DORMA Installation Manual Extension kit I/O module in the B6L 4P

Upload: vohanh

Post on 06-May-2019

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

DORMA Installation Manual Extension kit I/O module in the B6L 4P

Page 2: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P Contents

2

Contents

1 General information . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.1 Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.2 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.3 Safety instructions and warnings. . . . . . . . . . . . . . 3

1.4 Other sources of information . . . . . . . . . . . . . . . . . 4

1.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.6 Operating principle . . . . . . . . . . . . . . . . . . . . . . . 4

1.7 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . 6

2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.1.1 Module address . . . . . . . . . . . . . . . . . . . . . . . . 7

2.1.2 Terminating resistors . . . . . . . . . . . . . . . . . . . . 7

2.2 Configuration of relay contacts . . . . . . . . . . . . . . . 8

2.3 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.3.1 Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.3.2 Tampering input . . . . . . . . . . . . . . . . . . . . . . . . 8

2.4 Connecting/disconnecting the mains voltage . . . . . . 9

2.5 Physical installation . . . . . . . . . . . . . . . . . . . . . . 10

2.6 Electrical installation . . . . . . . . . . . . . . . . . . . . . . 11

2.7 Optical interfaces and operating elements . . . . . . . 12

2.7.1 Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

2.7.2 Bus activity . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.8 Assignment of readers to input/output modules . . 13

2.9 Terminal diagram. . . . . . . . . . . . . . . . . . . . . . . . 14

3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

3.1 Maintenance and troubleshooting . . . . . . . . . . . . . 15

3.1.1 Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Page 3: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

3

1 . General information

1 .3 Safety instructions and warnings The I/O module extension kit has been designed and tested in accordance with all currently applicable technical regula-tions. All safety features were in proper working order when it left the factory.The user must observe the instructions and warnings given in this installation guide to maintain proper working order and ensure risk-free operation.

• The device may only be used for the purpose intended by the manufacturer.

• Installation and assembly of electrical equipment may be carried out by a qualified electrician only.

• Before opening the unit, always switch off the power sup-ply and check that it is inactive by measuring the current.

• During installation, please ensure that the requirements laid down in the relevant equipment safety standard for the unit are adhered to since non-compliance could affect the safety of the device.

• Before switching on, ensure that the connected operating and control voltages do not exceed the permissible values specified in the technical data.

• This I/O module extension kit complies with EN 60950-1. Operating voltage 24 V/DC Protection Class III

Electromagnetic compatibility:• PCBs can be damaged by static electricity discharge, so

suitable precautionary measures such as grounding must be implemented.

The extension kit may only be operated when installed.

The locking screws on unassigned connection terminals must be screwed in as far as they will go.

If you believe that the device can no longer be operated safely, take it out of operation and secure it against accidental use.

If a unit failure or malfunction may result in injury to persons or animals, or in damage to works equipment, this must be prevented by taking additional safety measures, such as limit switches and safety devices.

General Installation Guidelines See Manual 1006G-B0

1 .1 Preface This installation manual is intended to assist you in con-necting and putting into operation a second I/O module in the B6L 4P.

1 .2 Correct use A second I/O module can be fitted into the box to increase the maximum number of doors operated by the B6L 4P from four to eight and is designed for use with this device only.Use for any other purpose than the one described is not per-mitted.

Drawing no.: 1101G-00-B2Date: 01/12 V1.11

Page 4: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 1 . General information

4

1 .4 Other sources of information

Further documents are available on request. General installation guidelinesSpecifications for planning attendance recording and access control systems with our wired components.

Planner Manual Examples of cross-system solutions

B6L 4P Installation Manual

1 .5 Disposal

This I/O module extension kit has been manufactured using high-quality materials and components that can be recycled.

Information for EU countriesThis I/O module extension kit falls under the European Directive 2002/96 EC and therefore must not be disposed of with household waste.We, the manufacturer, will take back our electric and elec-tronic products and dispose of them for you free of charge. You may also contact your waste disposal company instead.

