 Doble Sol ut io ns fo r IEC 61 85 0 Jun Verzosa Jay Gosalia Nestor Casilla Doble Enginee ring Company Topics Covered Doble Protection Diagnostics Brief Introduction of IEC61850 IEC 61850 9-2 LE Requirements F6150 Process Bus Implementation Data Interpretation T esting Demonstration 10th India Doble Power Forum Conference 3

Upload: dhanasekaran19731945

Post on 03-Nov-2015

29 views

Category:

Documents


0 download

DESCRIPTION

Doble Solutions for IEC61850

TRANSCRIPT

  • Doble Solutions for IEC 61850

    Jun VerzosaJay GosaliaNestor CasillaDoble Engineering Company

    Topics Covered

    Doble

    Protection Diagnostics

    Brief Introduction of IEC61850

    IEC 61850 9-2 LE Requirements

    F6150 Process Bus Implementation

    Data Interpretation

    Testing Demonstration

    10th India Doble Power Forum Conference 3

    Doble E

    ngineering

    Company

  • Doble Engineering

    Doble Engineering Company is the worldleader in diagnostic test instruments andknowledge services to the electric powerindustry.

    Now in 110 countries, Doble Engineering hasbeen helping clients in the electric powerindustry improve operations and optimizesystem performance for more than 85 years.

    Doble Engineering

    Doble offers diagnostic instruments, services,and the worlds premier library of statisticallysignificant apparatus test results for thebenefit of energy generation and deliverycompanies and industrial power usersworldwide.

    10th India Doble Power Forum Conference 4

    Doble E

    ngineering

    Company

  • Doble Engineering

    Doble was acquired by ESCO TechnologiesInc. (NYSE: ESE) in 2007. Doble continues tobe operated as a stand-alone company.

    Doble Engineering

    Doble has established products in the following areas:

    Circuit Breaker Diagnostics

    Continuous On-Line Diagnostics

    Insulation Analysis

    Oil/Materials Analysis/DOMINO

    10th India Doble Power Forum Conference 5

    Doble E

    ngineering

    Company

  • Doble Engineering

    Partial Discharge Detection

    Protection Diagnostics

    Surge Arresters Monitoring

    Sweep Frequency Response Analysis

    Transformer Diagnostics

    Protection Diagnostics

    Doble protection diagnostic instruments arecompact, rugged, field-portable devices usedworldwide by test engineers to diagnose andcalibrate electromechanical and numericalschemes. The instruments are designed toprovide fully automated steady-state, dynamic,and transient testing capability, in the field aswell as in a laboratory.

    10th India Doble Power Forum Conference 6

    Doble E

    ngineering

    Company

  • Protection Diagnostics

    Doble offers the following protection diagnostic instruments and software: F6150SV and F6150 Power System Simulator

    Protection Diagnostics

    F6350 Real Time Power System Simulation Interface

    Low Level Sources

    10th India Doble Power Forum Conference 7

    Doble E

    ngineering

    Company

  • Protection Diagnostics

    F6300 High-Power Current Amplifier

    Protection Diagnostics

    ProTesT

    F6Test

    Transwin

    Protection Suite

    10th India Doble Power Forum Conference 8

    Doble E

    ngineering

    Company

  • IEC61850 SolutionsVoltage and Current

    Analog or SV

    1. Fault SimulationIED 1

    BREAKER

    IED 2

    ProtectionFunction

    Reclose/Synch

    2. Trip

    3. New Position

    4. Reclose Command

    5. New Position

    GOOSE Message: Trip

    GOOSE Message: Position

    GOOSE Message: Reclose

    IEC61850 NETWORKS

    Voltage

    What Is IEC 61850?

    Borrowed from

    Siemens

    International Standard More than a Protocol A Framework for Substation Automation

    SubstationLAN

    Network

    HMI

    10th India Doble Power Forum Conference 9

    Doble E

    ngineering

    Company

  • What Is IEC 61850?

