dow.com dow.com/electrical www.generalcable.com Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power Cable Western Underground Committee Brent Richardson September 24, 2014

Upload: noah-riley

Post on 23-Dec-2015

219 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

dow.comdow.com/electricalwww.generalcable.com

Sustainable and Environmentally Sound

Lead-Free Filled EAM Insulation For Utility Medium Voltage Power Cable

Western Underground CommitteeBrent RichardsonSeptember 24, 2014

Page 2: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

2

Overview

Background and Value Proposition

Why Lead-Free? Why Elastomers?

ANSI/ICEA Ethylene Alkene Copolymer (EAM) Definition

LF Filled EAM Insulation for Cable Applications

LF Filled EAM Insulation Cable Testing

LF Filled EAM Insulation Cable Field Experience

Summary and Features & Benefits

Path Forward/Objectives

Page 3: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

3

Background

The medium voltage filled insulation market has been dominated by Ethylene Propylene Rubber (EPR) based “leaded” insulations for the last forty (40) years.

The solution for increasing cable performance, dealing with environmental concerns, and addressing changing market dynamics requires modifications to the insulation system’s base polymer and stabilization package.

Over the last ten (10) years the performance of metallocene catalyzed Ethylene-Alkene Copolymers (EAM’s) have improved significantly; in concert with GCC stabilizer package development, lead-free EAM insulation meeting Utility MV performance requirements has been created.

Page 4: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

4

Value Proposition

LF Filled EAM insulation offers: Improved installation performance and an environmentally conscious alternative for demanding MV insulation applications:

Improved flexibility and trainability Less spring-back Eliminates the last hazardous material from the MV cable Sustainable solution

LF Filled EAM has demonstrated thermal, wet & dry electrical stability: Meets or exceeds the Qualification and Production requirements of ANSI/ICEA

S-94-649, S-97-682 and AEIC CS8 Core Material Qualification (HVTT, Hot Impulse, Load Cycle, AWTT, etc.) Dry-Electrical Test for Class III Insulation (MV-105) Dissipation Factor Characterization Test Thermomechanical Qualification Test at 140°C

Good original and retention of physical properties Long term wet aging performance demonstrated by ACLT and AWTT testing Field installation and evaluation completed with Consolidated Edison

Page 5: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

5

Why Lead-Free?

With safety as a top concern, the industry has focused on removing hazardous materials from cable products.

RoHS, California Prop. 65, REACH all restrict lead use; EPA currently says that the lead content in MV EPR insulation is below threshold limit, but what will be the future limits?

> 250,000 lb of red lead oxide used in MV EPR insulation production by GCC per year; Each year as the volume of traditional EPR consumption keeps growing the amount of red lead oxide grows.

≈ 43 lb of red lead oxide per circuit mile of 4/0 Al 220 mils wall EPR-insulated MV cable.

Page 6: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

6

Why Elastomers are Used in Utility Cable Applications

Elastomers are polymers that exhibit high extension and flexibility when placed under low mechanical stress.

Low crystallinity of elastomers permit excellent flexibility that enables ease of cable installation.

Low crystallinity of elastomers permit higher filler incorporation that in turn permits cross linked compounds to exhibit high heat and oil resistance.

Page 7: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

7

Definition of Insulation Materials per ANSI/ICEA

ANSI/ICEA S-94-649 and S-97-682 allow alternate EAM insulating materials meeting the same physical and electrical requirements of XLPE, TRXLPE, and EPR.

EAM materials are first identified in a footnote under Table 4-1 in ANSI/ICEA S-94-649 and S-97-682 and are further explained in Appendix I and Appendix H respectively. EAM materials have been listed since 1996

Page 8: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

8

Definition of Insulation Materials per ANSI/ICEA

Ethylene Propylene Rubber (EPR) Insulating Compound is defined as a mixture of ethylene propylene base resin and selected ingredients.

Page 9: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

9

LF Filled EAM Insulation for Cable Applications

Continuing technological developments in polymer catalyst technology make available more diverse polymers suitable for medium voltage cable applications.

GCC developed LF Filled EAM with a Dow elastomer which uses the traditional ethylene backbone of an EPR formulation, but with a longer side chain.

The increasing side chain lengths in EAM compounds improves flexibility and the resulting electrical performance improved without lead Ease of installation: Improved flexibility and trainability; Less spring-back Environmental sustainability is gained and recyclability is improved

LF Filled EAM retains the inherent benefits of EPR insulations with improved thermal stability.

Page 10: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

10

Comparison of Insulation Materials

•The chart below compares key attributes of MV cables for each of the three major insulation types

TR-XLPE EPR EAM

Greater flexibility for ease of installation C B A

Environmental Sustainability A C A

Recyclability B C B

Suitability for constrained space C B A

105/140 C insulation rating A A A

Dielectric losses (dissipation factor) A C B

Highest Retained Breakdown Strength (AWTT) A C B

Insulation by TypeCable Attribute

Page 11: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

LF Filled EAM Insulation Cable Testing

Comparison testing between commercial Leaded EPR and Lead-Free EAM

EAM insulation systems have inherently higher elongation.

Heating Aging (Elongation)

11

Page 12: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

12

LF Filled EAM Insulation Cable Testing

Both compounds maintain high elongation during heat aging.

Heating Aging (Elongation)

Page 13: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

13

LF Filled EAM Insulation Cable Testing

Both compounds maintain high tensile during heat aging;> 80% of initial tensile strength retained through five (5) weeks.