1 .6 Functional principle

The B6L 4P I/O module determines the status of doors in an access control system and controls the electricalfunctional units.This module features nine digital inputs and eight relays for this purpose, each with a non-isolated changeover contact. The status of the non-isolated digital inputs is transmitted to a higher-level control unit. The control unit evaluates sta-tuses and can operate the relays.

Communication between the I/O module and the access control unit is sent via an RS485 interface.

The B6L 4P I/O module is only available for direct installa-tion in a B6L 4P.

DORMA AllgemeineInstallationsrichtlinien

Zeitw

irtsc

haft

Sich

erun

gste

chni

kZu

tritt

skon

trol

leZe

iterf

assu

ng

Funk

tions

wei

seG

elän

deAu

ßenh

aut

Inne

nber

eich

Mec

hatr

onik

Fluc

htw

eg &

TM

SSy

stem

lösu

ngSy

stem

über

sich

tFu

nktio

nsw

eise

Funk

tions

wei

se

Page 5: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

5

1 . General information

The information provided in these assembly instructions may be modified without prior notification. All previous ver-sions cease to be valid with the publication of these instruc-tions.

The information in these assembly instructions has been compiled to the best of our knowledge and in good faith. DORMA Time + Access GmbH accepts no liability for the correctness and completeness of the details provided.

In particular, DORMA Time + Access GmbH cannot accept liability for any consequential damages due to incorrect or incomplete information.

The recommendations for installation made in this manual are based on the assumption that prevailing basic condi-tions are favourable. DORMA Time + Access GmbH accepts no liability for the perfect functioning of the B6L 4P in non-system environments.

Despite every effort to prevent mistakes, they can never be completely avoided. Therefore, we would be grateful to receive notification of any errors or omissions.

DORMA Time + Access GmbH accepts no liability for the information included in this document being free of pro-tected third party rights. DORMA Time + Access GmbH does not provide any licences to its own or to third party patents or other protected rights with this document.

It is not permitted to print, reproduce or to pass this manual, or parts thereof, to third parties, other than for your own use, without the approval of DORMA Time + Access GmbH.

Alle Rechte vorbehalten . Dorma Time + Access GmbH Postfach 21 01 85 53156 Bonn http://www.dorma-time-access.de E-Mail [email protected]

© Copyright 2013 by Dorma Time + Access GmbH

Page 6: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 1 . General information

6

1 .7 Scope of delivery

A 1x I/O moduleB 1x cover plateC 6x spacer boltsD 6x screws

E 1x bus connection cableF 1x 24 V connection cableG 1x manual

G

B

A

D6x

C

E

6x DORMA Installation Manual

Extension kit I/O module in the B6L 4P

F

Page 7: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

7

2 . Installation

2 .1 Settings

2 .1 .1 Module address Before fitting the module, you must check the bus address of the new device and re-set if necessary.

Settings are made with the SW103 switch.The address for the extension I/O module is 18.The SW103 should be set as in the diagram.

SW102

SW101

OFFON

2 .1 .2 Terminating resistorsThe terminating resistors in the existing I/O module must be set to "Off" before fitting the second I/O module. The terminating resistors in the second I/O module must be set to "On".

24V0VPE

ST100

InAV+

+

-

+

-InKV-

ST401, 402, 403, 404, 405, 406, 407, 408Plusschaltend

Dig

In1

Wechsler (Common)Schliefler (normally open)

ST101, 102, 103, 104, 105, 106, 108, 109

Rel1

InAV+

InKV-

ST401, 402, 403, 404, 405, 406, 407, 408Mit einfachem Kontakt schaltend (unter Aus-nutzung der internen Spannung an den An-

V-

Dig

In1

A1

B3

ST501, 502

+24VDCWADCWB

0V

DCW

ST508

RX

TXGN

D

RS232ST507

ST111

B(-)

A(+)

RS485

1 6 2R

X7 3 8 4 9 5

TX GN

D

ST401, ...408

Rel1, ...8

GND

+24V

ST301, ...309

Digin1, ...9

GNDIN K

SW101 und SW102

On

Terminating resistors off

Terminating resistors on

Off

On

Off

Page 8: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 2 . Installation

8

The I/O module features eight relays. Each relay has a 4-pin plug connector in front of the output terminal. The relay con-tacts can be connected separately from one another with two jumpers so that they are isolated (Jumper Position A) or they can be allocated an auxiliary voltage (internal supply; Jumper Position B).

