I n d i c a t o r
N o . 5 7 1 4 V 1 0 1 - I N ( 0 9 5 1 )
F r o m s e r . n o . 0 6 0 1 3 7 0 0 1
http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/ -
8/22/2019 5714 V101 EnglishManual Jan2010
2/12
22 23
ProgrammabLe LeD inDiCator
Preview 5714
tabLe of Contents
Warnings ............................................................................ 24Safety instructions .............................................................. 25Declaration of Conformity .................................................. 27Front and back layout ........................................................ 28Applications ........................................................................ 29Technical characteristics .................................................... 29Mounting ............................................................................ 29Applications ........................................................................ 30Order .................................................................................. 31
Electrical specifications ...................................................... 29Sensor error detection ....................................................... 35Connections ....................................................................... 36Block diagram .................................................................... 37Routing diagram ................................................................. 38Scrolling help text .............................................................. 40Configuration / operating the function keys ...................... 42Graphic depiction of the relay function setpoint .............. 43
-
8/22/2019 5714 V101 EnglishManual Jan2010
3/12
24 25
symboL iDentifiCation
tl cl k: Warning / demand. Potentiallylethal situations.
t Ce kprovesthecomplianceofthemodulewiththeessentialrequirements of the directives.
warning!
This module is designed for connection to hazardous electricvoltages.Ignoringthiswarningcanresultinseverepersonalinjury or mechanical damage. To avoid the risk of electric shockand fire, the safety instructions of this manual must be observedandtheguidelinesfollowed.Thespecificationsmustnotbeexceeded, and the module must only be applied as described
inthefollowing.Priortothecommissioningofthemodule,thismanual must be examined carefully. Only qualified personnel(technicians) should install this module.
If the equipment is used in a manner not specified by themanufacturer, the protection provided by the equipment may beimpaired.
warning!
Until the module is fixed, do not connect hazardous voltages tothe module.
Thefollowingoperationsshouldonlybecarriedoutonadisconnected module and under ESD safe conditions:
Troubleshooting the module.
rp dl d Pr lcc a/s
l.
generaL
hazarD-
ous
voLtage
safety instruCtions
Definitions:
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, andalsotroubleshoottechnicallycorrectandinaccordancewithsafetyregulations.
Operators,beingfamiliarwiththecontentsofthismanual,adjustandoperatethe knobs or potentiometers during normal operation.
reCeiPt anD unPaCKing:
Unpackthedevicewithoutdamagingit.Thepackingshouldalwaysfollowthedevice until this has been permanently mounted. Check at the receipt of thedevicewhetherthetypecorrespondstotheoneordered.
environment:
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
aswellasrainandheavymoisture.Ifnecessary,heatinginexcessofthestatedlimitsforambienttemperaturesshouldbeavoidedbywayofventilation.
All modules fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
mounting:
Onlytechnicianswhoarefamiliarwiththetechnicalterms,warnings,andinstructionsinthemanualandwhoareabletofollowtheseshouldconnectthemodule.
Should there be any doubt as to the correct handling of the module, pleasecontact your local distributor or, alternatively,
PR electronics A/S, Lerbakken 10, DK-8410 Rnde, Denmark,
tel: +45 86 37 26 77.
Mountingandconnectionofthemoduleshouldcomplywithnationallegislation
formountingofelectricmaterials,i.a.wirecrosssection,protectivefuse,andlocation.DescriptionsofInput/Outputandsupplyconnectionsareshowninthe block diagram and side label.
-
8/22/2019 5714 V101 EnglishManual Jan2010
4/12
26 27
Thefollowingapplytofixedhazardousvoltages-connectedmodules:
Themax.sizeoftheprotectivefuseis10Aand,togetherwithapowerswitch,itshouldbeeasilyaccessibleandclosetothemodule.Thepowerswitchshouldbemarkedwithalabeltellingitwillswitchoffthe
voltage to the module.
uL instaLLation requirements:
For use on a flat surface of a type 1 enclosureUse 60/75C copper conducters onlyMax. ambient temperature ..................... 60CMax.wiresize,pins41...46.................... AWG 30-16Max.wiresize,others ............................ AWG 30-12UL file number ........................................ E248256
CaLibration anD aDjustment:
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. Thetechnician must use tools and instruments that are safe to use.
normaL oPeration:
Operatorsareonlyallowedtoadjustandoperatemodulesthataresafelyfixedin panels, etc., thus avoiding the danger of personal injury and damage. Thismeans there is no electrical shock hazard, and the module is easily accessible.