    Proc

    ess

    Leve

    lBa

    y Le

    vel

    Stat

    ion

    Leve

    l HMI

    Station Bus

    Process Bus (sampled analog

    values)Conventional CTs and VTs

    with hard wiring are used today

    Borrowed from

    Siemens

    What Is IEC 61850?

    The core idea is a description language,that completely describes the datastructure and functionality of asubstation information system in astandardized manner.

    10th India Doble Power Forum Conference 10

    Doble E

    ngineering

    Company

  • What Is IEC 61850?

    The core idea is a description language, that completely describes the data structure and functionality of a substation information system in a standardized manner.

    IEC61850 Documents

    Basic principles Part 1

    Glossary Part 2

    General Requirements Part 3

    System and project management Part 4

    Communication requirements Part 5

    Substation Automation System Configuration Part 6

    Basic Communication Structure Part 7

    Part 9Sampled Measured Values

    Part 8

    Conformance testing Part 10

    Mapping to Ethernet

    Mapping to MMS and Ethernet

    10th India Doble Power Forum Conference 11

    Doble E

    ngineering

    Company

  • This standardized language can be understood by devices from different manufacturers ensuring one of the key goals of IEC 61850, Multi-Vendor Inter-Operability.

    Borrowed from

    Siemens

    IEC 61850

    What Is IEC 61850?

    What Is IEC 61850?

    Borrowed from

    Siemens

    IEC 61850

    This standardized language can be understood by devices from different manufacturers ensuring one of the key goals of IEC 61850, Multi-Vendor Inter-Operability.

    10th India Doble Power Forum Conference 12

    Doble E

    ngineering

    Company

  • IEC61850 : Defining Devices

    CB1

    IED1

    PTOC

    RREC

    XCBR

    XSWI

    MMXU

    MMTR Metering

    CSWI

    CSWI

    Borrowed from

    Siemens

    Measurement Unit

    Disconnect SwitchIndication & Control

    Circuit BreakerIndication & Control

    Auto Reclosing

    Time Over Current

    IEC61850 : Defining Devices

    CB1

    IED1

    PTOC

    RREC

    XCBR

    XSWI

    MMXU

    MMTR

    CSWI

    CSWI

    Borrowed from

    Siemens

    10th India Doble Power Forum Conference 13

    Doble E

    ngineering

    Company

  • IEC61850 : Defining Devices

    CB1

    IED1

    PTOC

    RREC

    XCBR

    XSWI

    MMXU

    MMTR

    IED1Logical Device

    CSWI

    CSWI

    The description of the logical device

    (i.e. the IED) is what you will find in

    a device description file. (called

    ICD)

    Borrowed from

    Siemens

    Accessing Data :Think Windows Explorer

    PTOC (Time Over Current LN )RREC (Autorecloser LN )XCBR (Switchgear Circuit Breaker)CSWI (Control - Circuit Breaker)XSWI (Switchgear Disconnect)CSWI (Control - Disconnect)MMXU (Measurement Unit)MMTR (Metering)

    +

    +

    +

    +

    +

    +

    IED1

    IED1

    +

    +

    Borrowed from

    Siemens

    IED1/XCBR

    10th India Doble Power Forum Conference 14

    Doble E

    ngineering

    Company

  • Accessing Data :Tree view

    Mode (Mode)Beh (Behavior )Health (Health)Name (Name plate)Loc (Local operation)EEHealth (External equipment)EEName (External equipment name plate)OperCnt (Operation counter)Pos (Switch position)BlkOpen (Block opening)BlkClos (Block closing)ChMotEna (Charger motor enabled)CBOpCap (Circuit breaker operating capability)POWCap (Point On Wave switching capability)

    +

    +

    +

    +

    +

    +

    +

    +

    +

    +

    ++

    +

    +

    XCBR

    PTOCRREC

    +

    +

    -

    IED1/XCBRIED1

    Borrowed from

    Siemens

    IED1/XCBR.Pos

    Accessing Data :Tree view

    Mode (Mode)Beh (Behavior )Health (Health)Name (Name plate)Loc (Local operation)EEHealth (External equipment)EEName (External equipment name plate)OperCnt (Operation counter)Pos (Switch position)

