Download - 01 Presentasi Sogi Litbang - Solida 01
SISTEM OTOMASI GARDU INDUK
(SOGI)
Jakarta, 1 Juni 2011 PT PLN (Persero) P3B Jawa Bali
Fungsi Yang Terpasang Di P3B JBNo 1 2 Perangkat RTU C264 SAS Pacis Fungsi % 100 80 Time Tag di HMI, Lokal HMI, IED beda Keterangan
3 4
PLC T390 PLC 5000
40 0 Belum berfungsi
Uji Fungsi SCADA Di P3B JBSOGINARI RCS 9698 L ABB SYS 600 L Siemens SICAM PAS L ALSTOM PACIS BL
RTUL = Lulus BL = Belum Lulus
SELTA STCE L
ABB 560 L
Siemens AK 1703 L
ALSTOM C264 L
SOGI
Standard SPLN Teleinformasi Data untuk Pemeliharaan Instalasi Sistem Tenaga Listrik SPLN S5.002:2008 dengan SK Dir No.169.K/DIR/2009 Protokol IEC 61850 : IED proteksi dan IED BCU Protokol IEC 60870-5-101
Syarat Teknis
Relay Proteksi lulus Real Time Digital Simulator (RTDS) dari PLN PUSLITBANG Lulus uji protokol IEC 60870-5-101 dan IEC 61850 Lulus komunikasi partyline dan serial port RS232 Lulus uji digital input, digital output ,analog input, analog output Time tag di IED, Lokal HMI, Dispatcher
Syarat Non Teknis Surat keterangan kepuasan pengguna dari P3B JB Sudah diimplementasikan di negara maju diluar negara pembuat Original Engineering Manufacture
Proses Lelang Dua sampul satu tahap : Sampul pertama : Syarat administrasi dan teknik dan Uji fungsi Sampul ke dua : Penawaran harga
Perencanaan PLNMembangun secara terpadu untuk : Gardu Induk SOGI yang memenuhi Teleinformasi Data untuk Pemeliharaan Instalasi Sistem Tenaga Listrik SPLN S5.002:2008 dengan SK Dir No.169.K/DIR/2009
Konfigurasi Master Station01 02 03 04 05 06SD
PROLIANT
8000
ESC
SD
DLT
A
B
C
D
E
F
G
HSELECTED ON-LINE
A
B
C
D
E
F
G
HSELECTED ON-LINE
SD
CONSOLE LOOP BRI S/T CONSOLE WIC 0 OK FDX 100 LNK AUX LOOP DSU CPU S3 WIC 1 OK SD DSU CPU S3
Cisco 1720WIC 0 OK
BRI S/T
FDX 100 LNK
AUX
WIC 1 OK
08LCD 1 bh
12 13
Cisco 1720
14
OK
OK
Inter Center Link ( IEC 870-6 (ICCP) )
LP
B1
B2
LP
B1
B2
07
09
A
B
C
D
E
F
G
HSELECTED ON-LINE
11A B C D E F G HSELECTED ON-LINE
RTU IEC 870-5-101, DNP 3.0 Serial RTU IEC 870-5-104 Ethernet
SD
PROLIANT
8000
ESC
15SD
16DLT
10
Arsitektur SOGI
Kinerja SOGI Kapasitas station unit minimal 10.000 I/O. Kapasitas Otomasi GI minimal 96 IED Kapasitas switch 48 bh, fault recovery time max 150 ms. Pertukaran data peer to peer melalui protocol IEC 61850 maksimal 30 milidetik. Keakuratan telemetering dari IED BCU: Arus dan tegangan kelas 0,5 Daya aktif dan reaktif (MW dan MVAr) kelas 0,5 Energi meter (MWh dan MVArh) kelas 1,0
Switchover otomatis (failover) station unit maksimal 30 detik. Penyimpanan urutan kejadian minimal 120.000 event dan 60 recording pengukuran selama 100 hari.
Kapan SOGI Di Bangun Gardu Induk Baru Penambahan Bay baru Rehabilitasi Gardu Induk Tersedia media komunikasi 64 kbps
Opsi Pembangunan SOGIBay Level Opsi 1 Opsi 2 Opsi 3 : : : RTU IED I/O Proteksi Existing Existing Panel Kontrol Existing BCU per CB BCU & IED Proteksi Bay Baru BCU & IED Prot BCU & IED Prot
Yang Tidak Dibahas Pada Spesifikasi SOGI Peralatan tegangan tinggi Power supply Telekomunikasi Disturbance fault recorder Fault locator Energy meter
Standard Teleinformasi SCADA Fungsi Operasi Dan PemeliharaanMnemoVDCF
DesignationVDC FAILURE..