CLeaning:
Whendisconnected,themodulemaybecleanedwithaclothmoistenedwithdistilledwater.
LiabiLity:
To the extent the instructions in this manual are not strictly observed, thecustomercannotadvanceademandagainstPRelectronicsA/Sthatwouldotherwiseexistaccordingtotheconcludedsalesagreement.
DeCLaration of ConformityAs manufacturer
Pr lcc a/s
Lkk 10
DK-8410 rd
herebydeclaresthatthefollowingproduct:
tp: 5714
n: Pl LeD dc
isinconformitywiththefollowingdirectivesandstandards:
The EMC Directive 2004/108/EC and later amendments
en 61326-1
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the module.
TheLowVoltageDirective2006/95/ECandlateramendmentsen 61010-1
Rnde, 22 December 2009 Kim Rasmussen
Manufacturers signature
-
8/22/2019 5714 V101 EnglishManual Jan2010
5/12
28 29
front anD baCK Layout
Pc 1:FrontofPReview5714.
Pc 2: BackofPReview5714.
ProgrammabLe LeD inDiCator
Preview 5714
4-digit 14-segment LED indicator
Input for mA, V, potentiometer, RTD and TC
2 relays and analogue output
Universal voltage supply Front key programmable
applc:
Displayfordigitalreadoutofcurrent,voltage,temperatureorpotentiometer
signals.
Processcontrolwith2pairsofpotential-freerelaysand/oranalogueoutput.
Forlocalreadoutinextremelywetatmosphereswithaspeciallydesigned
splash-proof cover.
tccl ccc:
4-digitLEDindicatorwith13.8mm14-segmentcharacters.Max.displayreadout-1999...9999withprogrammabledecimalpoint,relayON/OFFindi-
cation.
Alloperationalparameterscanbeadjustedtoanyapplicationbyuseofthe
front keys.
PReview5714isavailablefully-configuredacc.tospecificationsreadyfor
process control and visualisation.
Helptextsineightlanguagescanbeselectedviaamenuitem.
Inversionswithrelayoutputstheusercanminimisetheinstallationtesttime
by activating / deactivating each relay independently of the input signal.
m:
Tobemountedinfrontpanel.Theincludedrubberpackingmustbemounted
betweenthepanelcutoutholeandthedisplayfronttoobtainIP65(NEMA4)
tightness.Forextraprotectioninextremeenvironments,PReview5714can
bedeliveredwithaspeiallydesignedsplash-proofcoverasaccessory.
-
8/22/2019 5714 V101 EnglishManual Jan2010
6/12
+
-
12
11
26
25
24
23
22
21
32
31
1 2
1 2
+
- +
-
46
45
44
43
42
41
4 3 2
TC1 2
+
-
30 31
Applications
Input signals:Current
Potentio-
meter
Output signals:
2 changeover relaysAnalogue, 0/4...20 mA
Supply:
21.6...253 VAC
or
19.2...300 VDC
Voltage
RTD -Connection,wires
2-wiretra
nsmitter
NB! Please order the splash-proof cover seperately. Order No. 8335.
elccl pcc:
spcc :
-20C to +60C
C pcc:
Supply voltage, universal ............................ 21.6...253 VAC, 50...60 Hz or19.2...300 VDC
Consumption
Isolation voltage, test / operation .............. 2.3 kVAC / 250 VACSignal- / noise ratio .................................... Min. 60 dB (0...100 kHz)Response time (0...90 %, 100...10 %), programmable:
Temperature input................................. 1...60 sCurrent / voltage input.......................... 0.4...60 s
Calibration temperature.............................. 20...28CAccuracy, the greater of general and basic values:
General values
Input type
Absoluteaccuracy
Temperaturecoefficient
All 0.1% of reading 0.01% of reading / C
Type Internal consumption Max. consumption
5714A 2.2 W 2.5 W
5714B 2.7 W 3.0 W
5714C 2.7 W 3.0 W
5714D 3.2 W 3.5W
tp v
5714 Standard. . . . . . . . . . . . . . . . . . .: A
2 relays . . . . . . . . . . . . . . . . . . . .: BAnalogue output . . . . . . . . . . . . .: CAnalogue output and 2 relys . . .: D
od: 5714
-
8/22/2019 5714 V101 EnglishManual Jan2010
7/12
32 33
Auxiliary supplies:2wiresupply(pin46...45)........................... 25...15 VDC / 0...20 mAWire size, pin 41...46 (max.) ........................ 1 x 1.5 mm2strandedwireWire size, others (max.) ............................... 1 x 2.5 mm2strandedwireRelative humidity ......................................... < 95% RH (non cond.)Dimensions (HxWxD) ................................... 48 x 96 x 120 mmCutout dimensions ...................................... 44.5 x 91.5 mmProtection degree (mounted in panel) ......... IP65
Weight ......................................................... 230 g
rtD d p p:
Input for RTD types:Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000Ni50, Ni100, Ni120, Ni1000
Cableresistancepr.wire,RTD(max.)......... 50
Input
type
Min.