    +

    +

    +

    +

    +

    +

    +

    +

    -

    XCBR

    PTOCRREC

    +

    +

    -

    ctlValstValpulseConfigoperTimqmore

    intermediate-state (0)off (1)on (2)bad-state (3)

    IED1/XCBR.Pos

    IED1

    Borrowed from

    Siemens

    IED1/XCBR.Pos.stVal

    10th India Doble Power Forum Conference 15

    Doble E

    ngineering

    Company

  • Logical Groupings Devices, Nodes, Classes & Data

    Physical Device(network address)

    Physical Device - server(network address)

    Logical Device(IED1)

    LN2(PDIS)

    LN1(XCBR)

    Logical Groupings Devices, Nodes, Classes & Data

    Pos Op

    gen. qstVal q

    Physical Device

    Logical Device(1 to n)

    Logical Node(1 to n)

    Data Class

    Data

    Borrowed from

    Siemens

    10th India Doble Power Forum Conference 16

    Doble E

    ngineering

    Company

  • IEC61850 Primary Parts

    Part 6-1: Substation Configuration Language (SCL) Part 7-2: Abstract Communications Service Interface

    (ACSI) and base types Part 7-3: Common Data Classes (CDC) Part 7-4: Logical Nodes Part 8-1: Specific Communications Service Mappings

    (SCSM) - MMS & Ethernet Part 9-2: SCSM - Sampled Values over Ethernet Part 10-1: Conformance Testing

    UCA : 9-2 LE Guide line Document

    10th India Doble Power Forum Conference 17

    Doble E

    ngineering

    Company

  • 9-2 LE Implementation Guideline

    Purpose of implementation guideline Support fast market introduction of the standard Define a subset to facilitate first implementations

    Logical device merging unit name: xxxxMUnnyy xxxx : alphanumeric name MU : fixed, stands for merging unit nn : merging unit number yy : 01 for protection (80 samples/cy), 02 for metering (256

    samples/cy)

    Examples: DOBLMU1201, A1Z9MU0401 Fixed dataset : 4 currents & 4 voltages (Phases A,

    B, C & Neutral)

    Data Structure : Sample Value Packet

    Preamble : 8 BytesStart of the Frame : 1 Byte

    Destination Address: 010CCD04

    Source Address: MAC Address : F6

    Priority Tagged : 4 BytesProtocol Data Unit : PDUData type :88BAApp ID : 0400Data Length :Reserved Bytes : 2 Bytes : 0000, 0000A,B,C,N : V & I Data : Quality and Value

    10th India Doble Power Forum Conference 18

    Doble E

    ngineering

    Company

  • F6TesT : SV Source Configuration

    Destination Address: 010CCD04

    Priority Tagged VLAN ID = 0VLAN Priority=4

    Process Bus : Data Capture

    10th India Doble Power Forum Conference 19

    Doble E

    ngineering

    Company

  • Process Bus : Data Capture

    Process Bus : Sampled values Data

    10th India Doble Power Forum Conference 20

    Doble E

    ngineering

    Company

  • Process Bus : Sampled Values

    svID : last two digit 01 : 80 samples/cy.smpCnt :829 : 0-4799 for 60Hz & rolls OversmpSynch : 1 : samples are synchronized

    Value is 32 bit integer. One bit is for sign.31 bit provides very wide dynamic rangeThis is expressed as peak value in mA(10-3) and cV (10-2)

    SV Packet : Quality Bits

    10th India Doble Power Forum Conference 21

    Doble E

    ngineering

    Company

  • Process Bus : 9-2 LE Requirements

    Protection sampled value should be sampled at 80 samples/Cycle & metering sampled value should be sampled at 256 Samples/Cycle Last two digit on svid indicates 01 (for 80 samples) & 02 (for 256

    Samples)

    Physical layer requirements : Fiber optic 100 Base FX Full Duplex with ST connector Electrical connection : 100 Base TX Full Duplex

    In the test mode : MU should flag the data as Test with a bit in quality bit

    MU should be synchronized with external 1 PPS signal with an accuracy of 1 microsecond to the absolute time

    Process Bus : 9-2 LE Requirements

    If the synchronization signal is lost SmpSynch in the SV packet should be set to false

    If Neutral current or voltage is not measured, MU should calculate and flag the value as calculated in quality field.