220RF 220VDC RECTIFIER FAILURE110RF 10VDC RECTIFIER FAILURE
Jumlah Input/Output IBTOperasiTelemetering 4
Pemeliharaan37
Remote ControlTelesignal Double Telesignal Single
36 17
1817 129
Station Level Opsi 1Control Center
Gateway Station Unit 1 Station Unit 2
Switch
Switch
Switch
Station Level Opsi 2Control Center
Gateway Station Unit 1 Station Unit 2
Switch
Switch
Switch
Bay TransformerBus A
Q0A
Q0AB
Q0B
Bus B
1 IED untuk bay TRAFO
Bay Level Double BusbarBus 1Bus 2 Q1 Q2 Q1 Q2 Q1 Q2 Q0
Single Line Diagram
Q0 Q9 Q8 OHL
Q0
Transfor mer
Bus Coupler
Station LAN IEC 61850: Ethernet 100 Mbps Fiber Optic single ring
switch
switch
switch
switch
switch
OHL
Trafo
Trafo
Busbar & Coupler
Common
BCU MPU BPU
BCU AVR
MPU BPU1 BPU2
BCU MPU BPU
IED I/O
Level 150 kV One Half BreakerBus AStation LAN IEC 61850: Ethernet 100 Mbps Fiber Optic single ring
Q0A
switchQ0ABOHL
switch
switch
switch
switch
switch
Diameter
Trafo
Trafo
Busbar
Common
MPUQ0B
BCU A BCU AB BCU B
AVR
MPU BPU 1 BPU 2 CCP
BUS PRO BUS A BUS PRO BUS B CBF AB(N Diemeter)
IED I/O
BPUBus B
CCP
Level 500 kV One Half BreakerBus AStation LAN IEC 61850: Ethernet 100 Mbps Fiber Optic single ring
Q0Aswitch Bay switch switch
switch
switch
switch
switch
switch
switch
Q0AB
OHL
OHLMPU 2 CCP 2
DiameterBCU A BCU AB BCU B
TrafoBCU 150 kV AVR RST
TrafoMPU1 BPU1 CCP1
TrafoMPU2 BPU2
BUSBARBUSPRO Bus A Main 1 BUSPRO Bus B Main 1 CBF AB1(n diameter)
BUSBARBUSPRO Bus A Main 2 BUSPRO Bus B Main 2 CBF AB2(n diameter)
COMMONIED I/O
Q0B Bus BMPU 1
CCP 1
CCP2
Penambahan Bay Baru dan Up Grade RTU
Gateway Station Unit 1 Station Unit 2
Switch
Switch
Switch
Switch
Switch
IED I/O
MPU BPU-1 BPU-2
BCU AVR
Bay Trafo Baru
Penambahan Diameter, Unit Pembangkit dan IBT
Station Level HMI Station Unit : Server redundant Fungsi SCADA, historikal data dan statistik Server berfungsi untuk manajemen dari IED dan workstation.
Gateway Dapat menampung IED sesuai kapasitas I/O Dapat meneruskan perintah kontrol dari Master station atau lokal kontrol. Inverter 110 VDC ke 220 VAC.
Peralatan Yang Diakusisi SOGI1. Pemutus (CB): a. Status & perintah open-close b. Counter of circuit Breaker c. Pressure (SF6) d. Alarm gangguan (misal: SF6 alarm)CB untuk transmisi
Kontrol box CB
Indicator alarm tekanan SF6 (berupa kontak saja)
Transducer: tekanan SF6 ke 4-20 mA untuk monitor SF6 Pressure
Peralatan Yang Diakusisi SOGI2. Pemisah (DS/isolator) a. Status & perintah open-close b. Alarm gangguan
Peralatan Yang Diakusisi SOGI3. Sakelar pentanahan (Earthing Switch) a. Status & perintah open-close b. Alarm gangguan
Peralatan Yang Diakusisi SOGI4. Lightning Arrester
Lightning Arrester dengan counter
Lightning Arrester tanpa signal untuk SOGI
Peralatan Yang Diakusisi SOGI5. Transformator (Daya & Inter Bus Transformator)
a. Tap position indication dari OLTC b. Counter pengoperasian OLTC c. Temperature winding & oil d. Transformer electromechanical protection (level alarm maupun trip) e. Sistim pendinginan f. Early Warning System g. Alarm gangguan
Peralatan Yang Diakusisi SOGI6. Counter operasi OLTC
Counter operasi OLTC
OLTC Motor Drive Unit
Peralatan Yang Diakusisi SOGI7. Automatic Voltage Regulator
Automatic Voltage Regulator
Kontrol panel
Peralatan Yang Diakusisi SOGI8. Panel distribusi tegangan menengah 20kV a. Status dari Circuit Breaker, Earthing Switch, posisi CB rack in-rack out. b. Kontrol CB c. Alarm gangguan d. Pengukuran besaran-besaran listrik
Penyulang 20kV dengan IED
IED Kontrol & proteksi
Peralatan Yang Diakusisi SOGI9. Ruang kendali GITET/GI Temperatur & Kelembaban
Ruang kendali GI
IED sensor kelembaban dan suhu
Peralatan Yang Diakusisi SOGI10. Sistim SOGIControl centreIEC 60870 101 -5Time synchr (optional)Log.IN1 1100
ICCP/TASE 2
Control centre Lokal HMI
F1 F2
1530 1530
1503 Log.IN2 Log.IN3 1530 2173
>12173
8888
Log.Out1
Ethernet IEC 60870-5-104 (eksisting) IEC 60870-5-103 (eksisting) IEC 60870-5-101 LFC Modbus (temperatur & kelembaban)
IEC 61850
Kesimpulan Sertifikasi uji fungsi dari PUSLITBANG Kepuasan pengguna Pembangunan terpadu peralatan Gardu Induk dengan SOGI Audit spesifikasi teknik, proses lelang dan pengujian Performance terbaik yang terpasang di PLN ALSTOM agar mengganti/memperbaiki PLC T390, PLC 5000 dan PACIS