value
Max.
value
StandardPt100Ni100
Potentiometer
-200C-60C10
+850C+250C100 k
IEC60751DIN 43760
-
Sensor current, RTD .................................... Nom. 0.2 mAEffect of sensor cable resistance(3-/4-wire),RTD......................................... < 0.002 /Sensor error detection, RTD ....................... YesShort curcuit detection, RTD....................... < 15
tC p:
NB.:TCinputtypeBcanbemeasuredandconfigureddownto0C,butthe basic accuracy is only valid in the range 85...1820C
Cold junction compensation (CJC)via internally mounted sensor ............... < 2.0C 0.2C/C
Sensor error detection, all TC types ........... YesSensor error detection ................................ YesSensor error current: when d ete ct ing ...................................... Nom. 2 A
else ........................................................ 0 A
C p:
Measurement range .................................... 0...20 mA
Programmable measurement ranges .......... 0...20 and 4...20 mAInput resistance ........................................... Nom. 20 + PTC 25 Sensor error detection:
loop break 4...20 mA ............................. Yes
vl p:
Measurement range .................................... 0...12 VDCProgrammable measurement ranges .......... 0...1 / 0,2...1 /
0...10 / 2...10 VDCInput resistance ........................................... Nom. 10 M
Type
Min.value
Max.value
Standard
BEJKLNRSTU
W3W5LR
0C-100C-100C-180C-200C-180C-50C-50C-200C-200C
0C0C
-200C
+1820C+1000C+1200C+1372C+900C+1300C+1760C+1760C+400C+600C+2300C+2300C+800C
IEC 60584-1IEC 60584-1IEC 60584-1IEC 60584-1DIN 43710
IEC 60584-1IEC 60584-1IEC 60584-1IEC 60584-1DIN 43710
ASTM E988-90ASTM E988-90GOST 3044-84
Basic values
Input type
Basicaccuracy
Temperaturecoefficient
mA 4 A 0.4 A / C
Volt 20 V 2 V / C
Potentiometer 0.1 0.01 / C
Pt100 0.2C 0.02C / C
Ni100 0.3C 0.03C / C
TC type:E, J, K, L, N, T, U
1C
0.05C / C
TC type: R, S,W3, W5, LR
2C
0.2C / C
TC type: B85...400C
4.5C
0.45C / C
TC type: B400...1820C
2C
0.2C / C
EMC immunity influence ..................................... < 0,5% of reading
-
8/22/2019 5714 V101 EnglishManual Jan2010
8/12
34 35
op:
Dpl:
Display readout ........................................... -1999...9999 (4 digits)Decimal point .............................................. ProgrammableDigit height .................................................. 13.8 mmDisplay updating ......................................... 2.2 times / s
Input outside input range isindicated by ................................................. Explanatory text
C :
Signal range (span)...................................... 0...20 mAProgrammable signal ranges ...................... 0...20 / 4...20 /
20...0 / 20...4 mALoad (max.) .................................................. 20 mA / 800 / 16 VDCLoad stability ............................................... 0.01% of span / 100 Sensor error detection ................................ 0 / 3.5 / 23 mA / noneNAMURNE43up/downscale .................. 23 mA / 3.5 mAOutput limitation:
on 4...20 and 20...4 mA signals............. 3,8...20.5 mAon 0...20 and 20...0 mA signals............. 0...20.5 mA
Current limit ................................................. 28 mA