    Up to 8 ASDUs can be transmitted in one PDU packet

    No SV messages are sent until Merging Unit is fully operational.

    10th India Doble Power Forum Conference 22

    Doble E

    ngineering

    Company

  • IED Communications

    Ethernet Ports for GOOSE and Setting

    Copper port

    F.O. port

    IRIB-BTime sync

    Copper port

    F.O. port

    Ethernet Ports for IEC61850 9-2 LE Sampled Values

    IED Communications

    Ethernet Ports for GOOSE and Setting

    IRIB-BTime sync

    F.O. Ports for IEC61850 9-2 LE Sampled Values

    10th India Doble Power Forum Conference 23

    Doble E

    ngineering

    Company

  • Configuring F6150 Sampled Values

    Configuring F6150 Sampled Values

    10th India Doble Power Forum Conference 24

    Doble E

    ngineering

    Company

  • F6150SV Communications

    F.O. port Sampled Values

    Copper port

    Sampled Values

    USB portF6 control & configuration

    2-port switchGSE messages

    F6 control & configuration

    F6150SV Communications

    10th India Doble Power Forum Conference 25

    Doble E

    ngineering

    Company

  • Testing the IED with F6150SV

    HUB

    SAMPLE VALUES

    GE UR Relay SEL 421 Relay

    IP 192.168.5.193

    IP 192.168.5.192

    IP 192.168.5.194

    GOOSE Messages

    IP 192.168.5.191

    Testing the IED with F6150SV

    GOOSE messages

    sampled values

    P444 IEDF6150SV

    F6TesT 3GSEIED swother sw

    10th India Doble Power Forum Conference 26

    Doble E

    ngineering

    Company

  • Testing the IED with F6150SV

    F6TesT 3GSEIED swother sw

    Configuring F6150 Sampled Values

    10th India Doble Power Forum Conference 27

    Doble E

    ngineering

    Company

  • Metering Test of SV

    Metering Test of SV

    10th India Doble Power Forum Conference 28

    Doble E

    ngineering

    Company

  • State Simulation Test using SV

    Waveforms recorded by IED from SV

    10th India Doble Power Forum Conference 29

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Create, import or discover GSE messages. Configures the F6150 Power System Simulator

    for GSE Message Subscription (Input or Reception) Publishing (Output or

    Simulation/Transmission). Supports GOOSE and GSSE messages.

    Doble IEC 61850 GSE Configurator

    Define GSE Messages and their payload (Dataset items) Discover, import SCL files, or manually create them.

    Select Dataset items from messages that will be used for testing

    Assign data items to F6150 Inputs and Outputs Download the Data Items and I/O mappings to

    the F6150 (Configure the instrument) Observe Live Data Status while testing

    10th India Doble Power Forum Conference 30

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble IEC 61850 GSE Configurator

    10th India Doble Power Forum Conference 31

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble IEC 61850 GSE Configurator

    10th India Doble Power Forum Conference 32

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble IEC 61850 GSE Configurator

    10th India Doble Power Forum Conference 33

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble IEC 61850 GSE Configurator

    10th India Doble Power Forum Conference 34

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble IEC 61850 GSE Configurator

    10th India Doble Power Forum Conference 35

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble IEC 61850 GSE Configurator

    10th India Doble Power Forum Conference 36

    Doble E

    ngineering

    Company

  • Doble IEC 61850 GSE Configurator

    Doble Solutions for IEC 61850

    10th India Doble Power Forum Conference 37

    Doble E

    ngineering

    Company