Heating Aging (Tensile)

Page 14: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

14

LF Filled EAM Insulation Cable Testing

Lead-Free EAM is more flexible than Leaded EPR;33% reduction in flex modulus when compared to Leaded EPR.

Flexibility Testing

Lead-Free EAM

Leaded EPR

Page 15: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

15

LF Filled EAM Insulation Cable Testing

Both compounds exceed ICEA HVTT requirements after AWTT wet aging;Lead-Free EAM performs equal or better than Leaded EPR.

AWTT High Voltage Time Test

Long term wet aging performance demonstrated in AWTT testing

Page 16: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

16

LF Filled EAM Insulation Cable Testing

Lead-Free EAM cables show stable dissipation factor under dry aging conditions;Lead-Free EAM has lower, more stable dissipation factor at elevated temperature.

Dry Electrical Testing (MV-105)

Page 17: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

17

LF Filled EAM Insulation Cable Testing

Accelerated Cable Life Testing (ACLT)

R&D testing beyond Industry Standard requirements

Tested per IEEE Std. 1407 Tests for MV (5 kV – 35 kV) Extruded Electric Power

Cables Using Water-Filled Tanks

37B Retained Breakdown Strength Protocol 72 hours pre-conditioning at 90°C Specimens are wet aged in a tank filled with

deionized water; Water is injected into the conductor during aging

3 Vg is applied continuously during wet aging The cable is load cycled with current for 8 hours each

day to achieve a conductor temperature of 75°C in water

The tank water temperature is controlled to 50°C

Page 18: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

18

LF Filled EAM Insulation Cable Testing

Lead-Free EAM performs equal or better than Leaded EPR;Good performance even in high stress design

Accelerated Cable Life Testing (ACLT)

Long term wet aging performance demonstrated in ACLT testing

Page 19: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

19

LF Filled EAM Insulation Cable Field Experience

EAM used as insulation for secondary low-voltage network cable for over a decade (Consolidated Edison 600V Network)

≈ 22,000 miles of 600V EAM-insulated network cables installed since 2000

Introduction of Lead-Free EAM to Consolidated Edison June 2007 for primary medium-voltage insulation

Initial field trial of 3x1/C Triplex 750 kcmil Cu LF-EAM FS PP 15kV Cable completed with Consolidated Edison in February 2010

Positive Feedback from Consolidated Edison Installation Crew “Holds its rack better and does not spring back as much” “A lot easier to rack in manhole than current cable” “Cable was easy to install.  Weather was very cold”

Cable installed along with equivalent leaded EPR design. Both cables removed from service in January 2012 for comparative evaluation

Lead-Free EAM performance was equal or better than Leaded EPR field aged cable

Page 20: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

20

LF Filled EAM Insulation Cable Field Experience

A second cable design manufactured in October 2011 consisting of 23,000 circuit feet of 3x1/C Triplex 500 kcmil Cu LF EAM FS PP 27kV Installation started January 2012 by Consolidated Edison. Cable is still in service

with no plans to remove it.

The development of the new insulation material has taken several years of testing to ensure reliability of and confidence in the product.

Consolidated Edison has given the green light to start completely transitioning over to Lead-Free EAM insulation for all medium-voltage primary cables First design transitioned in 3rd Quarter 2013; >250,000 linear feet shipped. Transitioning all MV cable designs between 3rd and 4th Quarter 2014.

Consolidated Edison cables are designed to perform in harsh operating environment High stress / Reduced insulation wall.

Page 21: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

21

Summary and Features & Benefits

Summary Lead-Free Filled EAM compounds offer improved installation performance and an

environmentally conscious alternative for demanding MV Utility insulation applications. Lead-free Filled EAM has demonstrated thermal, wet & dry electrical stability. GCC has commercialized Lead-free Filled EAM insulation (EmPowr® Fill LF).

Features & Benefits of Lead-free Filled EAM1. Improved flexibility; Improved trainability and less spring-back

– Easier handling during installations.– Appealing for the installation crew; Better ergonomics; Less fatigue after handling.

2. Better wet electrical aging performance vs. a Leaded EPR as demonstrated by AWTT and ACLT testing.

3. Meets or exceeds ANSI/ICEA S-94-649 & S-97-682 and AEIC CS8.4. GCC offers a “Green” Sustainable Solution

– Eliminates the last hazardous material from MV cable designs.– Low and stable dissipation factor (lower losses) at elevated temperatures.– Green solution may aid in rate case approvals.

Page 22: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

22

LF Filled EAM Insulation Path Forward/Objectives

For additional information from General Cable, contact Tom Lewnard or P-M Leblanc.

For additional information from Dow Chemical, contact Brent Richardson

Contact Information:

Brent Richardson:

The Dow Chemical Company

Manager, End Use Marketing-North America

Office-704.721.0288

Cell-704.995.4920

[email protected]

Tom Lewnard:

General Cable

Product Manager, Utility Products

Office: 859-572-8716

Mobile: 859-760-8536

[email protected]

Pierre-Marc Leblanc:

General Cable

Manager Specification Engineering, Utility Products

Office: 859-572-8385

Mobile: 859-802-9005

[email protected]

References Contact Information:

George Murray:

Section Manager, Distribution Cable Systems

Consolidated Edison Company

Office: 718-839-1632

Email: [email protected]

Tom Campbell:

Sr. Engineer, Distribution Cable Systems

Consolidated Edison Company

Office: 212-780-8562

Email: [email protected]

Page 23: Dow.com dow.com/electrical  Sustainable and Environmentally Sound Lead-Free Filled EAM Insulation For Utility Medium Voltage Power

ThankYou