rl p:
Relay function.............................................. SetpointHysteresis, in % / display counts ............... 0.1...25% / 1...2999On and Off delay ......................................... 0...3600 sSensor error detection ................................ Make / Break / Hold
Max. voltage ................................................ 250 VRMSMax. current ................................................ 2 A / ACMax.ACpower ........................................... 500 VAMax. current at 24 VDC............................... 1 A
m ppl:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No. 2.4
gost r ppl:
VNIIM, Cert. no. ........................................... Seewww.prelectronics.com
od : sdd:EMC 2004/108/EC ...................................... EN 61326-1LVD 2006/95/EC .......................................... EN 61010-1UL, Standard for Safety .............................. UL 508
Sensor error check in 5714 variants
Variant: Configuration Sensor error detection:
5714A Always: ON
5714BERR1=NONE, ERR2=NONE: OFF
else: ON
5714CO.ERR=NONE: OFF
else: ON
5714D
ERR1=NONE, ERR2=NONE, O.ERR=NONE: OFF
else: ON
s dc / dc d :
Outside range readout (IN.LO, IN.HI):If the valid range of the A/D converter or the polynomial is exceeded
Input Range Readout Limit
VOLT
0..1 V / 0.2..1 VIN.LO < -25 mV
IN.HI > 1.2 V
0..10 V / 2..10 VIN.LO < -25 mV
IN.HI > 12 V
CURR 0..20 mA / 4..20 mA IN.LO < -1.05 mA
IN.HI > 25.05 mA
POTM -IN.LO < -0.5%
IN.HI > 100.5%
TEMP TC / RTD IN.LO < temperature rangeIN.HI > temperature range
Sensor error detection (SE.BR, SE.SH):
Input Range Readout Limit
CURR Loop break (4..20mA) SE.BR = 21 mA
TEMP
TC SE.BR > ca. 750 kohm / (1,25V)
Pt1002-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Pt1003-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Pt1004-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Displayreadoutbelowmin./abovemax.(-1.9.9.9,9.9.9.9):
Input Range Readout Limit
CURR All-1.9.9.9 Display readout 9999
VOLT All-1.9.9.9 Display readout 9999
POTM --1.9.9.9 Display readout 9999
-
8/22/2019 5714 V101 EnglishManual Jan2010
9/12
+-
+- +-Tx
+-
31 32
41 42 43 44 45 4641 42 43 44 45 4641 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46 41 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46
+- mA
11 12
R2R1
21 22 23 24 25 26
I+ Gnd.
11
12
31
32
CPU
AD
EEPROM
0.2mA
PTC 2
0
5714
1
2
3
4
46
45
44
43
42
41
TC
+
V
4
3
2
2122
23
2425
26
R1
R2
13
2
Tx+ +
+
mA
36 37
ConneCtions
RTD,2-wire RTD,3-wire RTD,4-wire
PotentiometerVoltage
TC 2-wiretransmitter Current
Current Relays
ip:
op:Supply:
I
Output
Common
Relay1N.O.
Relay1N.C.
Common
Relay2N.O.
Relay2N.C.
Supply
Supply
21.6...253VAC
or
19.2...300VDC
VersionD
Int.
CJC
2-wiresupply
>15VDC
Input+,
mA
Inputgnd.
RTD,
wires
Potm.
bLoCK DiagramReadoutathardwareerrorError search Readout Error cause
Test of internal communication uC / ADC HW.ER Permanent error in ADC
Test of internal CJC sensor CJ.ER CJC sensor defect
Check-sum test of the configuration in RAM RA.ER Error in RAM
Check-sum test of the configuration in EEPROM EE.ER Error in EEPROM
! Error indications in the display blink once a second. The help text explains the error.