You must remember that you may only connect eight low-power strikes with 150 mA power con-sumption each to ensure a 30-minute emergency power supply can be provided for the whole access control.

Maximum current per relay contact: 1 A.

Each relay context is equipped with a self-resetting thermal fuse. Inductive loads must be provided with freewheeling diodes if a DC power supply is used.When connecting an alternating current, an RC element or a voltage regulative diode (Item no. 1900001662276) must be used in place of a freewheeling diode for interference suppression.

2 .2 Configuration of relay contacts

SW102

SW101

Jumpers in factory default setting

Jumpers in factory default settingChangeover contact (common)Closing contact (normally open)

Jumpers in factory default settingChangeover contact (common)Closing contact (normally open)

0V 24V

0V 24V

Jumper Setting A – (factory default setting)Relay jumper setting in the case of isolated contacts

Jumper Setting B –Relay jumper setting in the case of looped-in voltage

2 .3 Inputs 2 .3 .1 Digital inputsThe I/O module has nine optocoupler inputs (negative switching). The contact load is a maximum of 10 mA.

The inputs must not be supplied with an external voltage.

2 .3 .2 Tampering input The tampering input on the extension I/O module is not used. No electrical connections need to be made.

24V0VPE

ST100

InAV+

+

-

+

-InKV-

ST401, 402, 403, 404, 405, 406, 407, 408Plusschaltend

Dig

In1

Wechsler (Common)Schliefler (normally open)

ST101, 102, 103, 104, 105, 106, 108, 109

Rel1

InAV+

InKV-

ST401, 402, 403, 404, 405, 406, 407, 408Mit einfachem Kontakt schaltend (unter Aus-nutzung der internen Spannung an den An-

V-

Dig

In1

A1

B3

ST501, 502

+24VDCWADCWB

0V

DCW

ST508

RX

TXGN

D

RS232ST507

ST111

B(-)

A(+)

RS485

1 6 2R

X7 3 8 4 9 5

TX GN

D

ST401, ...408

Rel1, ...8

GND

+24V

ST301, ...309

Digin1, ...9

GNDIN K

SW101 und SW102

On

Terminating resistors off

Terminating resistors on

Off

On

Off

Page 9: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

9

2 . Installation

2 .4 Connecting/disconnecting the mains voltage

NL

10A400V

2,5503 Si

2 .

1 .

1 .

3 .

5 .

4 .

Page 10: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 2 . Installation

10

2 .5 Physical installation

Open the B6L 4P box while observing the aforementioned safety instructions.Take the I/O module (A) out of its protective sleeve while taking into account the safety instructions on handling components at risk from ESD and fasten it to the installed I/O module using spacer bolts.

After fitting the cover plate (B) for the newly installed I/O mod-ule, physical installation is complete.

A

C

B

D

Page 11: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

11

2 . Installation

2 .6 Electrical installation

The enclosed cables are used to connect the bus and the 24 V current.The bus cable (E) connects the ST101 plugs on the two I/O modules with one another.The 24 V cable (F) connects the ST311 plugs on the two I/O modules with one another.

The connection to the TP4 base card remains unchanged via the ST102 plug-in connection in the lower I/O module.

SW102

SW101S

T30

1

ST3

02

ST3

03

ST3

04

ST3

05

ST3

06

ST3

07

ST3

08

ST3

09

ST101

EF

SW102

SW101

ST3

01

ST3

02

ST3

03

ST3

04

ST3

05

ST3

06

ST3

07

ST3

08

ST3

09

ST311

ST101 ST102

Page 12: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 2 . Installation

12

2 .7 .1 Online

2 .7 .2 Bus activity

LED

Off

Yellow

Green

Red

Bedeutung

No reference data to/from the I/O module via the communication inter-face

Receiving reference data

Sending reference dataa) Positive DP1 response telegramsb) DP1 message telegrams

Sending reference dataa) Negative DP1 response telegrams

LED

Yellow

Off

Meaning

The online LED lights up as long as the I/O module is being polled by the higher-level control unit.