-
8/22/2019 5714 V101 EnglishManual Jan2010
10/12
-
8/22/2019 5714 V101 EnglishManual Jan2010
11/12
40 41
sCroLLing heLP textDpl dl , d :se.br --> SENSOR WIRE BREAKAGEse.sh --> SENSOR SHORT CIRCUITin.hi --> INPUT OVERRANGEin.Lo --> INPUT UNDERRANGE9.9.9.9 --> DISPLAY OVERRANGE-1.9.9.9 --> DISPLAY UNDERRANGEhw.er --> HARDWARE ERRORee.er --> EEPROM ERROR -
CHECK CONFIGURATIONra.er --> RAM MEMORY ERRORCj.er --> CJC SENSOR ERROR
f (eld):f.setreL1 --> FAST SET MENU -
SELECT RELAYreL2 -->
setPxxxx --> RELAY SETPOINT - PRESS OK TO SAVE
f (Dld):setPxxxx --> RELAY SETPOINT - READ ONLY
C :LangDE --> DE - WAEHLE DEUTSCHEN HILFETEXTDK --> DK - VAELG DANSK HJAELPETEKSTES --> ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOLFR --> FR - SELECTION TEXTE DAIDE
EN FRANCAISIT --> IT - SELEZIONARE TESTI DIAIUTO ITALIANI
SE --> SE - VALJ SVENSK HJALPTEXTUK --> UK - SELECT ENGLISH HELPTEXTCZ --> CZ - VYBER CESKOU NAPOVEDU
Passxxxx --> SET CORRECT PASSWORD
inC.LIN* --> TEXT ENTERED BY USER IN PRESETCURR --> CURRENT INPUT
VOLT --> VOLTAGE INPUTPOTM --> POTENTIOMETER INPUTTEMP --> TEMPERATURE SENSOR INPUT
rang w c lcd:0-20 --> INPUT RANGE IN mA4-20 --> INPUT RANGE IN mA
rang w l lcd:0-10 --> INPUT RANGE IN VOLT2-10 --> INPUT RANGE IN VOLT0.0-1 --> INPUT RANGE IN VOLT0.2-1 --> INPUT RANGE IN VOLT
Ca.LoYES --> CALIBRATE POTENTIOMETER LOWNO --> CALIBRATE POTENTIOMETER LOW
Ca.hiYES --> CALIBRATE POTENTIOMETER HIGHNO --> CALIBRATE POTENTIOMETER HIGH
DeC.P1111 --> DECIMAL POINT POSITION111.1 --> DECIMAL POINT POSITION11.11 --> DECIMAL POINT POSITION1.111 --> DECIMAL POINT POSITION
Di.Loxxxx --> DISPLAY READOUT LOW
Di.hi -->xxxx --> DISPLAY READOUT HIGH
reL.uPERC --> SET RELAY IN PERCENTAGEDISP --> SET RELAY IN DISPLAY UNITS
tyPePT --> SELECT PT SENSOR TYPENI --> SELECT NI SENSOR TYPETC --> SELECT TC SENSOR TYPE
Pt.ty10 --> SELECT PT SENSOR TYPE20 --> SELECT PT SENSOR TYPE50 --> SELECT PT SENSOR TYPE100 --> SELECT PT SENSOR TYPE200 --> SELECT PT SENSOR TYPE250 --> SELECT PT SENSOR TYPE300 --> SELECT PT SENSOR TYPE400 --> SELECT PT SENSOR TYPE500 --> SELECT PT SENSOR TYPE1000 --> SELECT PT SENSOR TYPE
ni.ty50 --> SELECT NI SENSOR TYPE100 --> SELECT NI SENSOR TYPE120 --> SELECT NI SENSOR TYPE1000 --> SELECT NI SENSOR TYPE
Conn w P d n lcd2W --> SELECT 2-WIRE SENSOR CONNECTION3W --> SELECT 3-WIRE SENSOR CONNECTION4W --> SELECT 4-WIRE SENSOR CONNECTION
tC.tyTC. B --> SELECT TC SENSOR TYPETC. E --> SELECT TC SENSOR TYPETC. J --> SELECT TC SENSOR TYPETC. K --> SELECT TC SENSOR TYPETC. L --> SELECT TC SENSOR TYPETC. N --> SELECT TC SENSOR TYPETC. R --> SELECT TC SENSOR TYPETC. S --> SELECT TC SENSOR TYPETC. T --> SELECT TC SENSOR TYPE
TC. U --> SELECT TC SENSOR TYPETC.W3 --> SELECT TC SENSOR TYPETC.W5 --> SELECT TC SENSOR TYPETC.LR --> SELECT TC SENSOR TYPE
DeC.P w p lcd1111 --> DECIMAL POINT POSITION111.1 --> DECIMAL POINT POSITION
unitC --> DISPLAY AND RELAY SETUP IN CELSIUSF --> DISPLAY AND RELAY SETUP IN
FAHRENHEIT
reL1SET --> ENTER RELAY 1 SETUPSKIP --> SKIP RELAY 1 SETUPOFF --> RELAY 1 DISABLED
setPxxxx --> RELAY SETPOINT
aCt1INCR --> ACT IVATE AT INCREASING SIGNALDECR --> ACTIVATE AT DECREAS ING SIGNALL
hys1xxxx --> RELAY HYSTERESIS
err1HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERRORDEAC --> DEACTIVATE RELAY AT ERRORNONE --> UNDEFINED STATUS AT ERROR
on.Dexxxx --> RELAY ON-DELAY IN SECONDS
of.Dexxxx --> RELAY OFF-DELAY IN SECONDS
reL2SET --> ENTER RELAY 2 SETUPSKIP --> SKIP RELAY 2 SETUPOFF --> RELAY 2 DISABLED
setP
xxxx --> RELAY SETPOINT
aCt2INCR --> ACT IVATE AT INCREASING SIGNALDECR --> ACTIVATE AT DECREAS ING SIGNAL
hys2xxxx --> RELAY HYSTERESIS
err2HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERRORDEAC --> DEACTIVATE RELAY AT ERRORNONE --> UNDEFINED STATUS AT ERROR
on.Dexxxx --> RELAY ON-DELAY IN SECONDS
of.Dexxxx --> RELAY OFF-DELAY IN SECONDS
a.out0-20 --> OUTPUT RANGE IN mA4-20 --> OUTPUT RANGE IN mA20-0 --> OUTPUT RANGE IN mA20-4 --> OUTPUT RANGE IN mA
o.Loxxxx --> DISPLAY VALUE FOR OUTPUT LOW
o.hixxxx --> DISPLAY VALUE FOR OUTPUT HIGH
o.err23 mA --> NAMUR NE43 UPSCALE AT ERROR3,5 mA --> NAMUR NE43 DOWNSCALE AT ERROR0mA --> DOWNSCALE AT ERRORNONE --> UNDEFINED OUTPUT AT ERROR
resPxxx,x --> ANALOGUE OUTPUT RESPONSE TIME
IN SECONDS
e.PasNO --> ENABLE PASSWORD PROTECTION
YES --> ENABLE PASSWORD PROTECTIONn.Pasxxxx --> SELECT NEW PASSWORD
-
8/22/2019 5714 V101 EnglishManual Jan2010
12/12
tOff N.C.On N.C. On N.C.
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
0
Off N.O. Off N.O.On N.O.
t
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
0
Off N.O. Off N.O.On N.O.
Off N.C.On N.C. On N.C.
42 43
Configuration / oPerating the
funCtion Keys
Documentation for routing diagram.
i l:
When configuring the display you are guided through all parameters, you can
choosethesettingswhichfittheapplication.Foreachmenuthereisascrol-
linghelptextwhichisautomaticallyshowninthedisplay,thisstartsafter5
seconds if no key has been activated.
Configuration is carried out by using the 3 function keys.
1 willincreasethenumericalvalueorchoosethenextparameter.
2 willdecreasethenumericalvalueorchoosethepreviousparameter.
3 willacceptthechosenvalueandendthemenu.
If a function does not exist in the display all parameters are skipped to make
the configuration as simple as possible.
Oncetheconfigurationhasbeenenteredthedisplaywillshow----.
Pressing and holding3willreturntothepreviousmenuorreturntothedefault
state(1.0)withoutsavingthechangedvaluesorparameters.
Ifnokeyisactivatedfor2minutes,thedisplaywillreturntothedefaultstate
(1.0)withoutsavingthechangedvaluesorparameters.
f pl:
f p d d l :Thesemenusallowyoutochange
the set point quickly and to check the operation of the relays.
Pressing 1 and2atthesametimewillchangethestateoftherelaythischange
is indicated by the diodes on the display. Pressing3willsavethesetpoint
change.
Holdingdown3formorethan0.5secondswillreturntheunittothedefault
statewithoutchangingthesetpoint.
Pd pc:
Usingapasswordwillstopaccesstothemenuandparameters.Therearetwo
levelsofpasswordprotection.Passwordsbetween00004999allowaccess
tothefastsetpointadjustmentandrelaytest.(Usingthispasswordstops
accesstoallotherpartsofthemenu).Passwordsbetween50009999stop
access to all parts of the menu, fast set point and relay test. (Current set
pointisstillshown).Byusingthemasterpassword2008,allconfiguration
menus are available.
gpc dpc l c p:
Relay unitsRelay units
Setpoint = 50
Hysteresis = 10
Hysteresis = 10
Setpoint = 50
rl c: ic rl c: Dc