If the I/O module is not polled for more than 15 seconds, the online LED goes out.

2 .7 Optical interfaces and operating elements

SW102

SW101

SW102

SW101

SW102

SW101

Page 13: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

13

2 . Installation

2 .8 Assignment of readers to input/output module

Door Cards

ReaderI/O module 1 Out

Door relay(operating current strike)

I/O module 1 OutAlarm relay

I/O module 1 InDoor status contact

I/O module 1 InDoor opening contact

5 9 ST401 ST301

5 10 ST402 ST302

6 11 ST403 ST303

6 12 ST404 ST304

7 13 ST405 ST305

7 14 ST406 ST306

8 15 ST407 ST307

8 16 ST408 ST308

ST401 ST402 ST403 ST404 ST405 ST406 ST407 ST408

ST3

01

ST3

02

ST3

03

ST3

04

ST3

05

ST3

06

ST3

07

ST3

08

ST3

09

LINPUT N

OUTBATCHOGBUMAPG

10A400V

2,5503 Si

SW102

SW101

The extension I/O module is connected to the electrical operating units for Doors 5 to 8 in the same ways as for Doors 1 to 4.The following table gives an overview of connections:

Page 14: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 2 . Installation

14

SW102

SW101

Door openingcontact

Door statuscontact

Operatingcurrent

Door opener

Connectionto the lowerI/O module

Connectionto the lowerI/O module

Alarm relay

...max. 4x each...max. 4x each

Door 5Door 5

0V

NO

NC

0V

NO

NC

0V

NO

NC

0V

NO

NC

0V

NO

NC

0V

NO

NC

0V

NO

NC

0V

NO

NC

0V

K 0V

K 0V

K 0V

K 0V

K 0V

K 0V

K 0V

K 0V

K

ST3

01

ST3

02

ST3

03

ST3

04

ST3

05

ST3

06

ST3

07

ST3

08

ST3

09

ST401 ST402 ST403 ST404 ST405 ST406 ST407 ST408 ST101 ST102

2 .9 Terminal diagram

Page 15: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P

15

3 . Maintenance

3 .1 . Maintenance and troubleshooting

3 .1 .1 FuseAn internal SMD safety fuse SI101 (Littlefuse type 0454.002T, 2AT) is installed as protection in the bot-tom right-hand half of the casing. There is also an SI102 replacement fuse on the component module.

SW102

SW101

Page 16: DORMA Installation Manual Extension kit I/O module in the ...products.dorma.com/content/download/38351/419482/Installation...I/O-Modul / B6L 4P 3 1 . General information 1 .3 Safety

I/O-Modul / B6L 4P 4 . Technical data

16

DORMA Time + Access GmbH Postfach 21 01 85 • D-53156 Bonn • Mainzer Straße 36-52 • D-53179 Bonn Tel. +49 (0) 2 28/85 54-0 • Fax +49 (0) 2 28/85 84-1 75 • www.dorma-time-access.de

DORMA GmbH + Co. KG Postfach 40 09 • D-58247 Ennepetal • DORMA Platz 1 • D-58256 Ennepetal Tel. +49 (0) 23 33 / 793-0 • Fax +49 (0) 23 33 / 79 34 95 • www.dorma.com

Supply voltage via ST101 and ST10224 V DC

Supply voltage via ST311/ST31224 V DC maximum

Power consumptionI/O module itself: max. 5 W (200 mA at 24 V)Supply via ST101/ST102: about 2 W

Interface RS485DP1 protocol

Outputs8x relays contact rating max. 24 W

Digital inputs9x optocouplers (negative switching)Max. load: 24 V DC/10 mA

Ambient conditionsOperating temperature range: -20 °C to +50 °CStorage temperature range: -20 °C to +70 °CHumidity range: up to 80% non-condensing

General designDIN EN 60950-1

Protection rating IP00

Resistance to interferenceSee B6L 4P Installation Manual

Interference emissionsSee B6L 4P Installation Manual

Technical data I/O-Modul B6L 4P

We reserve the right to make technical modifications and improvements in the course of the further development our equipment.